SIMATIC system power supply
SIMATIC ET200SP PS
Manual
SIMATIC ET200SP PS
6EP7133
-6AB00-0BN0 24 V/5 A
SIMATIC ET200SP PS
6EP7133
-6AE00-0BN0 24 V/10 A
03.2018
A5E43207434
Overview
Safety instructions
1
Description, device design,
dimension drawing
2
Mounting/removal
3
Mounting position, mounting
clearances
4
Installation
5
Technical data
6
Safety, approvals, EMC
7
Environmental conditions
8
Applications
9
Environment
10
Service & Support
11
A5E43207434
03/2018 Subject to change
Copyright © Siemens AG 2018.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 3
Overview
The 1-phase ET200SP PS from the SIMATIC ET200SP product line is a powerful regulated
system power supply for automated systems and machines. In addition to a high efficiency,
these power supply units have an outstanding overload behavior.
The key benefits of the product include:
1-phase 120/230 V AC input voltage with automatic switchover function allowing the units
to be connected to almost any 1-phase line supply around the world.
The output voltage can be adjusted in the range 22.8 - 28 V
Brief overload capability of 150% for 5 s/min (extra power)
Integrated signaling contact for "24 V O.K."
Ambient temperature -30 ... 70 °C
Overview
SIMATIC ET200SP PS
4 Manual, 03.2018, A5E43207434
Ordering data
The following device options are available:
Regulated power supply unit ET200SP PS
Type
Order number
1-phase 120/230 V AC input,
24 V/5 A DC output
6EP7133-6AB00-0BN0
1-phase 120/230 V AC input,
24 V/10 A DC output
6EP7133-6AE00-0BN0
Validity
This manual provides information on the following products:
SIMATIC ET200SP PS 24 V DC/5 A, SIMATIC ET200SP PS 24 V DC/10 A
Article number: 6EP7133-6AB00-0BN0, 6EP7133-6AE00-0BN0
Product state (PS): 1
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 5
Table of contents
Overview................................................................................................................................................. 3
1 Safety instructions ................................................................................................................................... 7
1.1 General safety instructions ....................................................................................................... 7
1.2 Safety instructions for hazardous zones ................................................................................... 7
2 Description, device design, dimension drawing........................................................................................ 9
2.1 Device description ..................................................................................................................... 9
2.2 Connections and terminal designation.................................................................................... 10
2.3 Potentiometer .......................................................................................................................... 11
2.4 Status displays and signaling ................................................................................................. 12
2.5 Block diagram ......................................................................................................................... 14
2.6 Dimensions and weight ........................................................................................................... 15
3 Mounting/removal ................................................................................................................................. 17
4 Mounting position, mounting clearances ................................................................................................ 19
4.1 Standard mounting position .................................................................................................... 19
4.2 Other mounting positions ........................................................................................................ 20
4.2.1 6EP7133-6AB00-0BN0 ........................................................................................................... 20
4.2.2 6EP7133-6AE00-0BN0 ........................................................................................................... 21
5 Installation ............................................................................................................................................ 23
5.1 Line-side connection ............................................................................................................... 23
5.2 Output-side connection ........................................................................................................... 25
6 Technical data ...................................................................................................................................... 27
6.1 Input ........................................................................................................................................ 27
6.2 Output ..................................................................................................................................... 29
6.3 Efficiency ................................................................................................................................. 32
6.4 Closed-loop control ................................................................................................................. 33
6.5 Protection and monitoring ....................................................................................................... 33
6.6 MTBF ...................................................................................................................................... 33
6.7 Mechanical system ................................................................................................................. 34
6.8 Dimension drawing ................................................................................................................. 34
Table of contents
SIMATIC ET200SP PS
6 Manual, 03.2018, A5E43207434
7 Safety, approvals, EMC ........................................................................................................................ 35
7.1 Safety ..................................................................................................................................... 35
7.2 Test voltage ............................................................................................................................ 36
7.3 Approvals ............................................................................................................................... 37
7.4 EMC ....................................................................................................................................... 37
8 Environmental conditions ...................................................................................................................... 39
9 Applications .......................................................................................................................................... 41
9.1 Parallel connection to increase the power rating ................................................................... 41
9.2 Series connection for increased voltage ................................................................................ 43
9.3 Overload protection in the 24 V output circuit ........................................................................ 44
9.4 Protection against short-time voltage dips ............................................................................. 45
9.5 Protecting against longer power failures ................................................................................ 46
10 Environment ......................................................................................................................................... 49
11 Service & Support ................................................................................................................................. 51
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 7
Safety instructions
1
1.1
General safety instructions
WARNING
Correct handling of the devices
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
1.2
Safety instructions for hazardous zones
WARNING
OPERATE POTENTIOMETERS OR SWITCHES IN NON-HAZARDOUS AREAS ONLY!
