SIMATIC S5 S5-135U CPU 928B Introduction 1 User Program 2 Program Execution 3 Operating Modes and Program Processing Levels 4 Interrupt and Error Diagnosis 5 Integrated Special Functions 6 Extended Data Block DX 0 7 Programming Guide Order No. 6ES5 998-2PR21 Release 01 Memory Assignment and Memory Organization Memory Access Using Absolute Addresses Multiprocessor Mode and Communication 9 10 PG Interfaces and Functions 11 Appendix 12 Further Reading 13 List of Abbreviations Index List of Tables and Figures 14 The CPU 922/CPU 928/CPU 928B/CPU 948 List of Operations, Order No. 6ES5 997-3UA22 is included with this manual. C79000-H8576-C898-01 8 Copyright Copyright (c) Siemens AG 1994 All Rights Reserved The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Disclaimer of liability We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed. Technical data subject to change. Safety-related guidelines This manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger: ! ! Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. Caution indicates that minor personal injury or property damage can result if proper precautions are not taken. Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are defined as persons who are authorized to commission, to ground and to tag equipment, systems and circuits in accordance with established safety practices and standards. Siemens Aktiengesellschaft 6ES5 998-2PR21 EWK Elektronikwerk Karlsruhe Printed in the Federal Republic of Germany How to use this Manual Scope This programming guide describes the following versions of the CPU 928B-3UB11 and CPU 928B-3UB12 and its system software: The additional functions of the CPU 928B-3UB12 are indicated in the manual. Some of them can be retrofitted to the CPU 928B-3UB11 (see Section 1.8 for details). CPU 928B Programming Guide C79000-D8576-C898-01 0-1 How to Use this Manual Overview of the Chapters Chapter 1 This informs you about the areas of application of the S5-135U programmable controller with the CPU 928B and its device structure. It explains the typical mode of operation of the CPU and illustrates how a CPU program is structured. The chapter also contains suggestions about how to tackle programming and which characteristics of the CPU 928B are important for programming. If you have already worked with the CPU 928B-3UB11 and want to know the differences between these CPU and the CPU 928B-3UB12 you will find this information in this chapter. Chapter 2 This explains the components of a STEP 5 user program and how the program can be structured. Chapter 3 This is intended for readers who do not yet have much experience of using the STEP 5 programming language. It therefore deals with the basics of STEP 5 programming and explains the STEP 5 operations in detail (with examples). Experienced readers who may find that the information about specific operations in the pocket guide is inadequate, can use Section 3.5 as a reference section. Chapter 4 This provides an overview of the modes and program execution levels of the CPU 928B. It provides you with detailed information about various start-up modes and the associated organization blocks in which you can program your routines for differrent start-up situations. The chapter also explains the differences between the program execution levels "cyclic processing", "time-controlled processing" and "interrupt-driven processing" and which blocks are available for your user program. Chapter 5 This informs you about errors to be avoided when planning and writing your STEP 5 programs. The chapter tells you about the help you can obtain from the system program for diagnosing errors and which reactions can be expected and informs you about the blocks in which you can program reactions to certain errors. The chapter also explains the CPU 948 self-test. CPU 928B Programming Guide 0-2 C79000-D8576-C898-01 How to Use this Manual Chapter 6 This covers the special functions integrated in the system program. It tells you how to use the special functions and how to call and assign parameters to the special function OBs. The chapter also explains how to recognize and deal with errors in the processing of a special function. Chapter 7 This describes the use of data block DX 0 and its structure. The chapter informs you of the significance of the various DX 0 parameters. Based on examples, you will learn how to create data block DX 0 or how to assign the parameters in a screen form. Chapter 8 This is a reference section for experienced system users. It provides information about the memory organization of the CPU 928B and certain system data words which contain information that can be called up by the user. Chapter 9 This is also for experienced system users. The chapter explains how to address data in certain memory areas using absolute addresses. Chapter 10 This explains when the multiprocessor mode can be used and how data can be exchanged between the CPUs and CPs. The chapter provides information about programming for multiprocessor operation. The remainder of the chapter provides detailed information and application examples for exchanging larger amounts of data in the multiprocessor mode (multiprocessor communication). Chapter 11 This tells you how to connect your CPU to a PG and the functions provided by the PG software to test your STEP 5 program. Chapter 12 This contains the Appendix with technical specifications of the CPUs which can be used on the S5-135U, some reference tables with important information on error diagnostics and an ISTACK evaluation example. CPU 928B Programming Guide C79000-D8576-C898-01 0-3 How to Use this Manual Chapter 13 This lists documentation for further reading. Chapter 14 This is intended to help you find themes quickly and contains a list of abbreviations and a list of keywords as well as lists of all the numbered tables and figures. CPU 928B Programming Guide 0-4 C79000-D8576-C898-01 How to Use this Manual Conventions used in the text To provide you with an overview of the contents of the pages, the manual uses the following conventions in addition to a 2nd and 3rd order of titles: Entries in the margin Entries in the margin are keywords printed in italics on the left-hand edge of a page. They provide information about the contents of one or more paragraphs on the page. Fourth order entries Fourth order entries are not numbered but appear in the margin in bold face and identify a longer section of text. The following conventions are also used. Notes Note Important information is indicated in this format. Instructions Instructions (often a sequence of operations to be performed) are represented in tables, e.g. Step Action Result 1 Switch the mode selector from RUN to STOP. The CPU is in the stop mode. The STOP LED is lit continuously. 2 An OVERALL RESET is Hold the reset switch in the OVERALL RESET position; requested. The STOP LED at the same time, switch the flashes quickly. mode selector from STOP to RUN and back to STOP. CPU 928B Programming Guide C79000-D8576-C898-01 0-5 How to Use this Manual Reference tables Table 3-2 Specific information you may require at any time is contained in numbered tables as shown in the following example and can be found in the list of tables (refer to Chapter 14). Binary logic operations Operation Operand Function A AND logic operation with scan for signal state "1" O OR logic operation with scan for signal state "1" I 0.0 to 127.7 ...... Examples Example 1: of an input in the PII ........ Examples, some of which cover several pages, are highlighted by a gray frame. When the examples cover more than one page this is clearly indicated. Calling and assigning parameters to a function block in the methods of representation STL and LAD/CSF in a program block Method of representation STL ...... CPU 928B Programming Guide 0-6 C79000-D8576-C898-01 1 Introduction 1 Contents of Chapter 1 1.1 Area of Application for the S5-135U with the CPU 928B. . . . . . . . . . . . . . . . . . . . . . . . 1 - 4 1.2 Typical Mode of Operation of a CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 6 1.3 The Programs in a CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 8 System program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 8 User program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 10 1.4 Which Operands are available to the User Program? . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 12 1.5 Accessing Operand Areas and Memory Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 16 1.6 How to Tackle Programming? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 17 1.7 Programming Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 20 1.8 What is New with the CPU 928B? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 21 CPU 928B Programming Guide C79000-D8576-C898-01 1-1 1 Introduction 1 Aims of the manual This manual is intended to provide specialized information about programming the CPU 928B for users who already have basic knowledge of programming PLCs and want to use the CPU 928B in the S5-135U programmable controller. If you do not yet have this basic knowledge, we strongly advise you read the documentation introducing the programming language STEP 5 (STEP 5 Manual, refer to Chapter 13) or take part in a course at our training center. SIEMENS provides comprehensive training for SIMATIC S5. For more detailed information, contact your local SIEMENS office. Contents of Chapter 1 Chapter 1 explains how to use the manual and deals with the areas of application of the S5-135U programmable controller with the CPU 928B and its structure. The chapter explains the typical mode of operation of a CPU and the structure of the CPU program. You will also find a few suggestions about how to tackle programming and will learn some of the features of the CPU 928B (-3UB12) which are important for programming. If you have already worked with the CPU 928B (-3UB11) and would like to know the differences between these modules and the CPU 928B (-3UB12), refer to Section 1.8. CPU 928B Programming Guide C79000-D8576-C898-01 1-3 Area of Application for the S5-135U with the CPU 928B 1.1 Area of Application for the S5-135U with the CPU 928B SIMATIC S5 family The S5-135U programmable controller belongs to the family of SIMATIC S5 programmable controllers. With the CPU 928B, it is the most powerful multiprocessor unit for process automation (open and closed loop control, signalling, monitoring, logging). Owing to its modularity and high performance, it can be used for medium to extremely large control systems as well as for complex automation tasks at the plant and process supervision level. Suitability The S5-135U with the CPU 928B is particularly suitable for the following: * Tasks requiring fast bit and word-oriented processing and fast reaction times, i.e. with extremely fast open and closed loop controls. Examples of this are fast processes in mechanical engineering (bottling plant, packing machines or similar systems) and in the automobile industry. * Tasks requiring an extremely high storage capacity and fast access times, e.g. in the automobile industry, process and plant engineering. * Tasks requiring fast communication with other CPUs installed in the PLC and operating in the multiprocessor mode and with CP modules (e.g. when connected to bus systems, host computers, for visualization, operation and monitoring). * Complex tasks which can be handled efficiently and clearly using the high level languages C and SCL. CPU 928B Programming Guide 1-4 C79000-D8576-C898-01 Area of Application for the S5-135U with the CPU 928B 1 This p age has been left intentionally blank. CPU 928B Programming Guide C79000-D8576-C898-01 1-5 Typical Mode of Operation of a CPU 1.2 Typical Mode of Operation of a CPU Mode of operation of a CPU 1. The following modes of operation are possible in a CPU: 2. Time-controlled processing Cyclic processing Cyclic processing 3. Interrupt-driven processing This is the main part of all activities in the CPU. As the name already says, the same operations are repeated in an endless cycle. Cyclic processing can be divided into three main phases, as follows: Phase 1 2 3 Sequence All the input modules assigned to the CPU are scanned by the system program and the values read in are stored in the process image of the inputs (PII). The values contained in the PII are processed by the user program and the values to be output are entered in the process image of the outputs (PIQ). The values contained in the process image of the outputs are output by the system program to the output modules assigned to the CPU. Process C PU Input I 1.3 Read in process image of the inputs Input I 1.4 Input I 1.5 Evaluate input signals, set output signals I 1.5 & I 1.6 =1 I 1.4 I 1.3 & Q 3.1 Output process image of the outputs Output Q 2.0 Output Q 3.1 Output Q 4.7 CPU 928B Programming Guide 1-6 C79000-D8576-C898-01 Typical Mode of Operation of a CPU Time-controlled processing In addition to the cyclic processing, time-controlled processing is also available for processes requiring control signals at constant intervals, e.g. non-time critical monitoring functions performed every second. Interrupt-driven processing If the reaction to a particular process signal must be particularly fast, this should be handled with interrupt-driven processing. With, for example, a process interrupt, triggered via an interrupt generating module, you can activate a special processing section within your program. Processing according to priority The types of processing listed above are handled by the CPU according to their priority. Since a fast reaction is required to a time or interrupt event, the CPU interrupts cyclic processing to handle a time or interrupt event. Cyclic processing therefore has the lowest priority. CPU 928B Programming Guide C79000-D8576-C898-01 1-7 1 The Programs in a CPU 1.3 The Programs in a CPU The program existing on every CPU is divided into the following: * the system program and * the user progra m. System program The system program organizes all the functions and sequences of the CPU which do not involve a specific control task (refer to Fig. 1-2). Execute start-up Update process image of the inputs Output process image of the outputs Call System user program processing (inter- Manage memory faces) Handle communications via 2nd serial interface Handle errors Execute communications with the programmer Fig. 1-1 Tasks of the system program CPU 928B Programming Guide 1-8 C79000-D8576-C898-01 The Programs in a CPU Tasks The tasks include the following: 1) * cold and warm restart, 1 * updating the process image of the inputs and outputting the process image of the outputs, * calling the cyclic, time-controlled and interrupt-driven programs, * detection and handling of errors, * memory management, * communication with the programmer (PG). User interfaces As the user, you can influence the reaction of the CPU to particular situations and errors via special interfaces to the system program. Default system reaction The following chapters, except for Chapter 7, describe the default system reaction to process events or errors. Depending on the defaults, the CPU changes to the stop mode if an operation code error occurs and the error organization block is not loaded. Modifying the defaults You can modify the system response by assigning parameters for the data block DX 0. Chapter 7 describes the system response following modification . 1) When operating with several CPUs (multiprocessing) further tasks are involved. CPU 928B Programming Guide C79000-D8576-C898-01 1-9 The Programs in a CPU User program Tasks The user program contains all the functions required for processing a specific control task. In general terms, these functions can be assigned to the interface provided by the system program for the various types of processing, as follows: Type of processing Task Cold and warm restart To provide the conditions under which the other processing functions can start from a defined status following a cold or warm restart of the control system (e.g. assigning specific values to signals). Cyclic processing Constantly repeated signal processing (e.g. logic operations on binary signals, reading in and analyzing analog values, specifying binary signals for output, outputting analog values). Time-controlled processing Special, time-dependent processing with the following time conditions: - faster than the average cycle, - at a time interval greater than the average cycle time, - at a specified point in time. Interrupt-driven processing Special, fast reactions to certain process signals. Error reaction Handling problems within the normal sequence of the program. CPU 928B Programming Guide 1 - 10 C79000-D8576-C898-01 The Programs in a CPU Structure User memory 1 User program Code blocks Organization blocks Program blocks OB PB STEP 5 operations STEP 5 operations I 1.5 F 50.1 =1 I 1.4 FB/FX F 1.7 SEGMENT 1 NAME :TRANS F 50.2 F 50.3 STEP 5 operations FB 8 =1 & I 1.3 SB STEP 5 operations & I 1.6 Sequence blocks Function blocks Q 5.3 Q 3.1 0005 0006 0007 0008 0009 000A 000B I 2.6 S I 1.3 R Q :L IB 3 :T FW 200 :C DB 5 :DO FW 200 :L DW 0 :T QW 6 :BE Data blocks DB static or dynamic data (bits, bytes, words, double words) DX static or dynamic data (bits, bytes, words, double words) Fig. 1-2 1: 2: 3: 4: 5: 6: 7: KH KF KS KY KG KM = 0101; = +120; = xy; = 4.5; = = 1: 2: 3: 4: 5: 6: 7: KH KH KH KH KH KH = = = = = = FFFF; FFFF; FFFF; FFFF; FFFF; FFFF; Structure of a STEP 5 user program CPU 928B Programming Guide C79000-D8576-C898-01 1 - 11 The Programs in a CPU Storing the user program The CPU 928B has two areas for storing blocks: * User memory: max. 64 Kbytes The user memory is on a plug-in RAM or EPROM submodule and contains logic and data blocks (if the user memory is an EPROM submodule, the data blocks whose data are changed by the user program must be loaded in the DB RAM). Data block RAM (DB RAM): max. 46 Kbytes The DB RAM is an additional memory area for storin g d ata blocks. Interfaces to the system program Org anization blocks are available as interfaces to the system program for the special types of processing. CPU 928B Programming Guide 1 - 12 C79000-D8576-C898-01 Which Operands are available to the User Program? 1.4 Which Operands are available to the User Program? 1 The CPU 928B provides the following operand areas for programming: * process image and I/Os * flags (F flags and S flags) * timers/counters * data blocks Process image of the inputs and outputs PII/PIQ Characteristics The user program can access the following data types in the process image extremely quickly: - single bits, - bytes, - words, - double words Size 128 bytes each for inputs and outputs I/O area (P area) Characteristics The user program can access the I/O modules directly via the S5 bus. The following data types are possible: - bytes, - words. Size 256 bytes each for inputs and outputs Extended I/O area (O area) Characteristics The user program can access the I/O modules directly via the S5 bus. The following data types are possible: - bytes, - words. Size 256 bytes each for inputs and outputs CPU 928B Programming Guide C79000-D8576-C898-01 1 - 13 Which Operands are available to the User Program? F flags Characteristics Size The flag area is a memory area which the user program can access extremely quickly with certain operations. The flag area should be used ideally for working data required often. 2048 bits The following data types can be accessed: - single bits, - bytes, - words, - double words. Single flag bytes can be used as interprocessor com munication flags (IPC flags) to exchange data between the CPUs in the multiprocessor mode (refer to Chapter 10). IPC flags are updated by the system program at the end of the cycle via a buffer in the coordinator or CP/IP. S flags (extended flag area) Characteristics Size The CPU 928B also contains an additional flag area, the S flag area. The user program can also access this area extremely quickly as with the F flags. 8192 bits S flags cannot however by used as actual operands with function block calls nor as IPC flags for data exchange between the CPUs. The bit test operations of the CPU 948 can also not be used with the S flags. These flags can only be used with the PG system software "S5-DOS" from version 3.0 upwards or "S5-DOS/MT" from version 1.0 upwards. CPU 928B Programming Guide 1 - 14 C79000-D8576-C898-01 Which Operands are available to the User Program? Timers (T) Characteristics The user program loads timer cells with a time value between 10 ms and 9990 s and by means of a start operation, decrements the timer from this value at the preselected intervals until it reaches the value zero. Size 1 256 timer cells Counters (C) Characteristics Size The user program loads counter cells with a start value (max. 999) and then increments or decrements them. 256 counters Characteristics Size Data words in the current data block A data block contains constants and/or variables in the byte, word or double word format. With STEP 5 operations, you can always access the "current" data block (refer to Section 2.4.2). The following data types can be accessed: - single bits, - bytes, - words, - double words. 1) 256 words 1) In data blocks with a length greater than 256 words, you can only access data words with the numbers > 255 with operations for absolute memory access (refer to Chapter 9). CPU 928B Programming Guide C79000-D8576-C898-01 1 - 15 Accessing Operand Areas and Memory Areas 1.5 Accessing Operand Areas and Memory Areas STEP 5 operations use two different mechanisms for accessing operand areas and the entire memory: Relative addressing The majority of STEP 5 operations address a memory location relative to the beginning of the operand area. If these operations are used exclusively, code and data areas of the user program are protected against unintentional overwriting. At the same time, the user program is dependent on the CPU as long as the CPU has an appropriate operand area. Absolute addressing Some STEP 5 operations work with absolute addresses. These operations can be used to access the entire memory area. They can only be used in function blocks and should only be used with great care due to the danger of data corruption. These operations are dependent on the CPU used. However, there is no difference between the CPU 928 and CPU 928B regarding these operations. Current data block Data blocks are loaded into the user memory or the DB-RAM by the system program. Their location depends on the memory space available in each case. The lengths of the individual data blocks can vary and are set when programming the data blocks. The current data block is the data block whose starting address and length are entered in special registers. This entry is made via a special STEP 5 operation for calling or "opening" a data block (like the page of book). Unless operations with absolute addressing are used, the user program can only access the current data block. The following data types are possible: single bits, bytes, words and double words. CPU 928B Programming Guide 1 - 16 C79000-D8576-C898-01 How to Tackle Programming 1.6 How to Tackle Programming If you are an experienced user, you have probably found the most suitable method for creating programs for yourself and you can skip this section. Less experienced readers will find tips for designing, programming, testing and starting up your STEP 5 program. Implementation stages The implementation of the STEP 5 control program can be divided into three stages: Stage Activity 1 Determining the technological task 2 Designing the program 3 Creating, testing and starting the program Recursive procedure In practice, you will recognize that certain steps must be repeated (recursive procedure), e.g. when you realize that more signals are required to improve the handling of the task. Stage 1 Determining the technological task: Stage Activity 1 Create a general block diagram outlining the control tasks of your process. 2 Create a list of the input and output signals required for the task. 3 Improve the block diagram by assigning the signals and any particular time conditions and/or counter statuses to the individual blocks. CPU 928B Programming Guide C79000-D8576-C898-01 1 - 17 1 How to Tackle Programming Stage 2 Notes on the scope of cyclic processing Designing the program: Stage Activity 1 Based on the improved block diagram, decide on the types of processing required of your program (cyclic processing, time-controlled processing etc.) and select the OBs required for this. 2 Divide the types of processing into technological and/or functional units. 3 Check whether the units can be assigned to a program or function block and select the blocks you require (PB x, FB y etc.) 4 Find out which timers, counters and data or results memory you require. 5 Specify the tasks for each of the proposed logic blocks and the data for flags and data blocks which may be required. Create flow diagrams for the logic blocks. When deciding on the types of processing, keep the following conditions in mind: * The cycle must run through quickly enough. The process statuses must not change more quickly than the CPU can react. Otherwise the process can get out of control. * The maximum reaction time should be taken as twice the cycle time. The cycle time is determined by the cyclic processing of the system program and the type and scope of the user program. It is often not constant, since the cyclic user program may be interrupted when time and interrupt-driven program sections are called. CPU 928B Programming Guide 1 - 18 C79000-D8576-C898-01 How to Tackle Programming Stage 3 Creating, testing and starting up the program: 1 Stage Activity 1 Decide on the type of representation for the logic blocks (LAD, CSF or STL, refer to Chapter 2). Remember that function blocks can only be created in the STL method of representation. 2 Program all logic and data blocks (please refer to your STEP 5 manual). 3 Start up the blocks one after the other (you may have to program a different OB for each individual step, to call the logic blocks): 1a: load the block(s) 1b: test the block(s) (For more detailed information please refer to your STEP 5 manual and Chapter 11). 4 Note on test strategies When you are certain that all the logic blocks run correctly and all the data can be correctly calculated and stored, you can start up your whole program. When you actually start up your program for the first time in genuine process operation, i.e. with real input and more importantly output signals, is a decision that must be left up to yourself or to a team of experts. The more complex the process, the greater the risk and therefore the greater the care required when starting up. CPU 928B Programming Guide C79000-D8576-C898-01 1 - 19 Programming Tools 1.7 Programming Tools Suitable PGs The following programmers are available for creating your user program, PG 685, PG 710, PG 730, PG 750 and PG 770. You can check on the performance and characteristics of these devices in the catalog ST 59 (see Chapter 13). Note Enter the CPU ID for C PU 922 (0010H) in system data word RS 29 (see Chapter 8) in order to be able to use a PG 615 or a CP 3xx. In this case, you cannot use S flags. If you do not change the ID, this will lead to erroneous indicators, e.g. in the case of ISTACK output, or to the loss of some debugging aids. In all programmers, the STA TUS test function operates without restriction only at scan times of 2.5 s. This value is halved in the case of parallel operation of 2 programmer interfaces (see Chapter 11). Suitable software You can create user programs for SIMA TIC S5 programmable controllers as follows: * In the STEP 5 programming language, Here you require the STEP 5 programming package along with the system software STEP 5/ST or STEP 5/MT (description, refer to /3/ in Chapter 13), or * In a higher programming language: If you are familiar with programming in higher programming languages, you can also formulate your STEP 5 program for the CPU 928B as follows: - SCL (refer to /12/ in Further Reading, the SCL compiler is contained in the PG software "S5-DOS/MT" from version 6 upwards.) You can also create programs for sequence control systems in a graphic representation using the GRAPH 5 programming package (description, refer to /4/ in Chapter 13). Depending on the task, you can also incorporate "off-the-peg" standard function blocks in your user program. The performance and characteristics of these blocks are described in the catalog ST 57 (see Chapter 13). CPU 928B Programming Guide 1 - 20 C79000-D8576-C898-01 What is New with the CPU 928B (-3UB12)? 1.8 What is New with the CPU 928B (-3UB12)? The CPU 928B (-3UB12) offers you the following new functions compared to the CPU 928B (-3UB11). Additional restart type: RETENTIVE COLD RESTART 1) As well as the existing restart types (MANUAL/AUTOMATIC COLD RESTART; MANUAL/AUTOMATIC WARM RESTART) you can use the following additional restart types: * RETENTIVE MANUAL COLD RESTART * RETENTIVE AUTOMATIC COLD RESTART You can set these restart types by assigning parameters in DX 0. Delay interrupt As well as the familiar time interrupts, an additional delay interrupt is processed by the new OB 6 organization block. The delay interrupt has a time resolution of 1 ms. You assign parameters to the desired delay time with the new OB 153 organization block. Alternative loading of data blocks 1) You can use the programmer to load data blocks into DB RAM first, instead of into the user memory. Selection of the loading mode is controlled via bit 0 in system data word RS 144. SINEC L1 via the 2nd serial interface 1) Connection to the SINEC L1 LAN (with the new L1 interface card) has been expanded for communication via the second serial interface: * Use as slave in - Normal communication - Internode communication - Interrupt communication - Broadcast; * Use as master in point-to-point connections. 