Data Sheet FieldIT SS/267CS_4 2600T Series Pressure Transmitters Model 267CS Multivariable for mass flow selectable maximum working pressure up to 41MPa, 5945psi Base accuracy : 0.075% Span limits - 0.05 to 2000kPa, 0.2inH2O to 290psi differential pressure - 0.6 to 41MPa, 87 to 5945psia absolute pressure Fully compensated mass or volume flow measurement for gases, vapours, liquids - dynamical compensation of changes in pressure and temperature One transmitter replaces three separate transmitter, saving initial purchase cost Reduced process penetrations save money and reduce chances of leak Fewer transmitters, less wiring, and fewer shut off valves reduce installation costs Greater reliability due to fewer devices and less wiring Flexible configuration facilities - provided by PC configuration platform Multiple protocol availability - provides integration with HART(R), PROFIBUS PA, FOUNDATION Fieldbus and Modbus platforms offering interchangeability and transmitter upgrade capabilities Full compliance with PED category III ABB 2600T Series Engineered solutions for all applications 2600T Pressure Transmitters Model 267CS Functional Specifications The 267CS allows due to its multisensor technology the measurement of three separate process variables simultaneously and provides the ability of dynamic calculation of fully compensated mass or volume flowrate for gases, steam and liquids. It measures differential pressure and absolute pressure from a single sensor and process temperature from a standard 100-ohm Resistance Temperature Detector (RTD). The flow calculation of 267CS includes compensation of pressure and/or temperature as well as more complex variables such as discharge coefficient, thermal expansion, Reynolds number and compressibility factor. The 267CS includes flow equations for superheated steam, saturated steam, gases and liquids so that one model is all you need in your plant. The enhanced compensation approach of 267CS provides a much better accuracy than the "old approach" where three different transmitters, differential pressure, absolute pressure and temperature, report their values to a DCS, PLC or flow computer and where the calculation considers changes in temperature and pressure according to: Qm dp . p T The dynamic mass flow compensation of 267CS is based on AGA 3 and EN ISO 5167: Qm C . EV . Y1 . d2 dp . Qm C Ev Y1 d dp 2 = mass flowrate = discharge coefficient = velocity of approach factor = gas expansion factor = bore diameter = differential pressure = fluid density SS/267CS_4 Discharge coefficient It is defined as the true flowrate divided by the theoretical flowrate and corrects the theoretical equation for the influence of velocity profile (Reynolds number), the assumption of no energy loss between taps, and pressure tap location. It is dependent on the primary flow element, the ratio and the Reynolds number. Reynolds number is in turn dependent on the viscosilty, density and velocity of the fluid as well as the pipe diameter per the following equation: Re = v.D. v = velocity D = inside pipe diameter = fluid density = fluid viscosity Dynamical compensation for discharge coefficient provides high accuracy for orifice, Venturi and nozzles. 2600T Pressure Transmitters Model 267CS SS/267CS_4 Density of fluids Gas expansion factor It corrects for density differences between pressure taps due to expansion of compressible fluids. It does not apply for liquids which are essentially non-compressible. It directly effects the flowrate calculation. The 267CS compensates for density of fluids for changes in temperature and/or pressure as follows: The gas expansion factor is dependent on the Beta ratio, the Isentropic exponent, the differential pressure and the static pressure of the fluid per the following equation. - Heated steam as function of P and T based on steam tables For orifices: - Liquids as a function of T dp Y1 = 1 - (0.41 + 0.354 ) p. - Gases as a function of P and T per the gas law equations. - Saturated steam as function of P based on steam tables Mass flow calculation with 267CS will be configured for the following primary elements: Orifice Corner Taps, ISO For nozzles: Orifice Flange Taps, ISO Orifice D- and D/2-Taps, ISO Orifice Corner Taps, ASME Orifice Flange Taps, ASME Orifice D- and D/2-Taps, ASME Orifice Flange Taps, AGA3 Orifice 2,5D- and 8D-Taps = beta ratio Small bore orifice, flange taps dp = differential pressure Small bore orrifice, corner taps p = static pressure = Isentropic exponent Nozzle ISA 1932 Nozzle, Long Radius Wall Tap, ISO Nozzle, Long Radius Wall Tap, ASME Velocity of approach factor Is dependent on the Beta ratio as defined by the following equation: Ev = 1 1 - 4 In turn, Beta ratio is dependent on bore diameter and pipe diameter which are functions on temperature. The material of process