1
Solid-state Timer
H3CR
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions
or comments. Refer to Warranty and Application Considerations (page 52), and Safety Precautions (page 22, 44, 51).
DIN 48 48-mm Multifunctional Timer Series
Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low
Voltage, and EMC Directives.
Approved by UL and CSA.
Lloyds/NK approvals.
Six-language instruction manual provided.
Broad Line-up of H3CR Series
Note: H3CR-AS, H3CR-A8S: Transistor output models
Contents
Solid-state Timer
H3CR-A .......................................................................................................................................... 2
H3CR-F........................................................................................................................................... 26
H3CR-G .......................................................................................................................................... 34
H3CR-H .......................................................................................................................................... 42
Common to ALL Timers
Operation ........................................................................................................................................ 52
Accessories .................................................................................................................................... 54
Safety Precautions.......................................................................................................................... 58
H3CR
Multifunctional Timer Twin Timer Star-delta Timer Power OFF-delay Timer
H3CR-GH3CR-F
11-pin model
8-pin model
11-pin model
8-pin model
8-pin model
8-pin model
11-pin model
H3CR-A
H3CR-A
H3CR-AS
H3CR-AP
H3CR-A8
H3CR-A8S
H3CR-A8E
8-pin with
instantaneous
contact output
model
H3CR-F
H3CR-FN
H3CR-F8
H3CR-F8N
H3CR-G8L
H3CR-G8EL
H3CR-HRL
H3CR-H8L
H3CR-H8RL
H3CR-H
2
Solid-state Multi-functional Timers
H3CR-A
Multiple Operating Modes and Multiple Time
Ranges. DIN 48 x 48-mm Multifunctional
Timer.
A wide AC/DC power supply range greatly reduces the number
of timer models kept in stock.
A wide range of applications with multiple operating modes,
eight modes for 11-pin models and five modes for 8-pin models.
Ecological design with reduced current consumption.
Easy sequence checking with instantaneous outputs for a zero
set value.
Length of 75 mm or less when panel-mounted with a P3G-08
Socket (H3CR-A8E, 100 to 240 VAC, 100 to 125 VDC)
PNP input models available.
Standards: UL, CSA, NK, LR, CCC, EN 61812-1, and CE
Marking.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 3 for avail-
ability.
1. Number of Pins
None: 11-pin models
8: 8-pin models
2. Input Type for 11-pin Models
None: No-voltage input (NPN type)
P: Voltage input (PNP type)
3. Output
None: Relay output (DPDT)
S: Transistor output (NPN/PNP universal use)
E: Relay output (SPDT) with instantaneous relay output (SPDT)
4. Suffix
301: Double time scale (range) models (0.1 s to 600 h)
5. Supply Voltage
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC
24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC
24-48AC/DC: 24 to 48 VAC/VDC (Only for H3CR-A8E)
H3CR-A@ @ @ - @ @
123 45
H3CR-A
3
Ordering Information
List of Models
11-pin Models
8-pin Models
Output Supply voltage Input type Time range Operating mode
(See note 2) Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input 0.05 s to 300 h Eight multi-modes: A, B,
B2, C, D, E, G, J
H3CR-A
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
Voltage input Eight multi-modes: A, B,
B2, C, D, E, G, J
H3CR-AP
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input 0.1 s to 600 h H3CR-A-301
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Transistor
(Photocoupler) 24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
0.05 s to 300 h H3CR-AS
Output Supply voltage Input type Time range Operating mode
(See note 2) Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-input available 0.05 s to 300 h Five multi-modes: A, B,
B2, E, J
(Power supply start)
H3CR-A8
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
0.1 s to 600 h H3CR-A8-301
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Transistor
(Photocoupler) 24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
0.05 s to 300 h H3CR-A8S
Time-limit contact and
instantaneous contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
H3CR-A8E
24 to 48 VAC/VDC (50/60 Hz)
Supply voltage
Note: 1. Specify both the model number and supply voltage when ordering.
Example: H3CR-A 100-240AC/100-125DC
2. The operating modes are as follows
A: ON-delay D: Signal OFF-delay
B: Flicker OFF start E: Interval
B2: Flicker ON start G: Signal ON/OFF-delay
C: Signal ON/OFF-delay J: One-shot
H3CR-A
4
Accessories (Order Separately)
Adapter, Protective Cover, Hold down Clip, Setting Ring and Panel Cover
*1
The Y92A-48B Protective Cover and the Y92P-48G
@
Panel Cover can not be used at the same time with the Y92F-73/-74 Flush Mounting Adapter.
*2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-73/-74 Flush
Mounting Adapter and the Y92P-48G@ Panel Cover cannot be used at the same time with Y92A-48B Protective Cover.
*3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover.
*4
The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G
@
Panel Cover.
Sockets
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Note: For details, refer to your OMRON website.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-73 *1
Y92F-74 *1
Protective Cover Y92A-48B *2
Hold-down Clip (Sold in sets of
two) For PF085A Socket Y92H-8
For PL08 or PL11 Sockets Y92H-7
Setting Ring A Y92S-27 *3
Setting Ring B and C Y92S-28 *3
Panel Cover Light gray (5Y7/1) Y92P-48GL *4
Black (N1.5) Y92P-48GB *4
Timer Round Sockets
Pin Connection Terminal Models
11-pin Front Connecting DIN track mounting P2CF-11
DIN track mounting
(Finger-safe type)
P2CF-11-E
Back Connecting Screw terminal P3GA-11
Solder terminal PL11
Wrapping terminal PL11-Q
PCB terminal PLE11-0
8-pin Front Connecting DIN track mounting P2CF-08
DIN track mounting
(Finger-safe type)
P2CF-08-E
DIN track mounting PF085A
Back Connecting Screw terminal P3G-08
Solder terminal PL08
Wrapping terminal PL08-Q
PCB terminal PLE08-0
Application Model Remarks
For back connecting socket Y92A-48G For P3G-08 and P3GA-11
H3CR-A
5
Specifications
General
*1 The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.
For details, refer to your OMRON website.
*2 CCC certification requirements
Time Ranges
Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at
all time range settings.
For details, refer to your OMRON website.
Standard (0.05-s to 300-h) Models
Item H3CR-A/-AS/-A-301 H3CR-AP H3CR-A8/-A8S/-A8-301 H3CR-A8E
Operating mode A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval
G: Signal ON/OFF-delay
J: One-shot
A: ON-delay (power supply start)
B: Flicker OFF start (power supply start)
B2: Flicker ON start (power supply start)
E: Interval (power supply start)
J: One-shot (power supply start)
Pin type 11-pin 8-pin
Input type No-voltage input Voltage input ---
Time-limit output type H3CR-A/-A8/-AP/-A-301/-A8-301: Relay output (DPDT)
H3CR-AS/-A8S: Transistor output (NPN/PNP universal) *1
Relay output (SPDT)
Instantaneous output type --- Relay output (SPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC: GB/T 14048.5 *2
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1 for Timers with Contact Outputs.
Output category according to EN60947-5-2 for Timers with Transistor Outputs.
Recommended fuse Contact Output:
0216005 (250 VAC, 5 A), manufactured by Littelfuse
Transistor Output:
0216.100 (250 VAC, 100 mA) manufactured by Littelfuse
Rated operating voltage Ue
Rated operating current Ie
Contact Output:
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
Transistor Output:
DC-13: Ue: 30 VDC, Ie: 0.1 A
Rated insulation voltage 250 V
Rated impulse withstand
voltage
(altitude: 2,000 m max.)
4 kV (at 240 VAC)
Conditional short-circuit
current
1000 A
Time unit s (sec) ×10 s (10 sec) min (min) ×10 min (10 min) h (hrs) ×10 h (10 hrs)
Full scale
setting
1.2 0.05 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12
3 0.3 to 3 3 to 30 0.3 to 3 3 to 30 0.3 to 3 3 to 30
12 1.2 to 12 12 to 120 1.2 to 12 12 to 120 1.2 to 12 12 to 120
30 3 to 30 30 to 300 3 to 30 30 to 300 3 to 30 30 to 300
H3CR-A
6
Ratings
Note: 1. DC ripple rate: 20% max. (A single-phase, full-wave-rectification power supply can be used).
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24-
VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)
For details, consult your OMRON sales representative.
4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the
input circuit.
5. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
6. For details, see Input Connections: No-voltage Input Signal Levels on page 11, and Input Connections: Voltage Input Signal Levels on
page 12.
Rated supply voltage (See notes 1, 2, and 5.)
100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-A8E)
(See note 3.)
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Power reset Minimum power-opening time: 0.1 s
Input (See note 6.) No-voltage Input
ON impedance: 1 kΩ max.
ON residual voltage: 1 V max.
OFF impedance: 100 kΩ min.
Voltage Input
Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF
Load connectable in parallel with inputs (terminals 6 and 7).
100 to 240 VAC/100 to 125 VDC
High (logic) level: 85 to 264 VAC/85 to 137.5 VDC
Low (logic) level: 0 to 10 VAC/0 to 10 VDC
24 to 48 VAC/12 to 48 VDC
High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC
Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC
Power consumption H3CR-A/-A8
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.0 VA (1.6 W) Relay OFF: approx. 1.3 VA (1.1 W)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.8 W Relay OFF: approx. 0.2 W
H3CR-AP (See note 3)
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.5 VA (2.2 W) (See note 4.) Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.9 W (See note 4.) Relay OFF: approx. 0.3 W (See note 4.)
H3CR-A8E
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON/OFF: approx. 2 VA (0.9 W)
24 to 48 VAC/VDC
(When at 24 VDC)
Relay ON/OFF: approx. 0.9 W
H3CR-AS/-A8S
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Output ON: 0.3 W Output OFF: 0.2 W
Control outputs Models with Contact Outputs
H3CR-A/-A8/-AP
5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ = 1)
Minimum applied load: 10mA at 5 VDC (failure level: P reference value)
Contact materials: Ag-alloy
H3CR-A8E
5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ = 1)
Minimum applied load: 10mA at 5 VDC (failure level: P reference value)
Contact materials: AgSnIn
Transistor output: Open collector(NPN/PNP)
H3CR-AS/-A8S
100 mA max at 30 VDC max., residual voltage: 2 VDC max.
H3CR-A
7
Characteristics
Note: 1. The value is ±5% FS +100 ms to 0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.
2. The influence of voltage of the H3CR-A8E (24 to 48 VAC/12 to 48 VDC) is ±2.0% FS max. with a single-phase power supply with full-
wave rectification.