1) can be retrofitted to CPU 928B (-3UB11) CPU 928B Programming Guide C79000-D8576-C898-01 1 - 21 1 2 User Program 2 Contents of Chapter 2 2.1 STEP 5 Programming Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 The LAD, CSF, STL Methods of Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4 Structured Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 5 STEP 5 Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 6 Number Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 8 STEP 5 Blocks and Storing them in Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 12 2.2 Program, Organization and Sequence Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 16 2.2.1 2.2.2 Organization Blocks as User Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 18 Organization Blocks for Special Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 22 2.3 Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 23 2.3.1 2.3.2 2.3.3 2.3.4 Structure of Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Function Blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calling Function Blocks and Assigning Parameters to them . . . . . . . . . . . . . . . . . . . . . Special Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Data Blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 35 2.4.1 2.4.2 2.4.3 Creating Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 37 Opening Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 38 Special Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 41 2 - 24 2 - 26 2 - 28 2 - 33 CPU 928B Programming Guide C79000-B8576-C898-01 2-1 2 User Program 2 The following chapter explains the components that make up a STEP 5 user program for the CPU 928B and how it can be structured. CPU 928B Programming Guide C79000-B8576-C898-01 2-3 STEP 5 Programming Language 2.1 STEP 5 Programming Language With the STEP 5 programming language, you convert automation tasks into programs that run on SIMATIC S5 programmable controllers. You can program simple binary functions, complex digital functions and arithmetic operations including floating point arithmetic using STEP 5. Types of operation The operations of the STEP 5 programming language are divided into the following groups: B asic operations * you can use these operations in all logic blocks * methods of representation: ladder diagram (LAD), control system flowchart (CSF), statement list (STL). Supplementary operations and system operations: * can only be used in function blocks * only statement list (STL) method of representation * system operations: only experienced STEP 5 programmers should use system operations 2.1.1 The LAD, CSF, STL Methods of Representation When programming in STEP 5, you can choose between the three methods of representation ladder diagram (LAD), control system flowchart (CSF) and statement list (STL) for each individual logic block. You can choose the method of representation that best suits your particular application. The machine code MC5 that the programmers (PGs) generate is the same for all three methods of representation. If you follow certain rules when programming in STEP 5 (see /3/ in Chapter 13), the programmer can translate your user program from one method of representation into any other. Graphic representation or list of statements While the ladder diagram (LAD) and control system flowchart (CSF) methods of representation represent your STEP 5 program graphically, statement list (STL) represents STEP 5 operations individually as mnemonic abbreviations. CPU 928B Programming Guide 2-4 C79000-B8576-C898-01 STEP 5 Programming Language Ladder diagram Statement list Control system flowchart Programming with graphic symbols like a circuit diagram Programming with mnemonic abbreviations of function designations Programming with graphic symbols complies with DIN 19239 complies with DIN 19239 complies with IEC 117-15 DIN 40700 DIN 40719 DIN 19239 LAD STL CSF A AN A ON O = Fig. 2-1 I I I I I Q 2 & >=1 Methods of representation in the STEP 5 programming language Graphic representation of sequential controls 2.1.2 Structured Programming GRAPH 5 is a programming language for graphic representation of sequential controls. It is at a higher level than the LAD, CSF, STL methods of representation. A program written in GRAPH 5 as a graphic representation is automatically converted to a STEP 5 program by the PG. (Refer to /4/ in Chapter 13) Using STEP 5, you can structure your program by dividing it into self-contained program sections (blocks). This division of your program clarifies the essential program structures making it easy to recognize the system parts that are related within the software. CPU 928B Programming Guide C79000-B8576-C898-01 2-5 STEP 5 Programming Language Structured programmin g offers you the following advantages: * simple and clear creation of programs, even large ones * standardization of program parts * simple program organization * easy program changes * simple, section by section program test * simple system start-up What is a block? 2.1.3 STEP 5 Operations A block is a part of the user program that is distinguished by its function, structure or application. You can differentiate between blocks that contain statements (code) i.e. organization blocks, program blocks, function blocks or sequence blocks, and blocks that contain data (data blocks). A STEP 5 operation is the smallest independent unit of the user program. It is the work specification for the CPU. A STEP 5 operation consists of an operation and an operand as shown in the following example: Example Operation code :O Parameter F 54.1 Operand Operation (what is to be done?) (with what is the operation to be done?) CPU 928B Programming Guide 2-6 C79000-B8576-C898-01 STEP 5 Programming Language Absolute and symbolic operands You can enter the operand absolutely or symbolically (using an assignment list) as shown in the following example: Absolute representation: :A I 1.4 Symbolic representation: :A -Motor1 For more information on absolute and symbolic programming, refer to your STEP 5 manual. Application of STEP 5 operations The STEP 5 operation set enables you to do the following: * set or reset and combine binary values logically * load and transfer values * compare values and process them arithmetically * specify timer and counter values * convert number representations * call blocks and execute jumps within a block and * influence program execution Result of logic operation RLO The central bit for controlling the program is the result of logic operation RLO. This is obtained as a result of binary logic operations and is influenced by some operations. Section 3.5 describes the whole STEP 5 operation set and explains how the RLO is obtained. This section also includes programming examples for individual STEP 5 operations. CPU 928B Programming Guide C79000-B8576-C898-01 2-7 2 STEP 5 Programming Language 2.1.4 Number Representation To allow the CPU to logically combine, modify or compare numerical values, these values must be located in the accumulators (working registers of the CPU) as binary numbers. Depending on the operations to be carried out, the following number representations are permitted in STEP 5: Binary numbers: 16-bit fixed point numbers 32-bit fixed point numbers 32-bit floating point numbers (with a 24-bit mantissa) Decimal numbers: BCD-coded numbers (sign and 3 digits) Numerical input on the PG When you use a programmer to input or display number values, you set the data format on the programmer (e.g. KF or fixed point) in which you intend to enter or display the values. The programmer converts the internal representation into the form you have requested. Permitted operations You can carry out all arithmetic operations with the 16-bit fixed point numbers and floating point numbers, including comparison, addition, subtraction, multiplication and division. Note Do not use BCD-coded numbers for arithmetical operations, since this leads to incorrect results. Use 32-bit fixed point numbers to execute comparison operations. These are also necessary as an intermediate level when converting numbers in BCD code to floating point numbers. With the operations +D and -D they can also be used for addition and subtraction. The STEP 5 programming language also has conversion operations that enable you to convert numbers directly to the most important of the other numerical representations. CPU 928B Programming Guide 2-8 C79000-B8576-C898-01 STEP 5 Programming Language 16-bit and 32-bit fixed point numbers Fixed point numbers are whole binary numbers with a sign. Coding of fixed point numbers Fixed point numbers are 16 bit (= 1 word) or 32 bit (= 2 words) in binary representation. Bit 15 or bit 31 contains the sign. * '0' = positive number * '1' = negative number 2 The two's complement representation is used for negative numbers. PG input Permitted numerical range Input of 16-bit fixed point number data format at the PG: KF Input of 32-bit fixed point number data format at the PG: DH -32768 to +32767 (16 bit) -2147483648 to +2147483647 (32 bit) Using fixed point numbers Use fixed point numbers for simple calculations and for comparing number values. Since fixed point numbers are always whole numbers, remember that the result of dividing two fixed point numbers is also a fixed point number without decimal places. CPU 928B Programming Guide C79000-B8576-C898-01 2-9 STEP 5 Programming Language Floating point numbers Floating point numbers are positive and negative fractions. They always occupy a double word (32 bits). A floating point number is represented as an exponential number. The mantissa is 16 or 24 bits long and the exponent is 8 bits long. In the CPU 928B, the default mantissa (assuming you have not changed the setting) is 16-bits long (bits 8 to 23) for adding, subtracting, multiplying and dividing. The least significant (on the right) bits 0 to 7 always have the value "0". If you require floating point calculations with a higher accuracy (and can accept a slightly longer runtime), program the setting "floating point arithmetic with 24-bit mantissa" in DX 0 (see Chapter 7). The exponent indicates the order of magnitude of the floating point number. The sign of the exponent tells you whether the value of the floating point number is greater or less than 0.1. Using floating point numbers Use floating point numbers for solving extensive calculations, especially for multiplication and division or when you are working with very large or very small numbers! Accuracy The mantissa indicates the accuracy of the floating point number as follows: * Accuracy with a 24-bit mantissa: 2 -2 4 = 0.000000059604 (corresponds to 7 decimal places) * Accuracy with a 16-bit mantissa: 2 -16 = 0,00001525 8 (corresponds to 4 decimal places) If the sign of the mantissa is "0" the number is positive; if the sign is "1" it is a negative number in its two's complement representation. The floating point value '0' is represented as the binary value 8 0000000H (32 bits, see below). CPU 928B Programming Guide 2 - 10 C79000-B8576-C898-01 STEP 5 Programming Language Coding floating point numbers Coding a floating point number: 31 30 V 24 23 22 6 2 ... . ... 2 0 V 0 -1 2 .... . . . Exponent -23 . . ... 2 Mantissa 2 Specification of the data format for floating point numbers at the PG: KG Permissible numerical range 0.1469368 x 10 Input/output on PG a) -38 to 0.1701412 x 1039 in a logic block: You want to load the number N = 12.34567 as a floating point number. Input: :LKG1 234567+2 PG display after you enter the line: :L KG + 1234567 + 02 Mantissa with sign Exponent (base 10) with sign Value of the number input: +0.1234567 x 10+2 = 12.34567 b) in a data block: You want to define the number N = - 0.005 as a floating point constant. Input: 6: KG = -5 -2 PG display after you enter the line: 6: KG =- 5000000 - 02 Mantissa with sign Exponent (base 10) with sign Value of the number input: - 0.5 x 10-2 = 0.005 CPU 928B Programming Guide C79000-B8576-C898-01 2 - 11 STEP 5 Programming Language Numbers in BCD code Decimal numbers are represented as numbers in BCD code. With their sign and three digits, they occupy 16 bits (1 word) in an accumulator as shown in the following example: 15 V V V V 12 11 8 7 hundreds 4 3 tens 0 ones The individual digits are positive 4-bit binary numbers between 0000 and 1001 (0 and 9 decimal). The left bits are reserved for the sign as follows: Sign for a positive number: Sign for a negative number: Permissible numerical range 0000 1111 -999 to +999 CPU 928B Programming Guide 2 - 12 C79000-B8576-C898-01 STEP 5 Programming Language 2.1.5 STEP 5 Blocks and Storing them in Memory Identifier A block is identified as follows: 2 * the block type (OB, PB, SB, FB, FX, DB, DX) and * the block number (number between 0 and 255). Block types The STEP 5 programming language differentiates between the following block types: Organization blocks (OB) Organization blocks are the interface between the system program and the user program. They can be divided into two groups as follows: With OB 1 to OB 39, you can control program execution, the restart procedure of the CPU and the reaction in the event of an error. You program these blocks yourself according to your automation task. These OBs are called by the system program. OBs 40 to 100 are blocks belonging to the operating system. You must not call these blocks. OBs 121 to 255 contain special functions of the system program. You can call these blocks, if required, in your user program. Program blocks (PB) You require program blocks to structure your program. They contain program parts divided according to technological and functional criteria. Program blocks represent the heart of the user program. Sequence blocks (SB) Sequence blocks were originally special program blocks for step by step processing of sequencers. In the meantime, however, sequencers can be programmed with GRAPH 5. Sequence blocks have therefore lost their original significance in STEP 5. Sequence blocks now represent an extension of the program blocks and are used as program blocks. CPU 928B Programming Guide C79000-B8576-C898-01 2 - 13 STEP 5 Programming Language Function blocks (FB/FX) You use function blocks to program frequently recurring and/or complex functions (e.g. digital functions, sequence control systems, closed loop controls and signalling functions). A function block can be called several times by higher order blocks and supplied with new operands (assigned parameters) at each call. Using block type FX increases the maximum number of possible function blocks from 256 to 512. Data blocks (DB/DX) Data blocks contain the (fixed or variable) data with which the user program works. This type of block contains no STEP 5 statements and has a distinctly different function from the other blocks. Using block type DX doubles the number of possible data blocks. Formal structure of the blocks All blocks consist of the following two parts: * a block header and * a block body Block header The block header is always 5 words long and contains information for block management in the PG and data for the system program. Block body Depending on the block type, the block body contains the following: * STEP 5 operations (in OB, PB, SB, FB, FX), * variable or constant data (in DB, DX) and * a formal operand list (in FB, FX). CPU 928B Programming Guide 2 - 14 C79000-B8576-C898-01 STEP 5 Programming Language Block preheader The programmer also generates a block preheader (DV, DXV, FV, FXV) for block types DB, DX, FB and FX. These block preheaders contain information about the data format (for DB and DX) or the jump labels (for FB and FX). Only the PG can evaluate this information. Consequently the block preheaders are not transferred to the CPU memory. You cannot influence the contents of the block header directly. Maximum length A STEP 5 block can occupy a maximum of 4096 words in the program memory of the CPU (1 word corresponds to 16 bits). Available blocks You can program the following block types: OB 1 to 39 FB 0 to 255 FX 0 to 255 PB 0 to 255 SB 0 to 255 DB 3 to 255 DX 3 to 255 total 512 total 506 Data blocks DB 0, DB 1, DB2, DX 0, DX 1 and DX 2 contain parameters. These are reserved for specific functions and you cannot use them as normal data blocks. CPU 928B Programming Guide C79000-B8576-C898-01 2 - 15 2 STEP 5 Programming Language Block storage The programmer stores all programmed blocks in the program memory in the order in which they are transferred (Fig. 2-2). The programmer function "Transfer data blocks B" transfers first the code blocks then the data blocks to the PLC. In RAM mode, the RAM card is first to be filled with data blocks after transfer of the code blocks and then the remaining data blocks are written into internal DB RAM. The start addresses of all stored blocks are placed in data block DB 0. Address 0 PB1 FB1 Location of blocks in the user memory PB2 DB1 SB10 OB1 Fig. 2-2 Example of block storage in the user memory Alternative loading (only in the By setting bit 0 in system data word RS 144, you can load data blocks first into internal DB RAM first (i.e. as long as space is available) case of Version -3UB12) ("Alternative loading" - see Chapter 8/RS 144). Data blocks are transferred to the RAM card only when the DB RAM has been filled. Correcting and deleting blocks When you correct blocks in "RAM mode", the old block is declared invalid in the memory and a new block is entered. Similarly, when blocks are deleted , they are not really deleted, instead they are declared invalid. Deleted and corrected blocks therefore continue to use up memory space. Note You can use the COMPRESS MEMORY online function to make space for new blocks. This function optimizes the utilization of the memory by deleting blocks marked as invalid and shifting valid blocks together. Compression is handled separately according to memory card and internal RAM (see Section 11.2.2). CPU 928B Programming Guide 2 - 16 C79000-B8576-C898-01 Program, Organization and Sequence Blocks 2.2 Program, Organization and Sequence Blocks Program blocks (PBs), organization blocks (OBs) and sequence blocks (SBs) are the same with respect to programming and calling. You can program all three types in the LAD, CSF and STL methods of representation. Programming When programming organization, program and sequence blocks, proceed as follows: Step Action 1 First indicate the type of block and then the number of the block that you want to program. The following numbers are available for the type of block listed: - program blocks 0 to 255 - sequence blocks 0 to 255 - organization blocks 1 to 39 2 Enter your program in the STEP 5 programming language. When programming PBs, OBs and SBs, you can only use the STEP 5 b asic operations! A STEP 5 block should always be a self-contained program section. Logic operations must always be completed within a block. 3 Block calls Complete your program input with the block end operation "BE". With the exception of OB 1 to OB 39 you must call the blocks to process them. Use the special STEP 5 block call operations to call the blocks. You can program block calls inside an organization, program, function or sequence block. They can be compared with jumps to a subroutine. Each jump causes a block change. The return address within the calling block is buffered by the system. CPU 928B Programming Guide C79000-B8576-C898-01 2 - 17 2 Program, Organization and Sequence Blocks Block calls can be unconditional or conditional as follows: Unconditional call The "JU" statement belongs to the unconditional operations. It has no effect on the RLO. The RLO is carried along with the jump to the new block. Within the new block, it can be evaluated but no longer combined logically. The addressed block is processed reg ardless of the previous result of logic operation (RLO - see Section 3.4). Example: JU PB 100 Conditional call The JC statement belongs to the conditional operations. The addressed block is processed only if the previous R LO = 1. If the RLO = 0, the jump is not executed. Example: JC PB 100 Note After the conditional jump operation is executed, the RLO is set to " 1 " regardless of whether or not the jump to the block is executed. PB 1 JU O PB 5 PB 5 I 5.3 PB 10 A I 1.0 JC O PB 10 F 1.5 BE A I 2.0 BE PB 6 A JC A BE Fig. 2-3 I 1.5 PB 6 I 3.2 O I 3.0 BE Block calls that enable processing of a program block CPU 928B Programming Guide 2 - 18 C79000-B8576-C898-01 Program, Organization and Sequence Blocks Effect of the BE statement After the "BE" statement (block end), the CPU continues the user program in the block in which the block call was programmed. Program execution continues at the STEP 5 statement following the block call. The "BE" statement is executed regardless of the RLO. After "BE", the RLO can no longer be combined logically. However, the RLO or arithmetic result occurring directly before execution of the BE operation is transferred to the block where the call originated and can be evaluated there. When program execution returns from the block that has been called, the contents of ACCU 1, ACCU 2, ACCU 3 and ACCU 4, the condition codes CC 0 and CC 1 and the RLO are not changed. (Refer to Section 3.5 for more detailed information about the ACCUs, CC0/CC1 and RLO). 2.2.1 Organization Blocks as User Interfaces Organization blocks form the interfaces between the system program and the user program. Organization blocks OB 1 to OB 39 belong to your user program just as program blocks. By programming these OBs, you can influence the behavior of the CPU during start-up, program execution and in the event of an error. The organization blocks are effective as soon as they are loaded in the PLC memory. This is also possible while the PLC is in the run mode. Once the system program has called a specific organization block, the user program it contains is executed. Note You can program blocks OB 1 to OB 39 as user interfaces and they are called automatically by the system program as a reaction to certain events. For test purposes, you can also call these organization blocks from the user program (JC/JU OB xxx). It is, however, not possible to trigger a COLD RESTART, e.g. by calling OB 20. The following table provides you with an overview of the user interfaces (OBs). CPU 928B Programming Guide C79000-B8576-C898-01 2 - 19 2 Program, Organization and Sequence Blocks Table 2-1 Overview of the organization blocks for program execution Org anization blocks for controllin g program execution Block Function and call criterion OB 1 Organization of cyclic program execution; first call after a start-up, then cyclic call OB 2 Organization of interrupt-driven program execution; Call by interrupt signal of S5 bus (process interrupt) OB 3 to OB 5 OB 6 Not used with the CPU 928B Delay interrupt (from Version -3UB12) OB 7, OB 8 Not used with the CPU 928B OB 9 Processing clock-controlled time interrupts Time interrupts with fixed intervals: OB 10 call every 10 ms OB 11 call every 20 ms OB 12 call every 50 ms OB 13 call every 100 ms OB 14 call every 200 ms OB 15 call every 500 ms OB 16 call every 1 s OB 17 call every 2 s OB 18 call every 5 s CPU 928B Programming Guide 2 - 20 C79000-B8576-C898-01 Program, Organization and Sequence Blocks Table 2-2 Overview of the organization blocks for start-up Organization blocks to control the start-up procedure Block Function and call criterion OB 20 Call on request for COLD RESTART (manual and automatic) OB 21 Call on request for MANUAL WARM RESTART/RETENTIVE COLD RESTART OB 22 Call on request for AUTOMATIC WARM RESTART/RETENTIVE COLD RESTART Table 2-3 Overview of the organization blocks for error handling Organization blocks for reactions to device or 1) program errors Block Function and call criterion OB 19 Runtime error (LZF): called block not loaded OB 23 Timeout (QVZ) in user program (during direct access to I/O modules or other S5 bus addresses) OB 24 Timeout (QVZ) when updating the process image and transferring interprocessor communication flags OB 25 Addressing error (ADF) OB 26 Cycle time exceeded (ZYK) OB 27 Op. code error (BCF): substitution error OB 28 STOP by PG function/stop switch/ S5 bus 2) OB 29 Op. code error (BCF): code not permitted OB 30 Op. code error (BCF): parameter not permitted OB 31 Other runtime errors (LZF) OB 32 Runtime error (LZF): load and transfer error with data blocks OB 33 Collision of time interrupts (WECK-FE) CPU 928B Programming Guide C79000-B8576-C898-01 2 - 21 2 Program, Organization and Sequence Blocks Organization blocks for reactions to device or 1) program errors Block Function and call criterion Table 2-3 continued: OB 34 Error in closed loop controller processing (REG-FE) OB 35 Communication error on the second serial interface (FE-3) OB 36 to OB 39 do not exist for the CPU 928B 1) If the OB is not programmed, the CPU changes to the stop mode in the event of an error. EXCEPTION: if OB 23, OB 24 and OB 35 do not exist, there is no reaction. 2) OB28 is called before the CPU changes to the stop mode. The CPU stops regardless of whether and how OB 28 is programmed. EXCEPTION: OB28 is not called if the power is switched off. CPU 928B Programming Guide 2 - 22 C79000-B8576-C898-01 Program, Organization and Sequence Blocks 2.2.2 Organization Blocks for Special Functions The following organization blocks contain special functions of the system program. You cannot program these blocks, but simply call them (this applies to all OBs with numbers between 40 and 255!). They do not contain a STEP 5 program. Special function OBs can be called in all logic blocks. Table 2-4 Overview of organization blocks for special functions Integral organization blocks with special functions Block: Block function: OB 110 Access to the status (condition code) byte OB 111 Clear ACCU 1, 2, 3 and 4 OB 112 ACCU roll up OB 113 ACCU roll down OB 120 "Block all interrupts" on/off OB 121 "Block individual time interrupts" on/off OB 122 "Delay all interrupts" on/off OB 123 "Delay individual time interrupts" on/off OB 150 Set/read system time OB 151 Set/read time for clock-controlled time interrupt OB 152 Cycle statistics OB 153 Set/read time for delay interrupt OB 160-163 Counter loops OB 170 Read block stack (BSTACK) OB 180 Variable data block access OB 181 Test data blocks DB/DX OB 182 Copy data area OB 190, 192 Transfer flags to data block OB 191, 193 Transfer data fields to flag area OB 200, 202-205 Multiprocessor communication OB 216-218 Access to "pages" (CPs and some IPs) OB 220 Sign extension OB 221 Set cycle monitoring time OB 222 Restart cycle monitoring time CPU 928B Programming Guide C79000-B8576-C898-01 2 - 23 2 Program, Organization and Sequence Blocks Integral org anization blocks with special functions Block: Block function: Table 2-4 continued: OB 223 Compare restart type OB 224 Transfer blocks of IPC flags OB 226 Read word from the system program OB 227 Read checksum of the system program memory OB 228 Read status information of a program execution level OB 230-237 Functions for standard function blocks (handling blocks) OB 240 Initialize shift register OB 241 Process shift register OB 242 Clear shift register OB 250 Initialize PID controller algorithm OB 251 Process PID controller algorithm OB 254, 255 Transfer data block to the DB-RAM These special functions are described in detail in Chapter 6. CPU 928B Programming Guide 2 - 24 C79000-B8576-C898-01 Function Blocks 2.3 Function Blocks Function blocks (FB/FX) are also parts of the user program just like program blocks. FX function blocks have the same structure as FB function blocks and are programmed in the same way. You use function blocks to implement frequently recurring or very complex functions. In the user program, each function block represents a complex complete function. You can obtain function blocks as follows: * as a software product from SIEMENS (standard function blocks on diskette - see /11/ in Chapter 13); with these function blocks you can generate user programs for fast and simple open loop control, signalling, closed loop control and logging; or * you can program function blocks yourself. Compared with organization, program and sequence blocks, function blocks have the following four essential differences: OB, PB, SB 1. FB/FX Range of operations only basic operations 2. - basic operations, - supplementary operations - system operations Method of representation programming and call in STL, LAD, CSF 3. programming only in AWL Name name environment not possible (only number) 4. in addition to the number a name with max. 8 chars. can be assigned Operands none formal operands (block parameters). When the block is called formal operands are assigned actual operands CPU 928B Programming Guide C79000-B8576-C898-01 2 - 25 2 Function Blocks 2.3.1 Structure of Function Blocks The block header (five words) of a function block has the same structure as the headers of the other STEP 5 block types. The block bod y on the other hand, has a different structure from the bodies of the other block types. The block body contains the function to be executed in the form of a statement list in the STEP 5 programming language. Between the block header and the STEP 5 statements, the function block needs additional memory space for its name and for a list of formal operands. Since this list contains no statements for the CPU, it is skipped with an unconditional jump that the programmer generates automatically. This jump statement is not displayed when the function block is displayed on the PG! When a function block is called, only the block body is processed. Absolute or symbolic operands You can enter operands in a function block in absolute form (e.g. F 2.5) or symbolically (e.g. MOTOR1). You must store the assignment of the symbolic operands in an assignment list before you enter the operands in a function block (see /3/ in Chapter 13). Fig. 2-4 shows the structure of a function block in the memory of a programmable controller. 5 wo r d s Skip for m a l operand list JU Block header 1 wo r d Na m e o f th e F B / F X 4 wo r d s Formal operand 1 3 wo r d s Formal operand 2 3 wo r d s List o f fo r m a l operands Block body Formal operand 3 wo r d s n 1 s t ST EP 5 u s e r o p e r a t io n ST EP 5 user program BE Fig. 2-4 Structure of a function block (FB/FX) CPU 928B Programming Guide 2 - 26 C79000-B8576-C898-01 Function Blocks The memory contains all the information that the programmer needs to represent the function block graphically when it is called and to check the operands during parameter assignment and programming of the function block. The programmer rejects incorrect input. When handling function blocks, distinguish between the following procedures: * programming FB/FX and * callin g FB/FX and then assigning actual values to the parameters. Distinction: "programming" - "calling and assigning parameters" When programmin g, you specify the function of the block. You must decide which input operands the function requires and which output results it should transfer to the calling program. You define the input operands and output results as formal operands. These function as tokens. When a block is called by a higher order block (OB, PB, SB, FB, FX), the formal operands (block parameters) are replaced by actual operands; i.e. parameters are assigned to the function block. How to program IF... You want to program a function block "directly", i.e. without formal operands. T HEN... Program it as you would a program or sequence block. You want to use formal operands Proceed as explained on the in a function block. following pages. Make sure you keep to the required order: First program the FB/FX with the formal operands and keep it on the PG (offline) or in the CPU memory (online) Then program the block(s) to be called with the actual operands. CPU 928B Programming Guide C79000-B8576-C898-01 2 - 27 2 Function Blocks 2.3.2 Programming Function Blocks You can program a function block only in the "statement list" method of representation. When entering a function block at a programmer, perform the following steps: Step 1 Action Enter the block type (FB/FX) and the number of the function block. Number your function blocks in descending order starting with FB 255, so that they do not collide with the standard function blocks. The standard function blocks are numbered from FB 1 to FB 199. 