pipe and primary flow element expands or contracts with changes in temperature of the fluid being measured. The thermal expansion coefficients are depended on the the material of pipe and flow element and are used for calculating the change in diameters. This ensures high flowrate accuracy at low and high temperature applications. Venturi, Rough Cast Inlet, ISO Venturi, Machined Inlet, ISO Venturi, Welded Inlet, ISO Venturi, Rough Cast Inlet, ASME Venturi, Machined Inlet, ASME Venturi, Welded Inlet, ASME Venturi, Nozzle, ISO Area Averaging Meter Pitot tube, ISO 3966 V-Cone Wedge Element Integral Orifice Assembly Density Correction (unknown Primary Element) Configuration of full functionality of 267CS including all data necessary or mass flow compensation will be done via PC based tool SMART VISION with DTM for 2600T. 3 2600T Pressure Transmitters Model 267CS SS/267CS_4 Functional Specifications Operative limits Range and span limits Temperature limits C (F) : - Ambient (is the operating temperature) differential pressure sensors Sensor Code - Upper Range Limit (URL) Lower Range Limit (LRL) Minimum Span A 1kPa 10mbar 4inH2O 0 0.05kPa 0.5mbar 0.2inH2O C 6kPa 60mbar 24inH2O 0 0.2kPa 2mbar 0.8inH2O F 40kPa 400mbar 160inH2O 0 0.4kPa 4mbar 1.6inH2O L 250kPa 2500mbar 1000inH2O 0 2.5kPa 25mbar 10inH2O N 2000kPa 20bar 290psi 0 20kPa 0.2bar 2.9psi absolute pressure sensors Sensor Code Upper Range Limit (URL) Lower Range Limit (LRL) Minimum Span 1 600kPa 6bar 87psi 0abs 6kPa 0.06bar 0.87psi 2 2000kPa 20bar 290psi 0abs 20kPa 0.2bar 2.9psi 3 10000kPa 100bar 1450psi 0abs 100kPa 1bar 14.5psi 4 41000kPa 410bar 5945psi 0abs 410kPa 4.1bar 59.5psi Span limits Maximum span = URL IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. Zero suppression and elevation Inert filling: -20C and +85C (-4F and +185F) Lower ambient limit for Viton and PTFE gaskets: -20C (-4F) Note : For Hazardous Atmosphere applications see the temperature range specified on the certificate/approval relevant to the aimed type of protection Process Lower limit - refer to lower ambient limits Upper limit - Silicone oil: 121C (250F) for working pressure above 10kPa abs, 100mbar abs, 1.45psia(1) - Inert fluid: 121C (250F) (2) for working pressure above atmospheric pressure (1) 85C (185F) for application below 10kPa abs, 100mbar abs, 1.45psia down to 3.5 kPa abs, 35mbar abs, 0.5psia (2) 85C (185F) for application below atmospheric pressure down to 40kPa abs, 400mbar abs, 5.8psia. Storage Lower limit: -50C (-58F); -40C (-40F) for LCD indicators Upper limit: +85C (+185F) Pressure limits Overpressure limits (without damage to the transmitter) Lower limit - 0.5kPa abs, 5mbar abs, 0.07psia for silicone oil - 40kPa abs, 400mbar abs, 5.8psia for inert fluid Upper limit - 0.6MPa, 6bar, 87psi for differential pressure sensor code A - 2MPa, 20bar, 290psi or 10MPa, 100bar, 1450psi or 41MPa, 410bar, 5945psi for differential pressure sensor codes C, F, L, N according to selected code variant. Static pressure Transmitters for differential pressure model 267CS operates within specifications between the following limits Lower limit No suppression or elevation but zero based range as long as - 3.5kPa abs, 35mbar abs, 0.5psia for silicone oil - calibrated span minimum span - 40kPa abs, 400mbar abs, 5.8psia for inert fluid Process temperature range -50C to +650C (-58F to 1200F) by external four-wire RTD Damping Adjustable time constant : 0 to 60s. This is in addition to sensor response time Turn on time Operation within specification in less than 2.5s with minimum damping. Insulation resistance > 100M at 1000VDC (terminals to earth) 4 Silicone oil filling: -40C and +85C (-40F and +185F) Upper limit - 0.6MPa, 6bar, 87psi for differential pressure sensor code A - 2MPa, 20bar, 290psi or 10MPa, 100bar, 1450psi or 41MPa, 410bar, 5945psi for differential pressure sensor codes C, F, L, N according to selected code variant. Proof pressure The transmitter can be exposed without leaking to line pressure of up 1.5 times the nominal pressure simultaneously on both sides. 2600T Pressure Transmitters Model 267CS Environmental limits Electromagnetic compatibility (EMC) Definition Class 3 Radio suppression Limit class B (according to EN 550011) Fulfills NAMUR recommendation Low voltage directive Comply with 73/23/EEC Pressure equipment directive (PED) Instruments with maximum working pressure 41MPa, 410bar, 5945psi comply with 97/23/EEC Category III module H. Humidity Relative humidity: up to 100% annual average Condensing, icing: admissible Vibration resistance Accelerations up to 2g at frequency up to 1000Hz (according to IEC 60068-2-26) Shock resistance (according to IEC 60068-2-27) Acceleration: 50g Duration: 11ms Wet and dust-laden atmospheres The transmitter is dust and sand tight and protected against immersion effects as