POWER
LPS360-M Series
360 Watt AC-DC Power Supply
Total Power: 200 - 360 W
Input Voltage: 90 - 264 Vac
120 - 300 Vdc
Outputs: Single
SPECIAL FEATURES
Medical and ITE safeties
Active power factor correction
3” x 5” footprint
Less than 1U high
EN61000-3-2 compliant
Remote sense
Power fail
Adjustable main output
Level B Conducted EMI - Class I
or Class II inputs
Overvoltage protection
Overload protection
Thermal overload protection
12 V fan output
LPX200 enclosure kit available
5 V Standby output
Remote Inhibit
PMBus commands
Digital I2C interface
Class I and Class II approved
Dual AC fuses
Suitable for BF Type applications
SAFETY
TUV 60950, 60601-1
UL 60950, 60601-1
cULus 60950, 60601-1
CB Certicate & report
CE Mark (LVD & EMC)
CCC Approval
Electrical Specications
Input
Input ra nge: 90 - 264 Vac; 120 - 300 Vdc
Frequency: 47 - 63 Hz
Inrush current: 50 A max., cold start @ 25 °C
Efciency: Up to 93% at full load
EMI/RFI: FCC Class B conducted; CISPR22 Class B conducted;
EN55022 Class B conducted; VDE0878PT3 Class B conducted
Power factor: 0.99 typical
Safety ground leakage
current:
150 uA @ 132 Vac, 60 Hz for class I, 300 uA @ 264 Vac, 60 Hz for class II
Output
Maximum power: 200 - 240 W (see de-rating) for convection, 360 W with 400 LFM of forced air
Adjustment range: 12 V and 24 V models, -0%, +15%, 15 V and 48 V models, -5%, +10%
Standby output: 5 V @ 1A convection, 2 A with forced air
Fan output: 12 V @ 0.5 A convection, 1 A forced air
Hold-up time: 20ms @240W, 220Vac input; 12ms @ 360 W
Overload protection: Short circuit protection on all outputs. Case overload protected @ 110 - 160%
above rating
Overvoltage protection: 15 - 50% above nominal output
Logical Control
Power failure: Open collector logic signal goes high 100 - 500 msec after main output;
it goes low at least 6 msec before loss of regulation
Remote sense: Compensates for 0.5 V lead drop min. Will operate without remote sense
connected. Reverse connection protected.
Low Power Data Sheet
Environmental Specications
Operating temperature: -20 °C to 50 °C ambient, derate each output as 2.5% per degree from 50 °C to 70 °C;
-40 °C startup if Standby output ≤ 1A (any valid load on main output);
-30 °C startup if Standby output > 1A (any valid load on main output)
Storage temperature: -40 °C to +85 °C
Electromagnetic susceptibility: Designed to meet EN61000-4; -2, -3, -4, -5, -6, -8, -11 Level 3
Humidity: Operating; non-condensing 10% to 95% RH
Vibration: IEC68-2-6 to the levels of IEC721-3-2
Ordering Information
Model
Number
Output
Voltage
Minimum
Load
Maximum Load with
Convection Cooling
Maximum Load
with Forced Air
Peak
Load Regulation2
Ripple
P/P (PARD)3
LPS363-M 12 V 0 A 20 A 30 A 39 A ±2% 120 mV
LPS364-M 15 V 0 A 16 A 24 A 31 A ±2% 150 mV
LPS365-M 24 V 0 A 10 A 15 A 19.5 A ±2% 240 mV
LPS368-M 48 V 0 A 5 A 7.5 A 9.75 A ±2% 480 mV
1. Peak current lasting <3 seconds.
2 . At 25 °C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3 . Peak-to-peak with 20 mHz bandwidth and 10 µF (tantalum capacitor) in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.
Pin Assignments
Connector LPS360-M
J4 Pin 1 Neutral
Pin 3 Line
Barr Barr-1 Main output +
Barr-2 Main output common
J5 Pin 1 +V1 Remote sense
Pin 2 -V1 Remote sense
Pin 3 +5 V Standby
Pin 4 5 V Standby return
Pin 5 +Power fail
Pin 6
**
Forced air operation
Pin 7 Inhibit
Pin 8 GND
Pin 9 SDA
Pin 10 SCL
J3 Pin 1 +12 V Fan
Pin 2 12 V fan Return (isolated)
** For forced air operation, connect pin 6 to pin 8 of J5.
Mating Connectors
J4 AC Input Molex 09-50-3031 (connector)
PINS: 08-52-0072
J6 AC Ground Molex 01-90020001
DC Output
(Barr)
Molex 19141-0058/0063 or 19099/0048
Spade lug based on Cable Ampacity/AWG
J5 Control Signals Molex 90142-0010 (USA)
PINS: 90119-2110 or
Amp: 87977-3
PINS: 87309-8
J3 Fan Output Molex 51065-0200
Pins: 50212-8100
The Artesyn Connector Kit #70-841-029, includes all of the above.
1. Specications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±0.02”(±0.5 mm)
3. Mounting holes MH1 and MH2 should be grounded for EMI purposes.
4. Mounting hole MH1 is safety ground connection.
5. Specications are for convection rating at factory settings at 115 VAC input, 25 °C unless
otherwise stated.
6. This power supply requires mounting on metal standoffs 0.20” (5m) in height.
7. Warranty: 3 Years
8. Weight: 0.75 lb/0.34 kg
LPS360-M Series Data Sheet
Digital I2C Interface Accessories
73-769-001 USB to I2C Adapter with USB Cable
73-841-030 LPS360-M I2C Mating Connector
Artesyn Connector Kit #73-769-005 includes both of the above
WORLDWIDE OFFICES
Americas
2900 S.Diablo Way
Tempe, AZ 85282
USA
+1 888 412 7832
Europe (UK)
Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX
United Kingdom
+44 (0) 1384 842 211
Asia (HK)
14/F, Lu Plaza
2 Wing Yip Street
Kwun Tong, Kowloon
Hong Kong
+852 2176 3333
For more information: www.artesyn.com/power
For support: productsupport.ep@artesyn.com
www.artesyn.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Artesyn
Embedded Technologies assumes no responsibility, and disclaims all liability for damages resulting from use
of this information or for any errors or omissions. Artesyn Embedded Technologies, Artesyn and the Artesyn
Embedded Technologies logo are trademarks and service marks of Artesyn Embedded Technologies, Inc.
All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective
owners. © 2015 Artesyn Embedded Technologies, Inc.
LPS360-M Series Data Sheet
LPS360-M DS Rev. 01.20.15
Mechanical Drawings
Performance Data
J4
J6
J3
J5
BARR1(+) BARR2(-)
M4X0.7P
VR1 OUTPUT
VOLTAGE ADJUSTMENT POST
PIN 1(+V1 REMOTE SENSE)
3.00
[76.20]
2.55
[64.80]
4.55
[115.60]
5.00
[127.00]
0.16
[4.00]
0.16
[4.00]
0.16
[4.00]
0.16
[4.00]
1.36
[34.60]
0.197 MINIMUM STANDOFF HEIGHT
[5.00]
J5 PIN NUMBERING
15
610