Safety instructions
1.2 Safety instructions for hazardous zones
SIMATIC ET200SP PS
8 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 9
Description, device design, dimension drawing
2
2.1
Device description
The SIMATIC ET200SP PS is a primary-clocked power supply for connection to a 1-phase
AC line supply. An electronically regulated DC voltage that can be set via a potentiometer is
available at the output of the device. The output of the device is isolated, no-load proof and
short-circuit proof. The LED display indicates the operating status. The current monitoring
terminal is used to sense the output current. The operating state of the device can be
processed via the signaling contact.
AC input
DC output
Current monitoring terminals IMonitor (1 V ≙ Iout rated)
Signaling contact (13, 14)
Potentiometer 22.8 28 V
ON/OFF switch
Indicator light (24 V O.K.)
Button to manually release
Convection
Clearance above/below
Figure 2-1 Design
Description, device design, dimension drawing
2.2 Connections and terminal designation
SIMATIC ET200SP PS
10 Manual, 03.2018, A5E43207434
2.2
Connections and terminal designation
The line input terminals can be used to establish the connection to supply voltage.
The output terminals are used to connect to the loads to be supplied (see also Section
Installation (Page 23)).
The output current can be sensed via current monitoring terminal . The operating state of
the device can be processed via the signaling contact (function and contact rating, see
Chapter Status displays and signaling (Page 12)).
Connections and terminal designations
Line input L1, N, PE One spring-loaded terminal each
Output + 3 spring-loaded terminals
Output 3 spring-loaded terminals
Current monitoring terminals One spring-loaded terminal each
Signaling contact 13, 14 One spring-loaded terminal each
*1)
Do not subject the end stop to higher loads
Figure 2-2 Terminal data
Description, device design, dimension drawing
2.3 Potentiometer
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 11
2.3
Potentiometer
The potentiometer on the front of the device is used to set the output voltage.
The output voltage is set to the rated value at the factory and can be set within certain limits;
for example, to compensate voltage drops across long supply lines to the connected load.
Figure 2-3 Potentiometer
Type
Factory setting
Adjustment range
6EP7133-6AB00-0BN0
6EP7133-6AE00-0BN0
24 V 22.8 - 28 V
NOTICE
Thermal overload possible
When adjusting the output voltage to greater than the rated voltage, the output current must
be derated by 4 %/V, or the permissible ambient temperature must be taken into account
with 3° C/V.
Note
It is only permissible to use an insulated
screwdriver when actuating the potentiometer.
For information on actuating the potentiometer (screwdriver, torque), see Figure 2-2
Terminal data (Page 10).
Description, device design, dimension drawing
2.4 Status displays and signaling
SIMATIC ET200SP PS
12 Manual, 03.2018, A5E43207434
2.4
Status displays and signaling
6EP7133-6AB00-0BN0 (24 /5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Status display
LED green for 24 V O.K.
Signaling contact (13,14)
Contact rating (isolated): 30 V AC/0.5 A, 60 V DC/0.3 A, 30 V DC/1 A) for 24 V O.K.