3. Refer to the Life-test Curve (Reference).
4. Contact output only.
Life-test Curve (Reference)
Accuracy of operating
time
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)
Setting error ±5% FS ±50 ms (See note 1)
Reset time Min. power-opening time: 0.1 s max.
Min. pulse width: 0.05 s (H3CR-A/-AS)
Reset voltage 10% max. of rated supply voltage
Influence of voltage
(See note 2)
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)
Influence of temperature ±1% FS max. (±1%±10 ms max. in a range of 1.2 s or 3 s)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-
current-carrying metal parts)
2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP
Impulse withstand
voltage
5 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to
125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC
Noise immunity ±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance Destruction: 1,000 m/s2 3 times each in 6 directions
Malfunction: 100 m/s2 3 times each in 6 directions
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy
(See note 4)
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 3)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 90 g
10,000
5,000
1,000
500
100
01 23 45
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (x 103)
250 VAC/30
VDC (cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-A
8
Connections
Block Diagrams
H3CR-A/-AS/-A-301
AC (DC) input
Output circuit
Reset input, start input, and gate input Input circuit
Power supply
circuit
Oscillation
circuit
Counting
circuit
Zero setting
detection
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
H3CR-AP
AC (DC) input
Output circuit
Start Input circuit
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Counting
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
H3CR-A
9
I/O Functions
Note: H3CR-AP incorporates start input only.
Models H3CR-A8/-A8E/-A8S/-A8-301 do not have an input function.
Inputs (for -A/
-AS models) Start Starts time-measurement.
Reset Interrupts time-measurement and resets time-measurement value. Timing operation is stopped and the
control output turns OFF (it is reset).
Gate The timing operation is interrupted while the gate input is active.
Outputs Control output Outputs are turned ON according to designated output mode when preset value is reached.
H3CR-A8/-A8S/A8-301
AC (DC) input
Output circuit
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Counting
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
H3CR-A8E
AC (DC) input
Output circuit
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Counting
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
Instantaneous
output circuit
H3CR-A
10
Terminal Arrangement
Note: 1. The delayed contact of conventional Timers was indicated as
The contact symbol of the H3CR-A is indicated as because its operating mode is eight multi-modes (five multi-modes for the H3CR-A8).
2. Do not use an empty terminal on the H3CR-AP/-AS/-A8S as a relay terminal or otherwise.
11-pin Models
Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10
are the same as for the H3CR-A.
Note: 1. Terminal 5 is empty.
2. Separate power supplies can be used for the Timer and in-
puts.
8-pin Models
Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the
same as for the H3CR-A8.
H3CR-A/-A-301 (Contact Output)
Reset input
Start input
Gate input
Power supply
Power supply
Start input
H3CR-AP (Contact Output)
H3CR-A8/-A8-301 (Contact Output)
Power supply
H3CR-A8S (Transistor Output)
Power supply
H3CR-A8E (Contact Output)
Power supply
H3CR-A
11
Input Connections
H3CR-A/-AS/-A-301
5
6
7
2
+
5
6
7
2
+
5
6
7
2
The inputs of the H3CR-A/-AS/-A-301 are no-voltage (short-circuit or open) inputs.
No-voltage Input Signal Levels
No-contact Input Contact Input No-contact Input
No-voltage Inputs
Sensor Timer
Gate
Start
Reset
Operates with transistor ON
Timer
Operates with relay ON
Gate
Start
Reset
Input (0 V)
Sensor
Timer
Operates with transistor ON
Gate
Start
Reset
Input (0 V)
(Connection to NPN open
collector output sensor.)
12 to 24 VDC
(sensor power supply)
DC power
supply
Input (0 V)
No-contact
input
1. Short-circuit level
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 kΩ max.
2. Open level
Transistor OFF
Impedance when OFF: 100 kΩ min.
Contact
input
Use contacts which can
adequately switch 0.1 mA at 5 V
(Connection to a voltage
output sensor.)
12 to 24 VDC
(sensor power supply)
DC power
supply
H3CR-A
12
H3CR-AP
6
10
7
6
10
7
22
6
10
7
2
+
+
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Input Signal Levels
No-contact Input No-contact Input Contact Input
Sensor
Timer
Start
Operates with PNP transistor ON Operates with NPN transistor ON
Timer
Sensor
Timer
Operates with relay ON
Voltage Inputs
Input 0V
Start
Input 0V
Start
Input 0V
AC power supply
DC power supply
(Connection to PNP open
collector output sensor)
12 to 24 VDC
(sensor power supply)
DC power
supply
Power
supply (+)
Power
supply
()
(Connection to NPN open
collector output sensor)
12 to 24 VDC
(sensor power supply)
DC power
supply
Power
supply (+)
Power
supply ()
Note: The input circuit is isolated from the
power supply circuit. Thus, an NPN
transistor can be connected.
Power
supply (+)
Power
supply ()
Note: Refer to the signal levels in the
following table and be aware of the
minimum applicable load of the relay.
No-contact
input
1. Transistor ON
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact
input
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 VDC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
Note: Before making connections, refer to Safety Precautions (H3CR-
@
).
H3CR-A
13
Operation
Timing Chart (Refer to page 20 for application examples.)
H3CR-A/-AS/-AP*/-A-301
Note: 1. Allow at least 0.1 s for the Timer reset time if the power supply is reset due to an interruption in the power supply.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1)
4. H3CR-AP model incorporates start input only. As such, the power supply is reset.
5. Model H3CR-AS only has operation equivalent to time-limit contact: NO.
6. When the setting dial is turned all the way past 0 for instantaneous output, "t" (set time) in the above time chart is 0-sec operation.
7. During timer operation, the flash frequency changes when 90% of the set time has been reached.
Operating
mode
Timing chart
A: ON-delay
B:
Flicker OFF
start
B2:
Flicker ON
start
C:
Signal ON/
OFF-delay
t t
t
Power
Start
Output relay (NC)
Power indicator
Power
Output
Basic operation
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
(See note 4) Reset
(See Note 7)
t t t t
Basic operation
Power
Output
Power
Power indicator
Start
Output relay (NC)
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is invalid while
the Timer is in operation.
(See note 4) Reset
(See Note 7)
ttt t
Basic operation
Power
Output
Power
Start
Power indicator
Output relay (NC)
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
(See note 4) Reset
(See Note 7)
tttt
Basic operation
Power
Output
Power
Start
(See note 4) Reset
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is valid and
retriggerable while the Timer
is in operation.
(See Note 7)
H3CR-A
14
Gate Signal Input (This timing chart indicates the gate input in operating mode A (ON-delay operation).)
Operating
mode
Timing chart
D:
Signal OFF-
delay
E:
Interval
G:
Signal ON/
OFF-delay
J:
One-shot
output
t
Basic operation
Power
Output
Output relay (NC)
Power indicator
Power
Start
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(See note 5) Reset
(See Note 8)
t
Power
Start
Output relay (NC)
Power indicator
Power
Output
Output relay (NO)
(Output indicator)
Basic operation
Start
(See note)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(Previous start input
will be cancelled.)
(See note 5) Reset
(See Note 8)
tttt
Basic operation
Power
Output
Power
Start
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is valid and
retriggerable while the Timer
is in operation.
(See note 5) Reset
(See Note 8)
t
Basic operation
Output
Power
Power
Start
(See note 5) Reset
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
Start
(See note) 1±0.6 s
(Fixed)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(Previous start input will
be cancelled.)
(See Note 8)
t
1
t
2
Power
Start
Gate
Reset
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Output
relay
Note: 1. Allow at least 0.1 s for the Timer reset time if the power
supply is reset due to an interruption in the power supply.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter "t" in the timing charts indicates the set time, and
"t-a" means that the period is less than the set time.
(t - a < 1)
4.
In J Mode, there will be only one output even if the start input is
longer than the set time.
5. H3CR-AP model incorporates start input only.
As such, the
power supply is reset.
6. Model H3CR-AS only has operation equivalent to time-limit
contact: NO.
7. When the setting dial is turned all the way past 0 for
intantaneous output, "t" (set time) in the above time chart is
0-sec operation.
8. During timer operation, the flash frequency changes when
90% of the set time has been reached.
Note: The set time is the sum of t1 and t2.
Start and reset are also both enabled when the gate signal is ON.
H3CR-A
15
H3CR-A8/-A8S/-A8-301
Note: 1. Allow a timer reset time (Rt) of 0.1 s or longer.
2. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1)
3. Model H3CR-A8S only has operation equivalent to time-limit contact: NO.
4. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation.
5. You can use J Mode to use the power supply as the start input.
6. During timer operation, the flash frequency changes when 90% of the set time has been reached.
Operating
mode
Timing chart
A:
ON-delay
B:
Flicker OFF
start
B2:
Flicker ON
start
v
E:
Interval
J:
One-shot
output
t
Power
Output
Basic operation
Power
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
(See note 6)
Power
Output
tttt
Power
Output relay (NC)
Output relay (NO)
(output indicator)
t t t t
t Rt tat−a
Basic operation
Power indicator
(See note 6)
t t t t
Power
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Power indicator
(See note 6)
t
Power
Output
Basic operation
Power
Output relay (NC)
Output relay (NO)
(output indicator)
Power indicator
(See note 6)
t
Power
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
Power indicator
(See note 6)
H3CR-A
16
H3CR-A8E
Note: Refer to page 15.
Operating
mode
Timing chart
A:
ON-delay
B:
Flicker OFF
start
B2:
Flicker ON
start
E:
Interval
J:
One-shot
output
t
Power
Power indicator
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(See Note 6)
tttt
t t t t
t Rt tat−a
(See Note 6)
Power indicator
Power
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
Power
Output
tttt
Power
Power indicator
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(See Note 6)
t
Power
Output
Basic operation
Power
Power indicator
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(See Note 6)
t
Power
Power indicator
Power
Output
Basic operation
(Fixed) (Fixed)
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO) 1±0.6 s
(Fixed)
(See Note 6)
H3CR-A
17
Nomenclature
Operating mode display window
Scale range display windows
Time unit display window
Power indicator (green) (Flashes when Timer
operates; lit when Timer stops operating)
Output indicator (orange)
(Lit when output)
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale; with the H3CR-A@-301,
select from 2.4, 6, 24, or 60 at
full scale.)
Time setting
knob (set time)
Time unit selector (select one from
sec, 10s, min, 10m, hrs, and 10h)
Operating mode selector
Select a mode from:
A, B, B2, C, D, E, G, and J (H3CR-A, -AP, and -AS)
A, B, B2, E and J (H3CR-A8, -A8S, and -A8E)
Scale range display windows changes as below by
turning
the Time range selector clockwise.*
* On the H3CR-A@-301 type, the time is twice as long.