defined by IEC EN60529 (1989) to IP 67 (IP 68 on request) or by NEMA to 4X or by JIS to C0920. - Transmitters of the type of protection "Intrinsically safe EEx ia" according to the directions 94 / 9 / EC (ATEX) Transmitter with 4 to 20mA output signal and HART communication Marking (DIN EN 50 014): II 1/2 GD T50C EEx ia IIC T6 or resp. II 1/2 GD T95C EEx ia IIC T4 Supply and signal circuit type of protection Intrinsic Safety EEx ib IIB/IIC resp. EEx ia IIB/IIC for connection to supply units with maximum values: II 1/2 GD T50C EEx ia resp. ib IIC T6 resp. II 1/2 GD T95C EEx ia resp. ib IIC T4 for Temperature class T4 resp. T95C: Ui = 30V Ii = 200mA Pi = 0.8W for T4 with Ta = (-40 to +85)C / (-40 to +185)F Pi = 1.0W for T4 with Ta = (-40 to +70)C / (-40 to +158)F for Temperature class T6 resp. T50C: Pi = 0.7W for T6 with Ta = (-40 to +40)C / (-40 to +104)F effective internal capacitance, Ci 10nF effective internal inductance, negligible. Fieldbus transmitters (PROFIBUS PA / FOUNDATION Fieldbus) Marking (DIN EN 50 014): II 1/2 GD T50C EEx ia IIC T6 or resp. II 1/2 GD T95C EEx ia IIC T4 Supply and signal circuit type of protection Intrinsic Safety EEx ib IIB/IIC resp. EEx ia IIB/IIC for connection to FISCO supply units with rectangular or trapezoidal characteristics with maximum values: II 1/2 G EEx ia respectively ib IIC T4/T6 Ui = 17.5V Ii = 360mA Pi = 2.52W II 1/2 G EEx ia respectively ib IIB T4/T6 Ui = 17.5V Ii = 380mA Pi = 5.32W SS/267CS_4 resp. for connection to supply unit or barrier with linear characteristics with maximum values: II 1/2 G EEx ia respectively ib IIC T4/T6 Ui = 24V li = 250mA Pi = 1.2W effective internal inductance Li 10 H, effective internal capacitance Ci 0 Maximum permissible ambient temperatures depending on the temperature class: T4: -40C to +85C (-40F to +185F) T5, T6: -40C to +40C (-40F to +104F) - Transmitters of the type of protection "flameproof enclosure EEx d" according to the directions 94 /9 / EC (ATEX) Transmitter with 4 to 20mA output signal and HART communication and Fieldbus transmitters (PROFIBUS PA / FOUNDATION Fieldbus) Marking (DIN EN 50 014): II 1/2 G EEx d IIC T6 Ambient temperature range: -40C to +75C (-40F to +167F) - Transmitters of category 3 for the application in "Zone 2" Transmitter with 4 to 20mA output signal and HART communication according to the directions 94 / 9 / EC (ATEX) Marking (DIN EN 50 014): II 3 GD T50C EEx nL IIC T6 or resp. II 3 GD T95C EEx nL IIC T4 Operating conditions: Supply and signal circuit (terminals signal +/-): U 45V I 22.5mA connector for external passive temperature sensor supply and signal circuit: U 10.5V I 1.5mA P 4mW Ambient temperature range: Temperature class T4 Ta=-40C to +85C (-40F to +185F) Temperature class T5, T6 Ta=-40C to +40C (-40F to +104F) - Factory Mutual (FM) Transmitter with 4 to 20mA output signal and HART communication Intrinsically safe: Class I; Division 1; Groups A, B, C, D; Class I; Zone 0; Group IIC; AEx ia IIC Degree of protection : NEMA Type 4X (indoor or outdoor) Permissible ambient temperature depending on temperature class Umax = 30V, Ci = 10.5nF, Li = 10H Ambient Temperature -40 to +85 -40 to +70 -40 to +40 -40 to +40 C (-40 to +185 C (-40 to +129 C (-40 to +104 C (-40 to +104 F) F) F) F) Temperature Imax class T4 200mA T4 200mA T5 25mA T6 25mA Pi 0.8W 1W 0.75W 0.5W Fieldbus transmitters (PROFIBUS PA/FOUNDATION Fieldbus) Intrinsically Safe : Class I, II and III; Division 1; Groups A, B, C, D, E, F, G; Class I; Zone 0, AEx ia Group IIC T6; T4 Non-incendive Class I, II and III, Division 2; Groups A, B, C, D, F, G Transmitter with 4 to 20mA output signal and HART communication and Fieldbus transmitters (PROFIBUS PA/FOUNDATION Fieldbus) Explosion-Proof: Class I; Division 1; Groups A, B, C, D; Class II/III, Division 1; Groups E, F, G Degree of protection : NEMA Type 4X (indoor or outdoor) - Canadian Standard (CSA) Transmitter with 4 to 20mA output signal and HART communication and Fieldbus transmitters (PROFIBUS PA/FOUNDATION Fieldbus) Explosion-Proof: Class I; Division 1; Groups B, C, D Class II; Division 1; Groups E, F, G Class III Degree of protection : NEMA Type 4X (indoor or outdoor) 5 2600T Pressure Transmitters Model 267CS SS/267CS_4 Electrical Characteristics and Options Optional indicators HART digital communication and 4 to 20mA output Integral display Power Supply The transmitter operates from 10.5 to 45VDC with no load and is protected against reverse polarity connection (additional load allows operations over 45VDC). Minimum power supply is 14VDC with backlit indicator. For EEx ia and other intrinsically safe approval power supply must not exceed 30VDC. 2-line, 6-character 19-segment alphanumeric display with additional bar chart display, optionally with back illumination. User-specific display: percentage of the output current or