Current monitoring terminals
Voltage proportional to the output current: ~ 1 V ≙ I
out rated
±50 mV
Table 2- 1 IMonitor conversion table
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Output current
[A]
IMonitor
[V]
Output current
[A]
IMonitor
[V]
0.0
0.0
0.0
0.0
0.5
0.1
1.0
0.1
1.0
0.2
2.0
0.2
1.5
0.3
3.0
0.3
2.0
0.4
4.0
0.4
2.5
0.5
5.0
0.5
3.0
0.6
6.0
0.6
3.5
0.7
7.0
0.7
4.0
0.8
8.0
0.8
4.5
0.9
9.0
0.9
5.0
1.0
10
1.0
Figure 2-4 Operating displays and signaling
Description, device design, dimension drawing
2.4 Status displays and signaling
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 13
Signaling
6EP7133-6AB00-0BN0 (24 /5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
LED lights up green
Signaling contact ,
contact 13-14 closed
Normal operation, output voltage > 20 V ±0.5 V
LED off
Signaling contact ,
contacts 13-14 open (quiescent position)
Overload operation or power supply voltage missing
Description, device design, dimension drawing
2.5 Block diagram
SIMATIC ET200SP PS
14 Manual, 03.2018, A5E43207434
2.5
Block diagram
Figure 2-5 Block diagram
Description, device design, dimension drawing
2.6 Dimensions and weight
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 15
2.6
Dimensions and weight
Figure 2-6 Dimensions and weight
6EP7133-6AB00-BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Dimensions (W × H × D) in mm
160 × 117 × 66.5
160 × 117 × 66.5
Weight
Approx. 0.5 kg
Approx. 0.72 kg
Description, device design, dimension drawing
2.6 Dimensions and weight
SIMATIC ET200SP PS
16 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 17
Mounting/removal
3
WARNING
Installing the device in a housing or a control cabinet
SIMATIC ET200SP PS power supplies are built-in devices. They must be installed in a
housing or control cabinet where only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails (see Chapter
Mechanical system (Page 34))
Mounting
To mount the device, position it with the mounting rail guide at the upper edge of the
standard mounting rail and press down to lock it into place. If it is difficult to snap the device
into place, press the button at the same time, as described under "Removal".
Removal
To remove, press button (see Removal diagram (Page 17)) by hand downwards and
withdraw the device at the lower edge of the standard mounting rail. Then you can remove
the device from the upper edge of the standard mounting rail.
Figure 3-1 Removal
Mounting/removal
SIMATIC ET200SP PS
18 Manual, 03.2018, A5E43207434
WARNING
Use in hazardous zones
If the device is to be used in a hazardous zone (Ex II 3G Ex nA nC IIC T4 Gc) it must be
installed in a distributor box with degree of protection IP54 or higher.
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 19
Mounting position, mounting clearances
4
4.1
Standard mounting position
The device is mounted on standard mounting rails according to EN 60715 35×7,5/15.
The device must be mounted vertically in such a way that the terminals are at the bottom.
A clearance of at least 50 mm should be maintained above and below the device (maximum
depth of the cable duct, 50 mm).
No space is required at the side.
Output current as a function of the ambient temperature and mounting height
Figure 4-1 6EP7133-6AB00-0BN0: Output current in the standard mounting position
Figure 4-2 6EP7133-6AE00-0BN0: Output current in the standard mounting position
Mounting position, mounting clearances
4.2 Other mounting positions
SIMATIC ET200SP PS
20 Manual, 03.2018, A5E43207434
4.2
Other mounting positions
For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.
Note
In the case of mounting positions that deviate from the standard mounting position, reduced
mechanical resistance of the devices against vibration and shoc
k must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required, e.g. to prevent the device from slipping on the standard
mounting rail.
4.2.1
6EP7133-6AB00-0BN0
Figure 4-3 Mounting position (2)
Note
Other mounting positions are not permissible!
Mounting position, mounting clearances
4.2 Other mounting positions
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 21
4.2.2
6EP7133-6AE00-0BN0
Figure 4-4 Mounting position (2)
Note
Othe
r mounting positions are not permissible!
Mounting position, mounting clearances
4.2 Other mounting positions
SIMATIC ET200SP PS
22 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 23
Installation
5
WARNING
Hazard due to electric shock
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
5.1
Line-side connection
SIMATIC ET200SP PS power supplies are designed for connection to a 1-phase AC line
supply (TN or TT system according to IEC 60364-1) with a rated voltage of 120/230 V AC,
50/60 Hz.
Figure 5-1 Line supply connection
The line supply is connected using terminals L1, N and PE (see Figure 5-1 Line supply
connection (Page 23)), and must be implemented according to IEC 60364 . A protective
device (miniature circuit-breaker or circuit-breaker) and a disconnection unit for the power
supply must be provided. A ground-fault circuit interrupter is not permissible against indirect
contact as the only protective measure. This is true for the complete line supply protected by
the ground-fault circuit interrupter.
Installation
5.1 Line-side connection
SIMATIC ET200SP PS
24 Manual, 03.2018, A5E43207434
Protection
SIMATIC ET200SP PS
Recommended line-side protection
6EP7133-6AB00-0BN0
Miniature circuit breaker (IEC 898) characteristic B, 6 A and C, 3 A
6EP7133-6AE00-0BN0
Miniature circuit breaker (IEC 898) characteristic B, 10 A and C, 6 A
The protective conductor of the line supply must be connected at the PE terminal.
