Data Sheet FieldIT SS/264HS/NS_3 2600T Series Pressure Transmitters Model 264HS Gauge Model 264NS Absolute high overload overpressure up to 90MPa, 13050psi Base accuracy : 0.075% Span limits - 0.65 to 60000kPa; 2.6inH2O to 8700psi - 1.1 to 16000kPa abs; 8mmHg to 2320psia Reliable sensing system coupled with very latest digital technologies - provides large turn down ratio up to 100:1 Comprehensive sensor choice - optimize in-use total performance and stability 5-year stability Flexible configuration facilities - provided locally via local keys combined with LCD indicator or via hand held terminal or PC configuration platform Multiple protocol availability - provides integration with HART(R), PROFIBUS PA and FOUNDATION Fieldbus platforms offering interchangeability and transmitter upgrade capabilities Full compliance with PED Category IV - suitable for safety accessory application ABB 2600T Series Engineered solutions for all applications 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Functional Specifications Operative limits Range and span limits Temperature limits C (F) : Sensor Code Upper Range Limit (URL) Lower Range Limit (LRL) Minimum span G 65kPa 650mbar 260inH2O 0.07kPa abs 0.7mbar abs 0.5mmHg 264HS gauge 0.65kPa 6.5mbar 2.6inH2O H 160kPa 1600mbar 642inH2O 0.07kPa abs 0.7mbar abs 0.5mmHg 1.6kPa 16mbar 6.4inH2O 2.67kPa 26.7mbar 20mmHg M 600kPa 6bar 87psi 0.07kPa abs 0.7mbar abs 0.5mmHg 6kPa 0.06bar 0.87psi 10kPa 0.1bar 1.45psi P 2400kPa 24bar 348psi 0.07kPa abs 0.7mbar abs 0.5mmHg 24kPa 0.24bar 3.5psi 40kPa 0.4bar 5.8psi 8000kPa 80bar 1160psi 16000kPa 160bar 2320psi 60000kPa 600bar 8700psi 0.07kPa abs 0.7mbar abs 0.5mmHg 0.07kPa abs 0.7mbar abs 0.5mmHg 0.07kPa abs 0.7mbar abs 0.5mmHg 80kPa 0.8bar 11.6psi 160kPa 1.6bar 23.2psi 600kPa 6bar 87psi 134kPa 1.34bar 19.4psi 267kPa 2.67bar 38.7psi Q S V 264NS absolute 1.1kPa 11mbar 8mmHg Ambient (is the operating temperature) Model 264HS Model 264NS Sensors G to S Sensor V Sensors G to S -40 and +85 -40 and +85 -40 and +85 Silicone oil (-40 and +185) (-40 and +185) (-40 and +185) -10 and +65 -20 and +85 Inert Galden (+14 and +150) (-4 and +185) -10 and +65 -20 and +85 Inert (-4 and +185) Halocarbon (+14 and +150) -20 and +85 Inert Carbon Fluoride (-4 and +185) Filling Lower ambient limit for LCD indicators: -20C (-4F) Upper ambient limit for LCD indicators: +70C (+158F) Note : For Hazardous Atmosphere applications see the temperature range specified on the certificate/approval relevant to the aimed type of protection Process Lower limit - refer to lower ambient limits Upper limit - Silicone oil: 121C (250F) (1) - Inert fluid (Galden or Halocarbon): 100C (212F) (2) - Inert fluid (Carbon fluoride): 121C (250F) Span limits Maximum span = URL IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. (1) 100C (212F) for application below atmospheric pressure (2) 65C (150F) for application below atmospheric pressure Storage Lower limit: -50C (-58F); -40C (-40F) for LCD indicators Zero suppression and elevation Zero and span can be adjusted to any value within the range limits detailed in the table as long as: - calibrated span minimum span Damping Selectable time constant : 0, 0.25, 0.5, 1, 2, 4, 8 or 16s. This is in addition to sensor response time Turn on time Operation within specification in less than 1s with minimum damping. Insulation resistance > 100M at 1000VDC (terminals to earth) 2 Upper limit: +85C (+185F) 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Pressure limits Wet and dust-laden atmospheres Overpressure limits (without damage to the transmitter) 0.067kPa abs, 0.67mbar abs, 0.01psia (double with inert filling) to - 21MPa, 210bar, 3045psi for sensor codes G to S - 90MPa, 900bar, 13050psi for sensor code V Proof pressure The transmitter can be exposed without leaking to line pressure of up to - 40MPa, 400bar, 5800psi for sensor codes G to S - 90MPa, 900bar, 13050psi for sensor code V Meet ANSI/ISA-S 82.03 hydrostatic test requirements and SAMA PMC 27.1. Environmental limits Electromagnetic compatibility (EMC) Comply with EN 61000-6-3 for emission and EN 61000-6-2 for immunity requirements and test; Radiated electromagnetic immunity level: (according to IEC 1000-4-3, EN61000-4-3) 30V/m Conducted electromagnetic immunity level : (according to IEC 1000-4-6, EN 61000-4-6) 30V Surge immunity level (with surge protector): (according to IEC 1000-4-5 EN 61000-4-5) 4kV Fast transient (Burst) immunity level: (according to IEC 1000-4-4 EN 61000-4-4) 4kV Pressure equipment directive (PED) The transmitter is dust and sand tight and protected against immersion effects as defined by EN 60529 (1989) to IP 67 (IP 68 on request) or by NEMA to 4X or by JIS to C0920. Hazardous atmospheres With or without output meter/integral display - INTRINSIC SAFETY/EUROPE: ATEX/ZELM approval II 1 GD T50C, EEx ia IIC T6 (-40C Ta +40C) T95C, EEx ia IIC T4 (-40C Ta +85C) - TYPE "N"/EUROPE: ATEX/ZELM type examination (for HART) II 3 GD T50C, EEx nL IIC T6 (-40C Ta +40C) T95C, EEx nL IIC T4 (-40C Ta +85C) (FOUNDATION Fieldbus/PROFIBUS PA): pending - FLAMEPROOF/EUROPE: ATEX/CESI approval II 1/2 GD T85C, EEx d IIC T6 (-40C Ta +75C) - CANADIAN STANDARDS ASSOCIATION and FACTORY MUTUAL: - Explosionproof: Class I, Div. 1, Groups A, B, C, D - Dust ignitionproof : Class II, Div. 1, Groups E, F, G - Suitable for : Class II, Div. 2, Groups F, G; Class III, Div. 1, 2 - Nonincendive: Class I, Div. 2, Groups A, B, C, D - Intrinsically safe: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G AEx ia IIC T6/T4, Zone 0 (FM) - STANDARDS AUSTRALIA (SAA): pending TS/WCA Approval Ex d IIC T5 (Tamb +85C)/T6 (Tamb +70C) Class 1 Zone 1; Ex ia IIC T4 (Tamb +85C) /T5 (Tamb +55C) T6 Class 1 Zone 0 Comply with 97/23/EEC Category IV Modules D and B. (Category III Module H for sensor code V). Humidity Relative humidity: up to 100% annual average Condensing, icing: admissible Vibration resistance Accelerations up to 2g at frequency up to 1000Hz (according to IEC 60068-2-26) Shock resistance Acceleration: 50g Duration: 11ms (according to IEC 60068-2-27) 3 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Electrical Characteristics and Options Optional surge protection HART digital communication and 4 to 20mA output Power Supply Up to 4kV - voltage 1.2s rise time / 50s delay time to half value - current 8s rise time / 20s delay time to half value The transmitter operates from 10.5 to 42VDC with no load and is protected against reverse polarity connection (additional load allows operations over 42VDC). For EEx ia and other intrinsically safe approval power supply must not exceed 30VDC. Ripple Output signal Two-wire 4 to 20mA, user-selectable for linear or 5th order or two 2nd order switching point selectable programmable polynomial output. HART(R) communication provides digital process variable (%, mA or engineering units) superimposed on 4 to 20mA signal, with protocol based on Bell 202 FSK standard. 20mV max on a 250 load as per HART specifications Output current limits (to NAMUR standard) MINIMUM OPERATING VOLTAGES Overload condition no link on output indicator plugs with CoMeter indicator and HART communication with ProMeter output indicator 3.8mA - Upper limit: 20.5mA Transmitter failure mode (to NAMUR standard) with optional surge protection The output signal can be user-selected to a value of 3.7 or 22mA on gross transmitter failure condition, detected by self-diagnostics. with optional output analog indicator In case of CPU failure the output is driven <3.7mA or >22mA. with integral display (volts) 10.5 10.7 12.3 12.5 13.3 15.3 Load limitations 4 to 20mA and HART total loop resistance : Supply voltage - min. operating voltage (VDC) --------------------------------------- 22.5 A minimum of 250 is required for HART communication. R(k) = Optional indicators Output meter CoMeter and Prometer LCD : 5-digit (99999 counts) programmable with 7.6mm. high (3in), 7-segment numeric characters plus sign and digital point for digital indication of output value in percentage, current or engineer unit; 10-segment bargraph display (10% per segment) for analog indication of output in percentage; 7-digit with 6mm. high (2.3in), 14-segment alphanumeric characters, for engineer units and configuration display Analog : 36mm (1.4in) scale on 90. Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of analog output in percentage. User-definable matrix display mode with HART communication: - process variable in pressure unit or - output signal as percentage, current or engineering units Display also indicates in/out transfer function, static pressure, sensor temperature and diagnostic messages and provides configuration facilities. 4 - Lower limit: 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 PROFIBUS PA output FOUNDATION Fieldbus output Device type Device type Pressure transmitter compliant to Profiles 3.0 Class A & B; ident. number 052B HEX. Power supply The transmitter operates from 10.5 to 32VDC , polarity independent. For EEx ia approval power supply must not exceed 17.5VDC. Intrinsic safety installation according to FISCO model. Current consumption operating (quiescent): 10.5mA fault current limiting: 20mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Output interface PROFIBUS PA communication according to Profibus DP50170 Part 2/ DIN 19245 part 1-3. Output update time 25ms Function blocks 2 analog input, 1 transducer, 1 physical Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of output in percentage of the analog input function block assigned to the primary variable. User-definable matrix display mode: - process variable in pressure units or - primary variable in engineering units (output of transducer block) or - output as percentage or engineering units of analog input function blocks Display also indicates diagnostic messages and provides configuration facilities. Secondary variable, static pressure and sensor temperature can be read. Transmitter failure mode On gross transmitter failure condition, detected by self-diagnostics, the output signal can be driven to defined conditions, selectable by the user as safe, last valid or calculated value. If electronic failure or short circuit occur the transmitter consumption is electronically limited at a defined value (20mA approx), for safety of the network. LINK MASTER DEVICE Link Active Scheduler (LAS) capability implemented. Power supply The transmitter operates from 9 to 32VDC, polarity independent. For EEx ia approval power supply must not exceed 24VDC (entity certification) or 17.5VDC (FISCO certification), according to FF-816. Current consumption operating (quiescent): 