output current in mA or free process variable Diagnostic message, alarms, measuring range infringements and changes in the configuration are also displayed. Ripple Maximum permissible voltage ripple of power supply during the communication: 7Vpp at f = 50 to 100Hz 1Vpp at f = 100 to 200Hz 0.2Vpp at f = 200 to 300Hz Load limitations Output signal Two-wire 4 to 20mA, related to mass flow calculation, compensating all pressure (p) and temperature (T) effects completely. HART(R) communication provides digital process variable (%, mA or engineering units) superimposed on 4 to 20mA signal, with protocol based on Bell 202 FSK standard. Output function 4 to 20mA and HART total loop resistance : Mass flow calculation performed as per formula: Supply voltage - min. operating voltage (VDC) R(k) = --------------------------------------- 22.5 mA A minimum of 250 is required for HART communication. Qm C . EV . Y1 . d2 dp . where Qm C Ev Y1 d dp = mass flowrate = discharge coefficient = velocity of approach factor = gas expansion factor = bore diameter = differential pressure = fluid density Output current limits (to NAMUR standard) Overload condition - Lower limit: 3.8mA (configurable down to 3.5mA) - Upper limit: 20.5mA (configurable up to 22.5mA) Alarm current Min. alarm current: configurable from 3.5mA to 4mA, standard setting: 3.6mA Max. alarm current: configurable from 20mA to 22.5mA, standard setting: 21mA Standard setting: max. alarm current 6 2600T Pressure Transmitters Model 267CS SS/267CS_4 PROFIBUS PA output FOUNDATION Fieldbus output Device type Power supply Pressure transmitter compliant to Profile 3.0 Class A & B; ident. number 062D HEX. Power supply The transmitter operates from 10.2 to 32VDC with no polarity. For EEx ia approval power supply must not exceed 17.5VDC. Intrinsic safety installation according to FISCO model. Current consumption operating (quiescent): 11.7mA fault current limiting: 17.3mA max. The transmitter operates from 10.2 to 32VDC polarity independent. For EEx ia approval power supply must not exceed 24VDC (entity certification) or 17.5VDC (FISCO certification), according to FF-816. Current consumption operating (quiescent): 11.7mA fault current limiting: 17.3mA max. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Output signal Physical layer in compliance to IEC 1158-2/EN 61158-2 with transmission to Manchester II modulation, at 31.25kbit/sec. Function blocks/execution period 3 standard Analog Input blocks, 1 Multivariable Function Block/250ms max (each) Output interface PROFIBUS PA communication according to Profibus DP50170 Part 2/ DIN 19245 part 1-3. Output update time 250ms Function blocks 3 Analog Input, 2 Transducer, 1 MV (flow), 1 Physical Integral display 2-line, 6-character 19-segment alphanumeric display with additional bar chart display, optionally with back illumination. User-specific display: percentage of the output or OUT (input flow) Diagnostic message, alarms, measuring range infringements and changes in the configuration are also displayed. Additional blocks 1 custom Pressure with calibration Transducer block 1 enhanced resource block Number of link objects 10 Number of VCRs 16 Output interface FOUNDATION fieldbus digital communication protocol to standard H1, compliant to specification V. 1.5; FF registration in progress. Integral display 2-line, 6-character 19-segment alphanumeric display with additional bar chart display, optionally with back illumination. User-specific display: percentage of the output or Transmitter failure mode Permanent self-diagnostic; possible errors indicated in diagnostic parameters and in the status of process values. OUT (input flow) Diagnostic message, alarms, measuring range infringements and changes in the configuration are also displayed. Transmitter failure mode Permanent self-diagnostic; possible errors indicated in diagnostic parameters and in the status of process values. 7 2600T Pressure Transmitters Model 267CS Performance specifications Stated at reference condition to IEC 60770 ambient temperature of 20C (68F), relative humidity of 65%, atmospheric pressure of 1013hPa (1013mbar), mounting position with vertical diaphragm and zero based range for transmitter with isolating diaphragms in Hastelloy and silicone oil fill and HART digital trim values equal to 4-20mA span end points. Unless otherwise specified, errors are quoted as % of span. Some performance data (based to URL) are affected by the actual turndown (TD) as ratio between Upper Range Limit (URL) and calibrated span. IT IS RECOMMENDED TO SELECT THE TRANSMITTER SENSOR CODE PROVIDING THE TURNDOWN VALUE AS LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE CHARACTERISTICS. Dynamic performance (according to IEC 61298-1 definition) Standard configuration for instruments with turndown up to 30:1. Dead