0 0.2 0.4 0.6 0.8 1.0 1.2
0 0.5 1 1.5 2 2.5 3
024681012
0 5 10 15 20 25 30
H3CR-A
18
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Note: There are no restrictions to the mounting direction.
*These dimensions vary with the kind of DIN track (reference value).
48
48
66.6
52.3
15
6
44.8 × 44.8
0.7
48
66.6
48
15
652.3
0.7
44.8 × 44.8
11 pins
39 dia.
8 pins
39 dia.
H3CR-A
H3CR-AP
H3CR-AS
H3CR-A-301
H3CR-A8
H3CR-A8S
H3CR-A8E
H3CR-A8-301
50 16.5
50
Dimensions with Set Ring
Y92S-27/-28 (Order Separately)
Panel cover
42 dia.
Time Setting
Ring
100.8* 98.5
2.3*
89.9* 87.6
2.3*
80
15 15 75
81.5 81.5
H3CR-A8@
H3CR-A8-301
H3CR-A8E
H3CR-A8S
Y92F-30
P3GA-11 Y92F-30 P3G-08
H3CR-A
H3CR-A-301
H3CR-AS
H3CR-AP
P2CF-11
P2CF-11-E
P2CF-08
P2CF-08-E
H3CR-A
H3CR-A-301
H3CR-AS
H3CR-AP
+
Adapter
(When
Y92A-48G
mounted)
H3CR-A8@
H3CR-A8-301
H3CR-A8E
H3CR-A8S
+
Adapter
(When
Y92A-48G
mounted)
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@Dimensions with Back Connecting Socket
P3G-08/P3GA-11
H3CR-A
19
Accessories (Order Separately)
Protective Cover
Y92A-48B
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
This Protective Cover cannot be used together with the Y92F-73/-74
flush mounting adaptor or the panel cover.
Hold-down Clip
Y92H-8
The Y92H-8 Hold-down Clip is attached to the PF085A socket.
Y92H-7
Y92H-7 Hold-down Clip is attached with screws together with the
PL08 socket or the PL11 socket.
H3CR-A
20
Application Examples (H3CR-A)
A Mode: ON-delay
ON-delay operation (A mode) is a basic mode.
1.Power-ON Start/Power-OFF Reset
The Power-ON start/Power-OFF reset operation is a standard
operating method.
2.Signal Start/Signal Reset
The Signal start/Signal reset operation is useful for remote control of
the Timer.
3.Control of Integrated Time with Gate
Signal
Gate signal processing (during input or a temporary timing stop) is
possible with both power start and signal start.
B/B2 Mode: Flicker
The flicker operation in the B and B2 modes can be effectively
applied to lamp or buzzer (ON and OFF) alarms or the monitoring of
an intermittent operation with a display.
1.Power-ON Start/Power-OFF Reset (in B
Mode)
t
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
t
Reset (2 and 7)
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Reset (2 and 7)
Lit
(Power continuously supplied)
Start signal (remote control possible)
Reset signal
(remote control possible)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
t
1
t
2
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Gate (2 and 5)
t
1
+ t
2
: set time
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Gate signal (The operation is interrupted with the
gate signal if the Timer detects an abnormal signal.)
Externally
short-circuited
Power
supply
Power (2 and 10)
Start (2 and 6)
Power indicator Flashing
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Power
supply
Control output: NO (9 and 11)
NO (1 and 3)
H3CR-A
21
2.Signal Start/Signal Reset (in B Mode)
If there is an abnormal signal, flashing starts. When the abnormal
condition is restored, a reset signal stops the display flashing.
C Mode: Signal ON/OFF-delay
The Signal ON-/OFF-delay operation (C mode) is useful for the
control of distribution of products on a production line into boxes by
the specified number or time.
1.Power-ON Start/Instantaneous Operation/
Time-limit Reset
A set of these functions is useful for the operation of a machine for a
specified period when power is ON.
2.Signal-ON-OFF Start/Instantaneous
Operation/Time-limit Reset
D Mode: Signal OFF-delay
Signal OFF-delay operation (D mode) can be effectively used to keep
a load operating for a certain period. For example, this function
enables the cooling fan for a lamp or heater to operate for a certain
period after the lamp or heater is switched OFF.
1.Power-ON Start/Instantaneous Operation/
Time-limit Reset
Power (2 and 10)
Start (2 and 6)
Power indicator
Reset (2 and 7)
Lit Flashing Lit
(Power continuously supplied)
Start signal
Reset signal
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
tt
Power (2 and 10)
Start (2 and 6)
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
tt
Power indicator
Flashing Lit LitFlashing
Power (2 and 10)
Start (2 and 6)
Power indicator
Lit
Lit
Lit
Lit
(Power continuously supplied)
Flashing
Flashing
Flashing
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Start signal
(The operation starts with the signal ON or OFF)
Power
supply
Power (2 and 10)
Start (2 and 6)
Power indicator
Lit Flashing Lit
Start signal (NC to NO)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
H3CR-A
22
2.Signal Start/Instantaneous Operation/
Time-limit Reset
E Mode: Interval
1.Power-ON Start/Instantaneous Operation/
Time-limit Reset
This function is useful for the operation of a machine for a specified
period after power is ON.
2.Signal Start/Instantaneous Operation/
Time-limit Reset
This function is useful for the repetitive control such as the filling of
liquid for a specified period after each Signal start input.
Lit
Power (2 and 10)
Start (2 and 6)
Power indicator
Flashing Lit
Start signal (NO to NC to NO)
(Power continuously supplied)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
tt
Power indicator
Flashing Lit LitFlashing
Power (2 and 10)
Start (2 and 6)
Externally short-circuited
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power
supply
t t
Power (2 and 10)
Start (2 and 6)
Start signal
(Power continuously supplied)
Control output: NC (8 and 11)
NC (1 and 4)
Control output: NO (9 and 11)
NO (1 and 3)
Power indicator
Flashing Lit LitFlashing
Power
supply
H3CR-A
23
Safety Precautions (H3CR-A)
Refer to Safety Precautions for All Timers.
Note: The following precautions apply to all H3CR-A models.
Power Supplies
For the power supply of an input device of the H3CR-A use an
isolating transformer with the primary and secondary windings
mutually isolated and the secondary winding not grounded.
The H3CR-A’s power supply terminal 2 is a common terminal for
input signals to the Timer. Do not disconnect the wires on terminal 2,
otherwise the internal circuitry of the Timer will be damaged.
Input/Output
Relationship between Input and Power
Supply Circuits (except for H3CR-A8E)
The H3CR-A (except for H3CR-A8E) uses transformerless power
supply. When connecting a relay or transistor as an external signal
input device, pay attention to the following points to prevent short-
circuiting due to a sneak current to the transformerless power supply.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
differ in phase, otherwise the terminals will be short-circuited to one
another.
It is impossible to provide two independent power switches as shown
below regardless of whether or not the Timers are different in phase.
S,G, R
5, 6, 7
2
10
2
H3CR-A
Power supply
Isolation transformer is required.
Input device
Input
terminal
Correct
H3CR-A
Power
supply
Input
terminal
Input device
10
2
2
Incorrect
Isolation
transformer
S,G, R
5, 6, 7
5, 6, 7
G, S, R
10
2
H3CR-A
Input terminal
AC or DC
Power Supply
Power supply
H3CR-A
H3CR-A
Power supply
Incorrect
Correct
Short-circuit current
Contact or transistor for
external input signal
Contact or transistor for
external input signal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
Power supply
Input
terminal
Input
terminal
Contact or transistor for
external input signal
H3CR-A
H3CR-A
24
Relationship between Input and Power
Supply Circuits (H3CR-A@/-A@S)
An appropriate input is applied to the input signal terminals of the
H3CR-A@/-A@S when one of the input terminals is short-circuited
with the common terminal (terminal 2) for the input signals. Never
use terminal 10 as the common terminal for this purpose, otherwise
the internal circuit of the Timer will be damaged.
*1 Power terminal 2 is a common terminal that is also used for the
input signal. Do not use terminal 10 as a common terminal as
this will damage the internal circuitry.
*2 If a relay or other load is connected here, high voltage will be
applied to the input terminal and damage the internal circuitry.
The transistor output of the H3CR-A@S is isolated from the internal
circuitry by a photocoupler, and can therefore be used either as an
NPN output type or a PNP (equivalent) output type.
Relationship between Input and Power
Supply Circuits (H3CR-AP)
Since the input circuit and the power supply circuit are configured
independently, the input circuit can be turned ON or OFF irrespective
of the ON/OFF state of the power supply.
It must be noted that a voltage equivalent to the power supply voltage
is applied to the input circuit.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
be different in phase or the terminals will be short-circuited to one
another (refer to the figures below).
When using the timer in an environment where considerable noise
occurs, keep the input signal source device, timer unit, and wiring as
far away as possible from the source of the noise. It is also
recommended that shielded wire be used for the input signal wiring
as a countermeasure for noise.
Common to All H3CR-A Models
With the H3CR-AP, input wires must be as short as possible. If the
floating capacity of wires exceeds 1,200 pF (approx. 10 m for cables
with 120 pF/m), the operation will be affected. Pay particular
attention when using shielded cables.
The H3CR-A@S transistor output is isolated from the internal
circuitry by a photocoupler. Therefore, either NPN or PNP output is
possible.
5, 6, 7
G, S, R
10
2
Input terminal
Correct
AC or DC
power supply
H3CR-A/-AS
10
2
5, 6, 7
G, S, R
H3CR-A/-AS
Input terminal
Incorrect
AC or DC
power supply
*1
10
2
5, 6, 7
G, S, R
Ry
Input terminal
AC or DC
power supply
Input
contact
H3CR-A/-AS
*2
Input circuit
H3CR-AP
AC/DC
power
supply Power supply
circuit
10
6
7
2
10
6
7
2
Incorrect
H3CR-AP Power supply
H3CR-AP Short-circuit current
Contact or transistor for
external input signal
10
6
7
2
10
6
7
2
Correct
Power supply
H3CR-AP
H3CR-AP
Short-circuit current
Contact or transistor for
external input signal
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
MEMO
25
26
Solid-state Twin Timers
H3CR-F
DIN 48 × 48-mm Twin Timers
Wide power supply ranges of High Voltage 100 to 240 VAC/100
to 125 VDC and Low Voltage 24 to 48 VAC/12 to 48 VDC.