10.5mA fault current limiting: 20mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Function blocks/execution period 2 standard Analog Input blocks/25ms max (each) 1 standard PID block/70ms max. Additional blocks 1 standard Resource block, 1 custom Pressure with calibration transducer block. Number of link objects 25 Number of VCRs 24 Output interface FOUNDATION fieldbus digital communication protocol to standard H1, compliant to specification V. 1.5; FF registration number IT019000. Integral display LCD, 15 lines x 56 column dot matrix providing 2 lines indication as - top: 5-digit (numeric) plus sign or 7-digit alphanumeric - bottom: 7-digit alphanumeric and additional 50-segment bargraph for indication of output in percentage of the analog input function block assigned to the primary variable. User-definable matrix display mode: - process variable in pressure units or - primary variable in engineering units (output of transducer block) or - output as percentage or engineering units of analog input function blocks Display also indicates diagnostic messages and provides configuration facilities. Secondary variable, static pressure and sensor temperature can be read. Transmitter failure mode The output signal is "frozen" to the last valid value on gross transmitter failure condition, detected by self-diagnostics which also indicate a BAD conditions. If electronic failure or short circuit occur the transmitter consumption is electronically limited at a defined value (20mA approx), for safety of the network. 5 2600T Pressure Transmitters Model 264HS, 264NS Performance specifications Stated at reference condition to IEC 60770 ambient temperature of 20C (68F), relative humidity of 65%, atmospheric pressure of 1013hPa (1013mbar), zero based range for transmitter with isolating diaphragms in AISI 316 L ss or Hastelloy and silicone oil fill and HART digital trim values equal to 4-20mA span end points, in linear mode. Unless otherwise specified, errors are quoted as % of span. Some performance data are affected by the actual turndown (TD) as ratio between Upper Range Limit (URL) and calibrated span. IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. SS/264HS/NS_3 Operating influences Ambient temperature per 20K (36F) change between the limits of -20C to +65C (-4 to +150F) : Sensor Code for TD up to 264HS G to V 15:1 (0.04% URL + 0.065% span) 264NS G to S 10:1 (0.04% URL + 0.065% span) Model Optional CoMeter and ProMeter ambient temperature Dynamic performance (according to IEC 61298-1 definition) Dead time: 40ms Time constant (63.2% of total step change): - sensor V: 150ms - sensors M to S: 70ms - sensor H: 100ms - sensor G: 130ms Response time (total) = dead time + time constant Total reading error per 20K (36F) change between the ambient limits of -20 and +70C (-4 and +158F) : 0.15% of max span (16mA). Supply voltage Within voltage/load specified limits the total effect is less than 0.005% of URL per volt. Load Within load/voltage specified limits the total effect is negligible. Radio frequency interference Accuracy rating % of calibrated span, including combined effects of terminal based linearity, hysteresis and repeatability. For fieldbus versions SPAN refer to analog input function block outscale range Total effect : less than 0.10% of span from 20 to 1000MHz and for field strengths up to 30V/m when tested with shielded conduit and grounding, with or without meter. Common mode interference No effect from 100Vrms @ 50Hz, or 50VDC Model 264HS - 0.075% for TD from 1:1 to 15:1 Mounting position URL - 0.005% x Span Stability for TD from 15:1 to 60:1 - 0.075% for TD from 1:1 to 10:1 6 0.10% of URL over a thirty-six-month period Vibration effect Model 264NS - 0.0075% x No effect URL for TD from 10:1 to 20:1 Span 0.10% of URL (according to IEC 61298-3) 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Physical Specification Optional extras (Refer to ordering information sheets for variant availability related to specific model or versions code) Mounting brackets For 60mm. (2in) pipes or wall mounting. Materials Output indicator Process isolating diaphragms (*) plug-in rotatable type, LCD or analog. AISI 316 L ss; Hastelloy C276TM; Monel 400TM;Tantalum; Hastelloy C276TM on AISI 316 L ss gasket seat. Process connection (*) AISI 316 L ss; Hastelloy C276TM; Monel 400TM. Sensor fill fluid Silicone oil (DC200); inert fill (Halocarbon 4.2TM or GaldenTM; carbon fluoride for sensor V) Mounting bracket (**) Zinc plated carbon steel with chrome passivation; AISI 316 L ss. Supplemental customer tag AISI 316 ss tag screwed/fastened to the transmitter for customer's tag data up to a maximum of 20 characters and spaces on one line for tag number and tag name, and up to a maximum of 3 spaced strings of 10 characters each for calibration details (lower and upper values plus unit). Special typing evaluated on request for charges. Surge protection (only as external unit for PROFIBUS PA and FF) Cleaning procedure for oxygen service Test Certificates (test, design, calibration, material traceability) Tag and manual language Communication connectors Sensor housing AISI 316 L ss. Process connections 1 Electronic housing and covers Barrel version - Copper-free content aluminium alloy with baked epoxy finish; - Low-copper content