___________________ Overview 1 ___________________ Safety instructions SIMATIC system power supply Description, device design, 2 ___________________ dimension drawing 3 ___________________ Mounting/removal SIMATIC ET200SP PS Manual Mounting position, mounting ___________________ 4 clearances ___________________ 5 Installation ___________________ 6 Technical data ___________________ 7 Safety, approvals, EMC ___________________ 8 Environmental conditions ___________________ 9 Applications ___________________ 10 Environment ___________________ 11 Service & Support SIMATIC ET200SP PS 6EP7133-6AB00-0BN0 24 V/5 A SIMATIC ET200SP PS 6EP7133-6AE00-0BN0 24 V/10 A 03.2018 A5E43207434 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by (R) are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NURNBERG GERMANY A5E43207434 03/2018 Subject to change Copyright (c) Siemens AG 2018. All rights reserved Overview The 1-phase ET200SP PS from the SIMATIC ET200SP product line is a powerful regulated system power supply for automated systems and machines. In addition to a high efficiency, these power supply units have an outstanding overload behavior. The key benefits of the product include: 1-phase 120/230 V AC input voltage with automatic switchover function allowing the units to be connected to almost any 1-phase line supply around the world. The output voltage can be adjusted in the range 22.8 - 28 V Brief overload capability of 150% for 5 s/min (extra power) Integrated signaling contact for "24 V O.K." Ambient temperature -30 ... 70 C SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 3 Overview Ordering data The following device options are available: Regulated power supply unit ET200SP PS Type Order number 1-phase 120/230 V AC input, 6EP7133-6AB00-0BN0 24 V/5 A DC output 1-phase 120/230 V AC input, 6EP7133-6AE00-0BN0 24 V/10 A DC output Validity This manual provides information on the following products: SIMATIC ET200SP PS 24 V DC/5 A, SIMATIC ET200SP PS 24 V DC/10 A Article number: 6EP7133-6AB00-0BN0, 6EP7133-6AE00-0BN0 Product state (PS): 1 SIMATIC ET200SP PS 4 Manual, 03.2018, A5E43207434 Table of contents Overview................................................................................................................................................. 3 1 2 Safety instructions ................................................................................................................................... 7 1.1 General safety instructions ....................................................................................................... 7 1.2 Safety instructions for hazardous zones ................................................................................... 7 Description, device design, dimension drawing........................................................................................ 9 2.1 Device description..................................................................................................................... 9 2.2 Connections and terminal designation....................................................................................10 2.3 Potentiometer ..........................................................................................................................11 2.4 Status displays and signaling .................................................................................................12 2.5 Block diagram .........................................................................................................................14 2.6 Dimensions and weight ...........................................................................................................15 3 Mounting/removal ................................................................................................................................. 17 4 Mounting position, mounting clearances ................................................................................................ 19 5 6 4.1 Standard mounting position ....................................................................................................19 4.2 4.2.1 4.2.2 Other mounting positions ........................................................................................................20 6EP7133-6AB00-0BN0 ...........................................................................................................20 6EP7133-6AE00-0BN0 ...........................................................................................................21 Installation ............................................................................................................................................ 23 5.1 Line-side connection ...............................................................................................................23 5.2 Output-side connection ...........................................................................................................25 Technical data ...................................................................................................................................... 