ON- and OFF-times can be set independently and so
combinations of long ON- or OFF-time and short OFF- or ON-
time settings are possible.
Twenty-four time ranges from 0.05 s to 300 h depending on the
model to be used.
Models with a flicker ON start or flicker OFF start are available.
Easy sequence checks through instantaneous outputs for a
zero set value at any time range.
Length, when panel-mounted with a Socket, of 80 mm or less.
11-pin and 8-pin models are available.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
Note: When your order, specify the power supply voltage.
Ordering Information
List of Models
H3CR - F @ @ - @ @
1 2 3 5 4
1. Classification
F: Twin timers
2. Configuration
3. Twin Timer Mode
4. Time Range
None: 11-pin socket
8: 8-pin socket
None: Flicker OFF start
N: Flicker ON start
5. Supply Voltage
None: 0.05 s to 300 h models
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC
24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC
Operating modes Supply voltage 0.05 s to 300 h models
11-pin models 8-pin models
Flicker OFF start 100 to 240 VAC/100 to 125 VDC H3CR-F 100-240AC/100-125DC H3CR-F8 100-240AC/100-125DC
24 to 48 VAC/12 to 48 VDC H3CR-F 24-48AC/12-48DC H3CR-F8 24-48AC/12-48DC
Flicker ON start 100 to 240 VAC/100 to 125 VDC H3CR-FN 100-240AC/100-125DC H3CR-F8N 100-240AC/100-125DC
24 to 48 VAC/12 to 48 VDC H3CR-FN 24-48AC/12-48DC H3CR-F8N 24-48AC/12-48DC
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-F 100-240AC/100-125DC
Supply voltage
H3CR-F
27
Accessories (Order Separately)
Adapter, Protective Cover and Hold-down Clip
Note: Refer to Operation (Common) datasheet for details.
*1 The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time.
*2 The Y92A-48B Protective Cover is made from hard plastic.
Remove the Protective Cover to change the set value.
The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter also cannot be used at the same time.
Sockets
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Note: For details, refer to your OMRON website.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-73 *1
Y92F-74 *1
Protective Cover Y92A-48B *2
Hold-down Clip
(Sold in sets of two) For PF085A Socket Y92H-8
For PL08 or PL11 Sockets Y92H-7
Timer Round Sockets
Pin Connection Terminal Models
11-pin Front Connecting DIN track mounting P2CF-11
DIN track mounting
(Finger-safe type) P2CF-11-E
Back Connecting Screw terminal P3GA-11
Solder terminal PL11
Wrapping terminal PL11-Q
PCB terminal PLE11-0
8-pin Front Connecting DIN track mounting P2CF-08
DIN track mounting
(Finger-safe type) P2CF-08-E
DIN track mounting PF085A
Back Connecting Screw terminal P3G-08
Solder terminal PL08
Wrapping terminal PL08-Q
PCB terminal PLE08-0
Application Model Remarks
For back connecting socket Y92A-48G For P3G-08 and P3GA-11
H3CR-F
28
Specifications
General
Note: For details, refer to your OMRON website.
*CCC certification requirements
Time Ranges
Note: The times that can be set are given. When the time setting knob is turned below “0” until the point where the time setting knob stops, the
output will operate instantaneously at all time range settings.
For details, refer to your OMRON website.
Ratings
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
Item H3CR-F H3CR-F8 H3CR-FN H3CR-F8N
Operating mode Flicker OFF start Flicker ON start
Pin type 11-pin 8-pin 11-pin 8-pin
Operating/Reset method Time-limit operation/Time-limit reset or self-reset
Output type Relay output (DPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC: GB/T 14048.5 *
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Recommended fuse 0216005 (250VAC, 5A), manufactured by Littelfuse
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 1.5 A
Rated insulation voltage 250 V
Rated impulse withstand
voltage
(altitude: 2,000 m max.)
4 kV (at 240 VAC)
Conditional short-circuit
current
1000 A
Time unit s (sec) ×10 s (10 sec) min (min) ×10 min (10 min) h (hrs) ×10 h (10 hrs)
Fullscale
setting
1.2 0.05 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12
30.3 to 3 3 to 30 0.3 to 3 3 to 30 0.3 to 3 3 to 30
12 1.2 to 12 12 to 120 1.2 to 12 12 to 120 1.2 to 12 12 to 120
30 3 to 30 30 to 300 3 to 30 30 to 300 3 to 30 30 to 300
Rated supply voltage (See notes 1, 2, and 3.) 100 to 240 VAC 50/60 Hz/100 to 125 VDC
24 to 48 VAC 50/60 Hz/12 to 48 VDC
Operating voltage range 85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models
Power reset Minimum power-opening time: 0.1 s
Power consumption 100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC
24 VAC/VDC: approx. 2 VA (1.7 W) at 24 VAC
approx. 1 W at 24 VDC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
H3CR-F
29
Characteristics
Note: Refer to the Life-test Curve (Reference).
Life-test Curve (Reference)
Accuracy of operating
time
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
Setting error ±5% FS ±50 ms max.
Reset time 0.1 s max.
Reset voltage 10% max. of rated voltage
Influence of voltage ±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 1.2 and 3 s)
Influence of temperature ±1% FS max. (±1% FS ±10 ms max. in ranges of 1.2 and 3s)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
5kV (between power terminals), however, 1kV for 24 to 48VAC, 12 to 48 VDC
5kV (between current-carrying terminal and exposed non-current-carrying metal parts), however 1.5 kV for 24 to 48 VAC,
12 to 48 VDC
Noise immunity ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance Destruction: 980 m/s2 three times each in six directions
Malfunction: 98 m/s2 three times each in six directions
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 100 g
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (x 10
3
)
250 VAC/30 VDC
(cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-F
30
Connections
Block Diagrams
H3CR-F/-F8/-FN/F8N
I/O Functions
Terminal Arrangement
Inputs ---
Outputs Control output Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.
ON indicator OFF indicator
One-chip microcomputer
ROM RAM Clock
AC (DC) input Power supply
circuit
Indicator
circuit
Zero setting
detection
circuit
Time range/unit
selectors
Output
circuit
(+)(~)
Power supply Power supply
H3CR-F8/-F8N H3CR-F/-FN
Note: Leave terminals 5, 6, and 7 open.
Do not use them as relay terminals.
H3CR-F
31
Operation
Timing Chart
tON: ON set time
tOFF: OFF set time
Note: 1. Allow a timer reset time (Rt) of 0.1 s or longer
2. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation.
Nomenclature
Operating mode Timing chart
Flicker OFF start
Flicker ON start
t
OFF
t
ON
t
OFF
t
ON
t
OFF
t
OFF
ON
OFF
Power
Rt
Lit
Not lit
Lit
Not lit
ON
OFF
ON
OFF
ONindicator
OFF indicator
Output NO
Output NC
t
ON tOFF tON tOFF tON tOFF
ON
OFF
Rt
Lit
Not lit
Lit
Not lit
ON
OFF
ON
OFF
Power
ONindicator
OFF indicator
Output NO
Output NC
OFF-time unit display window
ON-time unit display window
OFF indicator (green)
Lit when the output is OFF.
ON indicator (orange)
Lit when the output is ON.
Scale range display
windows
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale)
For both ON-time and OFF-time.
OFF-time unit selector (select one from sec.
10 s, min., 10 min, hrs, and 10 h)
ON-time setting knob (with orange pointer)
For ON-time setting
OFF-time setting knob (with green pointer)
For OFF-time setting
ON-time unit selector (select one
from sec, 10 s, min, 10 min, hrs, and
10 h)
Scale range display windows
changes as below by turning
the Time range selector clockwise.
0 0.2 0.4 0.6 0.8 1.0 1.2
0 0.5 1 1.5 2 2.5 3
024681012
0 5 10 15 20 25 30
H3CR-F
32
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Dimensions with Flush Mounting Adapter
H3CR-F
H3CR-FN
H3CR-F8
H3CR-F8N
66.6
44.8 × 44.8
44.8 × 44.8
52.3
0.7
6
17.4
5.7
37 din.
14 din.
11 pins
48
48
8 pins
66.6
52.3
0.7
6
17.4
5.7
48
48 37 din.
14 din.
5258
42
48
P3G
Back Connecting Socket
(Order separately)
Panel
45+0.6
-0
(N)
45+0.6
-0
0.5 R max.
Y92F-30 Flush Mounting Adapter (Order Separately)
Note: 1. The orientation of the Adapters for two or more Timers is
different for a horizontal or vertical layout. Make sure the
orientation is correct.
Consecutive Mounting of n Timers
Without Front Covers: N = (48n - 2.5) + 1 - 0
With Front Covers: N = (51n - 5.5) + 1 - 0
With Panel Covers: N = (50n - 4.5) + 1 - 0
2.
The applicable thickness of the mounting panel must be 1 to 5 mm.
Mounting Hole Dimensions
(Conform to DIN 43700.)
65 to 66
52 to 53
76±0.2
0.5 R max.
Adapter mounting holes: Two, 4.5 d
P3G
Back Connecting Socket
Panel
52.358
88 45±0.15
45±0.15
Insert the Timer
in this direction.*
Y92F-73 Flush Mounting Adapter (Order Separately)
Note: The applicable thickness of the mounting panel must be 1 to
3.2 mm.
*Insert the Timer from the back of the Adapter.
Note: A Front Cover and Flush Mounting Adapter cannot be used at the
same time.
H3CR-F
33
Accessories (Order Separately)
Protective Cover
Y92A-48B
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
This Protective Cover cannot be used together with the Y92F-73/-74
flush mounting adaptor or the panel cover.
Hold-down Clip
Y92H-8
The Y92H-8 Hold-down Clip is attached to the PF085A socket.
Hold-down Clip
Y92H-7
Y92H-7 Hold-down Clip is attached with screws together with the
PL08 socket or the PL11 socket.
58
56
45±0.2
50+0.2
0
45+0.5
-0
55+0.5
-0
43±0.2
68
52.3
P3G
Back Connecting Socket
Panel
0.5 R max.
Y92F-74 Flush Mounting Adapter (Order Separately)
Note: The applicable thickness of the mounting panel must be
1 to 3.2 mm.
Note: A Front Cover and Flush Mounting Adapter cannot be used at the
same time.