time: 30ms Time constant (63.2% of total step change): - sensors F to N: SS/267CS_4 Operating influences Ambient temperature (for turndown up to 15:1) per 20K (36F) change between the limits of -20C to +65C (-4 to +150F) for differential pressure sensor - (0.04% URL + 0.065% span) per 20K (36F) change between the limits of -40C to +80C (-40F to +176F) for absolute pressure sensor - (0.08% URL + 0.08% span) limited to (0.1% URL + 0.1% span) per the complete temperature range of 120K (216F) Static pressure (zero errors can be calibrated out at line pressure) Measuring range 150ms - sensor C: 400ms - sensor A: 1000ms Accuracy rating % of calibrated span, including combined effects of terminal based linearity, hysteresis and repeatability. For fieldbus versions SPAN refer to Analog Input Function Block outscale range For differential pressure sensor - 0.075% for TD from 1:1 to 10:1 URL - (0.075 + 0.005 x Span - 0.05)% for TD greater than 10:1 For absolute pressure sensor - 0.1% URL of absolute pressure sensor Process temperature measurement (RTD) - 0.3C Sensor A Sensors C, F, L, N on zero up to 2bar: 0.05% URL > 2bar: 0.05% URL/bar up to 100bar: 0.05% URL > 100bar: 0.05%URL/100bar on span up to 2bar: 0.05% span > 2bar: 0.05% span/bar up to 100bar: 0.05% span > 100bar: 0.05%span/100bar Supply voltage Within voltage/load specified limits the total effect is less than 0.001% of URL per volt. Load Within load/voltage specified limits the total effect is negligible. Radio frequency interference Total effect : less than 0.05% of span from 20 to 1000MHz and for field strengths up to 10V/m when tested with unshielded conduit, with or without meter. Common mode interference No effect from 250Vrms @ 50Hz, or 50VDC Mounting position Rotations in plane of diaphragm have negligible effect. A tilt from vertical causes a zero shift of sin x 0.35kPa (3.5 mbar, 1.4inH2O) of URL which can be corrected with the zero adjustment. No span effect. Stability 0.10% of URL over a thirty-six-month period Vibration effect 0.10% of URL (according to IEC 61298-3) 8 2600T Pressure Transmitters Model 267CS SS/267CS_4 Physical Specification Optional extras (Refer to ordering information sheets for variant availability related to specific model or versions code) Mounting brackets Materials Process isolating diaphragms (*) AISI 316 L ss; Hastelloy C276TM; Monel 400TM; Tantalum; Process flanges, adapters, plugs and drain/vent valves (*) AISI 316 L ss; Hastelloy C276TM; Monel 400TM, Kynar (PVDF) Sensor fill fluid Silicone oil; inert fill (Carbon Fluoride). Mounting bracket (**) For vertical and horizontal 60mm. (2in) pipes or wall mounting. Integral display plug-in rotatable LCD indicator. Supplemental customer tag AISI 316 ss tag fastened to the transmitter with stainless steel wire for customer's tag data up to a maximum of 30 characters and spaces. Cleaning procedure for oxygen service Hydrogen preparation Test Certificates (test, design, calibration, material traceability) AISI 316 L ss. Tag and manual language Gaskets (*) VitonTM; Perbunan (NBR); EPDM; PTFE (for sensors C, F, L, N) or FEP coated VitonTM (for sensor A) Sensor housing AISI 316 L ss. Bolts and nuts Stainless steel bolts and nuts Class A4-70 per ISO 3506, in compliance with NACE MR0175 Class II. Electronic housing and covers Process connections on flanges: 1/4in NPT on process axis selectable with 7/16in-20 UNF fixing threads or DIN 19213 connection with M10 fixing threads for working pressure up to 10MPa, 100bar , 1450psi or M12 fixing threads for greater working pressure up to 41MPa, 410bar, 6000psi on adapters: 1/2in NPT on process axis centre distance: 54mm (2.13in ) on flange; 51,54 or 57mm (2.01, 2.13 or 2.24in) as per adapters fittings. Electrical connections Barrel version Two 1/2 NPT or M20x1.5 threaded conduit entries, direct on housing. - Low-copper content aluminium alloy with baked epoxy finish; Communication connector - AISI 316 L ss. - HART : straight or angle Harting Han 8U connector and one plug. DIN version - PROFIBUS PA, FOUNDATION Fieldbus: M12x1 or 7/8 (without mating female plug). - Low-copper content aluminium alloy with baked epoxy finish. Covers O-ring VitonTM. Local zero and span adjustments Glass filled polycarbonate plastic (removable). Terminal block HART version: four terminals for signal/external meter plus four terminals for RTD connection wiring up to 2.5mm2 (14AWG) and four connection points for test and communication purposes. Fieldbus versions: two terminals for signal (bus connection) plus four terminals for RTD connection wiring up to 2.5mm2 (14AWG). Tagging AISI 316ss or plastic data plate attached to the electronics housing. Calibration Standard: at maximum span, zero based range, ambient temperature and pressure; Optional: at specified range and ambient conditions. Grounding Internal and external 4mm2 (12AWG) ground termination points are provided. Mounting position Transmitter can be mounted in any position. Electronics housing may be rotated by 360. A positive stop prevents over travel. Mass (without options) 3.5kg approx (8lb); add 1.5kg (3.4lb) for AISI housing. Add 650g (1.5lb) for packing. Packing Carton 23 x 25 x 27cm approx (9 x 10 x 11in). 