NOTICE
Country-specific regulations must be observed when installing.
Installation
5.2 Output-side connection
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 25
5.2
Output-side connection
SIMATIC ET200SP PS power supplies provide an isolated (= non-grounded) SELV output
voltage (Safety Extra Low Voltage). The output of the power supply is no-load, overload, and
short-circuit proof. If an overload occurs, the electronic current limitation limits the output
current to a maximum value (refer to chapter Technical data (Page 27)).
Figure 5-2 Connecting the output voltage
The output voltage is connected via the + and - terminals at the output of the power supply
(see Figure Connecting the output voltage (Page 25)). Ensure that the output cables are
dimensioned correctly for the maximum output current rms value and fused accordingly.
Note
If the safety concept of the plant or system specifies that the DC output circuit should be
grounded (PELV), then it is permissible that the output voltage of the SIMATIC power supply
is grounded. In this case, ideally, the grounding at the output should be directly connected
from terminal "
-" of the power supply to a suitable connection point of the protective
conductor system (P
E) of the plant or system.
Installation
5.2 Output-side connection
SIMATIC ET200SP PS
26 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 27
Technical data
6
Note
Technical data apply for a rated input voltage, rated load and 25
°C ambient temperature if
nothing else is specified.
6.1
Input
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Input
1-phase, AC
1-phase, AC
Rated voltage U
in rated
120 - 230 V
120 - 230 V
Voltage range
Comment
85 - 132/170 - 264 V
Derating at ≤ 60 °C:
85 V AC and 170 V AC: 90 % Pout rated
100 V AC and 200 V AC: 100 % Pout rated
between 85 V AC and 100 V AC, 170 V AC and 200 V AC linear interpolation
automatic range switchover
Yes
Yes
Connect/shutdown threshold, typical 68 V/59 V or
140 V/135 V
67 V/61 V or
142 V/137 V
Line supply buffering at Iout rated, min
20 ms
20 ms
Power-failure buffering
at 93/187 V
at 93/187 V
Rated line frequency
50 - 60 Hz
50 - 60 Hz
Line frequency range
47 - 63 Hz
47 - 63 Hz
Input current at rated input voltage
120 V
2.1 A 4.3 A
Input current at rated input voltage
230 V
1.2 A 1.9 A
Inrush current limiting (25 °C), max.
45 A
60 A
I
2
t, at AC 120 V, max.
1 A
2
s
5.6 A
2
s
I
2
t, at AC 230 V, max.
3.15 A
2
s
6.3 A
2
s
Integrated input fuse
Fuse T 3.15 A
Fuse T 6 A
Protection in the line feeder cable
(IEC 898)
Recommended: Miniature circuit
breaker, characteristic B, 6 A or C, 3 A
Recommended: Miniature circuit
breaker, characteristic B, 10 A or C, 6 A
Technical data
6.1 Input
SIMATIC ET200SP PS
28 Manual, 03.2018, A5E43207434
Figure 6-1 Power-failure buffering
Technical data
6.2 Output
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 29
6.2
Output
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Output
Regulated, isolated DC voltage
Regulated, isolated DC voltage
Rated voltage U
out rated
DC
24 V
24 V
Total tolerance, static ±
3 %
3 %
Static line regulation, approx. ±
0.1 %
0.5 %
Static load regulation, approx. ±
1 %
1 %
Residual ripple
Peak-peak, max.
150 mV 150 mV
Spikes peak-peak, max.
(bandwidth, 200 MHz)
240 mV 240 mV
Adjustment range
22.8 - 28.0 V
22.8 - 28.0 V
Product function output voltage
can be adjusted
Yes Yes
Output voltage setting
Remark
Using a potentiometer
Max. 120 W
Via potentiometer
Max. 240 W
Status display
LED green for 24 V O.K.
LED green for 24 V O.K.
Signaling
Contact rating (isolated): 30 V AC/0.5 A, 60 V DC/0.3 A, 30 V DC/1 A) for 24 V O.K.
Response when switching on/off
Overshoot of U
out
< 720 mV
Overshoot of U
out
< 720 mV
Starting delay, max.
300 ms
300 ms
Start delay, typ.