27 6.1 Input ........................................................................................................................................27 6.2 Output .....................................................................................................................................29 6.3 Efficiency .................................................................................................................................32 6.4 Closed-loop control .................................................................................................................33 6.5 Protection and monitoring .......................................................................................................33 6.6 MTBF ......................................................................................................................................33 6.7 Mechanical system .................................................................................................................34 6.8 Dimension drawing .................................................................................................................34 SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 5 Table of contents 7 Safety, approvals, EMC ........................................................................................................................ 35 7.1 Safety ..................................................................................................................................... 35 7.2 Test voltage............................................................................................................................ 36 7.3 Approvals ............................................................................................................................... 37 7.4 EMC ....................................................................................................................................... 37 8 Environmental conditions ...................................................................................................................... 39 9 Applications .......................................................................................................................................... 41 9.1 Parallel connection to increase the power rating ................................................................... 41 9.2 Series connection for increased voltage ................................................................................ 43 9.3 Overload protection in the 24 V output circuit ........................................................................ 44 9.4 Protection against short-time voltage dips ............................................................................. 45 9.5 Protecting against longer power failures ................................................................................ 46 10 Environment ......................................................................................................................................... 49 11 Service & Support ................................................................................................................................. 51 SIMATIC ET200SP PS 6 Manual, 03.2018, A5E43207434 Safety instructions 1.1 1 General safety instructions WARNING Correct handling of the devices When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage. Only appropriately qualified personnel may work on or in the vicinity of this equipment. Perfect, safe, and reliable operation of this equipment is dependent on proper transportation, storage, installation and mounting. Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. 1.2 Safety instructions for hazardous zones WARNING OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY! SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 7 Safety instructions 1.2 Safety instructions for hazardous zones SIMATIC ET200SP PS 8 Manual, 03.2018, A5E43207434 Description, device design, dimension drawing 2.1 2 Device description The SIMATIC ET200SP PS is a primary-clocked power supply for connection to a 1-phase AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LED display indicates the operating status. The current monitoring terminal is used to sense the output current. The operating state of the device can be processed via the signaling contact. AC input DC output Current monitoring terminals IMonitor (1 V Iout rated) Signaling contact (13, 14) Potentiometer 22.8 - 28 V ON/OFF switch Indicator light (24 V O.K.) Button to manually release Convection Clearance above/below Figure 2-1 Design SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 9 Description, device design, dimension drawing 2.2 Connections and terminal designation 2.2 Connections and terminal designation The line input terminals can be used to establish the connection to supply voltage. The output terminals