2 Enter the n ame of the function block. The name can have a maximum of eight characters and must start with a letter. 3 If the function block is to process formal operands: Enter the formal operands you require in the block as block parameters. Enter the following information for each formal operand: - the name of the block parameter (maximum 4 characters), the type of block parameter and the data type of the block parameter (if applicable) You can define a maximum of 40 formal operands. 4 Enter your STEP 5 program in the form of a statement list (STL). The formal operands are preceded by an equality sign (e.g. A = X1). They can also be referenced more than once at various positions in the function block. 5 Terminate your program input with the block end operation "BE". CPU 928B Programming Guide 2 - 28 C79000-B8576-C898-01 Function Blocks Note If you change the order or the number of formal operands in the formal operand list, you must also update all STEP 5 statements in the function block that reference a formal operand and also the block parameter list in the calling block! Program or change function blocks only on diskette or hard disk and then transfer them to your CPU! Formal operands The following parameter and data types are permitted as the formal operands of a function block (also known as block parameters): Table 2-5 Permitted formal operands for function blocks Parameter type Data type I = input parameter Q = output parameter BI/BY/W/D D = data KM/KH/KY/KS/KF/ KT/KC/KG B = block operation T = timer C = counter none (no type can be specified) I, D, B, T or C are parameters that are indicated to the left of the function symbol in graphic representation. Parameters labelled with Q are indicated on the right of the function symbol. The data type indicates whether you are working with bits, bytes, words or double words for I and Q parameters and which data format applies to D parameters (e.g. bit pattern or hexadecimal pattern). CPU 928B Programming Guide C79000-B8576-C898-01 2 - 29 2 Function Blocks 2.3.3 Calling Function Blocks and Assigning Parameters to them You can call every function block as often as you want anywhere in your STEP 5 program. You can call function blocks in a statement list or in one of the graphic methods of representation (CSF or LAD). To call a function block and assign parameters to it, perform the following steps: Step Action Reaction on PG 1 Make sure that the called function block exists either none in the PG memory (offline) or in the CPU memory (online). 2 Enter the call statement for the function block in the block where the call is to originate. You can program a function block call in an organization, program or sequence block or in another function block. 3 Assign the actual operand relevant to this call to each of the formal operands, i.e. you assign parameters to the function block. After you enter the call statement (e.g. JU FB200), the name of the relevant function block and the formal operand list appear automatically. none These actual operands can be different for separate calls (e.g. inputs and outputs for the first call of FB 200, flags for the second call). Using the formal operand list, you assign the required actual operands for each function block call. Unconditional/conditional call Unconditional call " JU FBn" for FB function blocks or "DOU FXn" for FX extended function blocks: the referenced function block is processed regardless of the previous result of logic operation (RLO). Conditional call "JC FBn" for FB function blocks or "DOC FXn" for FX extended function blocks: the referenced function block is only processed when the result of logic operation RLO = 1. If RLO = 0 the block call is not executed. Regardless of whether the block call is executed or not, the RLO is alsways set to "1". After the unconditional or conditional call, the RLO can no longer be combined logically. However, it is carried over to the called function block with the jump and can be evaluated there. CPU 928B Programming Guide 2 - 30 C79000-B8576-C898-01 Function Blocks Permitted actual operands Table 2-6 Which operands can be assigned as actual operands is shown in the following table. 2 Permitted actual operands for function blocks Parameter type Data type Actual operands permitted I, Q BI for an operand with bit address I Q F n.m n.m n.m input output flag BY for an operand with byte address IB QB FY DL DR PY OY n n n n n n n input byte output byte flag byte data byte left data byte right peripheral byte byte from extended periphery W for an operand with word address IW QW FW DW PW OW n n n n n n input word output word flag word data word peripheral word word from extended periphery ID QD FD DD n n n n input double word output double word flag double word data double word D D for an operand with double word address KM for a binary pattern (16 bits) Constants KY for two absolute numbers, one byte each, each in the range from 0 to 255 KH for a hexadecimal pattern with a maximum of four digits KS for two alphanumeric characters KT for timer value (BCDcoded) units .0 to .3 and values 0 to 999 KC for a counter value 0 to 999 CPU 928B Programming Guide C79000-B8576-C898-01 2 - 31 Function Blocks Parameter type Data type Actual operands permitted Table 2-6 continued: D KF for a fixed point number -32768 to +32767 KG for a floating point number1) (Cont.) B Constants Data type designation not possible DB n Data block; the operation C DB n is executed FB n Function block (permitted only without parameters) called unconditionally (JU . .n) OB n Organization block called unconditionally (JU . .n) PB n Program blocks - called unconditionally (JU . .n) SB n Sequence blocks - called unconditionally (JU . .n) T Data type designation not possible T 0 to 255 Timer C Data type designation not possible Z 0 to 255 Counter 1) 0.1469368 x 10 -38 to 0.1701412 x 1039 Note S flags are not permitted as actual operands for function blocks. After the jump to a function block, the actual operands from the block then called are used in the function block program instead of the formal operands. This feature of programmable function blocks allow them to be used for a wide variety of purposes in your user program. CPU 928B Programming Guide 2 - 32 C79000-B8576-C898-01 Function Blocks Examples Example 1: clarify the following (complete) example is intended to further the programming and calling of a function block and the assignment of parameters to it. You yourself can easily try out the example. 2 Programming the function block FB 202: FB 202 SEGMENT 1 NAME EXAMPLE DECL : INP1 DECL : INP2 DECL : OUT1 I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I I Q BI/BY/W/D: BI/BY/W/D: BI/BY/W/D: BI BI BI Formal operand list :A= INP1 :A= INP2 :== OUT1 STEP 5 : : BE ments Formal operands state- Parameter type Data type Function block FB 202 is called and has parameters assigned to it in program block PB 25: STL method of representation CSF/LAD method of representation PB 25 SEGMENT 1 NAME INP1 INP2 OUT1 : : : : : : JU FB 202 EXAMPLE I 13.5 F 17.7 Q 23.0 BE Formal operandes I 13.5 F 17.7 FB 202 EXAMPLE INP1 INP2 OUT1 Q 23.0 :BE Actual operands The following operations are executed after the jump to FB 202 : A : A : = I 13.5 F 17.7 Q 23.0 CPU 928B Programming Guide C79000-B8576-C898-01 2 - 33 Function Blocks Example 2: calling a function block and assigning parameters to it with the STL and CSF/LAD methods of representation in a program block. STL method of representation PB 25 SEGMENT 1 : : C DB 5 : : JU FB 201 NAME : REQUEST DATA : DW 1 RST : I 3.5 SET : F 2.5 MTIM : T 2 TIME : KT 010.1 TRAN : DW 2 BEC : Q 2.3 LOOP : Q 6.0 : BE Formal operands Actual operands CSF/LAD method of representation PB 25 SEGMENT 1 FB 201 DW 1 I 3.5 F 2.5 T 2 KT 010.1 REQUEST DATA RST SET MTIM TIME TRAN BEC LOOP DW 2 Q 2.3 Q 6.0 :BE CPU 928B Programming Guide 2 - 34 C79000-B8576-C898-01 Function Blocks 2.3.4 Special Function Blocks Apart from the function blocks that you program yourself, you can order standard function blocks as a finished software product. These contain standard functions for general use (e.g. signalling functions and sequence control). Standard function blocks are assigned numbers FB 1 to FB 199. If you order standard function blocks, remember the special instructions in the accompanying description (i.e. areas assigned and conventions etc.). The standard function blocks for the S5-135U are listed in catalog ST 57. Example Floating point root extractor RAD:GP FB 6 The function block RAD:GP extracts the root of a floating point number (8-bit exponent and 24-bit mantissa). It forms the square root. The result is also a floating point number (8-bit exponent and 24-bit mantissa). The least significant bit of the mantissa is not rounded up or down. If applicable, for the rest of the processing, the function block sets the "radicand negative" identifier. Numerical range: Radicand Root - 0.1469368 Exp. -38 to +0.1701412 Exp. +39 +0.3833434 Exp. -19 to +0.1304384 Exp. +20 Function: Y = A Y = SQRT; A = RADI Calling the function block FB 6: In the example, the root is extracted from a floating point number that is located in DD5 of DB 17 with an 8-bit exponent and a 24-bit mantissa. The result, another 32-bit floating point number, is written to DD 10. Prior to this, the appropriate data block must be opened. The parameter VZ (parameter type: Q, data type: BI) indicates the sign of the radicand: VZ = 1 for a negative radicand. Occupied flag words: FW 238 to FW 254. Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 2 - 35 2 Function Blocks "Floating point root extractor" continued: STL method of representation Segment 1 : C DB 17 : :*** : JU FB 6 Seg- NAME : RAD : GP ment RADI : DD 5 2 VZ : F 15.0 *) SQRT : DD 10 LAD method of representation SEGMENT 2 DD 5 FB 6 RAD RADI VZ SQRT F 15.0 DD 10 :BE DD= data double word *) Must be located in separate segments, since the operation "C DB 17" in segment 1 cannot be converted to LAD/CSF. Using FB 0 If you have not programmed organization block OB 1, the system program calls FB 0 (provided it is loaded) cyclically instead of OB 1. Since you have the total operation set of the STEP 5 programming language available in a function block, programming FB 0 instead of FB 1 can be an advantage, particularly when you wish to execute a short time-critical program. Note You should only use FB 0 for programming cyclic program execution (it must not contain parameters). If both OB 1 and FB 0 are loaded, the system program will only call organization block OB 1 cyclically. CPU 928B Programming Guide 2 - 36 C79000-B8576-C898-01 Data Blocks 2.4 Data Blocks Data blocks (DB) or extended data blocks (DX) are used to store the fixed or variable data with which the user program works. No STEP 5 operations are processed in data blocks. 2 The data of a data block includes the following: * various bit patterns (e.g. for status of a controlled process) * numbers (hexadecimal, binary, decimal) for timer values or arithmetic results * alphanumeric characters, e.g. for message texts. Structure of a data block A data block (DB/DX) consists of the following parts: * block preheader (DV, DXV), * block header * block body. Block preheader The block preheader is created automatically on the hard or floppy disk of the PG and not transferred to the CPU. It contains the data formats of the data words entered in the block body. You have no influence over the creation of the block preheader. Note When you transfer a data block from the PLC to diskette or hard disk, the corresponding block preheader can be deleted. For this reason, you must never modify a data block with different data formats in the PLC and then transfer it back to diskette, otherwise all the data words in the DB are automatically assigned the data format you selected in the presets screen form. CPU 928B Programming Guide C79000-B8576-C898-01 2 - 37 Data Blocks Block header The block header occupies five words in the memory and contains the following: * the block identifier * the programmer identifier * the block type and the block number * the library number * the block length (including the length of the block header). Block body The block body contains the data words with which the user program works. These data words are in ascending order in the block body, starting with data word DW 0. Each data word occupies one word (16 bits) in the memory. Maximum length A data block can occupy a total of maximum 32 767 words (including header) in the CPU memory. When you use your programmer to enter and transfer data blocks, remember the size of your CPU memory! CPU 928B Programming Guide 2 - 38 C79000-B8576-C898-01 Data Blocks 2.4.1 Creating Data Blocks To create a data block, perform the following steps: Step Action 1 Enter the block type (DB/DX) and data block number between 3 and 255. 2 Enter individual data words in the data format you require. (Do not complete your input of the data words with a BE statement!) Note Data blocks DB 0, DB 1, DX 0, DX 1 and DX 2 are reserved for specific functions and you cannot use them freely for other functions (see Section 2.4.3)! Table 2-7 Data formats permitted in a data block Type D ata format Exa mples KM Bit pattern 00100110 00111111 KH Hexadecimal 263F KY 2 Bytes 038,063 KF Fixed point number +09791 KG Floating point number +1356123+12 KS Character ?!ABCD123-+.,% KT Timer value 055.2 KC Counter value 234 CPU 928B Programming Guide C79000-B8576-C898-01 2 - 39 2 Data Blocks 2.4.2 Opening Data Blocks You can only open a data block (DB/DX) unconditionally . This is possible within an organization, program, sequence or function block. You can open a specific data block more than once in a program. To open a data block, perform the following steps: IF... Validity of a data block T HEN... You want to open a D B data block "C D B.." Type in the STEP 5 operation You want to open a D X data block "CX DX.." Type in the STEP 5 operation After you open a data block, all statements that follow with the operand area 'D' refer to the opened data block. The opened data block also remains valid when the program is continued in a different block following a block call. If a second data block is opened in this new block, the second data block is only valid in the newly called block from the point at which it is called. After program execution returns to the calling block, the old data block is once again valid. Access You can access the data stored in the opened data block during program execution using load or transfer operations (refer to Chapter 3 for more detailed information). With a binary operation , the addressed data word bit is used to form the RLO. The content of the data word is not changed. With a set/reset operation, the addressed data word bit is assigned the value of the RLO. The content of the data word may be changed. A load operation transfers the contents of the referenced data word into ACCU 1. The contents of a data word are not changed. A transfer operation transfers data from ACCU 1 to the referenced data word. The old contents of the data word are overwritten. CPU 928B Programming Guide 2 - 40 C79000-B8576-C898-01 Data Blocks Note Before accessing a data word, you must open the data block you require in your program. This is the only way that the CPU can find the correct data word. The referenced data word must be contained in the opened block, otherwise the system program detects a load or transfer error. With load and transfer operations, you can only access data word numbers up to 255! An opened data block remains valid until one of the following events occur: a) a second data block is opened or b) the block, in which the data block was opened, is completed with 'BE', 'BEC' or 'BEU'. Examples Example 1: transferring data words You want to transfer the contents of data word DW 1 from data block DB 10 to data word DW 1 of data block DB 20. Enter the following statements: :C :L : :C :T : : DB 10 DW 1 DB 20 DW 1 (open DB 10) (load the contents of DW 1 into ACCU 1) (open DB 20) (transfer the contents of ACCU 1 to DW 1) CPU 928B Programming Guide C79000-B8576-C898-01 2 - 41 2 Data Blocks Example 2: range of validity of data blocks (Fig. 2-5) Data block DB 10 is opened in program block PB 7 (C DB 10). During the subsequent program execution, the data of this data block are processed. After the call (JU PB 20) program block PB 20 is processed. Data block DB 10, however, remains valid. The data area only changes when data block DB 11 (C DB 11) is opened. Data block DB 11 now remains valid until the end of program block PB 20 (BE). After the jump back to program block PB 7, data block DB 10 is once again valid. PB C JU 7 PB 20 C DB 11 DB 10 PB 20 BE BE Range of validity of DB 10 Range of validity of DB 11 Fig. 2-5 Range of validity of an opened data block CPU 928B Programming Guide 2 - 42 C79000-B8576-C898-01 Data Blocks 2.4.3 Special Data Blocks DB 0 On the CPU 948 data blocks DB 0, DB 1, DX 0, DX 1 and DX 2 are reserved for special functions. They are managed by the system program and you cannot use them freely for other functions. * Data block DB 0 (see Section 8.3.2) 2 Data block DB 0 contains the address list with the start addresses of all blocks that are located in the data block RAM of the CPU. The system program generates this address list during initialization (following each POWER UP or OVERALL RESET) and it is updated automatically when you use a programmer to change data blocks or generate a new data block. DB 1 * Data block DB 1 (see Section 10.1.6) Data block DB 1 contains the list of digital inputs/outputs (P peripheral with relative byte addresses from 0 to 127) and the interprocessor communication (IPC) flag inputs and outputs that are assigned to the CPU. If applicable, the block may also contain a timer field length. DB 1 can have parameters assigned and be loaded as follows: to reduce the cycle time in single processor operation, since only the inputs, outputs or timers entered in DB1 are updated. D B 1 must be assigned parameters and loaded as follows: a) for multiprocessing b) when IPC flags exist with CPs DB 2 * Data block DB 2 (see Section 4.4.3) You use data block DB 2 to assign parameters to the closed loop controller structure R64. The closed loop control function can be ordered as a software product and operates supported by the system program. CPU 928B Programming Guide C79000-B8576-C898-01 2 - 43 Data Blocks DX 0 * Data block DX 0 (see Chapter 7) If you assign parameters to data block DX 0 and load it, you can change the defaults of certain system program functions (e.g. the start-up procedure) and adapt the performance of the system program to your particular application. DX 1 * Data block DX 1 Reserved. DX 2 * Data block DX 2 is used to specify the communication via the second serial interface. See the "CPU 928B Communication" Manual for details of assigning parameters to this block (/14/ in Chapter 13). CPU 928B Programming Guide 2 - 44 C79000-B8576-C898-01 Program Execution 3 Contents of Chapter 3 3.1 Principle of Program Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4 3.2 Program Organization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 5 3.3 Storing Program and Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 10 3.4 Processing the User Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 11 3.4.1 Definition of Terms used in Program Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 12 3.5 STEP 5 Operations with Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 15 3.5.1 Basic Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Binary logic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set/reset operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load and transfer operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Timer and counter operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Arithmetic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Comparison operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Block operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NOP/display/stop operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming Examples in the STL, LAD and CSF Methods of Representation . . . . . Supplementary Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Binary logic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital logic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set/reset operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Timer and counter operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load and transfer operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Arithmetic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.5.2 3.5.3 3 - 19 3 - 19 3 - 20 3 - 21 3 - 26 3 - 31 3 - 32 3 - 32 3 - 33 3 - 34 3 - 49 3 - 50 3 - 50 3 - 51 3 - 52 3 - 54 3 - 56 CPU 928B Programming Guide C79000-B8576-C898-01 3-1 3 Contents 3.5.4 3.5.5 Executive Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Jump operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shift operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conversion operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Decrement/increment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Processing operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Disabling/enabling process interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Semaphore Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 58 3 - 58 3 - 60 3 - 62 3 - 65 3 - 65 3 - 71 3 - 75 CPU 928B Programming Guide 3-2 C79000-B8576-C898-01 Program Execution 3 This chapter is intended for readers who do not yet have any great experience in using the programming language. The chapter therefore deals with the basics of STEP 5 programming and explains in detail (with examples) the STEP 5 operations for the CPU 928B. Experienced readers who require more information about a specific STEP 5 operation listed in the Pocket Guide can refer to the reference section in 3.5. CPU 928B Programming Guide C79000-B8576-C898-01 3-3 3 Principle of Program Execution 3.1 Principle of Program Execution You can process your STEP 5 user program in various ways. Cyclic program execution is most common with programmable controllers (PLCs). The system program runs through a program loop (the cycle, refer to Section 3.4) and calls organization block OB 1 cyclically in each loop (refer to Fig. 3-1). System program Us e r p r o g r a m from start-up OB 1 Tr i g g e r c y c l e t i m e Up d a t e in t e r processor comm. f la g in p u t s Up d a t e p r o c e s s im a g e in p u t s ( PI I ) PB 20 Ca l l P B 2 0 Call OB1 BE Up d a t e p r o c e s s im a g e o u t p u t s ( PI Q ) Up d a t e in t e r processor comm. f la g o u t p u t s Fig. 3-1 BE Principle of cyclic program execution CPU 928B Programming Guide 3-4 C79000-B8576-C898-01 Program Organization 3.2 Program Organization Program organization allows you to specify which conditions affect the processing of your blocks and the order in which they are processed. Organize your program by programming organization blocks with conditional or unconditional calls for the blocks you require. You can call additional program, function and sequence blocks in any combination in the program of individual organization, program, function and sequence blocks. You can call these one after another or nested in one another. For maximum efficiency, you should organize your program to emphasise the most important program structures and in such a way that you can clearly recognize parts of the controlled system which are related in the software. Figs. 3-2 and 3-3 are examples of a program structure. CPU 928B Programming Guide C79000-B8576-C898-01 3-5 3 Program Organization OB 1 PB 'A' Op e r a t in g mo d e program FB Stop to the system EMERGENCY OFF JU PB 'A' FB Go to in itia l state PB `B` Se q u e n c e control FB Co n t r o l o f sequence cascade SB Se q u e n c e step JU PB `B` SB Se q u e n c e step PB `C` I n d iv id u a l c o n t r o l le v e l FB Gr o u p in itia liza tio n FX DB I n t e r f a c e fla g s o f t h e in d iv id u a l control e le m e n t s I n d iv id u a l in itia liza tio n JU PB `C` FX I n d iv id u a l in itia liza tio n PB `D` Message output JU PB `D` FB Message output v ia st a n d a r d p e r ip h e r a ls FB Message output v ia st a n d a r d p e r ip h e r a ls DX Message texts BE Fig. 3-2 Example of the organization of the user program according to the program structure CPU 928B Programming Guide 3-6 C79000-B8576-C898-01 Program Organization OB 1 PB `X` Controlled system part `X` FB Individual control FB JU PB `X` Closed loop control 3 FX Signalling PB `Y` Controlled system part `Y` JU PB `Y` FB Sequence control FX Signalling FB `Z` Controlled system part `Z` JU PB `Z` FB Closed loop control FB Arithmetic FB Data logging output BE Fig. 3-3 Example of the organization of the user program according to the structure of the controlled system CPU 928B Programming Guide C79000-B8576-C898-01 3-7 Program Organization Nesting blocks OB 1 Fig. 3-4 shows the principle of nested block calls. PB 5 1st STEP 5 Op. C DB 20 JU = PB 20 Q 60.6 *) PB 20 1st STEP 5 Op. C JU PB 5 A F 200.5 *) BE *) BE DB 30 JU FB 30 NAME: KURV A I 55.0 *) BE Operation to which the program returns Fig. 3-4 Nested logic block calls Block addresses A block start address specifies the location of a block in the user memory (oder DB-RAM). For logic blocks, this is the address of the memory location containing the first STEP 5 operation (with FB and FX, the JU operation via the formal operand list); with data blocks, it is the address of the first data word. To enable the CPU to locate the called block in the memory, the start addresses of all valid blocks are entered in the block address list in data block DB 0. DB 0 is managed by the system program, you cannot call it yourself. The CPU stores a return address every time a new block is called. After the new block has been processed, this return address enables the program to find the block from which the call originated. The return address is the address of the memory location containing the next STEP 5 statement after the block call. The CPU also stores the start address and len gth of the d ata block valid at this location. CPU 928B Programming Guide 3-8 C79000-B8576-C898-01 Program Organization Nesting depth You can only nest 62 blocks within one another. If more than 62 blocks are called, the CPU signals an error and goes to the stop mode. Example of nesting depth Program processing level 3 OB 25 OB 2 OB 13 OB 1 PB 1 PB 131 FB 21 FB 131 FB 1 Nesting depth 1 Fig. 3-5 2 3 4 5 6 7 8 9 Example of block nesting depth You can determine the nesting depth of your program as follows: - Add all the organization blocks you have programmed (in the example: 4 OBs). - Add the nesting depth of the individual organization blocks (in the example: 2 + 2 + 1 + 0 = 5). - Add the two amounts together to obtain the program nesting depth (in the example: 4 + 5 = nesting depth 9). It may not exceed a value of 62. CPU 928B Programming Guide C79000-B8576-C898-01 3-9 Storing Program and Data Blocks 3.3 Storing Program and Data Blocks You must load your program into the user memory so that the CPU can process it. As program memory you can use a plug-in submodule (optional either RAM or EPROM) and the DB-RAM. Different storage types 1) * If you use a plug-in R A M submodule you can transfer your program directly from the programmer to the CPU. You can change the contents of a RAM submodule quickly and easily. A central back-up battery prevents your program being deleted in the memory if the power goes off. All programmed blocks are stored in random order in the RAM (see Section 2.1.5, Fig. 2-2). If you change a block, the sequence of the blocks in the RAM also changes. If you use a RAM submodule with a back-up battery , you can remove it from the CPU without losing data. Havin g its own b attery protects the submodule from loss of data and ensures that the d ata is retained until it is required again. * You can also store your complete program in plug-in EPR O M sub modules. Your program is completely protected in EPROM submodules even when the power goes off and no back-up battery is necessary. You cannot change the contents of an EPROM submodule from the PC. For this reason, data blocks that contain variable data that have to be changed during the course of your program must be copied from the EPROM submodule to the data block RAM of the CPU during the first cold restart following an overall reset. You must program this function (see special function OB 254 and OB 255, Section 6.4.6). * Data blocks DB/DX are written into the DB-RAM by generating or copying them. If you transfer data blocks from the PG to the CPU, they are written to the DB-RAM if the RAM submodule is full or if an EPROM submodule is plugged in. C aution Battery-backed RAM submodules must not be programmed via the EPROM interface; this can damage the RAM. 1) When storing data blocks, please note the possibility of "alternative loading" - Section 2.1.5. CPU 928B Programming Guide 3 - 10 C79000-B8576-C898-01 Processing the User Program 3.4 Processing the User Program The complete software on the CPU (consisting of the system program and the STEP 5 user program) has the following tasks: * CPU START-UP * Controlling an automation process by continuously repeating operations (CYCLE). 3 * Controlling an automation process by reacting to events occurring sporadically or at certain times (interrupts) and reacting to errors. For all three tasks, you can select special parts of your program to run on the CPU by programming user interfaces (organization blocks OB 1 to OB 35 - refer to Section 2.2.1). START-UP Before the CPU can start cyclic program execution, an initialization must be performed to establish a defined initial status for cyclic program execution and, for example, to specify a time base for the execution of certain functions. The way in which this initialization is performed depends on the event that led to a START-UP and on settings that you can make on your CPU. For more detailed information, refer to Chapter 4. You can influence the START-UP procedure of your CPU by programming organization blocks OB 20, OB 21 and OB 22 or by assigning parameters in DX 0 (refer to Chapter 7). CYCLE Following the START-UP, the system program goes over to cyclic processing. It is responsible for background functions required for the automation tasks (refer to Fig. 3-1 at the beginning of this section). After the system functions have been executed at the beginning of a CYCLE, the system program calls organization block OB 1 or function block FB 0 as the cyclic user program. You program the STEP 5 operations for cyclic processing in this block. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 11 Processing the User Program Reactions to interrupts and errors To allow you to specify the reactions to interrupts or errors, special organization blocks (OB 2, OB6 and OB9 to OB 18 for interrupt servicing, OB 19 and OB 23 to OB 35 for reactions to errors) are available on the CPU 928B. You can store an appropriate STEP 5 program in these blocks. When interrupts or errors are to be processed, the system program activates the corresponding organization block during cyclic processing. This means that the cyclic processing is interrupted to service an interrupt or to react to an error. The nesting of the organization blocks has a fixed priority (for further information, refer to Chapters 4 and 5). In addition to the organization blocks, you can also influence the reaction of the CPU to interrupt servicing by assigning parameters in data block DX 0. Organization blocks OB 1 to OB 39 can be called by the system program as soon as they are loaded in the program memory (also during operation). If the OBs are not loaded, there is either no reaction from the CPU or (in the event of errors) it goes to the stop mode (refer also to Section 5.4). You can also load data block DX 0 into the program memory during operation like the organization blocks. It is, however, only effective after the next COLD RESTART. If DX 0 is not loaded, the standard settings apply (refer to Chapter 7). 3.4.1 Definition of Terms used in Program Execution Cycle time The cycle begins when the cycle monitoring time is triggered and ends with the next trigger. The time that the CPU requires to execute the program between two triggers is called the cycle time. The cycle time consists of the runtime of the system program and the runtime of the user program. The cycle time therefore includes the following: * the time required to process the cyclic program (system and user program), * the time required to process interrupts (e.g. time-controlled interrupt), * the time required to process interruptions (errors). CPU 928B Programming Guide 3 - 12 C79000-B8576-C898-01 Processing the User Program Cycle time monitoring The CPU monitors the cycle time in case it exceeds a maximum value. The standard setting for this maximum value is 150 ms. You can set the cycle time monitoring yourself or restart it during user program execution (refer to DX 0/Chapter 7 and special function OB OB 221 and OB 222/Sections 6.22 and 6.23). Process input and output image (PII and PIQ) The process image of the inputs and outputs is a memory area in the internal RAM. Before cyclic execution of the user program begins, the system program reads the signal states of the input peripheral modules and transfers them to the process input image. The user program evaluates the signal states in the process input image and then sets the appropriate signal states for the outputs in the process output image. After the user program has been processed, the system program transfers the signal states of the process output image to the output peripheral modules. Buffering the I/O signals in the process image of the inputs and outputs avoids a change in a bit within a program cycle from causing the corresponding output to "flutter". The process image is therefore a memory area whose contents are output to the peripherals and read in from the peripherals once per cycle. Note The process image only exists for input and output bytes of the "P" peripherals with byte addresses from 0 to 127! Interprocessor communication IPC flags exchange data between individual CPUs (multiprocessing) or between the CPU and some communication processors. (IPC) flags The system program reads the input IPC flags of the CPU before cyclic execution of the user program begins. After the STEP 5 program is processed, the system program transfers the output IPC flags to the coordinator or to the communications processors. You define the input and output IPC flags when you create data block DB 1 (refer to Section 10.1.5). CPU 928B Programming Guide C79000-B8576-C898-01 3 - 13 3 Processing the User Program Interrupt events Cyclic program execution can be interrupted by the following: * process interrupt-driven program processing, * time-controlled program processing, * delay interrupt, * time interrupt clock-controlled. The cyclic program can be interrupted or even aborted completely by the following: * a device hardware fault or program error, * operator intervention (using the PC stop function, or setting the mode selector to "stop", multiprocessor stop MP-STP), * a stop operation. CPU 928B Programming Guide 3 - 14 C79000-B8576-C898-01 STEP 5 Operations with Examples 3.5 STEP 5 Operations with Examples A STEP 5 operation consists of the operation and an operand. The operation specifies wh at the CPU is to do (operation). The operand specifies with what an operation is to be executed. STEP 5 operations can be divided into the following groups: * basic operations (can be used in all logic blocks), 3 * supplementary operations, * executive operations (can only be used in FB/FX function blocks), * semaphore operations (can only be used in FB/FX function blocks). Accumulators as working registers The CPU 928B has four accumulators, ACCU 1 to ACCU 4. Most STEP 5 operations use two 32-bit registers (ACCU 1 and ACCU 2) as the source of operands and the destination for results. High word ACCU 1 24 23 31 High byte Low byte High byte 1) Low word 16 15 ACCU-1-HL ACCU-1-HH ACCU-1-H Low byte 8 7 0 ACCU-1-LH ACCU-1-LL ACCU-1-L The STEP 5 operation to be carried out affects the accumulators, e.g.: * ACCU 1 is always the destination in load operations. A load operation shifts the old contents of ACCU 1 to ACCU 2 (stack lift). Accumulators 3 and 4 are not changed by any load operations. 1) analogous for ACCU 2 to ACCU 4 CPU 928B Programming Guide C79000-B8576-C898-01 3 - 15 STEP 5 Operations with Examples * Arithmetic operations combine the contents of ACCU 1 with those of ACCU 2, write the result to ACCU 1 and transfer the contents of ACCU 3 to ACCU 2 and the contents of ACCU 4 to ACCU 3 (stack drop). In 16-bit fixed point arithmetic, only the low word or ACCU 3 is transferred to the low word of ACCU 2 and the low word of ACCU 4 to the low word of ACCU 3. * When a constant is added (ADD BF/KF/DH) to the contents of ACCU 1, the accumulators 2, 3 and 4 are not changed. Condition codes STEP 5 operations either set or evaluate condition codes. The condition codes are written to a condition code byte. Two groups of condition codes can be distinguished: condition codes of digital operations (word condition codes - bits 4 to 7 in the condition code byte) and condition codes from binary and executive operations (bit condition codes - bits 0 to 3 in the condition code byte). You can see how the various condition codes are influenced or evaluated by STEP 5 operations be referring to the operation list (see /1/ in Chapter 13). You can display the condition code byte on a programmer using the "STATUS" online function (refer to Section 11.2.3). The byte has the following structure: W ord condition codes CC 1 Bit condition codes Bit condition codes CC 0 OV OS Bit 7 6 5 4 * ER A B First bit scan OR 3 STA RLO ERAB 2 1 0 A logic operation sequence containing binary operations always begins with the first bit scan, following which a new RLO is formed. The bit condition code ERAB = 1 is then set. While the remaining logic operations in the sequence are being performed, ERAB remains set to 1 and the RLO cannot be changed by these logic operations. The active sequence of logic operations is terminated by a binary set/reset operation (e.g. S Q 5.0). The set/reset operation sets ERAB to 0; the RLO can be evaluated (e.g. by RLO-dependent operations) but can no longer be combined logically. The next binary logic operation following a binary set/reset operation is once again a first bit scan. CPU 928B Programming Guide 3 - 16 C79000-B8576-C898-01 STEP 5 Operations with Examples Example of ERAB Other bit condition codes :S Q 7.7 :A : : :O : :AN : :S : :JC : : : I 1.0 I 6.3 I 2.1 Q 2.4 FB 150 Last operation of the previous logic operation sequence ERAB is set to '1', the new RLO is formed by an AND operation The RLO is influenced by an OR operation The RLO is influenced by an AND NOT operation. ERAB is set to '0', the sequence is now complete The function block is called dependent on the RLO. * R LO Result of logic operation This is the result of bit logic operations. It is the truth statement for comparison operations (refer to operations list, binary logic operations or comparison operations). * STA Status For bit operations, this indicates the logical status of the bit just scanned or set. The status is updated in binary logic operations except for A(, O(,), O and for set/reset operations. * O R Or Internal CPU bit for handling "AND before OR" logic operations. Word condition codes * OV Overflow This indicates whether the permissible number range was exceeded during the arithmetic operation just completed. * OS Stored overflow It can be used in several arithmetic operations to indicate whether an overflow occurred at any point during the operations. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 17 3 STEP 5 Operations with Examples * CC 1 and CC 0 These are the result condition codes that you can interpret from the following table: Note To evaluate the condition codes directly, comparison and jump operations are available (refer to Sections 3.5.1 and 3.5.3). Table 3-1 Result condition codes of STEP 5 operations W ord condition codes CC 1 CC 0 0 0 0 1 Arithmetical operations Digital logic operations Comparison operations Shift operations For SED, SEE Jump operations executed Result =0 Result =0 ACCU 2 = ACCU 1 Shifted bit =0 Semaphore is set JZ Result <0 - ACCU 2 < ACCU 1 - - 1 0 Result >0 Result 0 ACCU 2 > ACCU 1 Shifted bit =1 Semaphore is set or enabled 1 1 Division by 0 - - - - JM JN JP JN JN Note When a change of level takes place, e.g. servicing a timed interrupt, all accumulators and the bit and word condition codes (RLO etc.) are saved and loaded again when the interrupted level is resumed. CPU 928B Programming Guide 3 - 18 C79000-B8576-C898-01 Basic Operations 3.5.1 Basic Operations You can use the basic operations in all logic blocks and all methods of representation (STL, LAD, CSF). Binary logic operations Table 3-2 3 Binary logic operations Operation Operand Function A AND logic operation after scanning for signal state "1" O OR logic operation after scanning for signal state "1" I Q F S D T C 0.0 to 127.7 0.0 to 127.7 0.0 to 255.7 0.0 to 4095.7 0.0 to 255.15 0 to 255 0 to 255 of an input in the PII of an output in the PIQ of a flag bit of an S flag bit of a data word bit of a timer of a counter AN AND logic operation after scanning for signal state "0" ON OR logic operation after scanning for signal state "0" I Q F S D T C 0.0 to 127.7 0.0 to 127.7 0.0 to 255.7 0.0 to 4095.7 0.0 to 255.15 0 to 255 0 to 255 of an input in the PII of an output in the PIQ of a flag bit of an S flag bit of a data word bit of a timer of a counter O - Combine AND operations through logic OR U( O( ) - ANDing of expressions in parentheses ORing of expressions in parentheses Close parenthesis (to complete the bracketed expression) Maximum of 8 levels are permitted, i.e. 7 opened brackets RLO formation The binary logic operations generate the result of logic operation (RLO). At the beginning of a logic sequence, the RLO only depends on the signal state scanned (first scan) and not on the type of logic operation (O = OR, A = AND). CPU 928B Programming Guide C79000-B8576-C898-01 3 - 19 Basic Operations Within a sequence of logic operations, the RLO is formed from the type of operation, previous RLO and the scanned signal state. A sequence of logic operations is completed by an operation (e.g. set/reset operations) which retains the RLO (ERAB = 0). Following this, the RLO can be evaluated but cannot be further combined. Example Program = A A A = : Q I I I Q 0.0 1.0 1.1 1.2 0.1 Status 0 1 1 0 0 R LO 0 1 1 0 0 ER A B 0 1 1 1 0 RLO retained first bit scan RLO retained, end of the logic operations sequence Set/reset operations Table 3-3 Operation Set/reset operations Operand Function Set if RLO = 1 Reset if RLO = 1 S R I Q F S D 0.0 to 127.7 0.0 to 127.7 0.0 to 255.7 0.0 to 1023.7 0.0 to 255.15 an input in the PII an output in the PIQ a flag an S flag a bit in the data word The RLO is assigned to = I Q F S D 0.0 to 127.7 0.0 to 127.7 0.0 to 255.7 0.0 to 1023.7 0.0 to 255.15 an input in the PII an output in the PIQ a flag an S flag a bit in the data word CPU 928B Programming Guide 3 - 20 C79000-B8576-C898-01 Basic Operations Load and transfer operations Table 3-4 Operation Load and transfer operations/part 1 Operand Function Load Transfer L T IB IW ID 0 to 127 0 to 126 0 to 124 an input byte from/to the PII an input word from/to the PII an input double word from/to the PII QB QW QD 0 to 127 0 to 126 0 to 124 an output byte from/to the PIQ an output word from/to the PIQ an output double word from/to the PIQ FB FW FD 0 to 255 0 to 254 0 to 252 a flag byte a flag word a flag double word SY SW SD 0 to 1023 0 to 1022 0 to 1020 an S flag byte an S flag word an S flag double word DR 0 to 255 the right byte of a data word from/to DB,DX DL 0 to 255 the left byte of a data word from/to DB,DX DW DD 0 to 255 0 to 254 a data word from/to DB, DX a data double word from/to DB, DX PY 0 to 127 a peripheral byte of the digital inputs/outputs (P area) PY 128 to 255 a peripheral byte of the analog or digital inputs/outputs (P area) PW 0 to 126 a peripheral word of the digital inputs/outputs (P area) PW 128 to 254 a peripheral word of the analog or digital inputs/outputs (P area) OY 0 to 255 a byte of the extended I/O area (O area) OW 0 to 254 a word of the extended I/O area (O area) 3 CPU 928B Programming Guide C79000-B8576-C898-01 3 - 21 Basic Operations Table 3-5 Load and transfer operations/part 2 Operation Operand Function Load L KB KS 0 to 255 2 ASCII characters a constant, 1 byte a constant, 2 ASCII characters KF -32768 to +32767 a constant as fixed point number KG KH DH KM KY 1) 0 to FFFF 0 to FFFF FFFF 16-bit pattern 0 to 255 for each byte a constant as floating point number a constant as hexadecimal number a double word constant as a hexadecimal number a constant as bit pattern a constant, 2 bytes KT KC 0.0 to 999.3 0 to 999 a constant timer value (in BCD) a constant counter value T C 0 to 255 0 to 255 a timer, binary coded a counter, binary coded LC Load T C 0 to 255 0 to 255 a timer a counter in BCD 1) -38 0,1469368 x 10 to 0,1701412 x 1039 Load operations Load operations write the addressed value into ACCU 1. The former contents of ACCU 1 are saved in ACCU 2 (stack lift). Transfer operations Transfer operations write the contents of ACCU 1 to the addressed memory location. CPU 928B Programming Guide 3 - 22 C79000-B8576-C898-01 Basic Operations Examples of load and transfer operations Example 1: Fig. 3-6 illustrates loading/transferring a byte, word or double word from/to a memory area organized in bytes (PII, PIQ, flags, I/O). :L IB i :L IW j :L FD k load byte i of the PII into ACCU-1-LL load bytes j and j+1 of the PII into ACCU-1-L load flag bytes k to k+3 in ACCU 1 7 0 31 23 0 1) 15 0 1) 3 7 0 1) 0 i ACCU 1 L IB i T IB i i Addresses in ascending order 31 23 0 1) 15 0 1) 7 j 0 ACCU 1 j+1 L IW j T IW j j j + 1 31 23 k 15 k+1 k k + 1 k + 2 k + 3 0 k+3 ACCU 1 L FD k T FD k 1) Fig. 3-6 7 k+2 only with load operations Load and transfer operations in a byte-oriented memory area CPU 928B Programming Guide C79000-B8576-C898-01 3 - 23 Basic Operations Example 2: Fig. 3-7 illustrates the loading/transfer of a byte, word or double word from/into a memory area organized in words. :L :L :L :L DR DL DW DD i j k l load load load load the right byte of data word i into ACCU-1-LL the left byte of data word j into ACCU-1-LL data word k into ACCU-1-L data words l and l+1 into ACCU 1 15 0 31 23 0 1) 15 0 1) 7 0 1) 0 i ACCU 1 L DR i T DR i right byte Addresses in ascending order D a t a w o r d i 31 23 0 1) 15 0 1) 7 0 1) 0 j ACCU 1 L DL j T DL j left byte D a t a w o r d j 31 15 0 1) 0 ACCU 1 k L DW k T DW k k 31 0 15 l l+1 ACCU 1 L DD l T DD l l l + 1 1 ) only Fig. 3-7 with load operations Load and transfer operations in a word-oriented memory area Note Load operations do not affect the condition codes . Transfer operations clear the OS bit. When a byte or word is loaded the extra bits are cleared in ACCU 1. CPU 928B Programming Guide 3 - 24 C79000-B8576-C898-01 Basic Operations Addressing I/Os You can use load and transfer operations to address the I/O peripherals as follows: * directly using the following operations: L../T.. ..PY, ..PW, ..OY, ..OW or * usin g the process image with the following operations: 3 L../T.. ..IB, ..IW, ..ID, .QB, ..QW, ..QD and with logic and set/reset operations Note If you use the transfer operations T PY 0 to 127 and T PW 0 to 126, the process output image is updated at the same time. Exception: command output is disabled by the STEP 5 operation BAS (refer to Section 3.5.4). Note the following points about I/O peripherals: * A process input/output image exists for 128 input and 128 output bytes of the P peripherals with byte addresses from 0 to 127. * No process image exists for the entire area of the O peripherals and the P peripherals with relative byte addresses from 128 to 256. (For more information on address space allocation see Section 8.2.2). * I/O modules with addresses of the O peripherals can only be plugged into expansion units (not in the central controller). * In one expansion unit, you can use either only P peripherals or only O peripherals. Caution If you use relative addresses of the O peripherals in an expansion unit, you can no longer use these addresses for I/O modules in the central controller (this would result in double addressing). CPU 928B Programming Guide C79000-B8576-C898-01 3 - 25 Basic Operations Timer and counter operations To load a timer using a start operation or a counter using a set operation, you must first load the value in ACCU 1. The following load operations are preferable: For timers: L KT, L IW, L QW, L FW, L DW, L SW. For counters: L KC, L IW, L QW, L FW, L DW, L SW. Starting a timer with the selected timer value requires an RLO signal change. A counter is set or started with the selected counter value when a positive-going RLO signal edge is detected. The following table indicates the signal edge change with corresponding arrows. Table 3-6 Timer and counter operations Operation Operand SP SE SD SS SF R T T T T T T 0 0 0 0 0 0 S R CU CD C C C C 0 to 255 0 to 255 0 to 255 0 to 255 1) to to to to to to 255 255 255 255 255 255 positive-going edge ( ): negative-going edge ( ): RLO Function 1) 1 Start a timer as a pulse Start a timer as extended pulse Start a timer as ON delay Start a timer as stored ON delay Start a timer as OFF delay Reset a timer 1 Set a counter (BCD number from 0 to 999) Reset a counter Count up Count down signal change from '0' to '1' signal change from '1' to '0' When executing the timer or counter operations SP T, SE T, SD T, SS T, SF T and S C the value in ACCU 1 is transferred to the timer or counter (as with the transfer operation) and the appropriate operation is started. CPU 928B Programming Guide 3 - 26 C79000-B8576-C898-01 Basic Operations Timer value With the operation L KT, you can load a timer value directly into ACCU 1 or indirectly from a flag or data word. The value must have the following structure (with L KT, you specify the time base after the period in the operand as shown below): Bit no. 15 14 13 12 11 10 9 8 6 7 5 2 3 4 10 1 10 2 1 0 10 0 3 Timer value 0 ... 999 in BCD 0: 1: 2: 3: Time base specified in BCD: These bits are irrelevant (i.e. they are ignored when the timer is started) 0.01 sec 0.1 sec 1 sec 10 sec Example You want to set a time of 127 sec.: Bit assignment: x x 1 0 0 2 0 0 1 1 0 0 1 0 0 2 1 1 1 7 Timer value 127 Time base 1 sec Irrelevant Note The start of each timer is liable to an inaccuracy of 1 time base! When using timers, you should therefore select the smallest possible time base (time base < timer value): Example: time value 4s not: but: 1sx4 inaccuracy: 1 s 0.01 s x 400 inaccuracy: 0.01 s CPU 928B Programming Guide C79000-B8576-C898-01 3 - 27 Basic Operations Counter value With the operation L KC, you can load a counter value directly in ACCU 1 or indirectly from a flag or a data word. The value must have the following structure: Bit no. 15 14 13 12 11 10 9 8 10 2 7 6 5 3 4 10 1 2 1 0 10 0 Counter value 0 ... 999 specified in BCD These bits are irrelevant, (i.e. they are ignored when the counter is set) Example You want to specify a counter value of 127: Bit assignment: x x x x 0 0 0 1 1 0 0 1 0 0 1 1 1 2 7 Counter value 127 Irrelevant In the timer or counter itself, the value is in binary code. If you want to scan the timer or counter, you can load the actual timer or counter value into ACCU 1 directly or in BC D code. CPU 928B Programming Guide 3 - 28 C79000-B8576-C898-01 Basic Operations Further examples of timer and counter values Loading timer values directly: Ti m e r v a l u e 9 0 Ti m e r T 1 0 0 ACCU 1 3 '0' "L T 10": 9 Loads the binary timer value of timer T 10 directly into ACCU 1 The time base is not loaded. Loading counter values directly: Counter value '0' "L C 10": 9 0 Counter C 10 9 0 ACCU 1 Loads the binary counter value of counter C 10 directly into ACCU 1 CPU 928B Programming Guide C79000-B8576-C898-01 3 - 29 Basic Operations Loading timer values in BCD code: Time base Timer 13 12 value 9 0 Binary '0' 13 12 T 10 BCD 11 8 7 10 2 Time Timer 4 10 1 base Timer 0 3 ACCU 1 10 0 value "LC T 10":Loads the timer value and time base of timer T 10 into ACCU 1 in BCD The time base is also loaded. Loading counter values in BCD code: Counter value 9 0 Binary '0' BCD 8 11 10 2 7 4 3 10 1 Counter value in "LC Counter C 10 0 ACCU 1 10 0 BCD C 10": Loads the counter value of counter C 10 into ACCU 1 in BCD If you load values in BCD, status bits 14 and 15 of the timer or 12 to 15 of the counter are not loaded. They have the value 0 in ACCU 1. The value in the ACCU can now be processed further. CPU 928B Programming Guide 3 - 30 C79000-B8576-C898-01 Basic Operations Arithmetic operations Table 3-7 Operation + x : F F F F + x : G G G G Arithmetic operations Operand Function - Add two fixed point numbers (16 bits) Subtract one fixed point number from another (16 bits) Multiply two fixed point numbers (16 bits) Divide one fixed point number by another (16 bits): quotient in ACCU-1-L, remainder in ACCU-1-H 3 Add two floating point numbers (32 bits) Subtract one floating point number from another (32 bits) Multiply two floating point numbers (32 bits) Divide one floating point number by another (32 bits) Arithmetic operations logically combine the contents of ACCU 1 and ACCU 2 (e.g. ACCU 2 - ACCU 1). The result is then contained in ACCU 1. An arithmetic operation changes the arithmetic registers as follows (in fixed point operations only the low word): ACCU 1 ACCU 2 ACCU 3 ACCU 4 before: after: Note Within the supplementary operations, there are operations for subtraction and addition of double word fixed point numbers . In addition, you can use the EN T operation from the set of supplementary operations for loading ACCU 3 and ACCU 4 (see Section 3.5.3). CPU 928B Programming Guide C79000-B8576-C898-01 3 - 31 Basic Operations Comparison operations Table 3-8 Operation != >< > >= < <= Comparison operations Operand Function - F D G Compare for equal to Compare for not equal to Compare for greater than Compare for greater than or equal to Compare for less than Compare for less than or equal to ...F: ...D: ...G: compare two fixed point numbers (16 bits) compare two fixed point numbers (32 bits) compare two floating point numbers (32 bits) Block operations Table 3-9 Operation Block operations Operand Function Jump unconditionally Jump conditionally (only when RLO = 1) JU JC OB 1 to 39 1) OB 110 to 255 PB 0 to 255 FB 0 to 255 SB 0 to 255 DOU DOC to an organization block to a system program special function to a program block to an FB function block to a sequence block Jump unconditionally Jump conditionally (only when RLO = 1) FX 0 to 255 - BE BEC BEU to an FX function block Block end Block end, conditional (only when RLO = 1) Block end, unconditional C CX DB DX 3 to 255 3 to 255 Call a DB data block Call a DX data block G GX DB DX 3 to 255 3 to 255 Generate data block DB Generate data block DX (ACCU 1 must contain the number of data words - maximum 4091 - that the new block is to have ) 1) only for test purposes! CPU 928B Programming Guide 3 - 32 C79000-B8576-C898-01 Basic Operations G DB/GX DX Generating a data block The operation G DBx generates a DB data block with the number x (3 x 255) in the user memory of the CPU. The content of the data block is not assigned the value 0, i.e. the data words can have any contents. Before programming this statement, you must store the number of data words that the new DB is to have in ACCU-1-L. The operation "G DB" or "GX DX" creates the block header. A data block generated in this way (without block header) can occupy a maximum of 4091 words. You can generate longer data blocks using OB 125. If the data block already exists, the length of the DB is not permitted or there is not enough space in the DB-RAM, the system program calls OB 31. If this is not loaded, the CPU goes to the stop mode. The GX DXx operation generates a DX data block in the DB-RAM and is otherwise the same as G DBx. NOP/display/stop operations Table 3-10 Operation NOP/display/stop operations Operand NOP0 NOP1 BLD Function - 0 to 255 STP No operation No operation Display generation operation for the PG: the CPU handles the operation like a no operation - CPU changes to soft STOP. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 33 3 Programming Examples in the STL, LAD and CSF Methods of Representation 3.5.2 Programming Examples in the STL, LAD and CSF Methods of Representation Logic operations AND operation STEP 5 representation Logical/circuit diagram I 1.1 1.3 1.7 Statement list Ladder diagram I 1.1 I 1.1 I 1.3 & I 1.3 I 1.7 Control system flowchart Q 3.5 I 1.1 A I 1.1 I 1.3 A I 1.3 I 1.7 A I 1.7 = Q3.5 & Q 3.5 I 1.7 Q 3.5 Q 3.5 Output Q 3.5 is "1" when all inputs are "1" simultaneously Output Q 3.5 is "0" if any of the inputs has signal state "0" The number of scans and the sequence of the logic statements are optional CPU 928B Programming Guide 3 - 34 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Logic operations (continued) OR operation STEP 5 representation Logical/circuit diagram Statement list Ladder diagram I 1.2 I 1.2 1.7 1.5 I 1.2 I 1.7 I 1.5 O I 1.2 O I 1.7 O I 1.5 = Q3.2 Control system flowchart Q 3.2 I 1.2 I 1.7 3 1 Q 3.2 I 1.5 I 1.7 1 Q 3.2 I 1.5 Q 3.2 Output Q 3.2 is "1" when at least one of the inputs is "1" Output Q 3.2 is "0" when all inputs have the signal state state "0" simultaneously The number of scans and sequence of programming is optional AND-before-OR operation STEP 5 representation Logical/circuit diagram I 1.5 I 1.6 Statement list I 1.5 I 1.4 I 1.3 I 1.5 & Ladder diagram I 1.5 I 1.1 I 1.4 A I 1.6 I 1.7 I 1.3 O I 1.4 1 Q 3.1 A & I 1.6 I 1.6 Control system flowchart Q 3.1 I 1.4 A I 1.3 = Q3.1 1 I 1.3 I 1.1 A & I 1.7 & Q 3.1 Q 3.1 Q 3.1 is "1" when at least one AND condition is satisfied Q 3.1 is "0" when no AND condition is satisfied CPU 928B Programming Guide C79000-B8576-C898-01 3 - 35 Programming Examples in the STL, LAD and CSF Methods of Representation Logic operations (continued) /1st example OR-before-AND operation STEP 5 representation Logical/circuit diagram Statement list I 6.0 I 6.2 I 6.3 I 6.0 Q 2.1 I 6.0 O I 6.1 A 1 Control system flowchart I 6.0 A I 6.0 I 6.1 I 6.2 I 6.3 Ladder diagram I 6.2 I 6.1 1 I 6.1 A( & I 6.1 & O I 6.3 I 6.2 I 6.3 O 1 1 I 6.2 I 6.3 Q 2.1 ) Q 2.1 = Q2.1 Q 2.1 Output Q 2.1 is "1" when input I 6.0 or input I 6.1 and one of the inputs I 6.2 or I 6.3 has signal state "1" Output Q 2.1 is "0" when input I 6.0 has signal state "0" and the AND condition is not satisfied /2nd example OR-before-AND operation STEP 5 representation Logical/circuit diagram Statement list Ladder diagram Control system flowchart A( I 1.4 I 1.5 I 1.4 I 2.0 I 2.1 I 1.4 1 I 1.5 I 2..0 I 1.4 I 1.4 O I 1.5 I 1.5 I 1.5 1 & Q 3.0 I 2.1 Q3.0 I 2.0 I 2.1 A( O I 2.0 O I 2.1 1 & I 2.1 ) I 2..0 Q 3.0 O 1 Q 3.0 ) = Q3.0 Output Q 3.0 is "1" when both OR conditions are satisifed Output Q 3.0 is "0" when at least one OR condition is not satisfied CPU 928B Programming Guide 3 - 36 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Logic operations (continued) Scan for signal state "0" STEP 5 representation Logical/circuit diagram I 1.5 Statement list Ladder diagram I 1.5 I 1.6 A I 1.5 I 1.6 Control system flowchart Q 3.0 I 1.5 I 1.5 I 1.6 & = 3 & I 1.6 AN I 1.6 Q 3.0 Q3.0 Q 3.0 Q 3.0 Output Q 3.0 is "1" only when input I 1.5 has signal state "1" (normally open contact activated) and input I 1.6 has signal state "0" (normally closed contact activated) Set/reset operations RS flip-flop for a latching signal output STEP 5 representation Logical/circuit diagram I 1.4 Statement list I 2.7 I 1.4 R I 2.7 S 1 1 A I 2.7 S Q 3.5 A I 1.4 R Q 3.5 Q 3.5 1 0 Ladder diagram I 2.7 Control system flowchart Q3.5 Q3.5 S I 1.4 R I 2.7 S I 1.4 R Q Q Q 3.5 Signal state "1" at input I 2.7 sets the flip-flop (signal state "1" at output Q 3.5). If the signal state at input I 2.7 changes to "0", the state of output Q 3.5 is retained (i.e. the signal is latched). Signal state "1" at input I 1.4 resets the flip-flop (signal state "0" at output Q 3.5). If the signal state at input I 1.4 changes to "0", the state of Q 3.5 is retained. When the set signal (input I 2.7) and the reset signal (input I 1.4) are applied at the same time, the scan operation programmed last (in this case AI 1.4) remains in effect for the rest of the program (reset priority). CPU 928B Programming Guide C79000-B8576-C898-01 3 - 37 Programming Examples in the STL, LAD and CSF Methods of Representation Set/reset operations (continued) RS flip-flop with flags STEP 5 representation Logical/circuit diagram I 1.3 Statement list I 2.6 I 1.3 R I 2.6 S 1 1 F 1.7 A I 2.6 S F 1.7 A I 1.3 R F 1.7 Ladder diagram I 2.6 Control system flowchart F 1.7 F 1.7 S I 2.6 S I 1.3 R Q I 1.3 1 0 R Q F1.7 Signal state "1" at input I 2.6 sets the flip-flop. If the signal state at input I 2.6 changes to "0", the signal state of the flag is retained, i.e. the signal is latched. Signal state "1" at input I 1.3 resets the flip-flop. If the signal state at input I 1.3 changes to "0", the signal state of the flag is retained. When the set signal (input I 2.6) and the reset signal (input I 1.3) are applied at the same time, the scan operation last programmed (in this case AI 1.3) remains in effect for the rest of the program (reset priority). CPU 928B Programming Guide 3 - 38 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Set/reset operations (continued) Simulation of a momentary contact relay (one shot) STEP 5 representation Logical/circuit diagram I 1.7 Statement list I 1.7 F4.0 F2.0 F2.0 A I 1.7 AN F 4.0 = F 2.0 A F 2.0 S F 4.0 AN I 1.7 R Ladder diagram Control system flowchart F 2.0 I 1.7 F 4.0 I 1.7 3 & F 4.0 F 2.0 F 2.0 F 4.0 F 4.0 S F 4.0 F 2.0 S I 1.7 R I 1.7 I 1.7 R F 4.0 Q Q F 2.0 On each leading edge of the signal at input I 1.7, the AND condition (AI 1.7 and AN F 4.0) is satisfied; the RLO is "1". This sets flags F 4.0 (edge flag) and F 2.0 (pulse flag). In the next processing cycle, the AND condition AI 1.7 and AN F 4.0 is not satisfied, since flag F 4.0 has already been set. Flag F 2.0 is reset. Flag F 2.0 therefore only remains "1" for one program run. Binary scaler (binary divider) STEP 5 representation Logical/circuit diagram I 1.0 I 1.0 M1.0 M1.1 Q3.0 F 2.0 Q 3.0 0 I 1.0 Q 3.0 Statement list A AN = A S AN R A A = A AN AN S A R I 1.0 F 1.0 F 1.1 F 1.1 F 1.0 I 1.0 F 1.0 F 1.1 Q3.0 F 2.0 F 1.1 Q3.0 F 2.0 Q 3.0 F 2.0 Q 3.0 Ladder diagram I1.0 Control system flowchart F1.0 F1.1 I1.0 & F1.1 F1.0 F1.1 F1.0 S I1.0 R Q F1.1 Q3.0 F 2.0 F1.1 F1.0 S I1.0 R Q F1.1 & F2.0 Q3.0 F1.1 Q3.0 F2.0 Q3.0 S F2.0 R Q F1.1 Q3.0 F2.0 & Q3.0 S F2.0 R Q The binary scaler (output Q 3.2) changes its state each time input I 1.0 changes its signal state from 0 to 1 (leading edge). Therefore, only half the input frequency appears at the output of the memory cell. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 39 Programming Examples in the STL, LAD and CSF Methods of Representation Timer operations Pulse timer STEP 5 representation Logical/circuit diagram Statement list I 3.0 I 3.0 R S 10s 1 T1 T1 Q4.0 Q4.0 A L SP AN R L T LC T A = I 3.0 KT 10.2 T 1 I 3.0 T 1 T 1 QW 0 T 1 QW 2 T 1 Q 4.0 Ladder diagram Control system flowchart T1 I 3.0 T1 1 KT 10.2 TV BI QW0 DE QW2 I 3.0 I 3.0 1 KT 10.2 TV BI QW0 DE QW2 Q Q4.0 = Q4.0 R Q R The timer is started during the first scan if the RLO is "1". Subsequent scans with an RLO of "1" do not affect the timer. If the RLO is "0", the timer is reset (cleared). The scan AT or OT produces the signal "1" as long as the timer is running. KT 10.2: The timer is loaded with the specified value (10). The number to the right of the decimal point indicates the time base: 0 = 0.1sec 2 = 1sec 1 = 0.1 sec 3 = 10 sec BI and DE are digital outputs of the timer. The time at output BI is in binary code. The time at DE is in BCD code with time base. I 3.0 Q4.0 T CPU 928B Programming Guide 3 - 40 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Timer operations (continued) Extended pulse timer STEP 5 representation Logical/circuit diagram Statement list I 3.1 A L SE A = I 3.1 R S 1 T2 I IW T T Q 3.1 15 2 2 4.1 Ladder diagram T2 I 3.1 1 IW15 TW T2 V BI I 3.1 1 IW15 TW V BI DE T2 DE Q4.1 T2 R Q4.1 Control system flowchart Q R Q Q4.1 = Q4.1 The timer is started during the first scan if the RLO is "1". (IB 15) An RLO of "0" does not affect the timer. 5 43 (IB 16) 07 10 2 The scan AT or OT produces a signal "1" as long as the timer is running. IW 15: Set the timer with the value of the operand I, Q, F or D in BCD code (in this example, input word 15). Time base 43 10 1 0 10 0 Timer value I 3.1 Q4.1 T T CPU 928B Programming Guide C79000-B8576-C898-01 3 - 41 3 Programming Examples in the STL, LAD and CSF Methods of Representation Timer operations (continued) ON-delay timer STEP 5 representation Logical/circuit diagram Statement list I 3.5 A L SD AN R A = I 3.5 R S 9s 0 T3 T3 I KT T I T T Q Ladder diagram 3.5 9.2 3 3.5 3 3 4.2 T3 I 3.5 KT9.2 Control system flowchart T3 T O I 3.5 TW BI KT9.2 TV DE O BI DE Q4.2 I 3.5 R Q R Q4.2 Q4.2 T Q Q4.2 = The timer is started during the first scan if the RLO is "1". An RLO of "1" during subsequent scans does not affect the timer. When the RLO is "0", the timer is reset (cleared). The scan AT or OT produces the signal "1" when the timer has elapsed and the RLO is still applied to the input. KT 9.2: The timer is loaded with the specified value (9). The number to the right of the decimal point indicates the time base: 0 = 0.1sec 1 = 0.1 sec I 3.5 Q4.2 T 2 = 10 sec 3 = 10 sec CPU 928B Programming Guide 3 - 42 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Timer operations (continued) Stored ON-delay timer STEP 5 representation Logical/circuit diagram I 3.2 R Statement list I 3.3 E S 20s 0 T4 I 3.3 T4 I 3.2 Q 4.3 A I L KT 20.2 3.3 SS T 4 A 3.2 I Ladder diagram Control system flowchart T4 T4 I 3.3 20.2 T S I 3.3 T S TV BI 20.2 TV BI DE I 3.2 T4 R T 4 A T 4 = Q 4.3 3 DE Q 4.3 R I 3.2 Q R Q Q 4.3 = Q 4.3 The timer is started during the first scan if the RLO is "1". An RLO of "0" does not affect the timer. I 3.3 The scan AT or OT produces the signal "1" when the Q 4.3 T timer has elapsed. The signal state does not change T to "0" until the R T operation resets the timer. OFF-delay timer STEP 5 representation Logical/circuit diagram Statement list I 3.4 R 0 A L S 1 T5 I 3.4 T5 I KT 3.4 Ladder diagram SF T 5 A T 5 T5 I 3.4 10.1 10.1 Control system flowchart T5 O T TV BI I 3.4 10.1 O T TV BI DE DE Q 4.4 Q 4.4 = T5 Q 4.3 R Q R Q Q 4.4 = Q 4.4 When the RLO at the start input changes from "1" to "0", the timer is started. It runs for the length of time programmed. When the RLO is "1", the timer is reset (cleared). I 3.4 Q 4.4 T T T The scan AT or OT produces signal state "1" if or the RLO at the input is "1". the timer is running CPU 928B Programming Guide C79000-B8576-C898-01 3 - 43 Programming Examples in the STL, LAD and CSF Methods of Representation Counter operations Set counter STEP 5 representation Logical/circuit operation Statement list A CU A L S I 4.1 KC 150 R S CI I C I KC C Ladder diagram 4.0 1 4.1 150 1 CU CU I 4.0 CD CD I 4.1 KC 150 binary 16 bits C1 C1 I 4.0 + CQ Control system flowchart S BI CV DE R I 4.1 KC 150 S BI CV DE R Q Q When the result of logic operation changes at the start input (I 4.1) from "0" to "1", the counter is loaded with the specified value (150). The flag necessary for edge evaluation of the set input is incorporated in the counter word. BI and DE are digital outputs of the counter cell. The value at BI is in binary code and the value at DE is in BCD. Reset counter STEP 5 representation Logical/circuit diagram A CD A R A = I 4.2 R S CI =0 / CQ Statement list I 4.0 C I C C Q 2 4.2 2 2 2.4 binary 16 bits Ladder diagram Control system flowchart C2 C2 I 4.0 CD I 4.0 CU I 4.2 CD CU S BI S BI CV DE CV DE R Q Q 2.4 I 4.2 R Q Q 2.4 = Q 2.4 An RLO of "1" (I 4.2) resets the counter to zero. An RLO of "0" does not affect the counter. CPU 928B Programming Guide 3 - 44 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Counter operations (continued) Count up STEP 5 representation Logical/circuit diagram Statement list A I 4.1 Ladder diagram C1 I 4.1 CD + CQ CU 1 R S CI I 4.1 3 C1 I 4.1 CU CU C Control system flowchart binary 16 bits CD S DU S BI CV DE CV DE R Q R Q The value of the addressed counter is incremented by "1" to a maximum value of 999. The function CU is only executed on a positive edge (from "0" to "1") of the logic operation programmed before CU. The flags necessary for edge evaluation of the counter inputs are incorporated in the counter word. Owing to the two separate edge flags for CU and CD, a counter with two different inputs can be used as an up/down counter. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 45 Programming Examples in the STL, LAD and CSF Methods of Representation Counter operations (continued) Count down STEP 5 representation Logical/circuit diagram Statement list A I 4.0 Ladder diagram C1 I 4.0 C1 I 4.0 CD CD C CU CQ CD 1 R S CI I 4.0 Control system flowchart binary 16 bits CU S BI S BI CV DE CV DE R Q R Q The value of the addressed counter is decremented by 1 to a maximum counter value of 0. The function is only executed on a positive edge (from "0" to "1") of the logic operation programmed before the CD. The flags necessary for edge evaluation of the counter inputs are incorporated in the counter word. Owing to the two separate edge flags for CU and CD, a counter with two different inputs can be used as an up/down counter. CPU 928B Programming Guide 3 - 46 C79000-B8576-C898-01 Programming Examples in the STL, LAD and CSF Methods of Representation Comparison operations Compare for equal to STEP 5 representation Logical/circuit diagram Statement list Ladder diagram Control system flowchart 3 IB19 IB20 V1 V2 = L I B19 L IB20 IB19 !=F = Q 3.0 IB20 V1 != F V2 Q IB19 C1 != F IB20 C2 Q Q 3.0 Q 3.0 = Q 3.0 The first operand is compared with the second operand by the comparison operation. The RLO of the comparison is binary. RLO = "1": comparison is satisfied if ACCU-1-L = ACCU-2-L RLO = "0": comparison is not satisfied, when ACCU-1-L is not equal to ACCU-2-L. The condition codes CC1 and CC0 are set as described in the list of operations. ACCU-2-H and ACCU-1-H are not involved in the operation for a 16-bit fixed point comparison. In a 32-bit fixed point comparison (! = D) and floating point comparison (! = G) the entire contents of ACCU 1 and ACCU 2 (32 bits) are compared with each other. During the comparison, the numerical representation of the operands is taken into account, i.e. the contents of ACCU-1-L and ACCU-2-L are interpreted here as a fixed point number. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 47 Programming Examples in the STL, LAD and CSF Methods of Representation Comparison operations (continued) Compare for not equal to STEP 5 representation Logical/circuit diagram IB21 DW3 V1 V2 =/ Statement list L I B21 L DW3 Ladder diagram IB21 >< F = Q 3.1 DW3 V1 >< F V2 Q Control system flowchart IB21 V1 >< F DW3 V2 Q Q 3.1 Q 3.1 =/ Q 3.1 The first operand is compared with the second operand by the comparison operation. The RLO of the comparison is binary. RLO = "1": comparison is satisfied if ACCU-1-L is not equal to ACCU-2-L. RLO = "0": comparison is not satisfied if ACCU-1-L equals ACCU-2-L. The condition codes CC1 and CC0 are set as described at the beginning of Section 3.5. ACCU-2-H and ACCU-1-H are not involved in the operation for a 16-bit fixed point comparison. ACCU-2-H and ACCU-1-H are involved in a 32-bit fixed point comparison and floating point comparison. This information also applies to comparison operations for "greater than", "greater than or equal to", "less than" and "less than or equal to" (see the operations list). During the comparison, the numerical representation of the operands is taken into account, i.e. the contents of ACCU-1-L and ACCU-2-L are interpreted here as a fixed point number. CPU 928B Programming Guide 3 - 48 C79000-B8576-C898-01 Supplementary Operations 3.5.3 Supplementary Operations You can use the supplementary operations set on the programmer only in function blocks (FB and FX). This means that the total operations set for function blocks consists of the basic operations and the supplementary operations. The system operations also belong to the supplementary functions. You can use the system operations, for example to overwrite the memory at optional locations or to change the contents of the working registers of the CPU. If you intend to use system operations, you should be familiar with Chapter 9 "Memory access". Caution Only experienced system programmers should use the system operations and then only with caution. You can only write operations in function blocks in STL. You cannot program function blocks in graphic form (LAD and CSF methods of representation). This section describes the supplementary operations and covers possible combinations of substitution operations with actual operands. System operations System operations are marked in the first column of the tables with S CPU 928B Programming Guide C79000-B8576-C898-01 3 - 49 3 Supplementary Operations Binary logic operations Table 3-11 Binary logic operations with formal operands Operation Operand Function A = AND operation, scan a formal operand for signal state '1' AN = AND operation, scan a formal operand for signal state '0' O = OR operation, scan a formal operand for signal state '1' ON = OR operation, scan a formal operand for signal state '0' Insert formal operand Inputs, outputs, data and flags addressed in binary (parameter types: I, Q; data type BI) and timers and counters (parameter type: T, C) are permitted as actual operands. Digital logic operations Table 3-12 Operation Digital logic operations Operand Function AW AND operation on the contents of ACCU-1-L and ACCU-2-L OW OR operation on the contents of ACCU-1-L and ACCU-2-L XOW Exklusive OR operation on the contents of ACCU-1-L and ACCU-2-L ACCUs 2, 3 and 4 are not affected, however, the condition codes CC 1 and CC 0 are affected (see word condition codes). CPU 928B Programming Guide 3 - 50 C79000-B8576-C898-01 Supplementary Operations Set/reset operations Table 3-13 Set/reset operations with formal operands Operation Operand Function S = Set a formal operand (binary) RB = Reset a formal operand (binary) 3 Reset a formal operand (digital) for timers and counters RD= = = Assign the value of the RLO to a formal operand Insert formal operand Inputs, outputs and F flags addressed in binary (parameter type: I, Q; data type BI) are permitted as actual operands. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 51 Supplementary Operations Timer and counter operations Table 3-14 Timer and counter operations with formal operands Operation Operand Function SP = Start timer specified by the formal operand as a pulse with the value stored in ACCU-1-L (parameter type T). SD = Start timer specified by the formal operand as ON delay with the value stored in ACCU-1-L (parameter type T). SEC = Start timer specified by the formal operand as extended pulse with the value stored in ACCU-1-L or set counter specified as formal operand with the counter value stored in ACCU-1-L (parameter type: T, C). SSU = Start timer specified by the formal operand as stored ON delay with the value stored in ACCU-1-L or increment a counter specified as formal operand (parameter type: T, C). SFD = Start timer specified by the formal operand as stored OFF delay with the value stored in ACCU-1-L or decrement a counter specified as formal operand (parameter type: D, C). FR Enable formal operand (timer/counter) for cold restart (see FR T or FR R); (parameter type: T, C). FR = T 0 to 255 C 0 to 255 Insert formal operand Enable timer for cold restart: The operation is only executed on the leading edge of the RLO (change from 0 to 1). The timer is restarted if the RLO is 1 at the time of the start operation. (See timing diagram below the table). Enable a counter for setting or resetting: The operation is executed only on the leading edge of the RLO (change from 0 to 1). The counter is only started if the RLO = 1 at the time of the start operation. RLO for SP T RLO for FR T t t Scan with A T CPU 928B Programming Guide 3 - 52 C79000-B8576-C898-01 Supplementary Operations Examples Function block call Program in the function block Program executed a) NAME ANNA BERT JOHN :JU FB 203 :EXAMPLE1 : I 10.3 : T 17 : Q 18.4 3 :A :L :SSU :U := =ANNA KT 010.2 =BERT =BERT =JOHN :A :L :SS :U := I 10.3 KT 010.2 T 17 T 17 Q 18.4 :A :SSU :A :SFD :A :L :SEC :AN := =MAXI =DORA =IRMA =DORA =EVA KC 100 =DORA =DORA =EMMA :A :CU :A :CD :A :L :S :AN := I 10.5 C 15 I 10.6 C 15 I 10.7 KC 100 C 15 C 15 F 58.3 :A :L :SEC :A := =BILL =EGON =JACK =JACK =YOGI :A :L :SE :A := I 10.4 IW 20 T 18 T 18 F 100.7 b) NAME MAXI IRMA EVA DORA EMMA :JU FB 204 :EXAMPLE2 : I 10.5 : I 10.6 : I 10.7 : C 15 : F 58.3 c) NAME BILL JACK EGON YOGI :JU FB 205 :EXAMPLE3 : I 10.4 : T 18 : IW 20 : F 100.7 CPU 928B Programming Guide C79000-B8576-C898-01 3 - 53 Supplementary Operations Load and transfer operations Table 3-15 Load and transfer operations with formal operands Operation L = Operand Function Load a formal operand: The value of the operand specified as a formal operand is loaded into the ACCU (parameter type: I, T, C, Q; data type: BY, W, D). LCD = Load a formal operand in BCD code: The value of the timer or counter specified as a formal operand is loaded into the ACCU in BCD code (parameter type: T, C). LW Load the bit pattern of a formal operand: The bit pattern of a formal operand is loaded into the ACCU (parameter type: D; data type: KF, KH, KM, KY, KS, KT, KC). = LWD = Load the bit pattern of a formal operand: The bit pattern of a formal operand is loaded into the ACCU (parameter type: D; data type: KG). T Transfer to a formal operand: The contents of the accumulator are transferred to the operand specified as a formal operand (parameter type: I, Q; data type: BY, W, D). = Insert formal operand Actual operands permitted include those of the corresponding basic operations except for S flags. For the "LW=" operation, permissible data types include a binary pattern (KM) or a hexadecimal pattern (KH), two absolute numbers of 1 byte each (KY), a character (KS), a fixed point number (KF), a timer value (KT) and a counter value (KC). For "LWD=" permissible data is a floating point number. CPU 928B Programming Guide 3 - 54 C79000-B8576-C898-01 Supplementary Operations Table 3-16 Operation L L T T Load and transfer operations with special operands Operand Function RI 0 to 255 Load a word from the interface data area into ACCU 1 (RI area) RJ 0 to 255 Load a word from the extended interface area into ACCU 1 (RJ area) RS 0 to 255 Load a word from the system data area into ACCU 1 (RS area) RT 0 to 255 Load a word from the extended system data area into ACCU 1 (RT area) RI 0 to 255 Transfer the contents of ACCU 1 to a word in the interface data area (RI area) RJ 0 to 255 Transfer the contents of ACCU 1 to a word in the extended interface data area (RJ area) RS 60 to 63 Transfer the contents of ACCU 1 to a word in the system data area (RS area) RT 0 to 255 Transfer the contents of ACCU 1 to a word in the extended system data area (RT area) 3 In contrast to the RI, RJ and RT areas, you can only use words RS 60 to RS 63 of the RS area. Refer to Section 8.3.4 "RS/RT Area". You can use the RT area in its complete length (RT 0 to RT 255) providing you do not use any standard function blocks. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 55 Supplementary Operations Arithmetic operations Table 3-17 Operation ENT Arithmetic operation ENT Operand Function - This causes a stack lift into ACCUs 3 and 4: := := := := ACCUs 1 and 2 are not changed. The old contents of ACCU 4 are lost. Example The following fraction must be calculated: (30 + 3 * 4) / 6 = 7 ACCU 1 Contents of the ACCUs before the sequence of arithmetic operations ACCU 2 ACCU 3 ACCU 4 a b c d 30 a c d L KF +3 3 30 c d ENT 3 30 30 c L KF +4 4 3 30 c x F 12 30 c c + F 42 c c c L KF +6 6 42 c c : 7 c c c L KF +30 F CPU 928B Programming Guide 3 - 56 C79000-B8576-C898-01 Supplementary Operations Table 3-18 Supplementary arithmetic operations Operation Operand Function S ADD BN Add a byte constant (fixed point) to ACCU-1-L (includes sign change)/the condition code in CC 0, CC 1, OV and OS are not affected! - ACCU-1-H and ACCUs 2 to 4 remain unchanged. S ADD S ADD 1) -128 to +127 3 KF -32 768 to +32 767 Add a fixed point constant (word) to ACCU-1-L/ the condition codes in CC 0, CC 1, OV and OS are not affected! - ACCU-1-H and ACCUs 2 to 4 remain unchanged. DH 0000 0000 to FFFF FFFF Add a double word fixed point constant to ACCU 1/the condition codes in CC 0, CC 1, OV and OS are not affected! - ACCUs 2 to 4 remain unchanged. S +D 1) Add two double word fixed point constants (ACCU 2 + ACCU 1)/the result can be evaluated in CC 0/CC 1. 2) S -D 1) Subtract two double word fixed point constants (ACCU 2 - ACCU 1)/the result can be evaluated in CC 0/CC 1. S TAK 2) Swap the contents of ACCU 1 and ACCU 2 1) Programming is dependent on the PG type and the release of the PG system software. 2) For changes in ACCU 2 and ACCU 3: see Section 3.5.1 "Basic Operations/Arithmetic Operations". CPU 928B Programming Guide C79000-B8576-C898-01 3 - 57 Executive Operations 3.5.4 Executive Operations The executive operations also include system operations. C aution System operations should only be used with care and then only by experienced programmers familiar with the system. System operations are indicated in the table by S Jump operations When you use the supplementary jump operations, you indicate the jump destination for unconditional jumps symbolically. The symbolic parameter of the jump operation is identical to the symbolic address of the destination statement. When programming, remember that the absolute jump distance should not exceed 127 words and a STEP 5 statement can consist of more than one word. You can only execute these jumps within a block; jumps over segment boundaries are not permitted ("segment" = structural element in PBs, SBs, FBs, FXs and OBs; see STEP 5 manual). Note The jump statement and jump destination (symbolic address) must be in the same segment. A symbolic address can only be used once per segment. Exception: this does not apply to the JUR jump for which you specify an absolute jump distance as the parameter. Table 3-19 Jump operations Operation JU = JC = JZ = Operand addr ( addr =symbolic address with maximum 4 characters) Function Jump unconditionally: The jump is executed regardless of conditions Jump conditionally: the conditional jump is executed only if the RLO is 1. If the RLO is 0, the statement is not executed and the RLO is set to 1. Jump if result is '0' : the jump is executed only if CC 1 is 0 and CC 0 is 0. The RLO is not changed. CPU 928B Programming Guide 3 - 58 C79000-B8576-C898-01 Executive Operations Operation Operand Function Table 3-19 continued: JN = addr JP = (addr = symbolic address with maximum 4 characters) 3 Jump on overflow: the jump is executed when the OV condition code is 1. If there is no overflow (OV is 0), the jump is not executed. The RLO is not changed. An overflow occurs when an arithmetic operation exceeds the permissible range for a given numerical representation. JO = S JUR Jump if result > '0' : the jump is only executed if CC 1 = 1 and CC 0 = O. The RLO is not changed. Jump if result < '0': the jump is only executed if CC 1 = 0 and CC 0 = 1. The RLO is not changed. JM = JOS Jump if result is not 0 : the jump is executed only if CC1 is not equal to CC0. The RLO is not changed. Jump when the OS (stored overflow) condition code is set: the jump is executed when the condition code OS is 1. If there is no overflow (OS is 0), the jump is not executed. The RLO is not changed. An overflow occurs when an arithmetic operation exceeds the permissible range for a given numerical representation. = -32 768 to +32 767 Relative jump within the user memory or within a function block (e.g. to arrive in a different segment). The operation is always executed regardless of conditions. The operand is the number of words difference between the address of the jump destination - the current destination. The jump is executed either to a higher (positive operand) or lower (negative operand) address than the current operation. Caution If you use JUR incorrectly, undefined statuses can occur in the system. It should only be used by extremely experienced programmers with detailed knowledge of the system. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 59 Executive Operations Shift operations Table 3-20 Operation Shift operations Operand Function (operation with ACCU 1) SLW 0 to 15 Shift a word to the left (vacant positions to the right are padded with zeros) SRW 0 to 15 Shift a word to the right (vacant position to the left are padded with zeros) SLD 0 to 32 Shift a double word to the left (vacant positions to the right are padded with zeros) SSW 0 to 15 Shift a word with sign to the right (vacant positions to the left are padded with the sign - bit 15) SSD 0 to 32 Shift a double word with sign to the right (vacant positions to the left are padded with the sign - bit 31) RLD 0 to 32 Rotate to the left RRD 0 to 32 Rotate to the right Only ACCU 1 is involved in the execution of shift operations. The parameter part of these operations specifies the number of positions by which the accumulator contents should be shifted or rotated. For the SLW, SRW and SSW operations, only the low word of ACCU 1 is involved in the shift operations. For SLD, SSD, RLD and RRD operations, the entire contents of ACCU 1 (32 bits) are involved. Shift operations are executed regardless of conditions. You can use jump operations to scan the value of the last bits shifted out using CC 1/CC 0. Shift: last bit shifted CC 1 CC 0 Jump operation 0 0 0 JZ= 1 1 0 JN= JP= CPU 928B Programming Guide 3 - 60 C79000-B8576-C898-01 Executive Operations Examples 1. You want to shift the contents of data word DW 52 four bits to the left and write them to data word DW 53. STEP 5 program: Contents of the data words: :L DW 52 :SLW 4 :T DW 53 KH = 14AF 3 KH = 4AF0 2. You want to read the input double word ID 0, and shift the contents of ACCU 1 so that the bit positions of the input double word shown in bold face are retained and the remaining bit positions are set to defined values (0H or 0FH). STEP 5 program: :L ID 0 :SLW 4 :SRW 4 :SLD 4 :SSW 4 :SSD 4 :RLD 4 :RRD 4 Contents of ACCU 1 (hexadecimal) ACCU-1-H: ACCU-1-L: 2348 2348 2348 3480 3480 0348 3480 0348 ABCD BCD0 0BCD BCD0 FBCD 0FBC FBC0 0FBC 3. Application: Multiplication by the 3rd power, e.g. new value = old value x 8 :L FW 10 :SLW 3 :T FW 10 Caution: do not exceed the positive area limit! 4. Application: Division by the 2nd power, e.g. new value = old value : 4 :C :L DB 5 DW 0 CPU 928B Programming Guide C79000-B8576-C898-01 3 - 61 Executive Operations Conversion operations Table 3-21 Operation Conversion operations Function CFW Form the 1's complement of ACCU-1-L (16 bits) CSW Form the 2's complement of ACCU-1-L (16 bits) CSD Form the 2's complement of ACCU 1 (32 bits) DEF Convert a fixed point number (16 bits) from BCD to binary DUF Convert a fixed point number (16 bits) from binary to BCD DED Convert a double word (32 bits) from BCD to binary DUD Convert a double word (32 bits) from binary to BCD FDG Convert a fixed point number (32 bits) to a floating point number (32 bits) GFD Convert a floating point number to a fixed point number (32 bits) DEF The value in ACCU-1-L (bits 0 to 15) is interpreted as a BCD number. After the conversion, ACCU-1-L contains a 16-bit fixed point number. DUF The value in ACCU-1-L (bits 0 to 15) is interpreted as a 16-bit fixed point number. After the conversion, ACCU-1-L contains a BCD number. 15 14 0 S 2 14 . . . . 15 SSSS S (sign): ...........20 DUF DEF 10 2 10 1 0 10 0 0 = positive 1 = negative CPU 928B Programming Guide 3 - 62 C79000-B8576-C898-01 Executive Operations DED The value in ACCU 1 (bits 0 to 31) is interpreted as a BCD number. After the conversion, ACCU 1 contains a 32-bit fixed point number. DUD The value in ACCU 1 (bits 0 to 31) is interpreted as a 32-bit fixed point number. After the conversion, ACCU 1 contains a BCD number. 31 30 0 S 2 30 . . . . .....20 DUD 3 DED 31 0 SSSS S (sign): 10 6 10 5 10 4 10 3 10 2 10 1 10 0 0 = positive 1 = negative FDG The value in ACCU 1 (bits 0 to 31) is interpreted as a 32-bit fixed point number. After the conversion, ACCU 1 contains a floating point number (exponent and mantissa). GFD The value in ACCU 1 (bits 0 to 31) is interpreted as a floating point number. After the conversion, ACCU 1 contains a 32-bit fixed point number. 31 30 S 2 0 30 .....20 .... FDG 31 30 ... ... 24 23 0 S 2 6 . . . . . . . . . . . . . . 2 0 S 2 -1 . . . . . Exponent GFD . . . . . 2 -23 Mantissa The conversion is made by multiplying the (binary) mantissa by the value of the (binary) exponent by shifting the mantissa value to more significant bits past an imaginary decimal point by the value of the exponent (base 2). After the multiplication, remnants of the original mantissa remain to the right of the imaginary decimal point. These bit places are cut off from the whole result. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 63 Executive Operations This conversion algorithm produces the following result classes: * Floating point numbers 0 or -1 result in the next lower number. * Floating point numbers < 0 and > -1 result in the value '0'. Conversion examples Floating point number GFD +5,7 -2,3 -0,6 +0,9 32-bit fixed point number 5 -3 0 0 Examples of CFW, CSW 1. You want the contents of data word DW 64 inverted bit for bit (reversed) and stored in data word DW 78. STEP 5 program: Assignment of the data words: :L DW 64 :CFW :T DW 78 KM = 0011111001011011 KM = 1100000110100100 2. The contents of data word DW 207 are interpreted as a fixed point number and stored in data word 51 with a reversed sign. STEP 5 program: Assignment of the data words: :L DW 207 :CSW :T DW 51 KF = +51 KF = -51 CPU 928B Programming Guide 3 - 64 C79000-B8576-C898-01 Executive Operations Decrement/ increment Table 3-22 Operation Decrement/increment operation Operand Function D 1 to 255 Decrement the low byte (bits 0 to 7) of ACCU-1-L by the value of the operand 1) I 1 to 255 Increment the low byte (bits 0 to 7) of ACCU-1-L by the value of the operand 1) 3 1) The contents of the low byte of ACCU-1-L are decremented or incremented by the number specified as the operand without a carry. The operation is executed regardless of conditions. Example STEP 5 program: :L DW 7 :I 16 :T DW 8 :D 33 :T DW 9 Assignment of the data words: KH = 1010 KH = 1020 KH = 10FF Processing operations Table 3-23 Operation DO Processing operations Operand Function DW 0 to 255 Process data word: the following operation is combined with the parameter specified in the address data word and executed. FW 0 to 254 Process flag word: the following operation is combined with the parameter specified in the addressed F flag and executed. DO = Process formal operand (parameter type B): Only C DB, JU PB, JU OB, JU FB, JU SB can be substituted. Insert formal operand CPU 928B Programming Guide C79000-B8576-C898-01 3 - 65 Executive Operations Operation Operand Function Table 3-23 continued: 1) S BI B 1) RS Indirect processing of a formal operand: execute an operation whose operation code is stored in a formal operand. The number of the formal operand must be stored in ACCU 1. 