103.2* 100.9
2.3*
92.3* 90.0
2.3*
80
17.4 17.4
75
81.5 81.5
Y92F-30 P3GA-11 Y92F-30 P3G-08
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@
H3CR-F
H3CR-FN
P2CF-11
P2CF-11-E
H3CR-F8
H3CR-F8N
P2CF-08
P2CF-08-E
Dimensions with Back Connecting Socket
P3G-08/P3GA-11
H3CR-F
H3CR-FN
+
Adapter
H3CR-F8
H3CR-F8N
+
Adapter
(When
Y92A-48G
mounted)
(When
Y92A-48G
mounted)
*These dimensions vary with the kind of DIN track (reference value). Note: There are no restrictions to the mounting direction.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
34
Solid-state Star-delta Timers
H3CR-G
DIN 48 × 48-mm Star-delta Timer
A wide star-time range (up to 120 seconds) and star-delta
transfer time range (up to 1 seconds).
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
Note: When your order, specify the power supply voltage.
Ordering Information
List of Models
H3CR - G 8 @ L @
12345
1. Classification
G: Star-delta timer
2. Configuration
8: 8-pin socket
3. Outputs
4. Dimensions
L: Long-body model
5. Supply Voltage
100-120AC: 100 to 120 VAC
200-240AC: 200 to 240 VAC
None: Star-delta operation contact
E: Star-delta operation contact
and instantaneous contact
Outputs Supply voltage 8-pin models
Time-limit contact 100 to 120 VAC H3CR-G8L 100-120AC
200 to 240 VAC H3CR-G8L 200-240AC
Time-limit contact and instantaneous contact 100 to 120 VAC H3CR-G8EL 100-120AC
200 to 240 VAC H3CR-G8EL 200-240AC
Note: Specify both the model number and supply voltage when ordering.
Example: H3CR-G8L 100-120AC
Supply voltage
H3CR-G
35
Accessories (Order Separately)
Accessories (Order Separately)
Adapter, Protective Cover, Setting Ring and Panel Cover
Note: Refer to Operation (Common) datasheet for detail.
*1
The Y92A-48B Protective Cover and the Y92P-48G
@
Panel Cover can not be used at the same time with the Y92F-70/-71 Flush Mounting Adapter.
*2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-70/-71 Flush
Mounting Adapter and the Y92P-48G@ Panel Cover cannot be used at the same time with Y92A-48B Protective Cover.
*3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@ Panel Cover.
*4
The Y92A-48B Protective Cover and the Y92F-70/-71 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G
@
Panel Cover.
Sockets
Note: 1. The P2CF-08-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Note: For details, refer to your OMRON website.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-70 *1
Y92F-71 *1
Protective Cover Y92A-48B *2
Hold-down Clip For PF085A Socket Y92H-2
For PL08 Sockets Y92H-1
Setting Ring A Y92S-27 *3
Setting Ring B and C Y92S-28 *3
Panel Cover Light gray (5Y7/1) Y92P-48GL *4
Black (N1.5) Y92P-48GB *4
Timer Round Sockets
Pin Connection Terminal Models
8-pin Front Connecting DIN track mounting P2CF-08
DIN track mounting
(Finger-safe type) P2CF-08-E
DIN track mounting PF085A
Back Connecting Screw terminal P3G-08
Solder terminal PL08
Wrapping terminal PL08-Q
PCB terminal PLE08-0
Application Model Remarks
For back connecting socket Y92A-48G For P3G-08 and P3GA-11
H3CR-G
36
Specifications
General
Note: For details, refer to your OMRON website.
*CCC certification requirements
Time Ranges
Ratings
Note: 1. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
2. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
Item H3CR-G8L H3CR-G8EL
Functions Star-delta timer Star-delta timer with instantaneous output
Pin type 8-pin
Operating/Reset method Time-limit operation/Self-reset
Output type Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Time-limit: SPST-NO (star operation circuit)
SPST-NO (delta operation circuit)
Instantaneous: SPST-NO
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC: GB/T 14048.5 *
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Recommended fuse 0216005 (250VAC, 5A) manufactured by Littelfuse
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 1.5 A
Rated insulation voltage 250 V
Rated impulse withstand
voltage
(altitude: 2,000 m max.)
4 kV (at 240 VAC)
Conditional short-circuit
current
1000 A
Time unit Star operation time ranges
Scale number (max.)
6Set time range0.5 to 6 s
12 1 to 12 s
60 5 to 60 s
120 10 to 120 s
Star-delta transfer time Programmable at 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s, or 1.0 s
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz)
Operating voltage range 85% to 110% of rated supply voltage
Power reset Minimum power-opening time: 0.5 s
Power consumption 100 to 120 VAC: approx. 6 VA (2.6 W) at 120 VAC
200 to 240 VAC: approx. 12 VA (3.0 W) at 240 VAC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
H3CR-G
37
Characteristics
Note: Refer to the Life-test Curve (Reference).
Accuracy of operating
time
±0.2% FS max.
Setting error ±5% FS ±50 ms max.
Accuracy of Star-delta
transfer time
±25% FS + 5 ms max.
Reset voltage 10% max. of rated voltage
Influence of voltage ±0.2% FS max.
Influence of temperature ±1% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
5 kV (between power terminals)
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance Destruction: 980 m/s2 three times each in six directions
Malfunction: 294 m/s2 three times each in six directions
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight H3CR-G8L: approx. 110 g; H3CR-G8EL: approx. 130 g
H3CR-G
38
Life-test Curve (Reference)
Connections
Block Diagrams
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (× 103)
250 VAC/30 VDC
(cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-G8L
AC input Star operation
Delta operation
Power
supply
circuit
Star operation
time
oscillation
circuit
Star
operation
time counting
circuit
Star
operation
time range
selector
Star-delta
transfer time
selector
Star-delta
transfer time
oscillation
circuit
Star-delta
transfer time
counting
circuit Output
circuit
Indicator
circuit
Star
operation
indicator
Delta
operation
indicator
H3CR-G8EL
Star operation
Delta operation
AC input Power
supply
circuit
Star operation
time
oscillation
circuit
Star
operation
time range
selector
Star
operation
time counting
circuit
Star-delta
transfer time
selector
Star-delta
transfer time
oscillation
circuit
Star-delta
transfer time
counting
circuit Output
circuit
Indicator
circuit
Instantaneous
output circuit
Star
operation
indicator
Delta
operation
indicator
H3CR-G
39
I/O Functions
Terminal Arrangement
Operation
Timing Chart
t1: Star operation time setting
t2: Star-delta transfer time
Nomenclature
Inputs ---
Outputs Control output If the time reaches the value set with the time setting knob, the star operation output will be turned OFF
and there will be delta operation output after the set star-delta transfer time has elapsed.
Model Timing chart
H3CR-G8L/-G8EL
H3CR-G8L H3CR-G8EL
Instantaneous contact
Delta
operation
contact
Star
operation
contact
Note: Leave terminals 1, 3, and 4 open.
Do not use them as relay terminals.
Delta
operation
contact
Star
operation
contact
Note: Leave terminal 4 open. Do not use
them as relay terminals.
t1
t2
0.5 s min.
Power (2 7)
Star operation indicator
Delta operation indicator
ON
OFF
Lit
Not lit
ON
OFF
ON
OFF
ON
OFF
Lit
Not lit
Instantaneous output
(1 3) (-E models)
Star operation
output (8 5)
Delta operation
output (8 6)
Star-delta transfer time display window
Star operation
indicator (green)
Delta operation
indicator (orange)
Scale range display
windows
Star operation time range selector
(select one from 6, 12, 60, and 120
at full scale)
Time unit display
(sec is fixed)
Time setting knob (for setting
star operation time)
Star-delta transfer time selector
(select one from 0.05 s, 0.1 s,
0.25 s, 0.5 s, 0.75 s, and 1.0 s)
Scale range display windows
changes as below by turning
the Time range selector clockwise.
0123456
024681012
0102030405060
0 20 40 60 80 100 120
H3CR-G
40
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Dimensio n of Timer main unit
Note: There are no restrictions to the mounting direction.
*These dimensions vary with the kind of DIN track (reference value).
44.8 44.8
(78)
63.7
79.4
0.7 13.6
6
15
39 dia.
48
48
50 16.5
50
Dimensions with Set Ring and Panel Cover
Y92S-27/-28 (Order Separately)
Time setting ring Panel cover
42 dia.
101.3* 99
2.3*
15
86.4
92.9
Y92F-30 P3G-08
H3CR-G8@L
Dimensions with Front Connecting Socket
P2CF-08-@
P2CF-08
P2CF-08-E
Dimensions with Back Connecting Socket
P3G-08
H3CR-G8@L
+
Adapter
(When
Y92A-48G
mounted)
H3CR-G
41
Accessories (Order Separately)
Protective Cover
Y92A-48B
To use the Protective cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
This Protective cover cannot be used together with the Y92F-70/-71
flush mounting adaptor or the panel cover.
Hold-down Clip
Y92H-2
The Y92H-2 Hold-down Clip is attached to the PF085A socket.
Y92H-1
Y92H-1 Hold-down Clip is attached with screws together with the
PL08 socket.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
42
Solid-state Power OFF-delay Timers
H3CR-H
DIN 48 48-mm Power OFF-delay Timer
Long power OFF-delay times;
S-series: up to 12 seconds,
M-series: up to 12 minutes.
Models with forced-reset input are available.
11-pin and 8-pin models are available.
For the most recent information on models that have been
certified for safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 42 for
availability.
List of Models
H3CR - H @ @ L @ @
1 2 3 4 5 6
1. Classification
H: Power OFF-delay timer
2. Configuration
3. Input
4. Dimensions
L: Long-body model
None: 11-pin socket
8: 8-pin socket
None: Without reset input
R: With reset input
5. Supply Voltage6. Time Range
S: 0.05 to 12 s
M: 0.05 to 12 min
100-120AC: 100 to 120 VAC
200-240AC: 200 to 240 VAC
24AC/DC: 24VAC/DC
48DC: 48 VDC
100-125DC: 100 to 125 VDC
Note: Specify the model number, supply voltage, and time range (S or M) when ordering.