are used to connect to the loads to be supplied (see also Section Installation (Page 23)). The output current can be sensed via current monitoring terminal . The operating state of the device can be processed via the signaling contact (function and contact rating, see Chapter Status displays and signaling (Page 12)). Connections and terminal designations Line input L1, N, PE One spring-loaded terminal each Output + 3 spring-loaded terminals Output - 3 spring-loaded terminals Current monitoring terminals One spring-loaded terminal each Signaling contact 13, 14 One spring-loaded terminal each *1) Do not subject the end stop to higher loads Figure 2-2 Terminal data SIMATIC ET200SP PS 10 Manual, 03.2018, A5E43207434 Description, device design, dimension drawing 2.3 Potentiometer 2.3 Potentiometer The potentiometer on the front of the device is used to set the output voltage. The output voltage is set to the rated value at the factory and can be set within certain limits; for example, to compensate voltage drops across long supply lines to the connected load. Figure 2-3 Potentiometer Type Factory setting Adjustment range 6EP7133-6AB00-0BN0 24 V 22.8 - 28 V 6EP7133-6AE00-0BN0 NOTICE Thermal overload possible When adjusting the output voltage to greater than the rated voltage, the output current must be derated by 4 %/V, or the permissible ambient temperature must be taken into account with 3 C/V. Note It is only permissible to use an insulated screwdriver when actuating the potentiometer. For information on actuating the potentiometer (screwdriver, torque), see Figure 2-2 Terminal data (Page 10). SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 11 Description, device design, dimension drawing 2.4 Status displays and signaling 2.4 Status displays and signaling 6EP7133-6AB00-0BN0 (24 /5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Status display LED green for 24 V O.K. Signaling contact (13,14) Contact rating (isolated): 30 V AC/0.5 A, 60 V DC/0.3 A, 30 V DC/1 A) for 24 V O.K. Current monitoring terminals Voltage proportional to the output current: ~ 1 V Iout rated 50 mV Table 2- 1 IMonitor conversion table 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Output current [A] IMonitor [V] Output current [A] IMonitor [V] 0.0 0.0 0.0 0.0 0.5 0.1 1.0 0.1 1.0 0.2 2.0 0.2 1.5 0.3 3.0 0.3 2.0 0.4 4.0 0.4 2.5 0.5 5.0 0.5 3.0 0.6 6.0 0.6 3.5 0.7 7.0 0.7 4.0 0.8 8.0 0.8 4.5 0.9 9.0 0.9 5.0 1.0 10 1.0 Figure 2-4 Operating displays and signaling SIMATIC ET200SP PS 12 Manual, 03.2018, A5E43207434 Description, device design, dimension drawing 2.4 Status displays and signaling Signaling 6EP7133-6AB00-0BN0 (24 /5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) LED lights up green Normal operation, output voltage > 20 V 0.5 V Signaling contact , contact 13-14 closed LED off Overload operation or power supply voltage missing Signaling contact , contacts 13-14 open (quiescent position) SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 13 Description, device design, dimension drawing 2.5 Block diagram 2.5 Figure 2-5 Block diagram Block diagram SIMATIC ET200SP PS 14 Manual, 03.2018, A5E43207434 Description, device design, dimension drawing 2.6 Dimensions and weight 2.6 Dimensions and weight Figure 2-6 Dimensions and weight 6EP7133-6AB00-BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Dimensions (W x H x D) in mm 160 x 117 x 66.5 160 x 117 x 66.5 Weight Approx. 0.5 kg Approx. 0.72 kg SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 15 Description, device design, dimension drawing 2.6 Dimensions and weight SIMATIC ET200SP PS 16 Manual, 03.2018, A5E43207434 Mounting/removal 3 WARNING Installing the device in a housing or a control cabinet SIMATIC ET200SP PS power supplies are built-in devices. They must be installed in a housing or control cabinet where only qualified personnel have access. The device can be mounted in a control cabinet on standard mounting rails (see Chapter Mechanical system (Page 34)) Mounting To mount the device, position it with the mounting rail guide at the upper edge of the standard mounting rail and press down to lock it into place. If it is difficult to snap the device into place, press the button at the same time, as described under "Removal". Removal To remove, press button (see Removal diagram (Page 17)) by hand downwards - and withdraw the device at the lower edge of the standard mounting rail. Then you can remove the device from the upper edge of the standard mounting rail. Figure 3-1 Removal SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 17 Mounting/removal WARNING Use in hazardous zones If the device is to be used in a hazardous zone (Ex II 3G Ex nA nC IIC T4 Gc) it must be installed in a distributor box with degree of protection IP54 or higher. SIMATIC ET200SP PS 18 Manual, 03.2018, A5E43207434 Mounting position, mounting clearances 4.1 4 Standard mounting position The device is mounted on standard mounting rails according to EN 60715 35x7,5/15. The device