aluminium alloy with baked epoxy finish; - AISI 316 L ss. Covers O-ring Buna N. Local zero and span adjustments: Glass filled polycarbonate plastic (removable). Tagging AISI 316ss data plate attached to the electronics housing. Calibration Standard: at maximum span, zero based range, ambient temperature and pressure; Optional: at specified range and ambient conditions. /2in NPT female or male; DIN EN837-1 G 1/2in B; adapter straight (180) entry; adapter angle (90) entry. fixing threads on adapter entries: 7/16in-20 UNF at 41.3mm centre distance. Electrical connections Two 1/2 NPT or M20x1.5 or PG 13.5 or 1/2 GK threaded conduit entries, direct on housing. Special communication connector (on request) - HART : straight or angle Harting Han connector and one plug. - FOUNDATION Fieldbus, PROFIBUS PA: M12x1 or 7/8. Terminal block HART version: three terminals for signal/external meter wiring up to 2.5mm2 (14AWG) and three connection points for test and communication purposes. Fieldbus versions: two terminals for signal wiring (bus connection) up to 2.5mm2 (14AWG) Grounding Internal and external 6mm2 (10AWG) ground termination points are provided. Mounting position Transmitter can be mounted in any position. Electronics housing may be rotated to any position. A positive stop prevents over travel. Mass (without options) 1.7kg approx (4lb); add 1.5kg (3.4lb) for AISI housing. Add 650g (1.5lb) for packing. Packing Carton 26 x 26 x 18cm approx (10 x 10 x 7in). 7 2600T Pressure Transmitters Model 264HS, 264NS Configuration Transmitter with HART communication and 4 to 20 mA Standard configuration Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the tag plate. If a calibration range and tag data are not specified, the transmitter will be supplied with the plate left blank and configured as follows: Engineering Unit Specify from table 4 mA Zero 20 mA Upper Range Limit (URL) Output Linear Damping 1 sec. Transmitter failure mode Upscale Software tag characters Blank Optional LCD indicator/display 0 to 100.0% linear Any or all the above configurable parameters, including Lower range-value and Upper range-value which must be the same unit of measure, can be easily changed using the HART hand-held communicator or by a PC running the configuration software SMART VISION with DTM for 2600T. The transmitter database is customized with specified flange type and material, O-ring and drain/vent materials and meter code option. Custom configuration (option) The following data may be specified in addition to the standard configuration parameters: Descriptor 16 alphanumeric characters Message 32 alphanumeric characters Date Day, month, year Transmitter with PROFIBUS PA communication Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the tag plate. If a calibration range and tag data are not specified, the transmitter will be supplied with the plate left blank and configured as follows: Measure Profile Pressure Engineering Unit kPa Output scale 0% Lower Range Limit (LRL) Output scale 100% Upper Range Limit (URL) Output Linear Hi-Hi Limit Upper Range Limit (URL) Hi Limit Upper Range Limit (URL) Low Limit Lower Range Limit (LRL) Low-Low Limit Lower Range Limit (LRL) Limits hysteresis 0.5% of output scale PV filter 0 sec. Address (settable by local key) 126 Tag 32 alphanumeric characters Any or all the above configurable parameters, including Lower range-value and Upper range-value which must be the same unit of measure, can be easily changed by a PC running the configuration software SMART VISION with DTM for 2600T. The transmitter database is customized with specified flange type and material, O-ring and drain/vent materials and meter code option. Custom configuration (option) The following data may be specified in addition to the standard configuration parameters: Descriptor 32 alphanumeric characters Message 32 alphanumeric characters Date Day, month, year 8 SS/264HS/NS_3 Transmitter with FOUNDATION Fieldbus communication Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the tag plate. If a calibration range and tag data are not specified, the transmitter will be supplied with the plate left blank and the analog input function block FB1 is configured as follows: Measure Profile Pressure Engineering Unit kPa Output scale 0% Lower Range Limit (LRL) Output scale 100% Upper Range Limit (URL) Output Linear Hi-Hi Limit Upper Range Limit (URL) Hi Limit : Upper Range Limit (URL) Low Limit Lower Range Limit (LRL) Low-Low Limit Lower Range Limit (LRL) Limits hysteresis 0.5% of output scale PV filter time 0 sec. Tag 32 alphanumeric characters The analog input function block FB2 is configured for the sensor temperature measured in C. Any or all the above configurable parameters, including the range values, can be changed using any host compliant to FOUNDATION fieldbus. The transmitter database is customized with specified flange type and material, O-ring and drain/vent materials and meter code option. For any protocol available engineering units of pressure measure are : Pa, kPa, MPa inH2O@4C, mmH2O@4C, psi inH2O@20C, ftH2O@20C, mmH2O@20C inHg, mmHg, Torr g/cm2, kg/cm2, atm mbar, bar TM Hastelloy is a Cabot Corporation trademark TM Monel is an International Nickel Co. trademark TM DC 200 is a Dow Corning Corporation trademark TM Galden is a Montefluos trademark TM Halocarbon is a Halocarbon Products Co. trademark (*) Wetted parts of the transmitter. (**) U-bolt material: AISI 400 ss; screws material: high-strength alloy steel or AISI 316 ss. 