150 ms
150 ms
Voltage rise
120 V/230 V AC max.
200 ms
200 ms
Voltage rise
120 V/230 V AC typ.
30 ms
30 ms
Rated current Iout rated 5 A 10 A
Current range
Remark
0 - 5 A
60 ... 70 °C derating: 3 % Iout rated/K
0 - 10 A
60 ... 70 °C derating: 3 % Iout rated/K
Active power output, typ.
120 W
240 W
Overload capability (Extra Power)
7.5 A for 5 s/min
15 A for 5 s/min
Short-time overload current for a
short circuit when powering up
15 A 30 A
Duration of the overload capability
for an overcurrent condition caused
by a short circuit while powering
up.
Remark
100 ms
once-only
100 ms
once-only
Short-time overload current for a
short circuit in operation, typ.
15 A 30 A
Technical data
6.2 Output
SIMATIC ET200SP PS
30 Manual, 03.2018, A5E43207434
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Duration of the overload capability
for an overcurrent condition caused
by a short circuit in operation.
Remark
100 ms
once-only
100 ms
once-only
Can be connected in parallel to
increase the power rating
Yes Yes
Number of devices that can be
connected in parallel to increase
the power rating, units
2 2
Output characteristic see Figure 6-3 Output characteristic
6EP7133-6AB00-0BN0 (Page 30)
see Figure 6-4 Output characteristic
6EP7133-6AE00-0BN0 (Page 31)
Capacitive load, max.
2 mF/A
2 mF/A
Figure 6-2 Startup delay/voltage rise
Figure 6-3 Output characteristic 6EP7133-6AB00-0BN0
Technical data
6.2 Output
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 31
Figure 6-4 Output characteristic 6EP7133-6AE00-0BN0
The device supplies a constant output voltage until the current limit is reached. In the event
of an overload, the output current and the output voltage are reduced.
Technical data
6.3 Efficiency
SIMATIC ET200SP PS
32 Manual, 03.2018, A5E43207434
6.3
Efficiency
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Efficiency at Uout rated, Iout rated
120 V/230 V AC approx.
87 %/88 % 89.5 %/90 %
Power loss at Uout rated, Iout rated
120 V/230 V AC approx.
17 W/15 W 27 W/26 W
Power loss when idling
120 V/230 V AC approx.
3 W/2.7 W 3.2 W/2.8 W
Figure 6-5 Efficiency, 6EP7133-6AB00-0BN0
Figure 6-6 Efficiency, 6EP7133-6AE00-0BN0
Technical data
6.4 Closed-loop control
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 33
6.4
Closed-loop control
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Dyn. line regulation
(Uin rated ±15 %), max.
0.3 % 0.3 %
Dyn. load regulation
(I
out
: 10/90/10 %), U
out
± max.
5 % 5 %
Dyn. load regulation
(I
out
: 10/90/10 %), U
out
± typ.
3 % 3 %
Load-step settling time
10 to 90 %, max.
1 ms 1 ms
Load-step settling time
10 to 90 %, typ.
1 ms 1 ms
Load-step settling time
90 to 10 %, max.
1 ms 1 ms
Load-step settling time
90 to 10 %, typ.
1 ms 1 ms
6.5
Protection and monitoring
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Output overvoltage protection
in the case of an internal fault U
out
< 31.8 V
in the case of an internal fault U
out
< 31.8 V
Current limitation, typ.
Remark
7.5 A
Overload capability with
150 % I
out rated
up to 5 s/min
15 A
Overload capability with
150 % I
out rated
up to 5 s/min
Short-circuit protection
Yes, current is statically limited
Yes, current is statically limited
Continuous short-circuit
current rms value, approx.
7 A 14.1 A
6.6
MTBF
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Mean Time Between Failures SN29500:
> 1000000 h
at 40 °C, rated load, 24 h operation
Technical data
6.7 Mechanical system
SIMATIC ET200SP PS
34 Manual, 03.2018, A5E43207434
6.7
Mechanical system
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Connection system
Spring-loaded terminal
Spring-loaded terminal
Connections: Line input
L, N, PE: 1 push-in terminal each for 0.2 - 2.5 mm² solid (finely stranded)
Connections: Output
+, -: 3 spring-loaded terminals each for 0.2 - 2.5 mm²
Connections: Auxiliary contacts Signaling contact: 1 spring-loaded terminals each for 0.2 - 2.5 mm²
Current monitoring terminals: 1 spring-loaded terminals each for 0.2 - 2.5 mm²
Width of the housing
160 mm
160 mm
Height of the housing
117 mm
117 mm
Depth of the housing
66.5 mm
66.5 mm
Installation width
160 mm
160 mm
Mounting height
217 mm
217 mm
Weight, approx.