must be mounted vertically in such a way that the terminals are at the bottom. A clearance of at least 50 mm should be maintained above and below the device (maximum depth of the cable duct, 50 mm). No space is required at the side. Output current as a function of the ambient temperature and mounting height Figure 4-1 6EP7133-6AB00-0BN0: Output current in the standard mounting position Figure 4-2 6EP7133-6AE00-0BN0: Output current in the standard mounting position SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 19 Mounting position, mounting clearances 4.2 Other mounting positions 4.2 Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Note In the case of mounting positions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected. Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. 4.2.1 6EP7133-6AB00-0BN0 Figure 4-3 Mounting position (2) Note Other mounting positions are not permissible! SIMATIC ET200SP PS 20 Manual, 03.2018, A5E43207434 Mounting position, mounting clearances 4.2 Other mounting positions 4.2.2 6EP7133-6AE00-0BN0 Figure 4-4 Mounting position (2) Note Other mounting positions are not permissible! SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 21 Mounting position, mounting clearances 4.2 Other mounting positions SIMATIC ET200SP PS 22 Manual, 03.2018, A5E43207434 5 Installation WARNING Hazard due to electric shock Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. 5.1 Line-side connection SIMATIC ET200SP PS power supplies are designed for connection to a 1-phase AC line supply (TN or TT system according to IEC 60364-1) with a rated voltage of 120/230 V AC, 50/60 Hz. Figure 5-1 Line supply connection The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line supply connection (Page 23)), and must be implemented according to IEC 60364 . A protective device (miniature circuit-breaker or circuit-breaker) and a disconnection unit for the power supply must be provided. A ground-fault circuit interrupter is not permissible against indirect contact as the only protective measure. This is true for the complete line supply protected by the ground-fault circuit interrupter. SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 23 Installation 5.1 Line-side connection Protection SIMATIC ET200SP PS Recommended line-side protection 6EP7133-6AB00-0BN0 Miniature circuit breaker (IEC 898) characteristic B, 6 A and C, 3 A 6EP7133-6AE00-0BN0 Miniature circuit breaker (IEC 898) characteristic B, 10 A and C, 6 A The protective conductor of the line supply must be connected at the PE terminal. NOTICE Country-specific regulations must be observed when installing. SIMATIC ET200SP PS 24 Manual, 03.2018, A5E43207434 Installation 5.2 Output-side connection 5.2 Output-side connection SIMATIC ET200SP PS power supplies provide an isolated (= non-grounded) SELV output voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload, and short-circuit proof. If an overload occurs, the electronic current limitation limits the output current to a maximum value (refer to chapter Technical data (Page 27)). Figure 5-2 Connecting the output voltage The output voltage is connected via the + and - terminals at the output of the power supply (see Figure Connecting the output voltage (Page 25)). Ensure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly. Note If the safety concept of the plant or system specifies that the DC output circuit should be grounded (PELV), then it is permissible that the output voltage of the SIMATIC power supply is grounded. In this case, ideally, the grounding at the output should be directly connected from terminal "-" of the power supply to a suitable connection point of the protective conductor system (PE) of the plant or system. SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 25 Installation 5.2 Output-side connection SIMATIC ET200SP PS 26 Manual, 03.2018, A5E43207434 6 Technical data Note Technical data apply for a rated input voltage, rated load and 25 C ambient temperature if nothing else is specified. 6.1 Input 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Input 1-phase, AC 1-phase, AC Rated voltage Uin rated 120 - 230 V 120 - 230 V Voltage range 85 - 132/170 - 264 V * Comment Derating at 60 C: 85 V AC and 170 V AC: 90 % Pout rated 100 V AC and 200 V AC: 100 % Pout rated between 85 V AC and 100 V AC, 170 V AC and 200 V AC linear interpolation automatic range switchover Yes Yes Connect/shutdown threshold, typical 68 V/59 V or 140 V/135 V 67 V/61 V or 142 V/137 V Line supply buffering at Iout rated, min 20 ms 20 ms Power-failure buffering at 93/187 V at 93/187 V Rated line frequency 50 - 60 Hz 50 - 60 Hz Line frequency range 47 - 63 Hz 47 - 63 Hz Input current at rated input voltage 120 V 2.1 A 4.3 A Input current at rated input voltage 230 V 1.2 A 1.9 A Inrush current limiting (25 C), max. 45 A 60 A I2t, A2s at AC 120 V, max. 1 5.6 A2s I2t, at AC 230 V, max. 3.15 A2s 6.3 A2s Integrated input fuse Fuse T 3.15 A Fuse T 6 A Protection in the line feeder cable (IEC 898) Recommended: Miniature circuit breaker, characteristic B, 6 A or C, 3 A Recommended: Miniature circuit breaker, characteristic B, 10 A or C, 6 A SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 27 Technical data 6.1 Input Figure 6-1 Power-failure buffering SIMATIC ET200SP PS 28 Manual, 03.2018, A5E43207434 Technical data 6.2 Output 6.2 Output 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Output Regulated, isolated DC voltage Regulated, isolated DC voltage Rated voltage Uout rated DC 24 V 24 V Total tolerance, static 3% 3% Static line regulation, approx. 