Specifications are subject to change without notice 1
Type EIC
Current and Voltage Controls
AC/DC under current (closed circuit)
metering relay
Measuring through external shunt
3-position rotary switch for selection of measuring range
Measuring range: 10-50 mV, 12-60 mV, 30-150 mV or
20-100 mV, 24-120 mV, 60-300 mV
Adjustable limit on relative scale
Adjustable time function (0.1-10 s)
Adjustable hysteresis
Output: 5 A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22.5 mm Euronorm housing
LED-indication for relay and power supply ON
Galvanically separated power supply
Housing
Function
Type
Output
Power supply
EIC C 230
Product Description Ordering Key
EIC is a precise AC/DC under
current (shunt) metering re-
lay. Measures the voltage of
an externally connected stan-
dard shunt also for high cur-
rent applications. The built-in
LED's indicate the exact sta-
tus of the output relay.
Type Selection
Mounting Output Measuring range Supply: 24 VAC Supply: 115 VAC Supply: 230 VAC
For DIN-rail SPDT 10 - 300 mV EIC C 024 EIC C 115 EIC C 230
Input Specifications
Input
Through terminals Y1 & Y2 Range x 1
Through terminals Y1 & Y3 Range x 2
Measuring ranges Internal resist. Max. volt.
x 1 input:
Rotary 1: 10 - 50 mV 270 1 V
Switch 2: 12 - 60 mV 270 1 V
Position 3: 30 - 150 mV 270 1 V
x 2 input:
Rotary 1: 20 - 100 mV 540 2 V
Switch 2: 24 - 120 mV 540 2 V
Position 3: 60 - 300 mV 540 2 V
Max. line voltage 277/480 VAC/DC
Output Specifications
Output SPDT relay
Rated insulation voltage 250 VAC (contact/elect.)
Contact ratings (AgCdO) µ (micro gap)
Resistive loads
AC 1
5 A, 250 VAC
DC 1
5 A, 24 VDC
Small inductive loads
AC 15
2 A, 250 VAC
DC 13
3 A, 24 VDC
Mechanical life 40 x 106operations
Electrical life 105operations
(at max. load)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage (IEC 60038)
Through term. A1 & A2024
24 VAC ±15%, 45 to 65 Hz
115
115 VAC ±15%, 45 to 65 Hz
230
230 VAC ±15%, 45 to 65 Hz
Voltage interruption 40 ms
Dielectric voltage 2 kVAC (rms)
Rated impulse withstand
voltage 4 kV (1.2/50 µs)
Rated operational power 1.5 VA
1-Phase AC/DC Under Current (Shunt)
2Specifications are subject to change without notice
EIC
General Specifications
Power ON delay < 2 s
Power OFF delay > 200 ms
Reaction time τ< 200 ms
worst case reaction time
may be up to 5 x τ
Adjustable delay on release
built-in (0.1-10 s)
Accuracy
Input ±10% (DC/AC @ 50 Hz)
OFF delay 10 s, -1/+3 s on max.
< 0.1 s on min.
Temperature drift 0.2%/°C (0.11%/°F)
Indication for
Power supply ON LED, green
Output ON LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature -2 0 ° to + 5 0 ° C ( - 4 ° to +122°F)
Storage temperature
-50° to +85°C (-58° to +185°F)
Weight 140 g
Screw terminals
Tightening torque
M
ax. 0.5 Nm acc. to IEC 60947
Approvals UL, CSA
Mode of Operation
EIC measures both AC and
DC current (voltage) through
an external standard shunt.
Example 1
The relay operates when the
measured value exceeds the
set level plus the hysteresis.
When the voltage (current)
drops below the set level for
more than the set delay, or
when power supply is inter-
rupted, the relay r eleases.
The yellow LED is flashing un-
til the delay has expired, or
until the measured value ex-
ceeds the set level plus the
hysteresis.
Range/Level/Time Setting
Upper knob:
Setting of current (voltage)
range on rotary switch.
Centre knob:
Level setting on relative scale.
Lower knob:
Setting of OFF delay on abso-
lute scale (0.1-10 s).
Hysteresis
Normally 5%. The hysteresis
can be extended by inserting
a resistor between terminals
Z1 & Z2.
Approx.
10%: 39 k
25%: 12 k
50%: 4.7 k
75%: 2.2 k
100%: 1.5 k
Wiring Diagram
Example 1
Operation Diagram
Power supply
Set level
Relay ON
Hysteresis
Hysteresis
adjustment
µ