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 MOUNTING DIMENSIONS (not for construction unless certified) - dimensions in mm (in) Transmitter with barrel housing on bracket for 60mm (2in) pipe mounting Adjustments Identification tag 127 (5.00) 26 (1.02) 17 (0.67) Min. clearance to remove the cover Electrical connections 36 (1.42) 17 (0.67) 86 (3.39) Certification label L ES C CI R I R C U E T QU AN E'T H E N W ERCLE BIEN F UV E CO VER TI GH RM E P CO T E Terminal side GARD ER KE L Integral display housing Covers locking screw ! Electronic side N IO NS 100 (3.94) SONT SO I TS AL I V US T E E CU TS I o 65 (2.56) 135 (5.31) 18 (0.71) 16 (0.63) 19 (0.75) 36 (1.42) Output meter housing CH 32 57 (2.24) 1 /2in - 14 NPT female connection for sensors G, H, M, P, Q, S Adjustments 26 (1.02) 17 (0.67) Min. clearance to remove the cover Identification tag 127 (5.00) Electrical connections 36 (1.42) 17 (0.67) 86 (3.39) L ES C CI R I R C U E T QU AN E'T H E N W ERCLE BIEN F UV E CO VER TI GH RM E P CO T E Covers locking screw GARD ER KE L Integral display housing Terminal side ! Electronic side SONT SO I TS AL I V US T E E CU TS I N IO NS 100 (3.94) Certification label 50 (1.97) Output meter housing 56 (2.20) CH27 135 (5.31) 1 /2in - 14 NPT female connection for sensor V (NOT FOR 264NS) 9 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Adjustments Identification tag 127 (5.00) 36 (1.42) 17 (0.67) 86 (3.39) Terminal side Integral display housing GARD ER KE L E T QU AN E'T H E N W ! 100 (3.94) N IO NS Electronic side SONT SO I TS AL I V US T E E CU TS I Covers locking screw L ES C CI R I R C U Certification label Min. clearance to remove the cover ERCLE BIEN F UV E CO VER TI GH RM E P CO T E 26 (1.02) 17 (0.67) Electrical connections 18 (0.71) 16 (0.63) 42 (1.65) 57 (2.24) Output meter housing o 17.5 (0.69) CH 32 G 1/2"B o 65 (2.56) 135 (5.31) 57 (2.24) DIN-EN837-1 G 1/2in B connection for sensors G, H, M, P, Q, S Identification tag 127 (5.00) Electrical connections 36 (1.42) 17 (0.67) 86 (3.39) Certification label L ES C CI R I R C U Covers locking screw GARD ER KE L Terminal side ! Integral display housing SONT SO I TS AL I V US T E E CU TS I E T QU AN E'T H E N W Electronic side N IO NS 100 (3.94) 26 (1.02) 17 (0.67) Min. clearance to remove the cover ERCLE BIEN F UV E CO VER TI GH RM E P CO T E Adjustments 58 (2.28) Output meter housing 56 (2.20) 135 (5.31) DIN-EN837-1 G 1/2in B connection for sensor V (NOT FOR 264NS) 10 G 1/2" B CH22 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Identification tag 127 (5.00) 36 (1.42) 17 (0.67) Min. clearance to remove the cover Electrical connections 86 (3.39) 100 (3.94) Certification label L ES C CI R I R C U Covers locking screw GARD ER KE L Terminal side ! Integral display housing SONT SO I TS AL I V US T E E CU TS I N IO NS Electronic side E T QU AN E'T H E N W 26 (1.02) 17 (0.67) ERCLE BIEN F UV E CO VER TI GH RM E P CO T E Adjustments 18 (0.71) 16 (0.63) 39 (1.54) 54 (2.13) Output meter housing 1/2" - 14 NPT o 65 (2.56) CH 32 135 (5.31) /2 in - 14 NPT male connection for sensors G, H, M, P, Q, S 26 (1.02) 17 (0.67) Identification tag 127 (5.00) Electrical connections 86 (3.39) 36 (1.42) 17 (0.67) E T QU AN E'T H E N W 100 (3.94) Terminal side GARD ER KE L Integral display housing SONT SO I TS AL I V US T E E CU TS I ! Electronic side Covers locking screw N IO NS Certification label Min. clearance to remove the cover L ES C CI R I R C U Adjustments ERCLE BIEN F UV E CO VER TI GH RM E P CO T E 1 57 (2.24) 55 (2.17) Output meter housing CH22 56 (2.20) 135 (5.31) 1 /2 in - 14 NPT male connection for sensor V (NOT FOR 264NS) 11 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Identification tag Adjustments 127 (5.00) 26 (1.02) 17 (0.67) Min. clearance to remove the cover Electrical connections 86 (3.39) 36 (1.42) 17 (0.67) L ES C CI R I R C U E T QU AN E'T H E N W GARD ER KE L ERCLE BIEN F UV E CO VER TI GH RM E P CO T E Terminal side Integral display housing SONT SO I TS AL I V US T E E CU TS I ! Electronic side Covers locking screw N IO NS 100 (3.94) Certification label 18 (0.71) 17.5 (0.69) 16 (0.63) 34 (1.34) Output meter housing o 41.3 o 65 (2.56) 135 (5.31) 57 (2.24) o 65 (2.56) Adapter straight (180) entry connection (7/16in - 20 UNF drilling) for sensors G, H, M, P, Q, S Identification tag Electrical connections 36 (1.42) 17 (0.67) 86 (3.39) Certification label Covers locking screw o 39 (1.54) 135 (5.31) 42.5 (1.67) 18 (0.71) 16 (0.63) 31 (1.22) o 41.3 (1.63) 49.5 (1.95) Output meter housing Adapter angle (90) entry connection (7/16in - 20 UNF drilling) for sensors G, H, M, P, Q, S 12 L ES C CI R I R C U Terminal side GARD ER KE L Integral display housing SONT SO I TS AL I V US T E E CU TS I ! Electronic side N IO NS 100 (3.94) Min. clearance to remove the cover E T QU AN E'T H E N W 127 (5.00) 26 (1.02) 17 (0.67) ERCLE BIEN F UV E CO VER TI GH RM E P CO T E Adjustments o 65 (2.56) 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Electrical connections HART Version Internal ground termination point M+ - 0 2 3 4 7 6 5 9 60 40 20 0 Remote indicator 8 10 80 10 % 0 Kent-Taylor