0.1 % 0.5 % Static load regulation, approx. 1% 1% Residual ripple Peak-peak, max. 150 mV 150 mV Spikes peak-peak, max. (bandwidth, 200 MHz) 240 mV 240 mV Adjustment range 22.8 - 28.0 V 22.8 - 28.0 V Product function - output voltage can be adjusted Yes Yes Output voltage setting Using a potentiometer Via potentiometer Max. 120 W Max. 240 W Status display LED green for 24 V O.K. LED green for 24 V O.K. Signaling Contact rating (isolated): 30 V AC/0.5 A, 60 V DC/0.3 A, 30 V DC/1 A) for 24 V O.K. Response when switching on/off Overshoot of Uout < 720 mV Overshoot of Uout < 720 mV Starting delay, max. 300 ms 300 ms Start delay, typ. 150 ms 150 ms Voltage rise 200 ms 200 ms 30 ms 30 ms * Remark 120 V/230 V AC max. Voltage rise 120 V/230 V AC typ. Rated current Iout rated 5A 10 A Current range 0-5A 0 - 10 A 60 ... 70 C derating: 3 % Iout rated/K 60 ... 70 C derating: 3 % Iout rated/K Active power output, typ. 120 W 240 W Overload capability (Extra Power) 7.5 A for 5 s/min 15 A for 5 s/min Short-time overload current for a short circuit when powering up 15 A 30 A * Remark Duration of the overload capability 100 ms for an overcurrent condition caused by a short circuit while powering up. once-only * Remark 100 ms Short-time overload current for a short circuit in operation, typ. 30 A 15 A once-only SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 29 Technical data 6.2 Output 6EP7133-6AB00-0BN0 (24 V/5 A) Duration of the overload capability 100 ms for an overcurrent condition caused by a short circuit in operation. 6EP7133-6AE00-0BN0 (24 V/10 A) 100 ms once-only once-only Can be connected in parallel to increase the power rating Yes Yes Number of devices that can be connected in parallel to increase the power rating, units 2 2 Output characteristic see Figure 6-3 Output characteristic 6EP7133-6AB00-0BN0 (Page 30) see Figure 6-4 Output characteristic 6EP7133-6AE00-0BN0 (Page 31) Capacitive load, max. 2 mF/A 2 mF/A * Remark Figure 6-2 Startup delay/voltage rise Figure 6-3 Output characteristic 6EP7133-6AB00-0BN0 SIMATIC ET200SP PS 30 Manual, 03.2018, A5E43207434 Technical data 6.2 Output Figure 6-4 Output characteristic 6EP7133-6AE00-0BN0 The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 31 Technical data 6.3 Efficiency 6.3 Efficiency Efficiency at Uout rated, Iout rated 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) 87 %/88 % 89.5 %/90 % 17 W/15 W 27 W/26 W 3 W/2.7 W 3.2 W/2.8 W 120 V/230 V AC approx. Power loss at Uout rated, Iout rated 120 V/230 V AC approx. Power loss when idling 120 V/230 V AC approx. Figure 6-5 Efficiency, 6EP7133-6AB00-0BN0 Figure 6-6 Efficiency, 6EP7133-6AE00-0BN0 SIMATIC ET200SP PS 32 Manual, 03.2018, A5E43207434 Technical data 6.4 Closed-loop control 6.4 Closed-loop control Dyn. line regulation 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) 0.3 % 0.3 % 5% 5% 3% 3% 1 ms 1 ms 1 ms 1 ms 1 ms 1 ms 1 ms 1 ms (Uin rated 15 %), max. Dyn. load regulation (Iout: 10/90/10 %), Uout max. Dyn. load regulation (Iout: 10/90/10 %), Uout typ. Load-step settling time 10 to 90 %, max. Load-step settling time 10 to 90 %, typ. Load-step settling time 90 to 10 %, max. Load-step settling time 90 to 10 %, typ. 6.5 Protection and monitoring 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Output overvoltage protection in the case of an internal fault Uout < 31.8 V in the case of an internal fault Uout < 31.8 V Current limitation, typ. 7.5 A 15 A Overload capability with 150 % Iout rated up to 5 s/min Overload capability with 150 % Iout rated up to 5 s/min Short-circuit protection Yes, current is statically limited Yes, current is statically limited Continuous short-circuit current rms value, approx. 7A 14.1 A * Remark 6.6 MTBF 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Mean Time Between Failures SN29500: > 1000000 h at 40 C, rated load, 24 h operation SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 33 Technical data 6.7 Mechanical system 6.7 Mechanical system 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Connection system Spring-loaded terminal Spring-loaded terminal Connections: Line input L, N, PE: 1 push-in terminal each for 0.2 - 2.5 mm solid (finely stranded) Connections: Output +, -: 3 spring-loaded terminals each for 0.2 - 2.5 mm Connections: Auxiliary contacts Signaling contact: 1 spring-loaded terminals each for 0.2 - 2.5 mm Current monitoring terminals: 1 spring-loaded terminals each for 0.2 - 2.5 mm Width of the housing 160 mm 160 mm Height of the housing 117 mm 117 mm Depth of the housing 66.5 mm 66.5 mm Installation width 160 mm 160 mm Mounting height 217 mm 217 mm Weight, approx. 