0.5 kg
0.72 kg
Product feature of the housing:
housing that can be lined up next
to one another
Yes Yes
Type of mounting: Wall/panel
mounting
No No
Type of mounting: Rail mounting
Yes
Yes
Type of mounting: S7-300 rail
mounting
No No
Mounting
Can be snapped onto standard TH35 15/7,5 mounting rails (EN 60715)
6.8
Dimension drawing
See chapter Dimensions and weight (Page 15)
CAD data that can be downloaded from the Internet:
6EP7133-6AB00-0BN0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01416)
6EP7133-6AE00-0BN0
(http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01419)
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 35
Safety, approvals, EMC
7
7.1
Safety
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Primary/secondary galvanic isolation
Yes
Galvanic isolation SELV output voltage Uout acc. to EN 60950-1
Transformer according to EN 61558-2-16
Protection class
Class I
Degree of protection (EN 60529) IP20
Leakage current, typ.
1 mA
Leakage current, max.
3.5 mA
Test voltage See Table 7-1 Test voltage for 6EP7133-6AB00-0BN0 and
6EP7133-6AE00-0BN0 (Page 36)
Safety, approvals, EMC
7.2 Test voltage
SIMATIC ET200SP PS
36 Manual, 03.2018, A5E43207434
7.2
Test voltage
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another (L, N)
Connect the output terminals, signaling contact, IMonitor and PE with one another
Test (C)
Connect the output terminals, signaling contact and current monitoring terminal with one
another and measure with respect to PE
Table 7- 1 Test voltage for 6EP7133-6AB00-0BN0 and 6EP7133-6AE00-0BN0
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test 60 s 4200 V DC 2200 V DC 700 V DC
60 s
3000 V AC
1500 V AC
500 V AC
Production test 1 s 2200 V DC 2200 V DC 500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Remark:
Tripping current for DC measurement: 0
mA
Tripping current for AC measurement: < 100 mA
Safety, approvals, EMC
7.3 Approvals
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 37
7.3
Approvals
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
CE marking
yes, (2014/35/EU, 2014/30/EU and 2011/65/EU)
CSA approval
yes, CSA C22.2 No. 60950-1, being prepared
UL/cUL approval
cULus-listed (UL 508, CSA 22.2 No. 107.1), File E197259
Explosion protection
UL/cUL: ANSI/ISA-12.12.01-2015 Class I, Div. 2, Group ABCD, T4
CB approval
Yes
CB-Scheme
IEC 60950-1
7.4
EMC
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
2400 - 2700 MHz 10 V/m
Fast transient disturbance
variables (burst)
EN 61000-4-4 4 kV at line connections
2 kV at DC output
Surge voltages EN 61000-4-5 2 kV symmetrical at the line connections
4 kV asymmetrical at the line connections
500 V symmetrical/asymmetrical on DC output cables
High-frequency fields
EN 61000-4-6
10 V; 0.15 - 80 MHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
Voltage dips EN 61000-4-11 100% for 20 ms,
60% for 200 ms,
30% for 500 ms
Voltage interruptions
EN 61000-4-11
100% for 5000 ms
Emitted interference
EN 55022
Class B
Line harmonics limitation
EN 61000-3-2
Class A
Generic standards
EN 61000-6-2
Immunity for industrial environments
EN 61000-6-3
Emission for residential areas
Safety, approvals, EMC
7.4 EMC
SIMATIC ET200SP PS
38 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 39
Environmental conditions
8
6EP7133-6AB00-0BN0 (24 V/5 A)
6EP7133-6AE00-0BN0 (24 V/10 A)
Ambient temperature
Remark
-30 … 70 °C for natural convection (self convection)
Derating at ≤ 60 °C:
85 V AC and 170 V AC: 90 % Pout rated
100 V AC and 200 V AC: 100 % Pout rated
between 85 V AC and 100 V AC, 170 V AC and 200 V AC linear interpolation
at > 60 °C: Additionally, 3 % Iout rated /K
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Transport and storage temperature -40 … 70 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 acc. to EN 60721, 5 - 95 % without condensation
Mechanical stressing during operation Tested according to:
EN 60068-2-6, test FC
3.5 mm deflection in the range of 5 - 8.4 Hz
2 g acceleration in the range of 8.4 - 150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s2, test duration 11 ms
Damaging gases Tested according to:
EN 60068-2-42 sulfur dioxide
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure Operation:
1080 - 795 hPa (-1000 - 2000 m)
Overvoltage category:
II to 2000 m (EN 60950-1)
Storage:
1080 - 660 hPa (-1000 - 3500 m)
Environmental conditions
SIMATIC ET200SP PS
40 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 41
Applications
9
9.1
Parallel connection to increase the power rating
To increase the power rating, power supplies of the same type can be directly connected in
parallel.
