Specifications are subject to change without notice (09.10.06) 1
Monitoring Relays
Product Description Ordering Key
Housing
Function
Type
Item number
Output
Power supply
DC undervoltage monitoring relay
Measuring if power supply is below the set level
Measures on own power supply
Measuring ranges: 8 - 28 V DC and 38 - 58 V DC
Adjustable hysteresis: 4 to 50%
Output: 5 A SPDT NE relay
For mounting on DIN-rail in accordance with
DIN/EN 50 022
17.5 mm housing (DIN 43880)
LED indication for relay and power supply ON
Type Selection
Mounting Output Measuring range Supply : 12/24 VDC Supply: 48 VDC
DIN-rail SPDT 8 to 28 VDC DUA 52 C 724
DIN-rail SPDT 38 to 58 VDC DUA 52 C 748
Input (voltage level) Terminals A1, A2
Measures on own power
supply
Measuring ranges
Direct Level
48 VDC 38 to 58 VDC
12 to 24 VDC 8 to 28 VDC
DC Under Voltage
Type DUA52
Input Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2) µ
Resistive loads AC 1 5 A @ 250 VAC
DC 12 5A@24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations
Electrical life 105operations
(at 8 A, 250 V
,cos ϕ=1)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand volt. 4kV (1.2/50 µs)
Output Specifications
DUA 52 C 724
DUA52 is a voltage monitor-
ing relay that measure its own
power supply. The measuring
ranges are 8-28 VDC and 38-
58 VDC. It has separate
potentiometers for setpoint
and hysteresis. Typical appli-
cations are monitoring of
backup batteries, batteries on
diesel generator sets and the
like.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1 and A2 724 8to 28 VDC
748 38 to 58 VDC
Dielectric voltage None
Dielectric voltage
Supply to output 2 kV
Rated operational power 1.5 W
Supply Specifications
2Specifications are subject to change without notice (09.10.06)
Operation Diagram Wiring Diagram
Selection of level:
Centre knob:
Setting of level on absolute
scale.
Lower knob:
Setting of hysteresis on rela-
tive scale
Range and Level Setting
DUA52
Mode of Operation
DUA52 monitors the DC val-
ue of its own power supply.
The output is energized
when the measured voltage
is rising above the setpoint
plus hysteresis, and is deen-
ergized when the measured
voltage drops below the set-
point value.
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions 17.5 x 81 x 67.2 mm
Material PA 66
Weight Approx. 75 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA
CE Marking Yes
General Specifications
Relay ON
Setpoint
Hysteresis
67.2
18.7
45
17.5
81
2
Dimensions
Power ON delay <200 ms
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 200 ms
Alarm OFF delay < 200 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Alarm delay ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Output relay ON LED, yellow