Line load M + 3 4 2 8 1 7 5 6 Harting pin (male) identification + + 250 ohm min GND TEST COMM - 691HT External ground termination point F1 F2 + Test points 4 to 20mA F3 - F4 PV REVIEW - + Power source CONF SERIAL LINK TRIM A B C Hand-held communicator D E F 2 3 M N O P Q R 4 5 6 S T U V W X Y Z # 7 8 9 @ % & / + - 0 Optional G H I 1 J K L Receiver HART hand-held communicator may be connected at any wiring termination point in the loop, providing the minimum resistance is 250 ohm. If this is less than 250 ohm, additional resistance should be added to allow communications FIELDBUS Versions 7/8" connector 1 3 2 4 Internal ground termination point M12 x 1 connector 2 1 3 Fieldbus line (polarity independent) BUS CONNECTIONS 4 PIN (male) IDENTIFICATION FOUNDATION PROFIBUS Fieldbus PA 1 FFPA+ 2 FF+ GROUND 3 SHIELD PA- 4 GROUND SHIELD External ground termination point Mating female plug NOT SUPPLIED 13 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 BASIC ORDERING INFORMATION model 264HS Gauge Pressure Transmitter Select one character or set of characters from each category and specify complete catalog number. Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required. BASE MODEL - 1st to 5th characters 2 6 4 H S X X X X X Gauge Pressure Transmitter - BASE ACCURACY 0.075% SENSOR - Span limits - 6th character 0.65 and 65kPa 6.5 and 650mbar 2.6 and 260inH2O 1.6 and 160kPa 16 and 1600mbar 6.4 and 642inH2O 6 and 600kPa 0.06 and 6bar 0.87 and 87psi 3.5 and 348psi 24 and 2400kPa 0.24 and 24bar 80 and 8000kPa 0.8 and 80bar 11.6 and 1160psi 160 and 16000kPa 1.6 and 160bar 23.2 and 2320psi 600 and 60000 kPa 6 and 600bar 87 and 8700 psi Diaphragm material / Fill fluid (wetted parts) - 7th character AISI 316 L ss Silicone oil Hastelloy C276TM (on AISI seat) Silicone oil Hastelloy C276TM Silicone oil Monel 400TM Silicone oil Tantalum Silicone oil AISI 316 L ss Inert fluid - Galden Hastelloy C276TM (on AISI seat) Inert fluid - Galden Hastelloy C276TM Inert fluid - Galden (Carbon fluoride for sensor V) Monel 400TM Inert fluid - Galden Tantalum Inert fluid - Galden AISI 316 L ss Inert fluid - Halocarbon Hastelloy C276TM (on AISI seat) Inert fluid - Halocarbon Hastelloy C276TM Inert fluid - Halocarbon Monel 400TM Inert fluid - Halocarbon Tantalum Inert fluid - Halocarbon th Process connection material (wetted parts) - 8 character 1 AISI 316 L ss /2in NPT female 1 AISI 316 L ss /2in NPT male DIN EN837-1 G 1/2in B AISI 316 L ss Adapter straight (180 ) entry (not available for bracket) AISI 316 L ss Adapter angle (90 ) entry AISI 316 L ss 1 /2in NPT female Hastelloy C276TM 1 /2in NPT male Hastelloy C276TM DIN EN837-1 G 1/2in B Hastelloy C276TM Adapter straight (180 ) entry (not available for bracket) Hastelloy C276TM Adapter angle (90 ) entry Hastelloy C276TM 1 /2in NPT female Monel 400TM 1 /2in NPT male Monel 400TM DIN EN837-1 G 1/2in B Monel 400TM Housing material and electrical connection - 9th character Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) G H M P Q S V (Note 2) (Note 2) NACE NACE NACE NACE (Note 2) (Note 2) (Notes 1, 2) (Notes 1, 2) (Note 1) (Notes 1, 2) (Notes 1, 2) (Notes 1, 2) (Notes 1, 2) (Notes 1, 2) (Notes 1, 2) (Notes 1, 2) NACE NACE NACE NACE NACE NACE NACE NACE (Note 3) (Note 3) (Note 3) (Notes 2, 3) (Notes 2, 3) (Note 4) (Note 4) (Note 4) (Notes 2, 4) (Notes 2, 4) (Note 5) (Note 5) (Note 5) NACE NACE NACE NACE NACE NACE NACE NACE NACE NACE NACE NACE NACE 1 /2in NPT M20 x 1.5 (CM 20) Pg 13.5 1 /2in GK Harting Han connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM 20) Pg 13.5 1 /2in GK Harting Han connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM20) Pg 13.5 1 /2in GK Fieldbus connector (Note 6) (general purpose only) (Note 6) (general purpose only) (Note 6) (general purpose only) (Note 6) (general purpose only) (Note 6) (general purpose only) S H K M T A B F C D L Q P 4 5 B T P A N E K D F C 3 A B D C E G H L N M P R S T V U Z Output/Additional options - 10th character HART digital communication and 4 to 20mA HART digital communication and 4 to 20mA PROFIBUS PA PROFIBUS PA FOUNDATION Fieldbus FOUNDATION Fieldbus 14 No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") (Notes 7, 8) (Note 7) (Notes 7, 8) (Note 8) (Notes 7, 8) (Note 8) H 1 P 2 F 3 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 ADDITIONAL ORDERING INFORMATION for model 264HS Add one or more 2-digit code(s) after the basic ordering information to select all required options XX XX XX XX XX XX XX XX XX XX XX XX XX XX Drain/vent valve (wetted parts) AISI 316 L ss (Notes 2, 9) NACE VA Hastelloy C276TM (Notes 2, 10) NACE VB Monel 400TM (Notes 2, 11) NACE VC Electrical certification ATEX Group II Category 1 GD - Intrinsic Safety EEx ia ATEX Group II Category 1/2 GD - Flameproof EEx d ATEX Group II Category 3 GD - Type of protection "N" EEx nL design compliance ((Note 12) Canadian Standard Association (CSA) (only 1/2in NPT, M20 and Pg 13.5 housing) Intrinsic Safety-Flameproof to Standards Australia SAA Ex ia IIC T6/T5/T4 + Ex d II C T6/T5 (Note 12) Factory Mutual (FM) approval (only with 1/2in NPT, M20 and Pg 13.5 electrical connection) Output meter ProMeter, Standard calibration ProMeter, Special calibration Analog output indicator linear 0-100% scale Analog output indicator, special graduation (to be specified for