9 2600T Pressure Transmitters Model 267CS Configuration Transmitter with HART communication and 4 to 20 mA Standard configuration Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the type plate. If calibration range and tag data are not specified, the transmitter will be supplied configured as follows: 4 mA Zero 20 mA Upper Range Limit (URL) Output Linear Damping 0.125s Transmitter failure mode 21mA Any or all the above configurable parameters, including Lower range-value and Upper range-value which must be the same unit of measure, can be easily changed by a PC running the configuration software SMART VISION with DTM for 2600T. The transmitter database is customized with specified flange type and material, o-ring and filling liquid. Transmitter with PROFIBUS PA communication Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the type plate. If calibration range and tag data are not specified, the transmitter will be supplied configured as follows: Measure Profile Pressure Engineering Unit mbar/bar Output scale 0% Lower Range Limit (LRL) Output scale 100% Upper Range Limit (URL) Output Linear Hi-Hi Limit Upper Range Limit (URL) Hi Limit Upper Range Limit (URL) Low Limit Lower Range Limit (LRL) Low-Low Limit Lower Range Limit (LRL) Limits hysteresis 0.5% of output scale PV filter 0.125s. Address 126 Any or all the above configurable parameters, including Lower range-value and Upper range-value which must be the same unit of measure, can be easily changed by a PC running the configuration software SMART VISION with DTM for 2600T. The transmitter database is customized with specified flange type and material, o-ring and filling liquid. 10 SS/267CS_4 Transmitter with FOUNDATION Fieldbus communication Transmitters are factory calibrated to customer's specified range. Calibrated range and tag number are stamped on the type plate. If calibration range and tag data are not specified, the transmitter will be supplied configured as follows: Measure Profile Pressure Engineering Unit mbar/bar Output scale 0% Lower Range Limit (LRL) Output scale 100% Upper Range Limit (URL) Output Linear Hi-Hi Limit Upper Range Limit (URL) Hi Limit : Upper Range Limit (URL) Low Limit Lower Range Limit (LRL) Low-Low Limit Lower Range Limit (LRL) Limits hysteresis 0.5% of output scale PV filter 0.125s Address Not necessary Any or all the above configurable parameters, including lower range value and upper range value which must be the same unit of measure, can be changed by any FOUNDATION Fieldbus compatible configurator. The transmitter database is customized with specified flange type and material, o-ring and filling liquid. TM Hastelloy is a Cabot Corporation trademark TM Monel is an International Nickel Co. trademark TM Viton is a Dupont de Nemour trademark (*) Wetted parts of the transmitter. (**) U-bolt material: AISI 400 ss; screws material: AISI 316 ss. 2600T Pressure Transmitters Model 267CS SS/267CS_4 MOUNTING DIMENSIONS (not for construction unless certified) - dimensions in mm (in) Transmitter with barrel housing 114 (4.49) 58 (2.28) 20 (0.79) Clearance for cover removal Terminal side 26 (1.02) Additional tag plate 61 (2.40) 30 (1.18) 41.3 (1.63) Process connection Drain/vent valve (side position) 108 (4.25) Transducer plate 186 (7.32) Housing rotation stop screw Threads for fixing screws (see process connection data) Space must be available to rotate the key-board cover 70 (2.76) 9 (0.35) 23 (0.91) with LCD indicator 54 (2.13) 96 (3.78) 71 (2.80) 90 (3.54) 83 (3.27) Identification plate Housing cover Captive screw for keys unit cover 117 (4.61) Electrical connection (with gland) Plate with keys legend 11 2600T Pressure Transmitters Model 267CS SS/267CS_4 Transmitter with DIN housing Transducer plate 96 (3.78) 54 (2.13) 83 (3.27) 117 (4.617 41.3 (1.63) Process connection 70 (2.76) Threads for fixing screws (see process connection data) Terminal side Identification plate Space must be available to rotate the key-board cover 43 (1.69) Electrical connection (with gland) Additional tag plate Electrical connection (with plug) Housing cover 27 (1.06) 48 (1.89) 20 (0.79) 139 (5.47) Housing rotation stop screw 90 (3.54) 61 (2.40) Captive screw for keys unit cover Plate with keys legend 20 (0.79) 107 (4.21) 138 (5.43) 168 (6.61) 12 23 (0.91) 2600T Pressure Transmitters Model 267CS SS/267CS_4 Possible mounting with bracket 72 (2.83) o 10 (0.4) o 11 (0.43) 60(2.36) 135.5 (5.33) 56(2.20) 136 (5.35) 72 (2.83) 57(2.24) 72 (2.83) 110 (4.33) 214 (8.43) Vertical pipe mounting Horizontal pipe mounting Vertical pipe mounting and transmitter above the mounting bracket Horizontal pipe mounting and transmitter above the mounting bracket 13 2600T Pressure Transmitters Model 267CS SS/267CS_4 Electrical connections Standard Terminal block and fieldbus connector versions Earthing/potential equalizing terminal 7/8" connector Cable entry 4-wire RTD connection Test sockets for 4...20mA (not in function with fieldbus transmitters) 14 12 13 11 Screw terminals for 0.5...2.5mm2 - wires 1 3 2 4 M12 x 1 connector 2 1 3 4 Output signal/ power supply PIN (male) IDENTIFICATION FOUNDATION PROFIBUS Fieldbus PA 1 FFPA+ 2 FF+ GROUND 3 SHIELD PA- 4 GROUND SHIELD Mating female plug NOT SUPPLIED Harting Han 8U connector 1 2 + Harting pin identification (view onto socket) 14 2600T Pressure Transmitters Model 267CS SS/267CS_4 BASIC ORDERING INFORMATION model 267CS Multivariable Transmitter for mass flow Select one character or set of characters from each category and specify complete catalog number. Refer to additional ordering information code and specify one or more codes for each transmitter if additional options are required. 2 BASE MODEL - 1st to 5th characters 6 7 C S X X X X X X X Multivariable transmitter for mass flow - BASE ACCURACY 0.075% SENSOR - Span limits - 6th character 0.05 and 1kPa 0.5 and 10mbar 0.2 and 6 kPa 2 and 60mbar 0.4 and 40kPa 4 and 400mbar 2.5 and 250kPa 25 and 2500mbar 20 and 2000kPa 0.2 and 20bar A C F L N 0.2 and 4nH2O 0.8 and 24inH2O 1.6 and 160inH2O 10 and 1000inH2O 2.9 and 290psi Static pressure range - 7th character 0 to 0.6MPa 0 to 2MPa 0 to 10MPa 0 to 41MPa 0 to 6bar 0 to 20bar 0 to 100bar 0 to 410bar 0 to 87psi 0 to 290psi 0 to 1450psi 0 to 5945psi (Note 1) (Note 2) (Note 2) (Note 2) 1 2 3 4 (Note 3) (Note 3) (Note 3) (Note 3) (Note 3) NACE NACE NACE NACE NACE NACE NACE NACE NACE NACE Diaphragm material / Fill fluid (wetted parts) - 8th character AISI 316 L ss Hastelloy C276TM Monel 400TM Monel 400TMg old plated Tantalum AISI 316 L ss Hastelloy C276TM Monel 400TM Monel 400TM gold plated Tantalum Silicone oil Silicone oil Silicone oil Silicone oil Silicone oil Inert fluid Inert fluid Inert fluid Inert fluid Inert fluid S K M V T A F C Y D Process flanges/adapters material and connection (wetted parts) - 9th character 1 AISI 316 L ss (Horizontal connection) /4in NPT-f direct (7/16in UNF U.S. drilling) 1 AISI 316 L ss (Horizontal connection) /4in NPT-f direct (DIN 19213) 1 AISI 316 L ss (Horizontal connection) /2in NPT-f through adapter (7/16in UNF U.S. drilling) 1 Hastelloy C276TM (Horizontal connection) /4in NPT-f direct (7/16in UNF U.S. drilling) 1 Hastelloy C276TM (Horizontal connection) /4in NPT-f direct (DIN 19213) 1 /2in NPT-f through adapter (7/16in UNF U.S. drilling) Hastelloy C276TM (Horizontal connection) 1 Monel 400TM (Horizontal connection) /4in NPT-f direct (7/16in UNF U.S. drilling) 1 Monel 400TM (Horizontal connection) /4in NPT-f direct (DIN 19213) 1 Monel 400TM (Horizontal connection) /2in NPT-f through adapter (7/16in UNF U.S. drilling) Kynar (PVDF) (Horizontal connection) (MWP=1MPa,10bar) 1/4in NPT-f direct (7/16in UNF U.S. drilling) NACE NACE NACE NACE NACE NACE NACE NACE NACE A C B D F E G L H P Bolts/Gasket (wetted parts) - 10th character Stainless steel (NACE) Stainless steel (NACE) Stainless steel (NACE) Stainless steel VitonTM PTFE (MWP 10MPa) EPDM Perbunan (Note 3) NACE NACE NACE 3 4 5 6 Housing material and electrical connection - 11th character Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) Aluminium alloy (Barrel version) AISI 316 L ss (Barrel version) AISI 316 L ss (Barrel version) Aluminium alloy (DIN version) Aluminium alloy (DIN version) Aluminium alloy (DIN version) 1 /2in NPT M20 x 1.5 (CM 20) Harting Han 8U connector Fieldbus connector 1 /2in NPT M20 x 1.5 (CM20) M20 x 1.5 (CM 20) Harting Han 8U connector Fieldbus connector (Not available FM, CSA) (Note 4) (Not available, ATEX EExd, FM, CSA) (Note 4) (Not available, ATEX EExd, FM, CSA) (Not available FM, CSA) (Not available FM, CSA) (Note 4) (Not available, ATEX EExd, FM, CSA) (Note 4) (Not available, ATEX EExd, FM, CSA) A B E G S T J K W Output/Additional options - 12th character HART digital communication and 4 to 20mA HART digital communication and 4 to 20mA PROFIBUS PA PROFIBUS PA FOUNDATION Fieldbus FOUNDATION Fieldbus Modbus RS485 Modbus RS485 Modbus RS232 Modbus RS232 No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") No additional options Options requested (to be ordered by "Additional ordering code") (Notes 5, 6) (Note 5) (Notes 5, 6) (Note 6) (Notes 5, 6) (Note 6) (Notes 5, 6) (Notes 5, 6) (Notes 5, 6) (Notes 5, 6) H 1 P 2 F 3 M 5 N 6 15 2600T Pressure Transmitters Model 267CS SS/267CS_4 ADDITIONAL ORDERING INFORMATION for model 267CS