0.5 kg 0.72 kg Product feature of the housing: housing that can be lined up next to one another Yes Yes Type of mounting: Wall/panel mounting No No Type of mounting: Rail mounting Yes Yes Type of mounting: S7-300 rail mounting No No Mounting Can be snapped onto standard TH35 15/7,5 mounting rails (EN 60715) 6.8 Dimension drawing See chapter Dimensions and weight (Page 15) CAD data that can be downloaded from the Internet: 6EP7133-6AB00-0BN0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01416) 6EP7133-6AE00-0BN0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01419) SIMATIC ET200SP PS 34 Manual, 03.2018, A5E43207434 Safety, approvals, EMC 7.1 7 Safety 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Primary/secondary galvanic isolation Galvanic isolation Yes SELV output voltage Uout acc. to EN 60950-1 Transformer according to EN 61558-2-16 Protection class Class I Degree of protection (EN 60529) IP20 Leakage current, typ. 1 mA Leakage current, max. 3.5 mA Test voltage See Table 7-1 Test voltage for 6EP7133-6AB00-0BN0 and 6EP7133-6AE00-0BN0 (Page 36) SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 35 Safety, approvals, EMC 7.2 Test voltage 7.2 Test voltage Figure 7-1 Test voltage diagram Only the manufacturer can perform the type test and production test; users can also perform the field test. Preconditions for performing the field test: Tests (A) & (B) Connect the input terminals with one another (L, N) Connect the output terminals, signaling contact, IMonitor and PE with one another Test (C) Connect the output terminals, signaling contact and current monitoring terminal with one another and measure with respect to PE Table 7- 1 Test voltage for 6EP7133-6AB00-0BN0 and 6EP7133-6AE00-0BN0 Type test Production test Field test Test time Prim sec (A) Prim PE (B) Sec PE (C) 60 s 4200 V DC 2200 V DC 700 V DC 60 s 3000 V AC 1500 V AC 500 V AC 1s 2200 V DC 2200 V DC 500 V DC 1s 1500 V AC 1500 V AC 350 V AC 1s 2200 V DC 2200 V DC 500 V DC 1s 1500 V AC 1500 V AC 350 V AC Remark: Tripping current for DC measurement: 0 mA Tripping current for AC measurement: < 100 mA SIMATIC ET200SP PS 36 Manual, 03.2018, A5E43207434 Safety, approvals, EMC 7.3 Approvals 7.3 Approvals 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) CE marking yes, (2014/35/EU, 2014/30/EU and 2011/65/EU) CSA approval yes, CSA C22.2 No. 60950-1, being prepared UL/cUL approval cULus-listed (UL 508, CSA 22.2 No. 107.1), File E197259 Explosion protection UL/cUL: ANSI/ISA-12.12.01-2015 Class I, Div. 2, Group ABCD, T4 CB approval Yes CB-Scheme IEC 60950-1 7.4 EMC 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Electrostatic discharge EN 61000-4-2 8 kV contact, 8 kV air Electromagnetic fields EN 61000-4-3 2400 - 2700 MHz 10 V/m Fast transient disturbance variables (burst) EN 61000-4-4 4 kV at line connections Surge voltages EN 61000-4-5 2 kV at DC output 2 kV symmetrical at the line connections 4 kV asymmetrical at the line connections 500 V symmetrical/asymmetrical on DC output cables High-frequency fields EN 61000-4-6 10 V; 0.15 - 80 MHz Magnetic fields EN 61000-4-8 30 A/m; 50 Hz Voltage dips EN 61000-4-11 100% for 20 ms, 60% for 200 ms, 30% for 500 ms Voltage interruptions EN 61000-4-11 100% for 5000 ms Emitted interference EN 55022 Class B Line harmonics limitation EN 61000-3-2 Class A Generic standards EN 61000-6-2 Immunity for industrial environments EN 61000-6-3 Emission for residential areas SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 37 Safety, approvals, EMC 7.4 EMC SIMATIC ET200SP PS 38 Manual, 03.2018, A5E43207434 Environmental conditions 8 6EP7133-6AB00-0BN0 (24 V/5 A) 6EP7133-6AE00-0BN0 (24 V/10 A) Ambient temperature * Remark -30 ... 70 C for natural convection (self convection) Derating at 60 C: 85 V AC and 170 V AC: 90 % Pout rated 100 V AC and 200 V AC: 100 % Pout rated between 85 V AC and 100 V AC, 170 V AC and 200 V AC linear interpolation at > 60 C: Additionally, 3 % Iout rated /K Tested according to: Transport and storage temperature * EN 60068-2-1 cold * EN 60068-2-2 dry heat * EN 60068-2-78 humid heat, constant * EN 60068-2-14 temperature change -40 ... 