linear scale) Programmable signal meter and HART configurator (CoMeter) Programmable signal meter and HART configurator (CoMeter - customer configuration) (Note (Note (Note (Note (Note (Note 12) 12) 12) 12) 12) 12) E1 E2 E3 E4 E5 E6 D1 D2 D3 D5 D7 D8 Integral LCD Digital LCD integral display L1 Mounting bracket (shape and material) For pipe mounting For pipe mounting (Not suitable for AISI housing) Carbon steel AISI 316 L ss B1 B2 Surge Surge/Transient Protector (Note 12) S1 Operating manual German Italian French M1 M2 M4 Labels & tag language German Italian French T1 T2 T4 Additional tag plate Laser printing of tag on stainless steel plate I2 Configuration N2 N3 N4 N5 N6 Standard - Pressure = inH2O/psi at 20 C; Temperature = deg. F Standard - Pressure = inH2O/psi at 4 C; Temperature = deg. F Standard - Pressure = inH2O/psi at 20 C; Temperature = deg.C Standard - Pressure = inH2O/psi at 4 C; Temperature = deg. C Custom Preparation procedure Oxygen service cleaning (only available with inert fill) Pmax = 12MPa for Galden, 9MPa for Halocarbon or 21MPa for Carbon fluoride; Tmax = 60 C/140 F P1 Certificates Inspection certificate EN 10204-3.1.B of calibration (9-point) Certificate of compliance with the order EN 10204-2.1 of instrument design C1 C6 Material traceability Certificate of compliance with the order EN 10204-2.1 of process wetted parts Inspection certificate EN 10204-3.1.B of process wetted parts H1 H3 Connector Fieldbus 7/8 Fieldbus M12x1 Harting Han - straight entry Harting Han - angle entry (RECOMMENDED for FOUNDATION Fieldbus) (RECOMMENDED for PROFIBUS PA) (Notes 8, 13) (Notes 8, 13) (Notes 7, 13) (Notes 7, 13) U1 U2 U3 U4 15 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 Note 1: Suitable for oxygen service Note 2: Not available with Sensor code V Note 3: Not available with Hastelloy C, Monel and Tantalum diaphragm code K, T, F, D, P, M, C, 4, 5 combined with sensor codes G to S Note 4: Not available with AISI 316 L ss, Hastelloy C on AISI seat and Monel diaphragm code S, H, A, B, L, Q, M, C, 4 Note 5: Not available with AISI 316 L ss, Hastelloy C on AISI seat, Hastelloy C and Tantalum diaphragm code S, H, K, T, A, B, F, D, L, Q, P, 5 Note 6: Select type in additional ordering code Note 7: Not available with Electronic Housing code Z, R, G Note 8: Not available with Electronic Housing code P, E Note 9: Not available with Process connection code E, K, D, F, C, 1, 2, 3 Note 10: Not available with Process connection code B, T, A, P, N, 1, 2, 3 Note 11: Not available with Process connection code E, K, D, F, C, B, T, A, P, N Note 12: Not available with PROFIBUS PA and FF output code 2 or 3 Note 13: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B TM Hastelloy is a Cabot Corporation trademark TM Monel is an International Nickel Co. trademark TM Galden is a Montefluos trademark TM Halocarbon is a Halocarbon Products Co. trademark Standard delivery items (can be differently specified by additional ordering code) - No drain/vent valve - General purpose (no electrical certification) - No meter/display, no mounting bracket, no surge protection - English manual and labels - Configuration with kPa and deg. C units - No test, inspection or material traceability certificates THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING. 16 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 BASIC ORDERING INFORMATION model 264NS Absolute Pressure Transmitter Select one character or set of characters from each category and specify complete catalog number. Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required. BASE MODEL - 1st to 5th characters 2 6 4 N S X X X X X Absolute Pressure Transmitter - BASE ACCURACY 0.075% SENSOR - Span limits - 6th character 1.1 and 65kPa 11 and 650mbar 8 and 480mmHg 2.67 and 160kPa 26.7 and 1600mbar 20 and 1200mmHg 10 and 600kPa 0.1 and 6bar 1.45 and 87psi 40 and 2400kPa 0.4 and 24bar 5.8 and 348psi 134 and 8000kPa 1.34 and 80bar 19.4 and 1160psi 267 and 16000kPa 2.67 and 160bar 38.7 and 2320psi Diaphragm material / Fill fluid (wetted parts) - 7th character AISI 316 L ss Silicone oil Hastelloy C276TM (on AISI seat) Silicone oil Hastelloy C276TM Silicone oil AISI 316 L ss Inert fluid - Galden Hastelloy C276TM (on AISI seat) Inert fluid - Galden Hastelloy C276TM Inert fluid - Galden AISI 316 L ss Inert fluid - Halocarbon Hastelloy C276TM (on AISI seat) Inert fluid - Halocarbon Hastelloy C276TM Inert fluid - Halocarbon Process connection material (wetted parts) - 8th character G H M P Q S NACE NACE (Note (Note (Note (Note (Note (Note 1) 1) 1) 1) 1) 1) 1 AISI 316 L ss /2in NPT female 1 AISI 316 L ss /2in NPT male AISI 316 L ss DIN EN837-1 G 1/2in B AISI 316 L ss Adapter straight (180 ) entry (not available for bracket) AISI 316 L ss Adapter angle (90 ) entry 1 Hastelloy C276TM /2in NPT female 1 Hastelloy C276TM /2in NPT male Hastelloy C276TM DIN EN837-1 G 1/2in B Hastelloy C276TM Adapter straight (180 ) entry (not available for bracket) Hastelloy C276TM Adapter angle (90 ) entry Housing material and electrical connection - 9th character Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) Aluminium alloy copper-free (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) NACE NACE NACE NACE (Note (Note (Note (Note (Note (Note (Note (Note (Note (Note 2) 2) 2) 2) 2) 3) 3) 3) 3) 