Input Output Supply voltage S-series M-series
11-pin models 8-pin models 11-pin models 8-pin models
Without
reset
input
DPDT
100 to 120 VAC --- H3CR-H8L 100-120AC S --- H3CR-H8L 100-120AC M
200 to 240 VAC H3CR-H8L 200-240AC S H3CR-H8L 200-240AC M
24 VAC/DC H3CR-H8L 24AC/DC S H3CR-H8L 24AC/DC M
48 VDC H3CR-H8L 48DC S H3CR-H8L 48DC M
100 to 125 VDC H3CR-H8L 100-125DC S H3CR-H8L 100-125DC M
With
reset
input
100 to 120 VAC H3CR-HRL 100-120AC S --- H3CR-HRL 100-120AC M ---
200 to 240 VAC H3CR-HRL 200-240AC S H3CR-HRL 200-240AC M
24 VAC/DC H3CR-HRL 24AC/DC S H3CR-HRL 24AC/DC M
48 VDC H3CR-HRL 48DC S H3CR-HRL 48DC M
100 to 125 VDC H3CR-HRL 100-125DC S H3CR-HRL 100-125DC M
SPDT
100 to 120 VAC --- H3CR-H8RL 100-120AC S --- H3CR-H8RL 100-120AC M
200 to 240 VAC H3CR-H8RL 200-240AC S H3CR-H8RL 200-240AC M
24 VAC/DC H3CR-H8RL 24AC/DC S H3CR-H8RL 24AC/DC M
48 VDC H3CR-H8RL 48DC S H3CR-H8RL 48DC M
100 to 125 VDC H3CR-H8RL 100-125DC S H3CR-H8RL 100-125DC M
Note: Specify the model number, supply voltage, and time range (S or M) when ordering.
Example: H3CR-H8L 100-120AC S
Supply voltage
Time range
H3CR-H
43
Accessories (Order Separately)
Adapter, Protective Cover and Hold-down Clip
Sockets
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Note: For details, refer to your OMRON website.
Name/specifications Models
Flush Mounting Adapters Y92F-30 Note: Refer to Operation
(Common) datasheet for
details.
*1.The Y92A-48B Protective
Cover and the Y92F-70/-71
Flush Mounting Adapter cannot
be used at the same time.
*2.The Y92F-48B Protective
Cover is made from hard
plastic.
Remove the Protective Cover
to change the set value.
Y92F-70 *1
Y92F-71 *1
Protective Cover Y92A-48B *2
Hold-down Clips For PF085A Socket Y92H-2
For PL08 or PL11 Sockets Y92H-1
Timer Round Sockets
Pin Connection Terminal Models
11-pin Front Connecting DIN track mounting P2CF-11
DIN track mounting
(Finger-safe type)
P2CF-11-E
Back Connecting Screw terminal P3GA-11
Solder terminal PL11
Wrapping terminal PL11-Q
PCB terminal PLE11-0
8-pin Front Connecting DIN track mounting P2CF-08
DIN track mounting
(Finger-safe type)
P2CF-08-E
DIN track mounting PF085A
Back Connecting Screw terminal P3G-08
Solder terminal PL08
Wrapping terminal PL08-Q
PCB terminal PLE08-0
Application Model Remarks
For back connecting socket Y92A-48G For P3G-08 and P3GA-11
H3CR-H
44
Specifications
General
Note: For details, refer to your OMRON website.
*CCC certification requirements
Time Ranges
Note: 1. If the above minimum power ON time is not secured, the H3CR may not operate. Be sure to secure the above minimum power ON time.
2. Do not use the Timer with a repeat period of less than 3 s. Doing so may result in abnormal heating or burning. Refer to Safety Precautions
(H3CR-H) on page 50 for details.
Ratings
Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. For contact input, use contacts which can adequately switch 1 mA at 5 V.
Item H3CR-H8L H3CR-H8RL H3CR-HRL
Operating/Reset method
Instantaneous operation/Time-limit reset
Instantaneous operation/Time-limit reset/Forced reset
Pin type 8-pin 11-pin
Input type --- No-voltage input
Output type Relay output (DPDT) Relay output (SPDT) Relay output (DPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC: GB/T 14048.5 *
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
Recommended fuse 0216005 (250VAC, 5A), manufactured by Littelfuse
Rated operating voltage Ue
Rated operating current Ie
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
Rated insulation voltage 250 V
Rated impulse withstand
voltage
(altitude: 2,000 m max.)
4 kV (at 240 VAC)
Conditional short-circuit
current
1000 A
Time unit S-series M-series
Scale number (max.) s (sec) min (min)
0.6 Set time range 0.05 to 0.6
1.2 0.12 to 1.2
60.6 to 6
12 1.2 to 12
Min. power ON time 0.1 s min. 2 s min.
Time-up operation repeat period 3 s min.
Forced-reset repeat period 3 s min.
Rated supply voltage (See notes 1 and 2.) 100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
100 to 125 VDC
Operating voltage range 85% to 110% of rated supply voltage
No-voltage input (See note 3.) ON-impedance: 1 kΩ max.
ON residual voltage: 1 V max.
OFF impedance: 500 kΩ min.
Power consumption 100 to 120 VAC: approx. 0.23 VA (0.22 W) at 120 VAC
200 to 240 VAC: approx. 0.35 VA (0.3 W) at 240 VAC
24 VAC/DC: approx. 0.17 VA (0.15 W) at 24 VAC
approx. 1.0 W at 24 VDC
48 VDC: approx. 0.18 W at 48 VDC
100 to 125 VDC: approx. 0.5 W at 125 VDC
Control outputs Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
The minimum applicable load is 10mA at 5VDC (P reference value).
Contact materials : Ag-alloy
H3CR-H
45
Characteristics
Note: Refer to the Life-test Curve(Reference).
Life-test Curve(Reference)
Accuracy of operating
time
±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Setting error ±5% FS ±50 ms max.
Operation start voltage 30% max. of rated voltage
Influence of voltage ±0.2% FS max. (±0.2% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Influence of temperature ±1% FS max. (±1% FS ±10 ms max. in ranges of 0.6 and 1.2 s)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
5 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;
1 kV for 24 VAC/DC, 48 VDC
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120 VAC, 200 to
240 VAC, 100 to 125 VDC;
1.5 kV for 24 VAC/DC, 48 VDC
Noise immunity ±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator
(pulse width: 100 ns/1 μs, 1-ns rise); ±1 kV (between power terminals) for 48 VDC
Static immunity Malfunction: 8 kV, Destruction:15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance Destruction: 980 m/s2 three times each in six directions
Malfunction: 98 m/s2 three times each in six directions
Ambient temperature Operating: 10°C to 55°C (with no icing),
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h) (See note)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interferenc: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Case color Light Gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 120 g
10,000
5,000
1,000
500
100
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ = 0.4)
Switching operations (× 10
3
)
250 VAC/30 VDC
(cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC for H3CR-H8L/-HRL and 100 mA at 5
VDC for H3CR-H8RL (failure level: P).
H3CR-H
46
Connections
Block Diagrams
I/O Functions
Terminal Arrangement
Note: DC models, including 24 VAC/DC models, have polarity.
Inputs Reset Turns off the control output and resets the elapsed time.
Outputs Control output Operates instantaneously when the power is turned on and time-limit resets when the set time is up
after the power is turned off.
Without Reset Input (H3CR-H8L)
LCD
AC (DC) input Power supply
circuit
Power failure
detection circuit
Oscillation
circuit
Time range/
unit selector
Counting
circuit Output
circuit
Indicator
circuit
Output
indicator
With Reset Input (H3CR-H8RL/-HRL)
LCD
Input circuit
AC (DC) input
Reset input
Power supply
circuit
Power failure
detection circuit
Oscillation
circuit
Time range/
unit selector
Counting
circuit
Output
circuit
Indicator
circuit Output
indicator
8-pin Models
Without Reset Input (H3CR-H8L)
Power supply
With Reset Input (H3CR-H8RL)
Power supply
Reset
input
Note: Leave terminal 3 open. Do not use
them as relay terminals.
11-pin Model
With Reset Input (H3CR-HRL)
Power supply
Reset input
Note: Leave terminal 6 open. Do not use
them as relay terminals.
H3CR-H
47
Operation
Timing Chart
t: Set time
Rt: Minimum power ON time (S-series: 0.1 s min.; M-series: 2 s min.)
If the power ON time is less than this value, the Timer may not operate (i.e., output may not turn ON).
Note: If the power is turned ON until the set time is up, the timer will be retriggered.
Model Timing chart
H3CR-H8L
H3CR-H8RL
H3CR-HRL
Rt tRt t
ON
OFF
Output (1 3)
Lit
Not lit
Output (1 4)
Output (8 6)
Output (8 5)
Power
(See note)
Output
indicator
tt
Rt
Rt
Lit
Not lit
ON
OFF
Output (8 6)
Reset input ON (Short-circuited)
OFF (Open)
0.05 s min. 0.05 s min.
Output (8 5)
Power
(See note)
Output
indicator
Rt
t
Rt
t
ON
OFF
Output (1 3)
Lit
Not lit
Output (1 4)
Output (11 9)
Output (11 8)
Reset input
0.05 s min.
Power
(See note)
Output
indicator
0.05 s
min.
H3CR-H
48
Nomenclature
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Note: There are no restrictions to the mounting direction.
*These dimensions vary with the kind of DIN track (reference value).
Output indicator (red)
Scale range display windows
Time range selector (select
one from 0.6, 1.2, 6, and 12 at
full scale)
Time unit display
S-series: sec
M-series: min
Time setting knob (for setting
power OFF-delay time)
Scale range display windows
changes as below by turning
the Time range selector clockwise.
0 0.1 0.2 0.3 0.4 0.5 0.6
0 0.2 0.4 0.6 0.8 1.0 1.2
0123456
024681012
H3CR-HRL
H3CR-H8L
H3CR-H8RL (78)
44.8 × 44.8
44.8 × 44.8
63.7
0.7 13.6
6
15
79.4
39 dia.
11 pins
48
48
(78)
63.7
0.7 13.6
6
15
79.4
39 dia.
48
48
8 pins
112.2* 109.9
2.3*
15 91.4
101.3* 99
2.3*
15 86.4
92.9 92.9
H3CR-HRL
Y92F-30
P3G-08
H3CR-H8@L
Y92F-30
P3GA-11
H3CR-HRL
+
Adapter
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@
P2CF-08
P2CF-08-E
P2CF-11
P2CF-11-E
H3CR-H8@L
+
Adapter
(When
Y92A-48G
mounted)
(When
Y92A-48G
mounted)
Dimensions with Back Connecting Socket
P3G-08/P3GA-11
H3CR-H
49
Accessories (Order Separately)
Protective Cover
Y92A-48B
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
This Protective Cover cannot be used together with the Y92F-70/-71
flush mounting adaptor or the panel cover.
Hold-down Clip
Y92H-2
The Y92H-2 Hold-down Clip is attached to the PF085A socket.
Y92H-1
Y92H-1 Hold-down Clip is attached with screws together with the
PL08.
H3CR-H
50
Safety Precautions (H3CR-H)
Note: The undermentioned is common for all H3CR-H models.