70 C Tests (packed for shipping) according to: * EN 60068-2-1 cold * EN 60068-2-2 dry heat * EN 60068-2-30 humid heat, cyclic Humidity class Climatic class 3K3 acc. to EN 60721, 5 - 95 % without condensation Mechanical stressing during operation Tested according to: * EN 60068-2-6, test FC 3.5 mm deflection in the range of 5 - 8.4 Hz 2 g acceleration in the range of 8.4 - 150 Hz * Damaging gases Atmospheric pressure EN 60068-2-27 shock, test Ea: acceleration 150 m/s2, test duration 11 ms Tested according to: * EN 60068-2-42 sulfur dioxide * EN 60068-2-43 hydrogen sulfide Operation: * 1080 - 795 hPa (-1000 - 2000 m) Overvoltage category: II to 2000 m (EN 60950-1) Storage: * * 1080 - 660 hPa (-1000 - 3500 m) SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 39 Environmental conditions SIMATIC ET200SP PS 40 Manual, 03.2018, A5E43207434 9 Applications 9.1 Parallel connection to increase the power rating To increase the power rating, power supplies of the same type can be directly connected in parallel. The following must be observed: The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external connection point (terminal strip) if possible. The power supplies connected in parallel must be switched on simultaneously with a common switch in the line feeder cable (e.g. with the main switch available in control cabinets). The output voltages measured in no-load operation for the power supplies that are not yet connected in parallel should not deviate more than a maximum of 50 mV. This usually corresponds to the factory setting. If the output voltage is changed, you should connect the "-" terminals and then, in no-load operation, measure the voltage difference between the "+" terminals that have not yet been connected. The voltage difference should not exceed 50 mV. Figure 9-1 Parallel connection correct - incorrect Note It is not permissible to take into account simultaneous overload capability (Extra-Power 150% for 5 s/min) of several power supplies connected in parallel when configuring the power supply system. SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 41 Applications 9.1 Parallel connection to increase the power rating NOTICE Protective circuit for the parallel connection of more than two power supplies When connecting more than two power supplies in parallel, additional measures must be taken to prevent high reverse currents in the event of a secondary device fault. For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point. SIMATIC ET200SP PS 42 Manual, 03.2018, A5E43207434 Applications 9.2 Series connection for increased voltage 9.2 Series connection for increased voltage To achieve an output voltage of 48 V DC, two 24 V SIMATIC power supplies of the same type can be connected in series. Note For additional details, see Catalog KT 10.1 Chapter 15 Technical information and configuring (see (http://w3app.siemens.com/mcms/infocenter/content/en/Pages/order_form.aspx?nodeKey=k ey_518431&infotype=catalogs)). WARNING SELV is not guaranteed in the case of a fault When connecting two power supplies in series, the continuous, permissible SELV voltage of a maximum of 60 VDC according to EN 60950-1 cannot be guaranteed in the case of a fault. Figure 9-2 Series connection SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 43 Applications 9.3 Overload protection in the 24 V output circuit 9.3 Overload protection in the 24 V output circuit If an overload occurs, the electronic current limiting function of the 24 V power supply limits the output current to a maximum value (see Section Technical data (Page 27)). The output cables are protected against a thermal overload if they are dimensioned corresponding to the maximum rms output current, or protected using additional components (for example, miniature circuit breaker, fuses). However, a load circuit that fails as a result of overload, for instance, should frequently be reliably and quickly identified and specifically switched off before the power supply goes into current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for all of the remaining 24 V loads). The SITOP PSE200U selectivity module with 4 outputs (versions with adjustable output current range for each output from 0.5 - 3 A and 3 - 10 A) is available for this purpose; this monitors the 24 V branches for overload and short circuit (Figure 9-3 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module (Page 44)). Brief current peaks, e.g. as a result of a high inrush current, are permitted, and branches with a longer overload are switched into a no-current condition. This is also ensured for cables in a high-ohmic condition and for short circuits that slowly develop over time. When an output fails, the fault is signaled using a group signal contact or as a single channel signal, and the branch of the module involved is displayed using an LED. For variants with single-channel signaling, function blocks for evaluation purposes are available for SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no charge. You can find additional information at: Manual SITOP selectivity modules (https://support.industry.siemens.com/cs/ww/en/view/108989004) Figure 9-3 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module SIMATIC ET200SP PS 44 Manual, 03.2018, A5E43207434 Applications 9.4 Protection against short-time voltage dips 9.4 Protection against short-time voltage dips For a drop in the line-side supply voltage, the 24 V power supply still maintains the output voltage for a short time in the millisecond range (see Chapter Technical data (Page 27)). For line supplies that manifest frequent brief voltage dips, in order to increase