The following must be observed:
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
Figure 9-1 Parallel connection correct - incorrect
Note
It is not permissible to take into account simultaneous overload capability (Extra
-Power
150% for 5
s/min) of several power supplies connected in parallel when configuring the
power supply system.
Applications
9.1 Parallel connection to increase the power rating
SIMATIC ET200SP PS
42 Manual, 03.2018, A5E43207434
NOTICE
Protective circuit for the parallel connection of more than two power supplies
When connecting more than two power supplies in parallel, additional measures must be
taken to prevent high reverse currents in the event of a secondary device fault. For this
purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker)
must be installed between each "+" terminal of the power supply and the common
connection point.
Applications
9.2 Series connection for increased voltage
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 43
9.2
Series connection for increased voltage
To achieve an output voltage of 48 V DC, two 24 V SIMATIC power supplies of the same
type can be connected in series.
Note
For additional details, see Catalog KT 10.1 Chapter 15 Technical information and configuring
(see
(
http://w3app.siemens.com/mcms/infocenter/content/en/Pages/order_form.aspx?nodeKey=k
ey_518431&infotype=catalogs
)).
WARNING
SELV is not guaranteed in the case of a fault
When connecting two power supplies in series, the continuous, permissible SELV voltage of
a maximum of 60 VDC according to EN 60950-1 cannot be guaranteed in the case of a fault.
Figure 9-2 Series connection
Applications
9.3 Overload protection in the 24 V output circuit
SIMATIC ET200SP PS
44 Manual, 03.2018, A5E43207434
9.3
Overload protection in the 24 V output circuit
If an overload occurs, the electronic current limiting function of the 24 V power supply limits
the output current to a maximum value (see Section Technical data (Page 27)). The output
cables are protected against a thermal overload if they are dimensioned corresponding to
the maximum rms output current, or protected using additional components (for example,
miniature circuit breaker, fuses).
However, a load circuit that fails as a result of overload, for instance, should frequently be
reliably and quickly identified and specifically switched off before the power supply goes into
current-limiting mode (in current-limiting mode, the supply voltage would also be reduced for
all of the remaining 24 V loads).
The SITOP PSE200U selectivity module with 4 outputs (versions with adjustable output
current range for each output from 0.5 - 3 A and 3 - 10 A) is available for this purpose; this
monitors the 24 V branches for overload and short circuit (Figure 9-3 Electronic protection of
24 V loads using the SITOP PSE200U selectivity module (Page 44)). Brief current peaks,
e.g. as a result of a high inrush current, are permitted, and branches with a longer overload
are switched into a no-current condition. This is also ensured for cables in a high-ohmic
condition and for short circuits that slowly develop over time.
When an output fails, the fault is signaled using a group signal contact or as a single channel
signal, and the branch of the module involved is displayed using an LED.
For variants with single-channel signaling, function blocks for evaluation purposes are
available for SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no
charge.
You can find additional information at:
Manual SITOP selectivity modules
(https://support.industry.siemens.com/cs/ww/en/view/108989004)
Figure 9-3 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module
Applications
9.4 Protection against short-time voltage dips
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 45
9.4
Protection against short-time voltage dips
For a drop in the line-side supply voltage, the 24 V power supply still maintains the output
voltage for a short time in the millisecond range (see Chapter Technical data (Page 27)).
For line supplies that manifest frequent brief voltage dips, in order to increase the power
supply reliability, it may make sense to increase the line buffering time in the device using an
additional SITOP PSE201U buffer module.
The SITOP PSE201U buffer module, based on electrolytic capacitors, is connected in
parallel to the power supply output (Figure 9-4 Buffering brief power failures using the
SITOP PSE201U buffer module (Page 45)). The buffer time is 200 ms at 40 A up to 1.6 s for
a load current of 5 A. This time can be increased a multiple number of times by connecting
buffer modules in parallel; the maximum buffer time is 10 s.