Power Supplies
The H3CR-H has a large inrush current; provide sufficient power
supply capacity. If the power supply capacity is too small, there may
be delays in turning ON the output.
With the H3CR-H
@
RL, for the power supply of an input device, use an
isolating transformer, of which the primary and secondary windings are
mutually isolated and the secondary winding is not grounded.
Input/Output (H3CR-H@RL)
An appropriate input is applied to the input signal terminal of the Timer
when the input terminal for the input signal is short-circuited. Do not
attempt to connect any input terminal to any terminal other than the input
terminal or to apply voltage across other than the specified input
terminals or the internal circuits of the Timer may be damaged.
The H3CR-H@RL uses transformerless power supply. When
connecting a relay or transistor as an external signal input device,
pay attention to the following points to prevent short-circuiting due to
a sneak current to the transformerless power supply.
If input is made simultaneously from one input contact or a transistor
to the H3CR-H and a Timer whose common input terminals are used
as power terminals, such as the H3CR-A, a short-circuit current will
be generated. Either input through isolated contacts, or isolate the
power supply for one of the Timers.
Wiring
The H3CR-H has a high impedance circuit. Therefore, the H3CR-H
may not be reset if the H3CR-H is influenced by inductive voltage. In
order to eliminate any influence of inductive voltage, the wires
connected to the H3CR-H must be as short as possible and should
not be installed alongside power lines. If the H3CR-H is influenced by
inductive voltage that is 30% or more of the rated voltage, connect a
CR filter with a capacitance of approximately 0.1 F and a resistance
of approximately 120 or a bleeder resistor between the power
supply terminals. If there is any residual voltage due to current
leakage, connect a bleeder resistor between the power supply
terminals.
Operation
An interval of 3 s minimum is required to turn on the H3CR-H after
the H3CR-H is turned off. If the H3CR-H is turned on and off
repeatedly with an interval of shorter than 3 s, abnormal heating or
burning may occur in internal elements.
After the forced reset function of the H3CR-H is activated, an interval
of 3 s minimum is required to activate the forced reset function again.
If the forced reset function is activated repeatedly with an interval of
shorter than 3 s, the internal parts of the H3CR-H may deteriorate
and the H3CR-H may malfunction.
If it is required that the output be turned on repeatedly with an
interval of shorter than 3 s, consider use of the H3CR-A in mode D
(signal OFF-delay).
On the H3CR-F@, do not set both the ON set dial and OFF set dial to
the lowest settings. Doing so may damage the contacts.
Others
If the H3CR-H is dropped or experiences some other kind of shock,
because a latching relay is used for output, contacts may be reversed
or go into a neutral state. If the H3CR-H is dropped, reconfirm correct
operation.
Correct
H3CR-H@RL
Power supply
Input
terminal
Input device Isolation transformer is required.
( ): H3CR-H8RL
< >: H3CR-HRL
(4) <7>
5, 6, 7
(7) <10>
10
(2) <2>
2
(1) <5>
2
Incorrect
Power supply
Input
terminal
H3CR-H@RL
( ): H3CR-H8RL
< >: H3CR-HRL
(4) <7>
5, 6, 7
(7) <10>
10
(2) <2>
2
(1) <5>
2
Input device Isolation
transformer
10, 7*
2, 2*
10
2
R.S.
7
6
G.
5
4*,
51*,
7
H3CR-H@RL
Short-circuit current
*: H3CR-H8RL
H3CR-A
Power
3 s min.
Output
state 1
Output
state 2
Power
3 s min.
Output
3 s min.
Reset
input
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
MEMO
51
52
Operation (Common)
Note: The undermentioned is common for all H3CR models.
Basic Setting
Setting of Selectors
The selectors can be turned clockwise and counterclockwise to
select the desired time unit, time range, or operating mode.
Each selector has a snap mechanism that secures the selector at a
given position. Set the selector at a position at which it is secured. Do
not set it midway between two securing positions or a malfunction
could result from improper setting.
Selection of Operating Mode
H3CR-A Multifunctional Timer
The operation mode A to E, G, and J of the H3CR-A can be selected.
Use a Phillips head or flathead screwdriver to turn the selector
switch. The operation mode can be set to one of eight modes. The
window on the top shows E, G, J, A, B, B2, C, or D to indicate the
selected mode. On the H3CR-A8, the window on the top shows E, J,
B, A, or B2.
Selection of Time Unit and Time Range
H3CR-A Multifunctional Timer
The desired time unit (sec, 10 s, min, 10 m, hrs, or 10 h) is
displayed in the window below the time setting knob by turning the
time unit selector located at the lower right corner of the front panel.
A time range (1.2, 3, 12, or 30 for H3CR-A@/2.4, 6, 24, or 60 for
H3CR-A@-301) is selected with the time range selector at the lower
left corner of the front panel, and the selected time range appears (in
the window at the lower right part) within the plastic frame of the time
setting knob.
H3CR-F Twin Timers
The display window at the bottom right inside the Time setting knob
shows 1.2, 3, 12, or 30 to indicate the scale number selected with the
selector switch on the front at bottom left.
Use a Phillips head or flathead screwdriver to turn the selector switch.
For ON-time, the desired time unit (sec, 10 s, min, 10 min, hrs, and 10 h)
is indicated in the ON-time unit display window at the lower right corner
of the front panel and can be changed by turning the ON-time unit
selector located below the ON-time unit display window.
For OFF-time, the desired time unit (sec, 10 s, min, 10 min, hrs and
10 h) is indicated in the OFF-time unit display window at the upper
right corner of the front panel and can be changed by turning the
OFF-time unit selector located below the OFF-time unit display
window.
(i.e., H3CR-A)
Operating mode
selector
Operating mode
display window
Groove for
screwdriver
Usable screwdrivers
Phillips head: No. 0-1
Flat head: Width 2.3 to 3.0 mm
Time unit selector
Time unit display window
Time setting
knob
Time range
selector
Scale range
display window
Time range
selector
Scale range display
windows
Time range selector
OFF-time setting knob
(with green pointer)
For OFF-time setting
OFF-time unit
display window
ON-time unit
display window
OFF-time unit
selector
ON-time unit
selector
OFF-time unit
selector
H3CR
53
H3CR-G Star-delta Timers
The display window at the bottom right inside the Time setting knob
shows 6, 12, 60, or 120 to indicate the scale number Star operation
time selected with the selector switch on the front at bottom left.
Use a Phillips head screwdriver or flathead screwdriver to turn the
selector switch. The display window at the bottom center of the Time
setting knob shows 0.05, 0.1, 0.25, 0.5, 0.75, or 1.0 to show the star
-delta transfer time selected with the selector switch on the front at
bottom right.
H3CR-H Power OFF-delay Timers
Use a Phillips head screwdriver or flathead screwdriver to turn the
selector switch. The display window at the bottom right inside the
Time setting knob shows 0.6, 1.2, 6, or 12 to indicate the scale
number selected with the selector switch on the front at bottom left.
Setting of Time
Use the time setting knob to set the desired time.
Using the Time Setting Ring for H3CR-A/-G
Locking the Set Time
Mount the Panel Cover on the Timer, set the desired time with the
time setting knob, and place Time Setting Ring A onto the time
setting knob so that the time setting notch of Time Setting Ring A is
in the center of the reset lock position of the Panel Cover.
Limiting the Setting Range
Example: To set a range of 10 and 20 s.
Mount the Panel Cover on the Timer, set the time setting knob to 10 s
(the lower limit of the setting range), and place Time Setting Ring C
onto the time setting knob so that the stopper of Time Setting Ring C
is on the right edge of the reset lock position of the Panel cover. Next,
set the time setting knob to 20 s (the upper limit of the setting range),
place Time Setting Ring B onto the time setting knob so that the
stopper of Time Setting Ring B is on the left edge of the reset lock
position of the Panel Cover.
Star operation time
range selector
Usable screwdrivers
Phillips head: No. 0-1
Flat head: Width 2.3 to 3.0 mm
Star-delta
switching time
selector switch
Scale range
display window
Star operation
time range
selector
Time setting
knob
Star-delta
switching time
display window
Time range
selector
Usable screwdrivers
Phillips head: No. 0-1
Flat head: Width 2.3 to 3.0 mm
Scale range
display window Time setting
knob
Reset lock position
Time Setting Ring A Panel cover
Example: To set the time to 10 s.
Time setting notch
Setting position
Time setting
notch
Stopper Reset lock position
Panel cover
Range
Time Setting
Ring B
Time Setting
Ring C
H3CR
54
Accessories (Order Separately) (Common)
Note: The undermentioned is common for all H3CR models.
Note: All units are in millimeters unless otherwise indicated.
Flush Mounting Adaptor
45+0.6
0
(N)
45+0.6
0
58 52
42
48
Y92F-30
Panel Cutout
(Conforms ro DIN 43700)
0.5 R max.
Panel
Note1: The adapters for two or more timers mounted in a vertical line are different in
orientation from those mounted in a horizontal line.
Note2: The applicable thickness of the mounting panel must be 1 to 5 mm.
N can be obtained as follows (n: the number of H3CR models arranged side by side)
Without a Cover: N = (48n - 2.5)+1/-0
With the Protective Cover: N = (51n - 5.5)+1/-0
With the Panel Cover: N = (50n - 4.5)+1/-0
P3G
Back Connecting Socket
88
58
45±0.15
43±0.2
58 45±0.2
50
+0.2
-0
56
68
76±0.2
45+0.5
0
55+0.5
0
45±0.15
52.3 (63.7)
52.3 (63.7)
Y92F-70/-73
Y92F-71/-74
Panel
Panel
Panel Cutout
Adapter mounting hole Two, 4.5 dia.
52 to 53
65 to 66
R0.5 max.
R0.5 max.
Note: The applicable thickness of the
mounting panel must be 1 to 3.2 mm.
Note: The applicable thickness of the
mounting panel must be 1 to 3.2 mm.
P3G
Back Connecting Socket
P3G
Back Connecting Socket
Note: The value shown in
parentheses is for
the Y92F-70.
(See note.)
Note: The value shown in
parentheses is for
the Y92F-71.
(See note.)
Unit insertion
direction*
Unit insertion
direction*
* Insert timer unit from back side
of adapter.
* Insert timer unit from back side
of adapter.
H3CR
55
Track Mounting/Front Connecting Socket
Track Mounting/Front Connecting Socket
7.8 3 4.5
35.4
4
40±0.2
40±0.2
7.8
4
35.4
20.3
19
3
1.3
5 4.5
70 max.