the power supply reliability, it may make sense to increase the line buffering time in the device using an additional SITOP PSE201U buffer module. The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in parallel to the power supply output (Figure 9-4 Buffering brief power failures using the SITOP PSE201U buffer module (Page 45)). The buffer time is 200 ms at 40 A up to 1.6 s for a load current of 5 A. This time can be increased a multiple number of times by connecting buffer modules in parallel; the maximum buffer time is 10 s. You can find additional information at: SITOP PSE201U manual Figure 9-4 Buffering brief power failures using the SITOP PSE201U buffer module SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 45 Applications 9.5 Protecting against longer power failures 9.5 Protecting against longer power failures Sudden and longer failures of the line supply voltage can result in undefined states and significant danger as a result of the associated failure of the plant or system control. The SITOP power supply product portfolio includes various DC-UPS solutions to prevent the failure of the 24 V power supply voltage. Power supply failures up into the minutes range can be buffered using the maintenance-free SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-5 24 V buffering to allow the saving of process data and controlled shutdown of PCs (Page 46)). Figure 9-5 24 V buffering to allow the saving of process data and controlled shutdown of PCs Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply integrated into PC-based automation solutions. This supports further processing of the status signals and safely running down the PC. You can find additional information at: Manual, DC UPS with capacitors (https://support.industry.siemens.com/cs/ww/en/ps/18042/man) Using DC UPS SITOP UPS1600 and SITOP UPS1100 battery modules, buffer times in the range of hours can be implemented. Intelligent battery management using Energy Storage Link automatically detects the UPS1100 energy storage device, and ensures optimum temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly integrated into the widest range of automation applications with its digital inputs/outputs as well as optional USB interface or Ethernet/PROFINET port. SIMATIC ET200SP PS 46 Manual, 03.2018, A5E43207434 Applications 9.5 Protecting against longer power failures Figure 9-6 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions, sensor measured values and position values For open, PC-based automation systems, configuration and monitoring is realized using the SITOP UPS Manager PC software, which is available at no charge. This allows PC responses to the operating states of the DC UPS to be freely selected - and offers comprehensive diagnostic functions. For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal. Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 - available at no charge - make it easy to integrate operating and diagnostics information into STEP 7 user programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no charge. You can find additional information at: DC UPS SITOP UPS1600/UPS1100 Manual (https://support.industry.siemens.com/cs/ww/en/view/84977415) SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 47 Applications 9.5 Protecting against longer power failures SIMATIC ET200SP PS 48 Manual, 03.2018, A5E43207434 Environment 10 The devices are in conformance with RoHS. As a rule, only non-silicon precipitating materials are used. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 49 Environment SIMATIC ET200SP PS 50 Manual, 03.2018, A5E43207434 Service & Support 11 Technical support Technical support for all IA/DT products can be accessed through the following communication channels: Telephone: + 49 (0) 911 895 7222 Internet: Web form for support request (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.com/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP home page: SITOP (http://www.siemens.com/sitop) Information material SITOP information can be downloaded from the Internet: Information and download center (http://www.siemens.com/sitop-infomaterial) CAx data 2D/3D data and circuit diagram macros can be downloaded from the Internet: Siemens image database (http://www.siemens.com/sitop-cax) Request all CAx data via the CAx download manager: CAx shopping cart (http://www.siemens.com/cax) SITOP Selection Tool Simply and quickly select the optimum the power supply or DC-UPS: SITOP Selection Tool (http://www.siemens.com/sitop-selection-tool) Online catalog and ordering system The online catalog and the online ordering system are available through the Industry Mall homepage: Industry Mall (http://www.siemens.com/industrymall/de) SIMATIC ET200SP PS Manual, 03.2018, A5E43207434 51 Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: On the Internet (http://www.automation.siemens.com/partner) Industry Mall (http://www.siemens.com/industrymall/de) SIMATIC ET200SP PS 52 Manual, 03.2018, A5E43207434