60 to 63 1) Execute an operation whose operation code is stored in the system data area (RS = free system data: RS 60 to 63). In 2-word operations the 2nd word must be loaded in RS n + 1. The value in the formal operand or system data is interpreted as the operation code of a STEP 5 operation and is then executed. Note Only the following operations can be combined with D O DW, or DO FW , D I or D O RS: - A.. , AN.. , O.. , ON.. , S.. , R.. , =.. with areas I, Q, F, S, - FR T, R T, SF T, SD T, SP T, SS T, SE T, - FR C, R C, S C, CD C, CU C, - L.., T.. with areas P, O, I, Q, F, S, D, RI, RJ, RS, RT, - L T, L C, - LC T, LC C, - JU=, JC=, JZ=, JN=, JP=, JM=, JO=, - SLW, SRW, - D, I, SED, SEE, - C DB, JU.. , JC.., G DB, GX DX, CX DX, DOC FX, DOU FX. The PG does not check the legality of the combinations! CPU 928B Programming Guide 3 - 66 C79000-B8576-C898-01 Executive Operations Examples of DO operations DO DW/DO FW Operand substitution Using the statements "DO DW" and "DO FW" you can access data with a substitution, e.g. in a program loop. The substituted access consists of the statement DO DW/DO FW followed immediately by one of the STEP 5 operations listed above. "Substituted" means that the operand for the operation is not programmed as a static value but is fixed during the course of the STEP 5 program. Select the operand type from the range permitted for the operation when you write your program, e.g. PB for the operation "JU PB nn": You must first load the operand value (nn in the example) in a data word or F flag word (parameter word) before the substituted access with DO DW/DO FW. 1 . Principle of substitution: :L :T :DO :L KF FW FW IB +120 14 14 0 load FW with the value "KF +120" before the operation "L IB" is executed, the operand value '0' is replaced by the value '120'; Operation executed: L IB 120 2. Data word as index register: The contents of data words DW 20 to DW 100 are set to signal state '0'. The index register for the parameter of the data words is DW 1. M001 :L :T :L :DO :T :L :L :+F :T :L :<=F :JC ... KF DW KF DW DW DW KF +20 1 +0 1 0 1 +1 supply the index register reset increment the index register DW 1 KF +100 =M001 jump if the index is within the range remaining STEP 5 program Continued on next page CPU 928B Programming Guide C79000-B8576-C898-01 3 - 67 3 Executive Operations Examples of operand substitution continued: 3. Jump distributor for subroutine techniques: + Jump distance M001 M002 M003 :DO :JU :JU :JU :JU :JU : . : . : . : . :BEU : . : . :BEU : . : . :BEU FW 5 =M001 Contents of flag word FW 5: =M002 =M003 jump distance =M004 (maximum 127) =M005 Advantage: all program sections are contained in one block. 4. Jump distributor for block calls: :DO :JU FW 10 PB 0 Contents of flag word FW 10: PB PB PB PB . . PB 0 1 2 3 Block no. x x Operand substitution with binary operations For operand substitutions with binary operations you can use the following operand types: inputs, outputs, F flags, S flags, timers and counters. In this substitution, the structure of the F flag word or data word (parameter word) depends on the operation you are using. Parameter word for inputs and outputs Bit no. 15 11 10 no significance 8 7 6 0 Bit address from 0 to 7 0 Byte address from 0 to 127 CPU 928B Programming Guide 3 - 68 C79000-B8576-C898-01 Executive Operations Parameter word for F flags Bit no. 15 11 10 no significance 8 7 Bit address from 0 to 7 0 Byte address from 0 to 255 Parameter word for S flags Bit no. 15 14 3 12 11 0 Bit address from 0 to 7 0 Byte address from 0 to 1023 Parameter word for timers and counters Bit no. 15 8 7 no significance 0 Number of timer or counter cell from 0 to 255 Principle of the substitution with a binary operation 15 11 10 8 4 DO DW 27 A I 7 0 0 30 DW 27 0.0 A I 30 . 4 statement executed CPU 928B Programming Guide C79000-B8576-C898-01 3 - 69 Executive Operations Example of DI operation In function block FB 1, STEP 5 operations are executed whose operation codes were transferred by a calling block as formal operands FW 10, FW 12 and FW 14. Which of the operation codes is executed is written by the calling block as a consecutive number in flag word FW 16. The result of the executed operation is then entered in ACCU 1 and is transferred to flag word FW 18. FB 1 NAME :TEST DECL :FW10 DECL :FW12 DECL :FW14 I/Q/D/B/T/C: D I/Q/D/B/T/C: D I/Q/D/B/T/C: D :L FW 16 : :DI :T FW 16 :BE KM/KH/KY/KS/KF/KT/KC/KG: KM/KH/KY/KS/KF/KT/KC/KG: KM/KH/KY/KS/KF/KT/KC/KG: KH KH KH cons. number of formal operand with required operation code transferred operation code is executed result from ACCU 1 FB 2 AUFR NAME FW10 FW12 FW14 : :L KF +1 :T FW 16 :JU =AUFR : : : :JU FB 1 :TEST : KH 4A5A : KH xxxx : KH yyyy :T FW 18 :BE cons. no. of formal operand with operation code call FB TEST op. code "L IB 90", other operation code, other operation code, ACCU 1 FW 18 List of actual operands in FB 2 FW 10 FW 12 FW 14 4A5AH xxxxH yyyyH formal operand 1 formal operand 2 formal operand 3 Principle of sequence in FB 1 FW 16 0001H :L ACCU 1 FW 16 0001H (cons. no. of actual operand) :L IB 90 :DI Operation executed with "DI" CPU 928B Programming Guide 3 - 70 C79000-B8576-C898-01 Semaphore Operations Disabling/enabling process interrupts Table 3-24 Disabling/enabling process interrupts Function IA Disable external process interrupt servicing RA Enable external process interrupt servicing 3 You can use operations "disable/enable process interrupts", for example to suppress external process interrupts when you are using time-driven processing. External process interrupt-driven processing is then no longer possible in the program section between the IA and RA operations. See also the special function OB 120 "disable interrupts", Section 6.5. 3.5.5 Semaphore Operations If two or more CPUs in one programmable controller (see Chapter 10) require access to the same global memory area (peripherals, CPs, IPs), there is a danger that one CPU will overwrite the data of another CPU or that one CPU could read invalid intermediate data statuses of another CPU and misinterpret them. You must therefore coordinate CPU accesses to the common memory areas. You can coordinate the individual CPUs using the SED and SEE operations. You can, for example, program the following coordination between two CPUs: a CPU involved in multiprocessing can only access the common memory area after it has successfully set a declared semaphore (SES). A semaphore xx can only be set by a single CPU. If a CPU fails to set (i.e. disable) the semaphore, it cannot access the memory area. In the same way, a CPU can no longer access the memory once it has released the semaphore again (SEE). CPU 928B Programming Guide C79000-B8576-C898-01 3 - 71 Semaphore Operations SED/SEE disable/enable semaphore Table 3-25 (non-system operations) Disable/enable semaphore Operation Operand Function SED 0 to 31 Disable (set) a semaphore SEE 0 to 31 Enable (release) a semaphore evaluation of the result of the operation via CC 0/CC 1 Note The SED xx and SEE xx operations must be programmed in all CPUs that require synchronized access to a common global memory area. Standard FBs, handling blocks and blocks for multiprocessor communication manage the coordination internally. If you use these blocks, you do not need to program the operations SEE xx and SED xx. Effect of SED/SEE The CPU that executes the operation SED xx (disable semaphore) accesses a specific byte in the coordinator (provided that no other CPU has access to that byte already). Once a CPU has reserved access, the other CPUs can no longer access the memory area protected by the semaphore (numbers 0 to 31). The area is therefore disabled for all other CPUs. Make sure that the coordination functions correctly, all CPUs requiring access to the same area of global memory must use the same semaphore. The SEE xx (enable semaphore) operation resets the byte on the coordinator. The protected memory area is then once again accessible to the other CPUs. A semaphore can only be enabled by the CPU that disabled it. CPU 928B Programming Guide 3 - 72 C79000-B8576-C898-01 Semaphore Operations Use of SED/SEE Fig. 3-8 illustrates the basic sequence of coordinated access using a semaphore. START Di s a b l e s e m a p h o r e SED Operation successful? No 3 Ye s Access to sem a phore protected global memory Enable semaphore: SEE End Fig. 3-8 Coordination of access to the global memory Before disabling or enabling a particular semaphore, the SED and SEE operations scan the status of the semaphore. The condition codes CC 0 and CC 1 are affected as follows: CC 1 CC 0 Evalu ation 0 0 JZ 1 0 JN, JP Significance Semaphore was disabled by another CPU and cannot be disabled/enabled. Semaphore was disabled/ enabled. CPU 928B Programming Guide C79000-B8576-C898-01 3 - 73 Semaphore Operations Note The scanning of a particular semaphore (= read procedure) and the disabling or enabling of the semaphore (=write procedure) are one unit. No other CPU can access the semaphore during these procedures! When using semaphores, remember the following points: * A semaphore is a global variable, i.e. the semaphore with number 16 exists only once in the entire system, even if your controller is using three CPUs. * All CPUs that require coordinated access to a common memory area must use the SED and SEE operations. * All participating CPUs must execute the same start-up type. During a COLD RESTART, all the semaphores are cleared. During a manual or automatic warm restart, the semaphores are retained. * Start-up in multiprocessor operation must be synchronized. For this reason, no test operation is allowed. CPU 928B Programming Guide 3 - 74 C79000-B8576-C898-01 Semaphore Operations Application example for semaphores Tasks: Four CPUs are plugged into an S5-135U. They output status messages to a status signalling device via a common memory area of the O peripherals (OW 6). A CPU must output each status message for 10 seconds. Only after a 10 second output can a new message be output from the same CPU or a different CPU overwrite the first message. The use of peripheral word OW 6 (extended I/O area, no process image) is controlled by a semaphore. Only the CPU that was able to reserve this area for itself by disabling the assigned semaphore can write this message to OW 6. The semaphore remains disabled for 10 seconds at a time (TIMER T 10). The CPU re-enables the semaphore only after this timer has elapsed. After the semaphore has been re-enabled, the other CPUs can access the reserved area. The new message can then be written to OW 6. If one CPU attempts to disable a semaphore and the semaphore is already disabled by a second CPU, the first CPU waits until the next cycle. It then re-attempts to set the semaphore and output its message. Implementation: The following program can run in all four CPUs, each with a different message. The blocks shown below are loaded. FB 100: DISABLE SEMAPHORE FB 0: MAIN PROGRAM FB 110: OUTPUT REPORT FB 10: REPORT FB 101: ENABLE SEMAPHORE 5 flags are used as follows: F 10.0 = 1: a message was requested or is being processed F 10.1 = 1: the semaphore was disabled successfully F 10.2 = 1: the timer was started F 10.3 = 1: the message was transmitted F 10.4 = 1: the semaphore was re-enabled Continued on next page CPU 928B Programming Guide C79000-B8576-C898-01 3 - 75 3 Semaphore Operations Semaphore application example continued: FB 0 NAME :MAIN :A F 10.0 :JC =M001 : :AN I 0.0 :BEC : :L KH 2222 :T FW 12 :AN F 10.0 :S F 10.0 : M001 :JU FB10 NAME :REPORT : :BE If no message is active, generate message and set "MESSAGE" flag. Call "REPORT" FB FB 10 NAME :REPORT :AN F 10.1 :JC FB 100 NAME :SEMADIS : :A F 10.1 :AN F 10.2 :S F 10.2 :L KT010.2 :SE T 10 : :A F 10.2 :AN F 10.3 :JC FB 110 NAME :MSGOUT : :A F 10.2 :AN F 10.4 :AN T 10 :JC FB 101 NAME :SEMAENAB : :AN F 10.4 :BEC : :L KH0000 :T FY10 :BE If no semaphore is disabled, call "disable semaphore" FB. If the semaphore is disabled and the timer has not started, start the timer. If the timer has started and no message is being transmitted, call "output message" FB. If the timer has started and the semaphore is not enabled and the timer has elapsed, call "enable semaphore" FB. If the semaphore is enabled, reset all flags. Continued on next page CPU 928B Programming Guide 3 - 76 C79000-B8576-C898-01 Semaphore Operations Semaphore application example continued: FB 100 NAME :SEMADIS :SED :JZ :AN :S M001 :BE 10 =M001 F 10.1 F 10.1 Disable semaphore no. 10 If the semaphore is disabled successfully, set "SEMAPHORE-DISABLED" flag. 3 FB 110 NAME:MSGOUT :L :T :AN :S : :BE FW12 OW 6 F 10.3 F 10.3 Transmit a message to the peripherals Set "TRANSFER MESSAGE" flag FB 101 NAME :SEMAENAB :SEE :JZ :AN :S : M001 :BE 10 =M001 F 10.4 F 10.4 Enable semaphore no. 10 Set "SEMAPHORE ENABLED" flag CPU 928B Programming Guide C79000-B8576-C898-01 3 - 77 Operating Modes and Program Processing Levels 4 4 Contents of Chapter 4 4.1 Introduction and Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 4 4.2 Program Processing Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 7 4.3 STOP Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 13 4.3.1 4.3.2 4.3.3 Characteristics and Indication of the Operating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 13 Requesting an OVERALL RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 15 Performing an OVERALL RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 16 4.4 RESTART Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 17 4.4.1 4.4.2 4.4.3 4.4.4 4.4.5 MANUAL and AUTOMATIC COLD RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MANUAL and AUTOMATIC WARM RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . Comparison of the Different Restart Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . User Interfaces for Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interruptions in the RESTART Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 RUN Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 27 4.5.1 4.5.2 Cyclic Program Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time-Driven Program Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Delay interrupt (from Version -3UB12) Clock-driven time interrupts TIME INTERRUPTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Collision of time interrupts (WECK-FE) CLOSED LOOP CONTROLLER INTERRUPT: Processing Closed Loop Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PROCESS INTERRUPT: Interrupt-Driven Program Execution . . . . . . . . . . . . . . . . . . Nested Interrupt-Driven and Time-Driven Program Execution . . . . . . . . . . . . . . . . . . . 4.5.3 4.5.4 4.5.5 4 - 18 4 - 19 4 - 21 4 - 22 4 - 25 4 - 28 4 - 31 4 - 31 4 - 33 4 - 35 4 - 36 4 - 38 4 - 39 4 - 42 CPU 928B Programming Guide C79000-B8576-C898-01 4-1 Operating Modes and Program Processing Levels 4 4 This chapter provides an overview of the operating statuses and program execution levels of the CPU 928B. It informs you in detail about various types of start-up and the organization blocks associated with them, in which you can program your own sequences for various situations when restarting. You will also learn the characteristics of the program execution modes "cyclic processing", "time-controlled processing" and "interrupt-driven processing" and will see which blocks are available for your user program. CPU 928B Programming Guide C79000-B8576-C898-01 4-3 Introduction and Overview 4.1 Introduction and Overview The CPU 928B has three operating modes: * STOP mode * RESTART mode * RUN mode In the RESTART and RUN modes, certain events can occur to which the system program has to react. In many cases, a specific organization block (a block from OB 1 to OB 35) is called as a reaction to an event and serves as the user interface. The modes are displayed by LEDs on the front panel of the CPU. Some of the modes must be activated using the operating elements on the front panel of the CPU. The position of the LEDs and operating elements can be seen in Fig. 4-1. S5-155U CPU948 Receptacle for memory card RUN Mode selector STOP RUN STOP SYS FAULT LED (green) LED (red) LED (red) RUCKSETZEN RESET Reset switch URLOSCHEN OVERALL RESET SIEMENS 6ES5 948-3UA11 QVZ ADF ZYK BASP SI1 SI2 INIT SI1 SI2 Error display LEDs (red) Error display LED (red) Interface error LEDs (red) Interface SI1 PG interface, 15-pin Second serial interface SI2 Receptacle for interface submodule Order number and version Lever Securing bolt Fig. 4-1 Front panel of the CPU 928B with display and operating elements CPU 928B Programming Guide 4-4 C79000-B8576-C898-01 Introduction and Overview LED display of modes Table 4-1 LED RUN Various LEDs on the front panel of the CPU signal the current CPU mode. The following table shows you the relationship between the STOP and RUN LED displays and the mode they indicate. Other LEDs (BASP, ADF, QVZ, ZYK) provide more information. Meaning of the LEDs "RUN" and "STOP" LED STOP Mode ON OFF The CPU is in the RUN mode. OFF ON The CPU is in the STOP mode. After a STOP request at the switch or from the PG, the STOP LED is lit continuously, because the STOP condition was requested by the user or, in multiprocessor operation, by another CPU and was not prompted by the CPU itself. OFF OFF The CPU is in the RESTART mode or the CPU is in the RESTART/RUN mode, the program test is active and the program has reached a breakpoint (wait state) or the CPU is in the RESTART/RUN mode, the program test is active and a breakpoint was eliminated again before it was reached (wait state) OFF flashing slowly The CPU is in the STOP mode. The CPU itself prompted the STOP condition (possibly also of the other CPUs). Typical causes: ADF, QVZ, LZF, BCF, CL controller error, interrupt collision, cycle time error, BSTACK overflow, ISTACK overflow, stop command, end of processing check. If you switch the mode selector to STOP, the flashing stops and the LED is lit continuously. OFF flashing quickly The CPU is in the STOP mode. An overall reset has been requested. This request can be prompted by the CPU itself or by an operator input. ON ON 4 Serious system error Remedy: - Overall Reset of CPU; if error persists, - Switch off voltage at PLC, remove and re-insert the CPU and perform Overall Reset; if error persists, - Replace CPU or have it repaired. CPU 928B Programming Guide C79000-B8576-C898-01 4-5 Introduction and Overview Signalling and error LEDs BASP LED This indicates whether the S5 bus signal BASP (disable command output) is active: In the single processor mode, the CPU clears BASP when it changes to the RUN mode and sets BASP when it changes to the STOP mode. BASP is activated in the RESTART and in the STOP mode and in the first cycle following a warm restart. In the multiprocessor mode, the conditions for BASP are identical with those in the single processor mode, provided the switch on the coordinator is set to RUN. (See your System Manual (/2/ in Chapter 13) for more information on the "Test mode" special case.) Note If BASP is active, all digital outputs are disabled. If an AUTOMATIC or MANUAL WARM RESTART has been executed before the transition to the RUN mode, the BASP LED goes out only after the remaining cycle has been processed. "QVZ" LED Timeout of an I/O module. "ADF" LED Addressing error; the user program has accessed an address in the process image for which there is no module inserted in the I/Os. "ZYK" LED Cycle error; cycle monitoring time has been exceeded. The errors ADF and QVZ can only occur in RESTART and in RUN, the cycle error ZYK can only occur in RUN. At the end of the program processing levels ADF, QVZ or ZYK, the error LED is cleared by the system program, if the CPU has not gone to the STOP mode. CPU 928B Programming Guide 4-6 C79000-B8576-C898-01 Program Processing Levels 4.2 Program Processing Levels Fig. 4-2 gives an overview of the operating states and the processing levels in the CPU 928B (-3UB12). The explanations of the abbreviations are on the following page. LED RUN: off LED STOP: on LED BASP: on LED RUN: off LED STOP: off LED BASP: on S T O P mode In multiproc. operation: Wait to start cycle together RUN mode RESTART mode STP PEU BAU DOPP STUEU STUEB CYCLE MANUAL COLD RESTART/ BCF RETENTIVE C. RESTART/ LZF WARM REST. ADF QVZ AUTOMAT. C. RESTART/ SSF RETENTIVE C. RESTART/ WARM REST. NAU NAU LED RUN: on LED STOP: off LED BASP: off TIMED JOB TIME INT. CONTR. INT. DELAY INTERRUPT PROCESS INTERRUPT 4 WECK-FE REG-FE ZYK BCF LZF ADF QVZ SSF STP PEU BAU DOPP STUEU STUEB ABORT (OB 28) (mode selector, PG-STP or MP-STP) POWER UP NAU POWER DOWN Fig. 4-2 Operating states and program processing levels CPU 928B Programming Guide C79000-B8576-C898-01 4-7 Program Processing Levels Program processing levels in RESTART: MANUAL COLD RESTART MANUAL WARM RESTART RETENTIVE MANUAL COLD RESTART RETENTIVE AUTOMATIC COLD RESTART AUTOMATIC COLD RESTART AUTOMATIC WARM RESTART BCF LZF ADF QVZ SSF (operating code error) (runtime error) (addressing error) (timeout) (interface error) Restart levels error levels Program processing levels in the RUN mode: CYCLE (cyclic program execution) TIMED JOB (time-driven program execution) TIME INT 5 sec (time-driven program execution) TIME INT 2 sec (time-driven program execution) TIME INT 1 sec (time-driven program execution) TIME INT 500 ms (time-driven program execution) TIME INT 200 ms (time-driven program execution) TIME INT 100 ms (time-driven program execution) TIME INT 50 ms (time-driven program execution) TIME INT 20 ms (time-driven program execution) TIME INT 10 ms (time-driven program execution) CONTROLLER INT (collision of time interrupts) DELAY INTERRUPT (time-driven program execution) 1) PROCESS INT (process interrupt-driven prog. execution) Basic levels WECK-FE REG-FE ZYK BCF LZF ADF (collision of time interrupts) (CL controller error) (cycle time error) (operating code error) (runtime error) (addressing error) Features of a program processing level A program processing level is characterized by specific features which are explained on the following pages. Error levels 1) from Version -3UB12 CPU 928B Programming Guide 4-8 C79000-B8576-C898-01 Program Processing Levels Nesting other levels When an event occurs, which requires higher priority processing, the current level is interrupted by the system program and the higher priority level is activated. This occurs in the following situations: * at error levels and program processing levels at RESTART: * all other levels: always at operation boundaries, at block or operation boundaries (depending on the setting in DX 0 refer to Chapter 7) 4 Specific system program Each program processing level has its special system program. Example: At the CYCLE processing level, the system program updates the process image of the inputs and outputs, triggers the cycle monitoring time and invokes management of the programmer interface (system checkpoint). ISTACK After the system program calls an organization block, the CPU executes the STEP 5 statements it contains. The current register record is saved in the ISTACK and a new register record is set up (register: ACCU 1 to 4, block stack pointer, block address register, data block start address, data block length, step address counter and the base address register). If "normal" program execution is interrupted by the occurrence of an event, following the execution of the OB, the CPU continues the program execution at the point of interruption as long as no stop is programmed in the OB. Example: WARM RESTART STP ADF ISTACK ADF ADF Depth 1 BCF ISTACK BCF BCF Depth 2 CYCLE ISTACK CYCLE CYCLE Depth 3 ISTACK = Image of the interrupted levels Fig. 4-3: Principle of level change and ISTACK CPU 928B Programming Guide C79000-B8576-C898-01 4-9 Program Processing Levels Priority Program processing levels have a fixed priority. Depending on this priority, they can interrupt each other or can be nested within each other. The warm restart and error levels differ from the basic levels in that they can always be nested at operation boundaries whenever the appropriate event occurs. They can be nested both in the basic levels and within each other. In the event of errors, the last to occur always has the highest priority. A basic level on the other hand can be nested in a lower priority level only at block boundaries unless this default is changed by writing the appropriate program in DX 0 (see Chapter 7). Priority of the "basic levels": CYCLE TIMED JOB TIME INT 5 s TIME INT 2 s . . CONTROLLER INT PROCESS INT ascending priority Example: A process interrupt occurs during the processing of a time interrupt. Since the process interrupt has a higher priority, the processing of the time interrupt level is interrupted at the next block boundary and the PROCESS INTERRUPT program processing level is activated. If, for example, an addressing error is detected while the process interrupt is being serviced, the process interrupt is stopped immediately at the next operation boundary to activate the ADF level. CPU 928B Programming Guide 4 - 10 C79000-B8576-C898-01 Program Processing Levels Response to double error Once an error level has been activated (ADF, BCF, LZF, QVZ, REG, ZYK) it cannot be activated again until it has been processed completely, not even if a different program processing level is nested within it. In this case, the PLC changes to the STOP mode owing to the double call of a program processing level (DOPP in the ISTACK). Collisions of time interrupts are an exception, refer to the relevant section). In the ISTACK, at depth "01", the DOPP identifier and the error level called twice are marked. Examples of double call errors Example 1: 4 During the processing of the ADF level (user interface OB 25) a further processing error occurs. Since the ADF level is still active, it cannot be called a second time; the CPU changes to STOP. STOP Addressing error in PB 30 causes STOP PB 25 OB 25 PB 30 PB 26 ADF Addressing error in FB 5: Call OB 25/ ADF level FB 5 OB 1 CYCLE Fig. 4-4 Change of level as a result of a double call error CPU 928B Programming Guide C79000-B8576-C898-01 4 - 11 Program Processing Levels Example 2: If an operation code error occurs in the LZF program processing level, the system program attempts to call the BCF level (user interface OB 29). This has, however, already been activated by the occurrence of a parameter error (user interface OB 30) and has not yet been completely processed. Calling the BCF level again at this point is not permitted; the CPU changes to STOP (see Fig. 4-5). STOP Op code error in FB 22 causes STOP FB 21 OB 31 FB 22 LZF Runtime error processing OB 30: OB 31 call / LZF level if substitution error OB 27 if op code error OB 29 if parameter error OB 30 PB 5 FB 7 BCF Parameter error in FB 3: OB 30 call / BCF level FB 2 FB 3 OB 1 CYCLE Fig. 4-5 Double call of error level BCD Description of the individual levels The individual program processing levels and the corresponding user interfaces are described in more detail in the following sections: Section 4.4 describes the program processing levels in RESTART. Section 4.5 describes the program processing levels in RUN Sections 5.6 and 5.7 describe the error levels in RESTART and RUN. CPU 928B Programming Guide 4 - 12 C79000-B8576-C898-01 STOP Mode 4.3 STOP Mode 4.3.1 Characteristics and Indication of the Operating Mode The STOP mode is distinguished by the following features: User program The user program is not processed. Retention of data If program execution has already been active, the values of counters, timers, flags and process images are retained at the transition to the stop mode. BASP signal The BASP signal (disable command output) is active. This disables all digital outputs. Exception: In multiprocessor mode the BASP signal is not active during the test mode of the coordinator - please see your System Manual (/2/ in Chapter 13) for more information. ISTACK If program execution was already active, there is an information field for each interrupted program processing level in the interrupt stack (ISTACK) that indicates the cause of the interrupt when the CPU is in the STOP mode (see Section 5.4). LEDs on the front panel of the CPU RUN LED: STOP LED: BASP LED: off on (steady or flashing) on (except in test mode) The STOP LED indicates the possible causes of the current stop state. The following paragraphs describe a continuously lit or flashing STOP LED. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 13 4 STOP Mode STOP LED lit continuously The STOP mode was triggered by the following: * in the single processor mode - the mode selector was switched from RUN to STOP the PLC STOP programmer function was activated a device fault occurred (BAU, PEU) an OVERALL RESET was performed * in the multiprocessor mode - by switching the mode selector on the coordinator to STOP, - by another CPU going into STOP as the result of a fault (a CPU not causing a fault is lit continuously). STOP LED flashes slowly (approximately once every two seconds) When the STOP LED flashes slowly, this normally indicates an error. In the multiprocessor mode, slow flashing indicates the CPU which caused the stop mode (owing to an error). The STOP LED flashes slowly in the following situations: - a stop operation was programmed in the user program - an operator error has occurred (e.g. DB 1 error, selection of an illegal start-up type, etc.) - programming or device errors (calling a block that is not loaded, addressing error, timeout, operation code error etc.); the following LEDs also light up to define the possible cause of error more exactly: ADF LED QVZ LED ZYK LED - the END PROGRAM TEST programmer function was activated in this CPU. The STOP LED flashes quickly (approximately twice per second) When the STOP LED flashes quickly, this is a warning that an OVERALL RESET is being requested. CPU 928B Programming Guide 4 - 14 C79000-B8576-C898-01 STOP Mode 4.3.2 Requesting an OVERALL RESET Request by the system program Each time you turn on the power and perform an overall reset, the CPU runs through an initialization routine. If errors are detected during this initialization, the CPU changes to the STOP mode and the STOP LED flashes quickly. Possible errors: Contents of the RAMs are not correct. Remedy: overall reset on the CPU Contents of the user EPROM are not correct Remedy: insert programmed EPROM and overall reset on the CPU You must deal with the cause of the problem and then perform an overall reset on the CPU again. OVERALL RESET is also requested if a CPU or system error occurs. You can recognize this error by the fact that the request appears again following an OVERALL RESET. In this case, call your SIEMENS representative. Operator request You request OVERALL RESET as follows: 1. Switch the mode selector from RUN to STOP. Result: the CPU is in the STOP mode. The STOP LED is lit continuously. 2. Hold the momentary-contact mode selector in the OVERALL RESET position; at the same time, switch the mode selector from STOP to RUN and back to STOP. Result: you request an OVERALL RESET. The STOP LED flashes quickly. Note If you do not want the OVERALL RESET that you requested to be executed, carry out a COLD RESTART or MANUAL WARM RESTART. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 15 4 STOP Mode 4.3.3 Performing an OVERALL RESET Regardless of whether you yourself or the system program requested an overall reset, you perform the OVERALL RESET as follows: * Hold the mode selector in the OVERALL RESET position; at the same time, switch the mode selector from STOP to RUN and once again to STOP. Result: the OVERALL RESET is performed, the STOP LED is lit continuously. * OR: use the PG function OVERALL RESET (If you perform an OVERALL RESET at the PG, the manual overall reset request using the switches and selector can be omitted. The position of the reset switch and mode selector are then irrelevant.) Result: the OVERALL RESET is performed. The STOP LED is lit continuously. Note Once you have performed an OVERALL RESET, the only permitted restart mode is a COLD RESTART. CPU 928B Programming Guide 4 - 16 C79000-B8576-C898-01 RESTART Mode 4.4 RESTART Mode The RESTART mode is distinguished by the following features: Transition from STOP to RUN The RESTART is the transition from the STOP mode to the RUN mode. Restart types The CPU 928B has the following restart modes: - COLD RESTART (manual or automatic) - WARM RESTART (manual or automatic) - RETENTIVE COLD RESTART (manual or automatic only with Version -3UB12) 4 Following a COLD RESTART, the cyclic user program is processed from the beginning. Following a WARM RESTART, the cyclic user program is processed from the point at which it was interrupted. Organization blocks The following organization blocks are called: for MANUAL or AUTOMATIC COLD RESTART: OB 20 for MANUAL WARM RESTART or RETENTIVE COLD RESTART: OB 21 for AUTOMATIC WARM RESTART or RETENTIVE COLD RESTART: OB 22 The length of the STEP 5 start-up program in the OBs is not restricted. The organization blocks are not time-monitored. Other blocks can be called in the start-up OBs. Data handling In each start-up type, the values of counters, timers, flags and process images are handled differently. BASP signal The BASP signal (disable command output) is active. This disables all digital outputs. Exception: in the test mode, BASP is not activated! (Please see your System Manual for information on the test mode.) LEDs on the front panel of the RUN LED: off CPU STOP LED: off BASP LED: on (except in test mode) Restart characteristics in multiprocessor mode For information on the start-up procedure in the multiprocessor mode, refer to Section 10.1.7. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 17 RESTART Mode 4.4.1 MANUAL and AUTOMATIC COLD RESTART When is a COLD RESTART permitted? A COLD RESTART is always permitted provided the system is not requesting an OVERALL RESET. MANUAL COLD RESTART You carry out a MANUAL COLD RESTART as follows: * Hold the mode selector in the RESET position; at the same time, switch the mode selector from STOP to RUN. * Or use the PC START programmer function (COLD RESTART). AUTOMATIC COLD RESTART AUTOMATIC COLD RESTART is triggered in the following case: After power failure/POWER OFF in RESTART or RUN followed by power restore/POWER ON, the CPU runs an initialization routing and then attempts to automatically execute a COLD RESTART as long as DX 0 is correctly parameterized (see Chapter 7). Prerequisite: * The switches on all CPUs and on the coordinator must remain at RUN. * There must have been no faults in the initialization run. * The CPU was not in the STOP mode when the power was switched off. In the case of power failure in an expansion unit (PEU signal), the CPU goes to STOP. It remains in STOP until the PEU signal is switched inactive and then attempts to execute an AUTOMATIC COLD RESTART or an AUTOMATIC WARM RESTART. CPU 928B Programming Guide 4 - 18 C79000-B8576-C898-01 RESTART Mode 4.4.2 MANUAL and AUTOMATIC WARM RESTART When is a WARM RESTART not permitted? A MANUAL WARM RESTART is not permitted in the following situations: * when the system is requesting OVERALL RESET or * after the following events: 4 - double call of a program processing level (ISTACK: DOPP), - OVERALL RESET (control bits: URGELOE), - start-up aborted (control bits: ANL-ABB), - STOP after the END PROGRAM TEST programmer function, - when compressing the memory in the STOP mode, - stack overflow, - when the user program has been modified in the STOP mode. MANUAL WARM RESTART You carry out a MANUAL WARM RESTART as follows: * The mode selector is in the mid-position. * Switch the mode selector from STOP to RUN. * Or use the PLC START programmer function (WARM RESTART). CPU 928B Programming Guide C79000-B8576-C898-01 4 - 19 RESTART Mode AUTOMATIC WARM RESTART If there is a power failure/POWER OFF during RESTART or RUN, when the power returns again/POWER ON, the CPU performs an initialization routine and then attempts to perform a WARM RESTART automatically, as long as DX 0 is correctly parameterized (see Chapter 7). Conditions: * The selectors on all the CPUs and on the coordinator remain set to RUN. * No errors are detected during the initialization. * The CPU was not in STOP before the power failure/POWER OFF. If there is a power failure in an expansion unit (PEU signal), the CPU changes to STOP. It remains in this state until the PEU signal is cleared and then attempts to perform an AUTOMATIC WARM RESTART or AUTOMATIC COLD RESTART. RETENTIVE COLD RESTART (from Version -3UB12) If the parameter "Retentive cold restart" is stored in DX 0, the system program executes RETENTIVE COLD RESTART instead of WARM RESTART. See the following section to find out how this differs to a "normal" COLD RESTART. CPU 928B Programming Guide 4 - 20 C79000-B8576-C898-01 RESTART Mode 4.4.3 Comparison of the Different Restart Types Table 4-2 Comparison of the different restart types COLD RESTART WARM RESTART RETENTIVE COLD RESTART manual manual System program performs manual automatic automatic automatic 4 Evaluation of: - DB 1 yes yes no no no no - DB 2 yes yes no no no no - DX 0 yes yes no no no no - DX2 yes yes no no no no - DB 0 no 1) no 1) no 1) no 1) no 1) no 1) - 9th track yes yes no no no no - Disable/ enable interrupts yes yes no no yes yes - Cycle statistics yes yes no no no no - Timed job yes yes no no no no - Delay interrupt yes yes yes yes yes yes yes yes no no yes yes - Process image of the inputs yes (completely) yes (completely) no no no no - Process image of the outputs/ digital I/O yes (completely) yes (completely) no no yes (acc. to 9th track) yes (acc. to 9th track) yes yes no no no no Initialization of: Deletion of: - ISTACK/ BSTACK - Analog I/O CPU 928B Programming Guide C79000-B8576-C898-01 4 - 21 RESTART Mode COLD RESTART WARM RESTART RETENTIVE COLD RESTART System program performs manual automatic manual automatic manual automatic - IPC flags yes yes no no no no - Semaphores yes yes no no no no - F flags and S flags yes yes no no no no - Timers and counters yes yes no no no no Processing of remaining cycle in the case of active BASP signal no no yes yes no no Restart type determined by OB 223 COLD RESTART COLD RESTART MANUAL WARM RESTART AUTO. WARM RESTART MANUAL WARM RESTART AUTO. WARM RESTART Indication of the restart type at the programmer in the ISTACK control bits NEUSTA NEUSTA + AWA MWA AWA ANL-6 + MWA ANL-6 + AWA OB 20 OB 20 OB 21 OB 21 OB 22 OB 22 Table 4-2 continued: Deletion of (cont.): User interface 1) DB 0 is always initialized after POWER ON or OVERALL RESET Definition of the "9th track" The "9th track" is a list of input and output bytes in the process image that acknowledged at the last COLD RESTART. If you program and load DB 1, then following a successful COLD RESTART, the 9th track contains only the input and output bytes listed in DB 1. You cannot access the 9th track with STEP 5 operations. 4.4.4 User Interfaces for Restart The organization blocks OB 20, OB 21 and OB 22 are used as user interfaces for the different restart types. You can store your STEP 5 program for each restart type in these blocks. CPU 928B Programming Guide 4 - 22 C79000-B8576-C898-01 RESTART Mode You can do the following in the RESTART OBs: * set flags, * start timers (the start is delayed by the system program until the user program enters the RUN mode), * prepare the data traffic of the CPU with the I/O modules, * execute synchronization of the CPs. OB 20 COLD RESTART: When the CPU executes a MANUAL or AUTOMATIC COLD RESTART, the system program calls OB 20 once. In OB 20, you can store a STEP 5 program that executes preparatory steps for restarting cyclic program execution: After OB 20 is processed, the cyclic program execution begins by calling OB 1 or FB 0. If OB 20 is not loaded, the CPU begins cyclic program execution immediately after the end of a COLD RESTART (following the system activities). OB 21 MANUAL WARM RESTART or RETENTIVE MANUAL COLD RESTART: When the CPU carries out a MANUAL WARM RESTART or RETENTIVE MANUAL COLD RESTART, the system program calls OB 21 once. In OB 21, you can store a STEP 5 program that carries out specific activities once before cyclic program execution is resumed. MANUAL WARM RESTART After OB 21 is processed, for MANUAL WARM RESTART the cyclic program execution continues with the next statement after the point at which it was interrupted. The following conditions apply: * The disable command output signal (BASP) remains active while the rest of the cycle is processed. It is only cleared at the beginning of the next (complete) cycle. * The process output image is reset at the end of the remaining cycle. If OB 21 is not loaded, then at the end of a MANUAL WARM RESTART and after performing system activities the CPU begins program execution again at the point at which the program was interrupted. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 23 4 RESTART Mode Note The CPU registers a power down (NAU or PEU) even when this occurs in the STOP mode. If you then trigger a MANUAL WARM RESTART, the CPU calls OB 22 before OB 21. If, instead, you trigger a MANUAL COLD RESTART, the previous events are ignored by the CPU and OB22 is not called. RETENTIVE MANUAL COLD RESTART If the parameter "RETENTIVE COLD RESTART" is entered in the data block DX 0, after processing OB 21, the system program then goes through a COLD RESTART (the CPU resumes program execution with the first STEP 5 statement in OB 1 or FB 0). The signal states of the flags, IPC flags, semaphore and the block address list (DB 0) are retained. OB 22 AUTOMATIC WARM RESTART or RETENTIVE AUTOMATIC COLD RESTART: When the CPU executes an AUTOMATIC WARM RESTART or a RETENTIVE AUTOMATIC COLD RESTART, the system program calls OB 22 once. Here you can store a STEP 5 program which executes specific actions once before restoration of program execution previously interrupted in RUN. AUTOMATIC WARM RESTART When the power is restored, the CPU carries out the system functions mentioned above and attempts to continue the program from the point at which it was interrupted. If it is loaded, OB 22 is called first. After OB 22 is processed, cyclic program execution resumes with the next statement after the point at which it was interrupted. After a power failure and subsequent restoration of power, the following conditions apply: * The BASP signal (disable command output) remains active while the remaining cycle is processed. It is cleared at the beginning of the next complete cycle. * The process output image is reset at the end of the remaining cycle. RETENTIVE AUTOMATIC COLD RESTART If the parameter "RETENTIVE COLD RESTART" is entered in the data block DX 0, after processing OB 22, the system program then goes through a COLD RESTART (the CPU resumes program execution with the first STEP 5 statement in OB 1 or FB 0). The signal states of the flags, IPC flags, semaphore and the block address list (DB 0) are retained. CPU 928B Programming Guide 4 - 24 C79000-B8576-C898-01 RESTART Mode 4.4.5 Interruptions in the RESTART Mode A start-up program can be interrupted by the following: * NAU (power failure) or PEU (power failure in expansion unit), * activating the stop switch, the stop operation, MP-STP or PG-STP, * program and device errors (see Section 5.6). If you want to continue an interrupted RESTART with one of the possible restart types, please remember the following points: Power failure at RESTART After power returns following a power failure you must distinguish between the situations listed in the following table: Selected mode: AUTOMATIC WARM RESTART The CPU is performing a COLD RESTART (OB 20): following the return of power after power failure, the organization block OB 22 (AUTOMATIC WARM RESTART) is activated at the point of interruption in OB 20. The CPU is performing a MANUAL WARM RESTART (OB 21): following the return of power after a power failure, organization block OB 22 (AUTOMATIC WARM RESTART) is activated at the point of interruption in OB 21. The CPU is already performing an AUTOMATIC WARM RESTART (OB 22): following the return of power after a power failure, no second OB 22 is activated. The interrupted OB 22 is not continued after the return of power but is aborted and then called again and processed from the beginning. AUTOMATIC COLD RESTART The CPU is performing a MANUAL or AUTOMATIC COLD RESTART or a MANUAL WARM RESTART: following the return of power after power failure, the interrupted OB 20 or OB 21 is not continued, but abandoned and the newly called OB 20 is processed. The same rules apply to an AUTOMATIC WARM RESTART following a PEU signal. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 25 4 RESTART Mode MANUAL WARM RESTART after aborting a RESTART If the CPU goes to the STOP mode during any RESTART (stop switch of ADF) and you then trigger a MANUAL WARM RESTART, the interrupted RESTART is continued from the point at which it was interrupted. OB 21 is not activated. MANUAL COLD RESTART after aborting a RESTART If the CPU goes to the STOP mode during any RESTART and you then trigger a MANUAL COLD RESTART, the interrupted RESTART is aborted and a COLD RESTART is performed (if it exists, OB 20 is called). Aborting RETENTIVE COLD RESTART RETENTIVE COLD RESTART is aborted by: * Power failure in the central controller (NAU) or in the expansion unit (PEU), * Stop switch, stop command, MP-STP or PG-STP or * Program errors and hardware faults (see Section 5.6). An aborted RETENTIVE COLD RESTART is not continued at warm restart. Instead, a new RETENTIVE COLD RESTART is started. Previous events and statuses are not taken into account in the selection of restart type. The following applies especially: * If a MANUAL or AUTOMATIC RETENTIVE COLD RESTART is aborted by POWER OFF or power failure in the expansion unit, a RETENTIVE AUTOMATIC COLD RESTART always takes place at POWER ON if all other restart conditions are met. * If a MANUAL or AUTOMATIC RETENTIVE COLD RESTART is initiated by one of the other abort types, a new RETENTIVE MANUAL COLD RESTART takes place. CPU 928B Programming Guide 4 - 26 C79000-B8576-C898-01 RUN Mode 4.5 RUN Mode When the CPU has executed a RESTART (and only then) it changes to the R U N mode. This mode is characterized by the following features: Execution of the user program The user program in OB 1 or in FB 0 is executed cyclically and additional interrupt-driven program sections can be nested in it. Timers, counters, process image All the timers and counters started in the program are running, the process image is updated cyclically. BASP signal The BASP signal (disable command output) is inactive. All the digital outputs are therefore enabled. IPC flags The interprocessor communication (IPC) flags are updated cyclically (provided this is programmed in DB1). LEDs on the front panel of the CPU RUN LED: on STOP LED: off BASP LED: off Note If an AUTOMATIC or MANUAL warm restart was executed before the CPU went into the RUN mode, the BASP LED remains lit until the rest of the cycle has been processed and the process image has been updated. The R U N mode is only possible after the RESTART mode. Program processing levels In the RUN mode there are 13 basic program processing levels, as follows: * CYCLE: the user program is executed cyclically * TI MED JOB: the user program is executed at fixed times you have programmed or once at a fixed time (clock-controlled time interrupt) CPU 928B Programming Guide C79000-B8576-C898-01 4 - 27 4 RUN Mode * 9 TI ME INTERRUPTS: the user program is processed at fixed intervals specified by the system. * CONTROLLER time-driven processing of a preset number of closed loop controllers. INTERRUPT : * D ELAY INTERRUPT * PROCESS INTERRUPT: The user program is processed once after a preset delay time has elapsed. process interrupt-driven user program execution. The processing levels differ from each other in the following aspects: * they are triggered by different events * the user interface for each program processing level is a different organization block or function block. You can program all basic processing levels at the same time in a CPU 928B. The levels are called by the system program according to the default priority (see Section 4.2). 4.5.1 Cyclic Program Execution Triggering Most functions of a programmable controller involve cyclic progra m execution (CYCLE program processing level). This cycle is known as a "free cycle", i.e. after reaching the end of the program, the next cycle is executed immediately (see Fig. 4-6). If the CPU completes the restart program without errors, it begins cyclic program execution. CPU 928B Programming Guide 4 - 28 C79000-B8576-C898-01 RUN Mode Principle The system program activities are as follows: from restart triggers the cycle time monitoring updates the IPC flag inputs updates the process input image (PII) calls the cyclic user program (OB 1 or FB 0) 4 User program including nesting of the other basic processing levels outputs the process output image (PIQ) updates IPC flag outputs system activities, e.g. loading or clearing blocks, compressing blocks. . . Fig. 4-6 User interface: OB 1 or FB 0 Cyclic program execution The system program calls organization block OB 1 or function block FB 0 as the user interface regularly during cyclic program execution. The system program processes the STEP 5 user program in OB 1 or FB 0 from the beginning through the various block calls you have programmed. Following the system activities, the CPU starts again with the first STEP 5 statement in OB 1 (or in FB 0). In OB 1, you program the calls for program, function and sequence blocks that are to be processed in your cyclic program. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 29 RUN Mode If you have a short time-critical user program in which you do not require structured programming, then program FB 0. Since you use the total STEP 5 operation set in this block, you do not require block calls and can reduce the runtime of your program. Note If both OB 1 and FB 0 are programmed, only OB 1 is called by the system program. If you use FB 0 as the user interface, it must not contain parameters. Interrupt points Cyclic program execution can be interrupted at block boundaries by the following: * process interrupt-driven program execution, * closed loop controller processing, * time-driven program execution. Note You can program DX 0 to enable these interruptions to occur at operation boundaries (see Chapter 7). Cyclic program execution can be interrupted at operation boundaries or aborted completely as follows: * if a device or program error occurs, * by operator intervention (PG function, stop switch, MP-STP), * by the STOP operation. ACCUs as data storage The arithmetic registers ACCU 1, 2, 3 and 4 of the CPU 928B can be used as data storage outside the cycle (from the end of one program cycle to the beginning of the next). CPU 928B Programming Guide 4 - 30 C79000-B8576-C898-01 RUN Mode 4.5.2 Time-Driven Program Execution Time-driven processing occurs when a time signal from a clock or internal clock pulse prompts the CPU to interrupt the current program and execute a specific program. After executing this program, the CPU returns to the point at which the previous program was interrupted and continues execution. This way, particular program sections can be inserted automatically into the cyclic program at a specified time. You can trigger time-driven program execution in different ways, as follows: * One-off triggering after a freely selectable delay time in the millisecond range, a " delay interrupt" (DELAY INTERRUPT program processing level). The OB 6 organization block is called via this interrupt. * Triggering using a freely selected time base or once only at an absolute time, a "clock-driven time interrupt" (program processing level TIMED JOB). This interrupt calls organization block OB 9. * Triggering in 9 different time bases with a range from 10 ms to 5 seconds by "time interrupts" (program processing levels TIME INTERRUPTS). An organization block (OB 10 to OB 18) is assigned to each time interrupt. These have a fixed cycle, i.e. the time between two program starts is fixed. Delay interrupt (from Version -3UB12) Small time intervals with a resolution of 1 ms can also be specified with the delay interrupt of the CPU 928B. When the set time has elapsed, the system program calls OB 6 once. Resolution A delay interrupt is generated by calling the special function organization block OB 153 (see Section 6.12). As soon as the delay time parameterized with OB 153 has elapsed, the system program interrupts the current program execution and calls OB 6. After this, program execution is resumed at the interrupt point. User interface OB 6 In the case of a delay interrupt, OB 6 is called as the user interface. In OB 6 you store a STEP 5 program to be executed in this case. If OB 6 has not been loaded, program execution will not be interrupted. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 31 4 RUN Mode Interruptions With the default setting, the TIMED INTERRUPTS level has the highest priority of the basic levels (can be modified by changing the parameter assignment in DX 0). In timed-controlled program execution, the servicing of the delayed interrupt has highest priority. Owing to the distribution of priorities, the processing of the delayed interrupt cannot be interrupted by any other user program. Special features * A delayed interrupt is only processed in the RUN mode. Delayed interrupts owing in the STOP mode, during power down or START-UP are discarded. * A generated delayed alarm (= OB 153 call was processed) is not retained in the transition to the STOP mode and during POWER OFF. * If you generate a new delayed interrupt, i.e. call OB 153 with new parameters, a previously set delayed interrupt is cancelled. A delayed interrupt currently being processed is continued. This means that only one delayed interrupt is valid at any one time. * If a delayed interrupt occurs without the previous one being completely processed, the new interrupt is discarded. Delayed interrupts are not checked for collisions! * Note the special functions OB 122 and OB 142 with which you can disable or delay the servicing of delayed interrupts. CPU 928B Programming Guide 4 - 32 C79000-B8576-C898-01 RUN Mode Clock-driven time interrupts The CPU 928B has a battery-backed clock (central back-up via the power supply of the central controller), which you can set and read out using a STEP 5 program. Using this clock, you can execute a program section time-driven. While the delay interrupt is used for high-speed jobs, the clock-driven time interrupt is especially suitable for processing one-off jobs or jobs occurring cyclically at large time intervals such as hourly, daily or every Monday. When the set time is reached, the system program calls OB 9. Triggering A clock-driven time interrupt (timed job) is generated by calling the special function organization block OB 151 (see Section 6.10). Once the time transferred to OB 151 (time of day, date) has been reached, the timed job is processed. This can be programmed to occur once (absolute time) or be repeated (time base). Once a job becomes due for processing, the system program interrupts the current program and calls OB 9 (program processing level TIMED JOB). Following this, the program is resumed at the point at which it was interrupted. Example: You want to trigger a time interrupt at the 55th second every minute. Setting using OB 151: SECONDS: JOB TYPE: 55 1 (every minute) 5'55 6'55 7'55 min Call OB 9 Call OB 9 Call OB 9 Generate clock-driven time interrupt (call OB 151) CPU 928B Programming Guide C79000-B8576-C898-01 4 - 33 4 RUN Mode User interface: OB 9 OB 9 is called as the user interface for a clock-driven time interrupt. You store a STEP 5 program in OB 9 that is to be processed whenever it is called. If you do not load OB 9, program execution is not interrupted. Interruptions The execution of a clock-controlled time interrupt can be interrupted at block boundaries, or operation boundaries (if selected in DX 0) by the following: * processing of a process interrupt * processing of a delay interrupt * processing of a closed loop controller interrupt. The processing can be interrupted at operation boundaries or aborted completely by the following: * the occurrence of a hardware fault or program error, * operator intervention (PG function, stop switch, MP-STP), * the stop operation. Special features * A clock-driven time interrupt is only processed in the RUN mode. Clock-driven time interrupts that occur in the STOP mode, when the power has failed or during RESTART are discarded providing the trigger time did not occur during STOP (see above). * A clock-driven time interrupt generated following OVERALL RESET and COLD RESTART (= OB 151 call) is retained during a WARM RESTART and following POWER OFF/POWER ON, providing the trigger time did not occur during STOP (see above). * If you generate a new clock-controlled time interrupt, i.e. you call OB 151 with new timer values, an already existing clock-driven time interrupt is cancelled. A currently active clock-driven interrupt is continued. Only one clock-driven time interrupt is ever valid at one time. * If a clock-driven time interrupt occurs when a previous clock-driven time interrupt has not been processed or not been completely processed, the new time interrupt is discarded. Clock-driven time interrupts are not checked for collisions. * You can use the special functions OB 120 and OB 122, to disable or delay the processing of clock-driven time interrupts. CPU 928B Programming Guide 4 - 34 C79000-B8576-C898-01 RUN Mode TIME INTERRUPTS Program execution in fixed time bases In the CPU 928B, you can execute up to 9 different time-driven programs, each program being called at a different time interval. Triggering A time interrupt is triggered automatically at a fixed time interval if the corresponding OB is programmed. User interfaces When a particular time interrupt occurs, the corresponding organization block is activated as the user interface at the next block boundary (or operation boundary). 4 Assignment of the time interrupt time to the OBs: Table 4-3 Assignment "Time interrupt time - called OB" Time b ase 10 ms 20 ms 50 ms 100 ms 200 ms 500 ms 1 sec 2 sec 5 sec Organization block called OB 10 OB 11 OB 12 OB 13 OB 14 OB 15 OB 16 OB 17 OB 18 Falling priority For example, program the program section to be inserted into the cyclic program every 100 ms in OB 13. Note OBs with shorter time bases have a higher priority and can interrupt OBs with longer time bases. Time since last interrupt processed Whenever a time interrupt OB is called (OB 10 to OB 18) ACCU 1 contains the number of time units that have occurred since the last time interrupt OB call, as follows: ACCU 1 := number of time units - 1 If, for example, ACCU 1 contains the number "5" when OB 11 is called, this means that 120 ms (6 time units) have elapsed since OB 11 was last called. As long as there is no collision of time interrupts, a "0" is transferred in ACCU 1. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 35 RUN Mode Interrupt points Time-driven program execution can be interrupted either at block boundaries (default) or at operation boundaries (programmed in DX 0) by the following: * processing of a process interrupt * processing of a delay interrupt * processing of a closed loop controller interrupt * renewed processing of a time interrupt Processing can be interrupted at operation boundaries or aborted completely by the following: * the occurrence of a hardware fault or program error * operator intervention (PG function, stop switch, MP-STP) * the stop operation STP. Note Time-driven program execution cannot be interrupted by the same time interrupt (collision of time interrupts). Collision of time interrupts (WECK-FE) If a time interrupt OB has not yet been completely processed and is called a second time, a collision occurs. A time interrupt collision also occurs if an OB is called a second time and the first call has not been processed. This is possible when the time interrupts can only interrupt the cyclic program at block limits, particularly if your STEP 5 program contains blocks with long runtimes. If a collision of time interrupts occurs, the error program processing level WECK-FE is activated and the system program calls OB 33 as the user interface. In OB 33, you can program a specific reaction to this problem. If OB 33 is not loaded, the CPU goes into Stop if an error occurs. Then WECK-FE is indicated on the programmer in the control bits "Output ISTACK" screen. The level ID of the relevant time interrupt (LEVEL) is indicated in the ISTACK. CPU 928B Programming Guide 4 - 36 C79000-B8576-C898-01 RUN Mode When the system program calls OB 33, it transfers additional information to ACCU 1 and ACCU 2 which provides more detail about the first error to occur. Table 4-4 Collision of time interrupt identifiers Error identifier ACCU-1L Explanation ACCU-2L 1001H 001H Collision of time interrupts with OB 10 ( 10 ms) 1001H 0014H Collision of time interrupts with OB 11 ( 20 ms) 1001H 0010H Collision of time interrupts with OB 12 ( 50 ms) 1001H 0010H Collision of time interrupts with OB 13 (100 ms) 1001H 000EH Collision of time interrupts with OB 14 (200 ms) 1001H 000CH Collision of time interrupts with OB 15 (500 ms) 1001H 000AH Collision of time interrupts with OB 16 ( 1 sec) 1001H 0008H Collision of time interrupts with OB 17 ( 2 sec) 1001H 0006H Collision of time interrupts with OB 18 ( 5 sec) 4 The identifier in ACCU-2-L is the level identifier (see Section 5.3) of the time interrupt which caused the error. Continuing program execution If you require the program to continue if a collision of time interrupts occurs, either program the block end statement "BE" in OB 33 or change the default in DX 0 so that the program is continued if a collision occurs and OB 33 is not programmed. After OB 33 is processed, the program is continued from the point at which it was interrupted. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 37 RUN Mode Note With respect to time-driven program execution, remember the special functions OB 120, OB 121, OB 122 and OB 12 3 with which you can disable or delay the processing of time interrupts for a particular program section. (This is possible either for all programmed time interrupts or for individual time interrupts.) The "faster" a time-driven program processing level is, the greater the danger of time interrupt collisions. If you have time interrupts with short time bases (e.g. the 10 ms and the 20 ms time interrupts) it is normally necessary to select interruption at operation boundaries. This means that the closed loop controller interrupt and the process interrupt must also be set to interrupt at operation boundaries (see Chapter 7, Assigning Parameters to DX 0). 