3) NACE NACE NACE NACE NACE NACE NACE NACE NACE NACE 1 /2in NPT M20 x 1.5 (CM 20) Pg 13.5 1 /2in GK Harting Han connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM 20) Pg 13.5 1 /2in GK Harting Han connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM20) Pg 13.5 1 /2in GK Fieldbus connector (Note 4) (general purpose only) (Note 4) (general purpose only) (Note 4) (general purpose only) (Note 4) (general purpose only) (Note 4) (general purpose only) S H K A B F L Q P B T P A N E K D F C A B D C E G H L N M P R S T V U Z Output/Additional options - 10th character HART digital communication and 4 to 20mA HART digital communication and 4 to 20mA PROFIBUS PA PROFIBUS PA FOUNDATION Fieldbus FOUNDATION Fieldbus No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") (Notes 5, 6) (Note 5) (Notes 5, 6) (Note 6) (Notes 5, 6) (Note 6) H 1 P 2 F 3 17 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 ADDITIONAL ORDERING INFORMATION for model 264NS Add one or more 2-digit code(s) after the basic ordering information to select all required options XX XX XX XX XX XX XX XX XX XX XX XX XX XX Drain/vent valve (wetted parts) AISI 316 L ss (Note 7) NACE VA Hastelloy C276TM (Note 8) NACE VB Electrical certification ATEX Group II Category 1 GD - Intrinsic Safety EEx ia ATEX Group II Category 1/2 GD - Flameproof EEx d ATEX Group II Category 3 GD - Type of protection "N" EEx nL design compliance (Note 9) Canadian Standard Association (CSA) (only 1/2in NPT, M20 and Pg 13.5 housing) Intrinsic Safety-Flameproof to Standards Australia SAA Ex ia IIC T6/T5/T4 + Ex d II C T6/T5 (Note 9) Factory Mutual (FM) approval (only with 1/2in NPT, M20 and Pg 13.5 electrical connection) Output meter ProMeter, Standard calibration ProMeter, Special calibration Analog output indicator linear 0-100% scale Analog output indicator, special graduation (to be specified for linear scale) Programmable signal meter and HART configurator (CoMeter) Programmable signal meter and HART configurator (CoMeter - customer configuration) (Note (Note (Note (Note (Note (Note 9) 9) 9) 9) 9) 9) E1 E2 E3 E4 E5 E6 D1 D2 D3 D5 D7 D8 Integral LCD Digital LCD integral display L1 Mounting bracket (shape and material) For pipe mounting For pipe mounting (Not suitable for AISI housing) Carbon steel AISI 316 L ss B1 B2 Surge Surge/Transient Protector (Note 9) S1 Operating manual German Italian French M1 M2 M4 Labels & tag language German Italian French T1 T2 T4 Additional tag plate Laser printing of tag on stainless steel plate I2 Configuration Standard - Pressure = inH2O/psi at 20 C; Temperature = deg. F Standard - Pressure = inH2O/psi at 4 C; Temperature = deg. F Standard - Pressure = inH2O/psi at 20 C; Temperature = deg.C Standard - Pressure = inH2O/psi at 4 C; Temperature = deg. C Custom N2 N3 N4 N5 N6 Preparation procedure Oxygen service cleaning (only available with inert fill) - Pmax =12MPa for Galden or 9MPa for Halocarbon; Tmax =60 C/140 F P1 Certificates Inspection certificate EN 10204-3.1.B of calibration (9-point) Certificate of compliance with the order EN 10204-2.1 of instrument design C1 C6 Material traceability Certificate of compliance with the order EN 10204-2.1 of process wetted parts Inspection certificate EN 10204-3.1.B of process wetted parts H1 H3 Connector Fieldbus 7/8 Fieldbus M12x1 Harting Han - straight entry Harting Han - angle entry 18 (RECOMMENDED for FOUNDATION Fieldbus) (RECOMMENDED for PROFIBUS PA) (Notes 6, 10) (Notes 6, 10) (Notes 5, 10) (Notes 5, 10) U1 U2 U3 U4 2600T Pressure Transmitters Model 264HS, 264NS Note 1: Suitable for oxygen service Note 2: Not available with Hastelloy C diaphragm code K, F, P Note 3: Not available with AISI 316 L ss and Hastelloy C on AISI seat diaphragm code S, H, A, B, L, Q Note 4: Select type in additional ordering code Note 5: Not available with Electronic Housing code Z, R, G Note 6: Not available with Electronic Housing code P, E Note 7: Not available with Process connection code E, K, D, F, C Note 8: Not available with Process connection code B, T, A, P, N Note 9: Not available with PROFIBUS PA and FF output code 2 or 3 SS/264HS/NS_3 Note 10: Not available with Electronic housing code U, S, T, V, H, M, L, N, D, C, A, B TM Hastelloy is a Cabot Corporation trademark TM Galden is a Montefluos trademark TM Halocarbon is a Halocarbon Products Co. trademark Standard delivery items (can be differently specified by additional ordering code) - No drain/vent valve - General purpose (no electrical certification) - No meter/display, no mounting bracket, no surge protection - English manual and labels - Configuration with kPa and deg. C units - No test, inspection or material traceability certificates THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING. 19 2600T Pressure Transmitters Model 264HS, 264NS SS/264HS/NS_3 The Company's policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. ABB has Sales & Customer Support expertise in over 100 countries worldwide (c) ABB 2004 ABB Ltd Howard Road, St. Neots Cambridgeshire, PE19 3EU UK Tel: +44(0)1480 475321 Fax: +44(0)1480 217948 ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB SACE spa Business Unit Instrumentation Via Statale 113 22016 Lenno (CO) Italy Tel: +39 0344 58111 Fax: +39 0344 56278 SS/264HS/NS_3 Printed in Italy (04.04) www.abb.com/instrumentation