Datasheet
CP M SNT 180W 24V 7,5A Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-2083
www.weidmueller.com
Technical data
Creation date September 10, 2010 5:15:05 PM CEST
Last update 28.06.2010 / We reserve the right to make technical changes. 2
Dimensions (1)
Weight 1.05 kg Length 150 mm
Width 50 mm Height 130 mm
temperature
Ambient temperature (operational) -25 °C...+70 °C Storage temperature -40 °C...+85 °C
Input
AC current consumption 0.9 A @ 230 V AC / 1.8 A @
115 V AC
Conductor connection system
Screw connection
DC current consumption 0.6 A @ 370 V DC / 1.7 A @
120 V DC
DC input voltage range 80…370 V DC (Derating @
120 V DC)
Frequency range AC 47...63 Hz Input fuse Yes
Input fuse (internal) Yes Input voltage AC, max. 264 V
Input voltage AC, min. 85 V Input voltage DC, max. 370 V
Input voltage DC, min.
80 V
Input voltage range AC 85…264 V AC (Derating @
100 V AC)
Recommended back-up fuse 6 A / DI, safety fuse
10 A, Char. B, circuit breaker
6 A, Char. C, circuit breaker
making current
max. 40 A
rated input voltage 100...240 V AC (wide-range
input)
output
Conductor connection system Screw connection Output current 7.5 A
Output voltage (adjustable via potentiometer
on front)
Output voltage type
DC
Output voltage, max. 29.5 V Output voltage, min. 22.5 V
Parallel connection option yes, max. 5 Powerboost @ 24 V DC, 60 °C 9 A for 1 min, ED = 5 %
Rated (nominal) output current @ UNom
7,5 A @ 60 °C
continous output current @ 24 V DC 9.0 A @ 45 °C, 8.0 A @ 55
°C, 5.6 A @ 70 °C
rated output voltage 24 V DC ± 1 % residual ripple, breaking spikes < 50 mVPP @ 24 V DC, IN
General data
AC failure bridging time @ INom > 20 ms @ 230 V AC / > 20
ms @ 115 V AC
Ambient temperature (operational)
-25 °C...+70 °C
Current limiting > 120 % IN DIN Rail compatibility TS 35
Degree of efficiency 91 % @ 230 V AC / 88 % @
115 V AC
Housing version
Metal, corrosion resistant
Indication
Operation, green LED
MTBF > 500,000 h acc. to IEC 1709
(SN29500
Mounting position, installation notice Horizontal on TS35 mounting
rail, with 50 mm of clearance
at top and bottom for air
circulation. Can be mounted
side by side with no space in
between.
Power factor (approx.)
> 0.94 @ 230 V AC / > 0.99
@ 115 V AC
Protection against reverse voltages from the
load 30…35 V DC