You can find additional information at:
SITOP PSE201U manual
Figure 9-4 Buffering brief power failures using the SITOP PSE201U buffer module
Applications
9.5 Protecting against longer power failures
SIMATIC ET200SP PS
46 Manual, 03.2018, A5E43207434
9.5
Protecting against longer power failures
Sudden and longer failures of the line supply voltage can result in undefined states and
significant danger as a result of the associated failure of the plant or system control.
The SITOP power supply product portfolio includes various DC-UPS solutions to prevent the
failure of the 24 V power supply voltage.
Power supply failures up into the minutes range can be buffered using the maintenance-free
SITOP UPS500 DC-UPS modules based on capacitors (Figure 9-5 24 V buffering to allow
the saving of process data and controlled shutdown of PCs (Page 46)).
Figure 9-5 24 V buffering to allow the saving of process data and controlled shutdown of PCs
Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply
integrated into PC-based automation solutions. This supports further processing of the status
signals and safely running down the PC.
You can find additional information at:
Manual, DC UPS with capacitors
(https://support.industry.siemens.com/cs/ww/en/ps/18042/man)
Using DC UPS SITOP UPS1600 and SITOP UPS1100 battery modules, buffer times in the
range of hours can be implemented. Intelligent battery management using Energy Storage
Link automatically detects the UPS1100 energy storage device, and ensures optimum
temperature-controlled charging and continuous monitoring. The UPS1600 can be flexibly
integrated into the widest range of automation applications with its digital inputs/outputs as
well as optional USB interface or Ethernet/PROFINET port.
Applications
9.5 Protecting against longer power failures
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 47
Figure 9-6 24 V buffering with SITOP UPS1600 to maintain communication, signaling functions,
sensor measured values and position values
For open, PC-based automation systems, configuration and monitoring is realized using the
SITOP UPS Manager PC software, which is available at no charge. This allows PC
responses to the operating states of the DC UPS to be freely selected and offers
comprehensive diagnostic functions.
For TIA-based automation systems, the UPS1600 is engineered using the TIA Portal.
Special function blocks for SIMATIC S7-300/400/1200 and S7-1500 available at no charge
make it easy to integrate operating and diagnostics information into STEP 7 user
programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no
charge.
You can find additional information at:
DC UPS SITOP UPS1600/UPS1100 Manual
(https://support.industry.siemens.com/cs/ww/en/view/84977415)
Applications
9.5 Protecting against longer power failures
SIMATIC ET200SP PS
48 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 49
Environment
10
The devices are in conformance with RoHS.
As a rule, only non-silicon precipitating materials are used.
Disposal guidelines
Packaging and packaging aids can and should always be recycled. The product itself may
not be disposed of as domestic refuse.
Environment
SIMATIC ET200SP PS
50 Manual, 03.2018, A5E43207434
SIMATIC ET200SP PS
Manual, 03.2018, A5E43207434 51
Service & Support
11
Technical support
Technical support for all IA/DT products can be accessed through the following
communication channels:
Telephone: + 49 (0) 911 895 7222
Internet:
Web form for support request (http://www.siemens.de/automation/support-request)
Technical documentation on the Internet
Operating instructions and manuals for SITOP are available in the Internet:
Operating instructions/manuals (http://www.siemens.com/sitop/manuals)
SITOP power supply homepage
General news about our power supplies is available in the Internet at the SITOP home page:
SITOP (http://www.siemens.com/sitop)
Information material
SITOP information can be downloaded from the Internet:
Information and download center (http://www.siemens.com/sitop-infomaterial)
CAx data
2D/3D data and circuit diagram macros can be downloaded from the Internet:
Siemens image database (http://www.siemens.com/sitop-cax)
Request all CAx data via the CAx download manager:
CAx shopping cart (http://www.siemens.com/cax)
SITOP Selection Tool
Simply and quickly select the optimum the power supply or DC-UPS:
SITOP Selection Tool (http://www.siemens.com/sitop-selection-tool)
Online catalog and ordering system
The online catalog and the online ordering system are available through the Industry Mall
homepage:
Industry Mall (http://www.siemens.com/industrymall/de)
Service & Support
SIMATIC ET200SP PS
52 Manual, 03.2018, A5E43207434
Contact persons
If you have any questions regarding the use of our products, then contact the Siemens
contact person in your regional Siemens sales office.
You can find these addresses as follows:
On the Internet (http://www.automation.siemens.com/partner)
Industry Mall (http://www.siemens.com/industrymall/de)