Add one or more 2-digit code(s) after the basic ordering information to select all required options XX XX XX XX XX XX XX XX XX XX XX Drain/vent valve (material and position) (wetted parts) AISI 316 L ss on process axis (Note 7) NACE AISI 316 L ss on flange side top (Note 7) NACE AISI 316 L ss on flange side bottom (Note 7) NACE Hastelloy C276TM on process axis (Note 8) NACE Hastelloy C276TM on flange side top (Note 8) NACE Hastelloy C276TM on flange side bottom (Note 8) NACE Monel 400TM on process axis (Note 9) NACE Monel 400TM on flange side top (Note 9) NACE Monel 400TM on flange side bottom (Note 9) NACE Electrical certification ATEX Group II Category 1/2 GD - Intrinsic Safety EEx ia ATEX Group II Category 1/2 G - Flameproof EEx d ATEX Group II Category 3 GD - Type of protection "N" EEx nL energy limited Factory Mutual (FM) - Intrinsically Safe Factory Mutual (FM) - Explosion Proof (only with 1/2in NPT electrical connection and stainless steel label) Canadian Standard Association - Intrinsically Safe (pending) Canadian Standard Association - Explosion Proof Integral LCD Digital LCD integral display Backlit digital LCD integral display Mounting bracket (shape and material) For pipe mounting AISI 316 L ss For wall mounting AISI 316 L ss Operating manual German V1 V2 V3 V4 V5 V6 V7 V8 V9 E1 E2 E3 EA EB ED EE L1 L2 B2 B4 Labels & tag language German in stainless steel (not available with DIN Electronic Housing code J, K, W) German and English plastic (not suitable for Factory Mutual - Explosion Proof) Additional tag plate In stainless steel Preparation procedure Oxygen service cleaning (only available with inert fill and Viton gasket)- Pmax = 12MPa/120bar/1740psi; Tmax = 60 C/140 F) Hydrogen service preparation M1 T1 TA I1 P1 P2 Certificates Inspection certificate EN 10204-3.1.B of calibration Inspection certificate EN 10204-3.1.B of the cleanliness stage according to DIN 25410 Inspection certificate EN 10204-3.1.B of helium leakage test of the sensor module Inspection certificate EN 10204-3.1.B of the pressure test Certificate of compliance with the order EN 10204-2.1 of instrument design C1 C3 C4 C5 C6 Material traceability Certificate of compliance with the order EN 10204-2.1 of process wetted parts Inspection certificate EN 10204-3.1.B of process wetted parts (small parts with certificate of compliance EN 10204) Test report EN 10204-2.2 of the pressure bearing and process wetted parts H1 H3 H4 Connector Fieldbus 7/8 (without mating female plug) Fieldbus M12x1 (without mating female plug) Harting Han 8U - straight entry Harting Han 8U - angle entry 16 (Notes 6, 10) (Notes 6, 10) (Notes 5, 10) (Notes 5, 11) U1 U2 U3 U4 2600T Pressure Transmitters Model 267CS Note 1: Not available with sensor code C, F, L, N Note 2: Not available with sensor code A Note 3: Suitable for oxygen service Note 4: Select type in additional ordering code Note 5: Not available with Electronic Housing code G and W Note 6: Not available with Electronic Housing code E and K Note 7: Not available with Process flanges/adapters code D, E, F, G, H, L, P Note 8: Not available with Process flanges/adapters code A, B, C, G, H, L, P Note 9: Not available with Process flanges/adapters code A, B, C, D, E, F, P SS/267CS_4 Note 10: Not available with Electronic housing code T, S, A, B, J Note 11: Not available with Electronic housing code T, S, A, B, J, K. TM Hastelloy is a Cabot Corporation trademark TM Monel is an International Nickel Co. trademark TM Viton is a Dupont de Nemour trademark Standard delivery items (can be differently specified by additional ordering code) - Adapters supplied loose - Plug on axis (no drain/vent valves) - General purpose (no Ex design) - No meter/display, no mounting bracket - English manual and labels (stainless steel nameplate for Barrel housing code A, B, E, G, S, T; plastic nameplate for DIN housing code J, K, W) - Configuration with kPa and deg. C units - No test, inspection or material traceability certificates THE SELECTION OF SUITABLE WETTED PARTS AND FILLING FLUID FOR COMPATIBILITY WITH THE PROCESS MEDIA IS A CUSTOMER'S RESPONSIBILITY, IF NOT OTHERWISE NOTIFIED BEFORE MANUFACTURING. 17 2600T Pressure Transmitters Model 267CS 18 SS/267CS_4 2600T Pressure Transmitters Model 267CS SS/267CS_4 19 2600T Pressure Transmitters Model 267CS SS/267CS_4 The Company's policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. ABB has Sales & Customer Support expertise in over 100 countries worldwide Printed in Italy (01.04) www.abb.com/instrumentation SS/267CS_4 (c) ABB 2004 ABB Ltd Howard Road, St. Neots Cambridgeshire, PE19 3EU UK Tel: +44(0)1480 475321 Fax: +44(0)1480 217948 ABB Inc. 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB Automation Products GmbH Schillerstrasse 72 D-32425 Minden Germany Tel: +49 (0) 551 905 534 Fax: +49 (0) 551 905 555