50 max.
20.3 max.
P2CF-08-E (Finger Safe Terminal Type)
Conforming to VDE0106/P100
Surface Mounting Holes
Two, 4.5 dia. or two, M4
50 max.
70 max.
21.5 max.
P2CF-08
Eight,
M3.5 × 7.5 sems
Two, 4.5 dia.
holes
Terminal Arrangement/
Internal Connections
(Top View)
Two, 4.5 dia.
holes
Eight,
M3.5 × 7.5 sems
40±0.2
7.8
3 4.5
35.4
4
7.8
4
40±0.2
35.4
30
5 4.5
3
1.2
Surface Mounting Holes
Two, 4.5 dia. or two, M4
70 max.
50 max.
31.2 max.
P2CF-11-E (Finger Safe Terminal Type)
Conforming to VDE0106/P100
70 max.
50 max.
31.2 max.
P2CF-11
Eleven,
M3.5 × 7.5 sems
Terminal Arrangement/
Internal Connections
(Top View)
Two, 4.5 dia.
holes
Eleven,
M3.5 × 7.5 sems
H3CR
56
Back Connecting Socket
Mounting Track
45
45 4.9 17
45
45
25.6
4.5
16.3
6.2
34
47.7 × 47.7
48 × 48
47.4
16.5 24.6 27.6
27 dia.
P3GA-11
27 dia.
Finger Safe Terminal Cover
Conforming to VDE0106/P100
Y92A-48G
Twelve, 6.4 dia. holes
P3G-08Terminal Arrangement/
Internal Connections
(Bottom View)
Terminal Arrangement/
Internal Connections
(Bottom View)
(Attachment for P3G-08/P3GA-11
Socket)
4.5
15 25 25 25 25
10 10
7.3±0.15
35±0.3 27±0.15
1
4.5
15 25 25 25 25 15
10 10
35±0.3 27 24
16
29.2
1 1.5
1,000
PFP-100N2
PFP-100N, PFP-50N
1,000 (500)
(See note)
Note: The values shown in parentheses are for
the PFP-50N.
15 (5)
(See note)
50
11.5
10
6.2 1.8
135.5 35.3
1.8
1.3
4.8
5
16
12
44.3 34.8
16.5
10
End Plate
PFP-M
M4 x 8
pan head
screw
Spacer
PFP-S
H3CR
57
Time Setting Ring/Panel Cover for H3CR-A/-G
There are two types of Panel Covers (Y92P-48GL, and Y92P-48GB),
all of which are available in two colors. Use the most suitable type of
Panel Cover with the design of the scaling plate according to the
application.
To lock the set time, you can lock the setting dial by using a Y92S-27
Setting Ring and a Y92P-48GL/-48GB Panel Cover. This will help to
prevent the set time from being changed accidentally.
To restrict the set time range, you can restrict the rotating range of
the setting dial by using a Y92S-28 Setting Ring and a 92P-48GL/-
48GB Panel Cover. Use them to restrict the upper and lower limits of
the setting range.
Refer to Using the Time Setting Ring for H3CR-A/-G on page 53 for
the procedure to attach the Setting Ring.
The Flush Mounting Adapter Y92F-70/Y92F-71 for H3CR-G, Y92F-
73/Y92F-74 for H3CR-A or the Protective Cover cannot be used.
Note: The Time Setting Ring/Panel Cover cannot be used for H3CR-
F model or H3CR-H model.
The Time Setting Ring and Panel Cover should be used as a pair.
Locking the Set
Time Time Setting Ring A (Y92S-27) and Panel
Cover (Y92P-48GL, or -48GB)
Limiting the setting
range Time Setting Ring B or C (Y92S-28), and
Panel Cover (Y92P-48GL, or -48GB)
Y92S-27
Time Setting A Y92S-28
Time Setting B Y92S-28
Time Setting C Y92P-48GL
Light Gray Y92P-48GB
Black
H3CR
58
Safety Precautions for All H3CR Models
Note: The undermentioned is common for all H3CR models.
Warning Indications
Meaning of Product Safety Symbols
Risk of fire and explosion due to arcing and relay heat
generation that accompanies switching. Do not use in an
environment where flammable or explosive gas is present.
The H3CR series uses a transformer-less power
supply. Exercise full caution as there is a risk of
electrical shock if input terminal is touched when
power voltage is applied.
The service life of the output relay varies widely
depending on switching capacity and switching
conditions. Use only within the rated load and
electrical life count, based on actual conditions of use.
Risk of contact sticking and burning if used past the
service life. Always use a load current that does not
exceed the rating, and if a heater is used, use a thermal switch in the
load circuit.
Do not remove the outer casing.
In rare circumstances there is a risk of slight electrical
shock, fire, or device damage. Do not disassemble,
modify, repair, or otherwise touch the inside.
In rare circumstances there is a risk of fire if the
screws become loose. Tighten the terminal screws to
the specified torque (1.08N·m).
Do not use the Timer in the following locations.
Locations with radical temperature changes.
Locations with high humidity that may result in condensation.
Locations with excessive vibration or shock.
Locations with corrosive gas or dust.
Locations where the Timer is exposed to sprayed water, oil, or
chemicals.
Pay the utmost attention not to make mistakes in polarity when wiring
the Timer.
Do not connect anything to terminals that are not used.
Risk of internal element damage if a voltage that exceeds the rating
is applied.
Using a surge absorber is recommended if surge voltages occur.
The H3CR Series uses a transformerless power supply. Do not touch
the input terminals while the supply voltage is applied, otherwise an
electric shock may be received.
Verify that the power and output LEDs (LCD) are operating normally.
In some usage environments, the LEDs/LCD/ resin components may
deteriorate faster than normal, resulting in display failure. Inspect and
replace regularly.
When disposing of this product, follow the procedures for disposal of
industrial waste that apply in your region.
Verify that the product is the desired product before use.
Exercise caution as the outer casing of the timer may be immersed in
organic solvents (thinner, benzene, etc.), strong alkali, or strong
acids.
Changing the Setting
Do not change the time unit, time range, or operation mode while the
Timer is in operation, otherwise the Timer may malfunction.
The time unit and time range can be set with the respective selectors
turned clockwise or counterclockwise.
The selectors are of notched so that they will snap when they are
properly set. Do not set the selectors midway between notches,
otherwise the Timer may break or malfunction.
Do not use H3CR-A models (except for H3CR-A@S) in flicker mode
at the lowest selector setting, or H3CR-F models at the lowest
selector setting. Doing so may result in damage to contacts.
CAUTION Indicates a potentially hazardous situation
which, if not avoided, may result in minor
or moderate injury or in property damage.
Precautions for
Safe Use Supplementary comments on what to do
or avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do
or avoid doing, to prevent failure to
operate, malfunction or undesirable effect
on product performance.
Used to warn of the risk of electric shock under
specific conditions.
Used for general prohibitions for which there is no
specific symbol.
Use to indicate prohibitions when there is a risk of
minor injury from electrical shock or other source if
the product is disassembled.
Used for general mandatory action precautions for
which there is no specified symbol.
CAUTION
Precautions for Safe Use
Precautions for Correct Use
H3CR
59
Power Supplies
A DC power supply can be connected if its ripple factor is 20% or
less and the mean voltage is within the rated operating voltage range
of the Timer.
An AC power supply can be connected to the power input terminals
without regard to polarity. A DC power supply must be connected to
the power input terminals as designated according to the polarity of
the terminals.
Make sure that the voltage is applied within the specified range,
otherwise the internal elements of the Timer may be damaged.
Connect the power supply voltage through a relay or switch in such a
way that the voltage reaches a fixed value at once, otherwise the
Timer may not be reset or a timer error may result.
Be aware that the operating voltage will rise by 5% if the rated
voltage is applied to the Timer continuously while the ambient
temperature is close to the maximum permissible ambient
temperature.
The power supply circuit of any H3CR-A model (except for H3CR-
A@S), H3CR-F 100-to-240-VAC model, and H3CR-G model is a
switching circuit. If the power line connected to the power supply
circuit has a transformer with high inductance, a counter-
electromotive voltage will be induced by the inductance. To suppress
the voltage, apply a CR filter to the power supply line.
Apply the power voltage at once through the switch and relay
contacts. If not applied at once, power reset may not take place or
time-up may occur.
When the power is turned on, a rush current (refer to your OMRON
website) may flow briefly and the timer may not start if there is
insufficient power capacity. Use a power supply with sufficient
capacity.
Mounting Direction
There are no restrictions to the mounting direction.
Precautions for EN61812-1
Conformance
The H3CR Series as a built-in timer conforms to EN61812-1
provided that the following conditions are satisfied.
Make sure that no voltage is applied to any terminals before
dismounting the Timer from the Socket.
The output section of the H3CR is provided only with basic isolation.
The H3CR itself is designed under the following conditions:
Overvoltage category III
Pollution degree 2
Isolation
Operation parts: Reinforced isolation
With clearance of 5.5 mm and creepage distance of 5.5 mm at
230 VAC
Output: Basic isolation (See note)
With clearance of 3 mm and creepage distance of 3 mm at
230 VAC
Note: The 11-pin model ensures basic isolation by itself and also
ensures basic isolation with the 11-pin model mounted to the
OMRON P2CF-11-@ or P3GA-11 Socket.
Connect the two output contacts different in polarity to the loads so
that they will be the same in potential.
Others
If the Timer is mounted to a control board, dismount the Timer from
the control board or short-circuit the control board circuitry before
carrying out a voltage withstand test between the electric circuitry
and non-charged metal part of the Timer. This protects the internal
circuitry of the Timer from damage.
If the timer is left for an extended time at high temperature in the
time-up state (internal relay ON), the internal components
(electrolytic capacitors, etc.) may deteriorate faster than normal. For
this reason, use in combination with a relay, and avoid leaving in the
time-up state for an extended time (for example, one month or
longer). (Excluding H3CR-H)
Reference example
Use as shown below.
Cleaning
Do not use solvents such as thinner. Use commercially available
alcohol.
X
X
1
T X
2
X
2
/b T/a X
1
/a X
1
/a
:
Auxiliary relay,
MY relay, etc.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
Authorized Distributor:
In the interest of product improvement,
specifications are subject to change without notice.
Cat. No. L084-E1-07 Printed in Japan
0613 (0696)
© OMRON Corporation 2013 All Rights Reserved.
OMRON Corporation Industrial Automation Company
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Contact: www.ia.omron.com
Tokyo, JAPAN
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China CSM_2_6_0419
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200