4.5.3 CLOSED LOOP CONTROLLER INTERRUPT: Processing Closed Loop Controllers Triggering In the CPU 928B, apart from cyclic, time and process interrupt program execution, it is also possible to process closed loop controllers. You select intervals (= sampling time) at which the cyclic or time-driven program execution is interrupted and the controller is processed. Following this, the CPU returns to the point at which the cyclic or time-driven program was interrupted and continues execution. A closed loop controller interrupt is triggered when the sampling time you have selected elapses. System program activities * It manages the user interface for closed loop controller processing. * It updates the controller process image. User interface: standard function block "closed loop controller structure R64" When processing a controller, the R64 standard function block is called as the user interface. In conjunction with the controller parameter assignment block DB 2, this allows up to 64 controllers to be processed. You assign a specific data block for each controller. In data block DB 2, known as the "controller list" you specify which controllers are to be processed by the system program at which point in time. DB 2 is reserved for this task. (When assigning parameters, starting up and testing the R64 standard FB, you are supported by a special program package: "COMREG", see Catalog ST 59.) CPU 928B Programming Guide 4 - 38 C79000-B8576-C898-01 RUN Mode Interrupt points Closed loop control processing can be interrupted either at block boundaries (default) or at operation boundaries (programmed in DX 0), by the following: * processing of a process interrupt, * processing of a delay interrupt. Processing can be interrupted at operation boundaries or aborted completely by the following: * the occurrence of a hardware fault or program error, * operator intervention (PG function, stop switch, MP-STP), 4 * the stop operation STP. 4.5.4 PROCESS INTERRUPT: Interrupt-Driven Program Execution Interrupt-driven program execution involves the S5 bus signal of an interrupt-capable digital input module (e.g. 6ES5 432-4UAxx) or a suitable IP module that causes the CPU to interrupt program execution and to process a specific program section. On completion of this program, the CPU returns to the point at which execution was interrupted and continues from there. The evaluation of a process interrupt can be triggered either by a signal level or signal edge. You can write a program to either disable, delay or enable the interrupt. OB 2 can interrupt the current program either at operation or block boundaries (when you program DX 0). Triggering The active state of an interrupt line on the S5 bus triggers the process interrupt. Depending on the slot in the rack, each CPU is assigned one of the interrupt lines (for more detailed information, refer to Chapter 4 in the System Manual). User interface OB 2 When a process interrupt occurs, OB 2 is called as the user interface. In OB 2, you program a specific program to be processed if a process interrupt occurs. If OB 2 is not programmed, the cyclic program is not interrupted. No interrupt-driven program execution takes place. CPU 928B Programming Guide C79000-B8576-C898-01 4 - 39 RUN Mode Interrupt points Process interrupt-driven program execution can only be interrupted by the following: * a program or device error (at operation boundaries) * operator intervention (PG function, stop switch, MP-STP), * the stop operation. Note Interrupt-driven program execution cannot be interrupted by time-driven program execution or by a further process interrupt. Multiple interrupts If further process interrupts occur during the interrupt-driven program execution, these are ignored until OB 2 has been completely processed (including all the blocks called in OB 2). The CPU then returns to the point of interruption and executes the program until the next block boundary. Only then is a new process interrupt accepted and OB 2 called again. This means that a permanently active interrupt cannot totally block cyclic program execution. (This is not the case if you selected process interrupts at operation boundaries in DX 0.) Note Multiple interrupts are not detected. OB 2 can also be called when the signal state of the interrupt line is passive again when the block boundary is reached. Edge-triggered process interrupts occurring during the execution of OB 2 and remaining active for a shorter time than OB 2 are not detected (if level triggered). The signal state of the interrupt signal between its becoming active and the completion of OB 2 (BE operation) is irrelevant. Process interrupt signal In the default (DX 0), the process interrupt signal for the CPU 928B is level-triggered. i.e. the active state of the interrupt line sets a request which causes OB 2 to be processed at the next block or operation boundary (depending on the setting of DX 0). CPU 928B Programming Guide 4 - 40 C79000-B8576-C898-01 RUN Mode A process interrupt is also recognized and processed when the interrupt signal is no longer active when the block boundary is reached. inactive Interrupt line active Process interrupt OB 2 OB 2 OB 2 OB 2 (at block boundaries) Cycle 4 = block boundaries Fig. 4-7 Process interrupt, level triggered When it is called, OB 2 is processed completely. If the interrupt signal is still active or active once again at the end of OB 2, a block is processed in the cyclic program and OB 2 is then called again. If the level is no longer active, OB 2 is only called again at the next change of signal state (from inactive to active). Active interrupt signal states before processing the block end operation (BE) of OB 2 are irrelevant. Process interrupt signal: edge-triggered You can select this setting by assigning parameters to DX 0. After OB 2 has been processed, a new process interrupt can only be triggered by a signal state change (from inactive to active). After processing the block end command (BE) of OB 2 an "inactive-active signal change" of the interrupt signal must follow to generate a process interrupt. A process interrupt is also recognized and processed when the interrupt is no longer active at the block boundary. inactive Interrupt line active Process interrupts OB 2 OB 2 OB 2 (at block boundaries) Cycle = block boundaries Fig. 4-8 Process interrupt, edge-triggered CPU 928B Programming Guide C79000-B8576-C898-01 4 - 41 RUN Mode Disabling interrupt-driven processing The system program inserts an interrupt-driven program into the cyclic program at a block boundary or at a STEP 5 operation boundary. An interruption of this type can have a negative effect if a cyclic program section has to be processed within a specific time (e.g. to achieve a specific response time) or if a sequence of operations should not be interrupted (e.g. when reading or writing related values). If a section of the user program should not be interrupted by interrupt-driven processing, you can use the following program procedures: * Program this section so that it does not contain a block change and retain the default in DX 0 (process interrupts at block limits). Program sections that do not contain block changes cannot be interrupted. * Program the disable process interrupts (IA) operation. Enable interrupt processing with the enable interrupts (RA) operation. No process interrupt driven program execution can take place between these two operations. IA and RA are only allowed in function blocks (supplementary operation set). * You can use the special functions OB 120 and OB 122 to disable or delay the processing of process interrupts for a particular program section. 4.5.5 Nested Interrupt-Driven and Time-Driven Program Execution Priorities for interrupt and If a process interrupt occurs during time controlled program time-driven program execution execution, the program is interrupted at the next interrupt point (block or operation boundary) and the process interrupt is processed. Following this, the time-controlled program is completed. If a time interrupt occurs during interrupt-driven program execution, the interrupt-driven program execution is completed first before the time-driven program execution is started. CPU 928B Programming Guide 4 - 42 C79000-B8576-C898-01 RUN Mode If a process interrupt and a time interrupt occur simultaneously the process interrupt is processed first at the next interrupt point. After this is completed, the pending time interrupt is then processed. Fig. 4-9 is a schematic representation of how program execution is interrupted at block boundaries by time-controlled and program-controlled interrupt processing. OB 1 PB cyclic Interrupt point at which interrupt or time-driven program execution can normally be inserted into cyclic, interrupt or time-driven program execution. Time-driven program execution can only be interrupted by a process interrupt and not vice-versa. OB 9/OB 13 time-driven OB 2 interrupt-driven Fig. 4-9 Interrupt-driven program execution at block boundaries CPU 928B Programming Guide C79000-B8576-C898-01 4 - 43 4 RUN Mode Response time The response time to a time interrupt request corresponds to the processing time of a block or a STEP 5 operation (depending on the selected preset). If, however, process interrupts are still in the queue when cyclic program execution is interrupted, the time-driven program is only processed after all pending process interrupts have been completely processed. The maximum response time between the occurrence and processing of a time interrupt is then increased by the processing time of the process interrupts. If you want to exclude as far as possible the chance of a collision for a particular time interrupt OB xy, remember the following rules: A + B + C< D where A = the sum of the processing times of all higher priority program processing levels (process, controller, time interrupt OBs) B = processing time of the time interrupt OB xy C = runtime of the longest block of all lower priority processing levels D = time base of the time interrupt OB xy Note If you run your program not only cyclically but also time and interrupt-driven, you run the risk of overwriting flags. This can occur if you use flags as intermediate flags both in the cyclic and in the inserted time-driven or interrupt-driven programs and the cyclic program is interrupted by a time or interrupt-driven program. For this reason, save the signal states of the flags in a data block at the beginning of time or interrupt-driven program execution and rewrite them into the (doubly assigned) flags at the end of the interrupt. Four special organization blocks are available for this purpose: OB 190 and OB 192 "transfer flags to data block" and OB 191 and 193 "transfer data fields to flag area" (refer to the relevant section). To avoid double assignment of flags, you can also use the S-flags for most applications. Special "saving procedures" for flags are then no longer necessary (there are enough S flags available). CPU 928B Programming Guide 4 - 44 C79000-B8576-C898-01 Interrupt and Error Handling 5 Contents of Chapter 5 5 5.1 Frequent Errors in the User Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 4 5.2 Error Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 5 5.3 Control Bits and Interrupt Stack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 10 5.3.1 5.3.2 5.3.3 Control bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ISTACK Content. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Explanation of the ISTACK screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Example of Error Diagnosis using the ISTACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4 Error Handling using Organization Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 29 5.5 Errors during RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 32 5.5.1 5.5.2 5.5.3 5.5.4 DB0-FE (DB 0 Errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DB1-FE (DB 1 Errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DB2-FE (DB 2 Errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DX0-FE (DX 0 or DX 2 Errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6 Errors in RUN and in RESTART. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 38 5.6.1 BCF (Operation Code Errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Substitution error (OB 27) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation code error (OB 29). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameter error (OB 30) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LZF (Runtime Errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LZF - calling a block that is not loaded (OB 19) . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load/transfer error (OB 32) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other runtime errors(OB 31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ADF (Addressing Error). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6.2 5.6.3 5 - 11 5 - 18 5 - 19 5 - 25 5 - 33 5 - 34 5 - 35 5 - 36 5 - 40 5 - 40 5 - 41 5 - 42 5 - 43 5 - 43 5 - 44 5 - 45 5 - 53 CPU 928B Programming Guide C79000-B8576-C898-01 5-1 Contents 5.6.4 5.6.5 5.6.6 5.6.7 5.6.8 5.6.9 QVZ (Timeout Error) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QVZ during direct access via the S5 bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QVZ during PII update and transfer of the IPC flags . . . . . . . . . . . . . . . . . . . . . . . . . ZYK (Cycle Time Exceeded Error). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . WECK-FE (Collision of Time Interrupts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REG-FE (Controller Error) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ABBR (Abort). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Errors (FE-3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 53 5 - 53 5 - 54 5 - 56 5 - 57 5 - 58 5 - 60 5 - 61 CPU 928B Programming Guide 5-2 C79000-B8576-C898-01 Interrupt and Error Handling 5 This chapter explains how to avoid errors when planning and programming your STEP 5 programs. You will see what help you can get from the system program for diagnosing and reacting to errors and which blocks you can use to program reactions to errors. 5 CPU 928B Programming Guide C79000-B8576-C898-01 5-3 Frequent Errors in the User Program 5.5 Frequent Errors in the User Program The system program can detect faulty operation of the CPU, errors in the system program processing or the effect of user errors in the program. This section contains a list of errors most likely to occur when you first run your user program. You can avoid these errors easily by remembering the following points when you write your STEP 5 program: * When specifying byte addresses for I/Os, make sure that the corresponding modules are plugged into the central controller or the expansion unit. * Make sure that you have provided correct parameters for all operands. * Make sure that outputs, flags, timers and counters are not processed at different points in the program with operations that counteract each other. * Make sure that all data blocks called in the program exist and are long enough. * Check that all blocks called are actually in the memory. * Be careful when changing existing function blocks. Check that the FBs/FXs are assigned the correct operands and that the actual operands are specified. * Make sure that timers are scanned only once per cycle (e.g. A T1). * Make sure that scratchpad flags (intermediate flags) are saved by interrupt and time-driven programs and are loaded again on completion of the inserted program when they are required by other blocks (e.g. standard FBs). CPU 928B Programming Guide 5-4 C79000-B8576-C898-01 Error Information 5.6 Error Information If an error occurs during system start-up or during cyclic execution of your program, there are various sources of information to help you find the problem, as follows: * LEDs on the front panel of the CPU * ISTACK interrupt stack and control bits * system data RS 3, RS 4 and RS 80 * error identifiers in ACCU 1 and ACCU 2 * BSTACK block stack 5 The following sections describe how to evaluate the information provided by these sources and how to use the error information to analyze a problem. LEDs on the Front Panel of the CPU If the CPU goes over to the STOP mode when you do not want it to, check the LEDs on the front panel. They can indicate the cause of the problem. LED display STOP LED lit continuously STOP LED flashes slowly STOP LED flashes quickly Meanin g The various states of the STOP LED indicate specific causes of interruptions and errors (see section 4.1). ADF LED lit continuously Addressing error QVZ LED lit continuously Timeout error ZYK LED lit continuously Cycle time exceeded error CPU 928B Programming Guide C79000-B8576-C898-01 5-5 Error Information OUTPUT ISTACK programmer online function You can get information about the status of the control bits and the contents of the interrupt stack (= ISTACK) using the ISTACK programmer online function. When the CPU goes over to the STOP mode, the system program enters the following information in the ISTA C K. This information is required for a warm restart: * register contents * accumulator contents * STEP 5 address counter SAC and * condition codes These entries can be very helpful for error diagnosis. Before the actual ISTACK is output on the programmer, the status of the control bits is displayed. The control bits mark the current operating status and certain characteristics of the CPU and the user program and provide additional information on the cause of an error. You can use the "Output ISTACK" function in the STOP, RESTART and RUN modes; however, in RESTART and RUN you only get information via the control bits and not via the contents of the ISTACK. The meaning of the control bits and the structure of the interrupt stack are described in more detail in Section 5.3. System data RS 3 and RS 4 If your CPU returns to the stop mode owing to an error during the R ESTART, the cause of the error is defined in greater detail in the system data words RS 3 and RS 4 (see Section 5.5). These involve errors detected by the system program when it sets up the address list in DB 0 or evaluates DB 1, DB 2, DX 0 or DX 2. CPU 928B Programming Guide 5-6 C79000-B8576-C898-01 Error Information The two data words are stored at the following absolute memory addresses: system data word RS 3: KH = EA03 system data word RS 4: KH = EA04 The error identifier in system data word RS 3 tells you what type of error has occurred. System data word RS 4 tells you where the error has occurred. The error identifiers are in the KH data format. Analyzing system data words RS 3 and RS 4 on the programmer Using the online function INFO ADDRESS (KH = EA03 or EA04) you can read out the contents of the two system data words directly and discover the cause of the error. 5 System data RS 80 If the system program detects a serious system error, it sets the control bit INF in the interrupt stack (see Section 5.3) and enters an additional error identifier in the data format KH in system data word RS 80. The system data word RS 80 has the absolute memory address KH = EA 50. You can read it out in the same way as the system data RS 3 and RS 4. Error identifiers in ACCU 1 and ACCU 2 If errors occur in the STEP 5 program execution in R ESTART or in the CYCLE for which there is a particular organization block as user interface, the system program automatically enters additional error information in the accumulators ACCU 1 and ACCU 2 when the organization block is called. These entries also define the cause of the error more exactly (see Section 5.6). The error identifier in ACCU 1 tells you what type of error has occurred. The error identifier in ACCU 2 (if entered) tells you where the error occurred. The error identifiers are in the KH data format. CPU 928B Programming Guide C79000-B8576-C898-01 5-7 Error Information Analysis of ACCU 1 and ACCU 2 on the programmer Using the online function OUTPUT ISTACK, you can read the contents of the two accumulators directly out of the ISTACK to find out the exact cause of the error. Analysis of ACCU 1 and ACCU 2 with STEP 5 Since the error identifiers are written to ACCU 1 and ACCU 2 automatically when an error organization block is called, you can take these identifiers into account when you program your error OB. This allows you to program specific reactions to various errors in your organization block depending on the error identifier transferrred to it. OUTPUT BSTACK online function The PG online function OUTPUT BSTACK gives you information in STOP about the contents of the block stack (BSTACK - see Section 3.2 "Nesting blocks"). Starting from OB 1 or FB 0, the BSTACK contains a list of all blocks called in sequence and not completely processed when the CPU went into the STOP mode. Since the BSTACK is filled from the bottom, the block on the uppermost level of the BSTACK display contains the block that was last processed and in which the error occurred. BSTACK information The top line contains the following information: Information BLOCK NO BLOCK ADDR Meaning Type and number of the block that called the faulty block Absolute start address of the calling block in the program memory RETURN ADDR Absolute address of the first STEP 5 operation of this block in the user memory. REL ADDR DB NO DB ADDR Relative address (= difference "RETURN ADDR - BLOCK ADDR") of the next operation to be processed in the calling block. (You can display relative addresses on a programmer in the mode "disable input"/key switch and with S5-DOS from Stage IV upwards using the function key "addresses"). Number of the last data block opened in the calling block Absolute start address in the program memory of the last data block opened in the calling block (address of data word DW 0) CPU 928B Programming Guide 5-8 C79000-B8576-C898-01 Error Information Example: Evaluating the BSTACK function: B LOCK NO BLOC K ADDR R ETURN ADDR REL ADDR DB NO DB ADDR OB 23 0063 0064 0001 13 0078 FB 5 006A 0072 0008 13 078 FB 6 008A 0091 0007 100 098 OB 1 009D 009E 0001 In the example above, the stoppage occurred in OB 23 when processing the STEP 5 statement at the absolute memory address "0064 - 1 = 0063". OB 23 (QVZ error OB) was called in FB 5 at the relative address "0008 1 = 0007". The data block DB 100 was opened in FB 6. When the CPU went into the stop mode, data block DB 13 was valid. Data block DB 13 was opened in FB 5. CPU 928B Programming Guide C79000-B8576-C898-01 5-9 5 Control Bits and Interrupt Stack 5.7 Control Bits and Interrupt Stack Using the PLC INFO and OUTPUT ISTACK online programmer functions, you can analyze the operating status, the characteristics of the CPU and the user program and any possible causes of errors and interruptions. Note You can display the control bits in any mode. You can display the ISTA C K only in the STO P mode. * The control bits indicate the current and previous operating status and the cause of the problem. If several errors occurred, the control bits indicate all of them. * The ISTA C K indicates the location of the interruption (addresses) with the current condition codes, the accumulator contents and the cause of the problem. If several errors occurred, a multiple level interrupt stack is constructed as follows: depth 01 = last cause of problem, depth 02 = next to last cause of problem etc. If an ISTACK overflow occurs (more than 13 entries) the CPU goes into the STOP mode immediately. If this happens, you must perform a POWER OFF/POWER ON and a cold restart. The meanings of the individual abbreviations in the control bits and in the ISTACK are described below. Note The text on the screen of your programmer depends on the PG software used. It may differ from the screen represented here. Nevertheless, the description of the individual positions on the screen in these programming instructions is valid. CPU 928B Programming Guide 5 - 10 C79000-B8576-C898-01 Control Bits and Interrupt Stack 5.7.1 Control Bits When you display the ISTACK on the PG the statuses of the control bits are shown on the first screen page (see Fig. 5-1). C O N T R O L B I T S >>STP<< STP-6 FE-STP BARBEND PG-STP STP-SCH STP-BEF MP-STP >>ANL<< ANL-6 M W A A W A ANL-2 >>RUN<< X RUN-6 NEUSTA X EINPROZ X BARB OB1GEL FB0GEL X NEUZU X OBPROZA MWA-ZUL X OBWECKA 8KWRAM X STP-VER EPROM KM-AUS KM-EIN ANL-ABB UA-PG UA-SYS DIG-EIN X UA-PRFE DIG-AUS X UA-SCH 32KWRAM 16KWRAM URGELOE URL-IA DX0-FE FE-22 MOF-FE RAM-FE DB0-FE DB1-FE DB2-FE KOR-FE N A U P E U B A U STUE-FE Z Y K Q V Z A D F WECK-FE B C F FE-6 FE-5 FE-4 FE-3 L Z F REG-FE DOPP-FE Fig. 5-1 5 Example of the first screen form page "OUTPUT ISTACK": control bits The control bits (>>STP<<, >>ANL<< and >>RUN<<) and the control bits in the first lines of the first screen page mark the current or previous status of the CPU and provide information about certain features of the CPU and your STEP 5 program. You can display the control bits in all modes. You can, for example, make sure that organization block OB 2 is loaded and that interrupt control program execution is possible at any time. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 11 Control Bits and Interrupt Stack The following tables explain the meaning of the individual bits. Table 5-1 Meaning of the control bits in the >>STP<< line >>STP<< line (CONTROL BITS) Control bit Meanin g STP CPU is in the STOP mode STP-6 Not used FE-STP Error stop: stop mode caused by NAU (power failure), PEU (peripherals not ready), BAU (battery not ready), STUEB (BSTACK overflow), STUEU (ISTACK overflow), DOPP (double call error) or CPU fault BARBEND Program test end: stop mode after PROGRAM TEST END online function (COLD RESTART required) Is not set if the END PROGRAM TEST function was executed with the CPU in the STOP mode. PG-STP PG-STOP: stop mode due to command from PG STP-SCH STOP switch: stop mode due to mode selector in position STOP STP-BEF Stop operation: -stop mode caused by STEP 5 operation "STP" -stop mode after stop command from system program, if error -organization block is not programmed MP-STP Multiprocessor STOP: -reset switch on the coordinator in STOP position or -different CPU in the STOP mode in multiprocessing CPU 928B Programming Guide 5 - 12 C79000-B8576-C898-01 Control Bits and Interrupt Stack Table 5-2 Meaning of the control bits in the >>ANL<< line >>ANL<< line (C ON TROL BITS) Control bit Meanin g ANL CPU is in the RESTART mode ANL-6 + MWA RETENTIVE MANUAL COLD RESTART ANL-6 + AWA RETENTIVE AUTOMATIC COLD RESTART NEUSTA MANUAL COLD RESTART requested (STOP) or was last RESTART type (RESTART/RUN) MWA MANUAL WARM RESTART requested (STOP) or was last RESTART type (RESTART/RUN) AW A AUTOMATIC WARM RESTART after power failure is requested (STOP) or was last RESTART type (RESTART/RUN) MWA + AWA AUTOMATIC COLD RESTART was requested (STOP) or was last RESTART type (RESTART/RUN) ANL-2 Double function: - is set after PROGRAM TEST END (in contrast to BARBEND in the first line, it is also set when PROGRAM TEST END is called in the STOP mode; prevents WARM RESTART) - is set after "compressing in the STOP mode"; prevents WARM RESTART NEUZU COLD RESTART permitted (STOP) or COLD RESTART was permitted when the last RESTART took place (RESTART/RUN) MWA-ZUL MANUAL WARM RESTART permitted (STOP) or COLD RESTART was permitted when the last RESTART took place (RESTART/RUN) CPU 928B Programming Guide C79000-B8576-C898-01 5 - 13 5 Control Bits and Interrupt Stack Table 5-3 Meaning of the control bits in the >>RUN<< line >>RUN<< line (CONTROL BITS) Control bit Meanin g RUN CPU is in the RUN mode (cyclic processing is active) RUN-6 Not used EINPROZ Single processor mode BARB PROGRAM TEST online function is active OB1GEL Organization block OB 1 is loaded in the user memory. Cyclic program execution is determined by OB 1 FB0GEL Function block FB 0 is loaded in the user memory. Cyclic program execution is determined by FB 0 if no OB 1 is loaded. If FB 0 and OB 1 are both loaded, OB 1 determines the cyclic program execution OBPROZA Process interrupt organization block OB 2 is loaded, i.e. process interrupt-driven program execution is possible OBWECK Time interrupt organization block loaded, i.e. time-driven program execution is possible Table 5-4 Meaning of the control bits in lines 4 and 5 Lines 4 and 5 (CONTROL BITS) Control bit Meaning 32KWRAM User memory submodule is a RAM with 32 x 210 words 16KWRAM User memory submodule is a RAM with 16 x 210 words 8KWRAM User memory submodule is a RAM with 8 x 210 words EPROM User memory submodule is an EPROM KM-AUS Address list for IPC flag outputs from DB 1 exists KM-EIN Address list for IPC flag inputs from DB 1 exists DIG-EIN Address list for digital inputs exists CPU 928B Programming Guide 5 - 14 C79000-B8576-C898-01 Control Bits and Interrupt Stack Lines 4 and 5 (CONTROL BITS) Control bit Meaning DIG-AUS Address list for digital outputs exists Table 5-4 continued: URGELOE Overall reset performed on CPU (COLD RESTART required) URL-IA Overall reset being performed on CPU STP-VER CPU caused CP stop ANL-ABB RESTART aborted (COLD RESTART required) UA-PG PG has requested OVERALL RESET UA-SYS System program has requested OVERALL RESET (no RESTART possible); OVERALL RESET must be performed UA-PRFE OVERALL RESET requested owing to CPU error UA-SCH OVERALL RESET requested at hardware switch: perform an OVERALL RESET or select a restart type if you do not want to perform the requested OVERALL RESET The control bits in the following table indicate errors that can occur in the RESTART (e.g. during an initial COLD RESTART) and RUN (e.g. during time-driven program execution) modes. If several errors occur, all causes of interruptions that have occurred up to now (and have not yet been processed) are displayed in the last three lines of the control bits. See also system data word RS 2, this contains the ICMK (interrupt condition code group word, 16 bits), in which all errors not yet processed are also entered (Section 8.3.5). CPU 928B Programming Guide C79000-B8576-C898-01 5 - 15 5 Control Bits and Interrupt Stack Table 5-5 Meaning of the control bits in lines 6 to 8 Lines 6 to 8 (CONTROL BITS) Control bit Meaning DX0-FE FE-22 Parameter assignment error in DX 0 or DX 2 Not used MOD-FE Error in contents of user submodule (OVERALL RESET required) RAM-FE Error in contents of system program RAM or of DB RAM (OVERALL RESET required) DB0-FE Structure of block address lists in DB 0 incorrect DB1-FE Structure of the address lists in DB 1 for process image updating is incorrect: - DB 1 not programmed and coordinator plugged in or multiprocessor operation required - structure or contents of DB 1 incorrect DB2-FE Error evaluating the parameter assignment data block DB 2 of controller structure R64 KOR-FE Error in data exchange with the coordinator NAU Power failure in the central controller PEU Peripherals not ready = power failure in expansion unit BAU Battery not ready = back-up battery failure in central controller STUE-FE Interrupt or block stack overflow (nesting depth too great; COLD RESTART required) ZYK Cycle monitoring time exceeded QVZ Timeout during data exchange with I/Os ADF Addressing error with inputs or outputs: error caused by accessing the process image, in which I/O modules were addressed that were not plugged in, defect or not specified in DB 1 at the last COLD RESTART CPU 928B Programming Guide 5 - 16 C79000-B8576-C898-01 Control Bits and Interrupt Stack Lines 6 to 8 (CONTROL BITS) Control bit Meaning WECK-FE Collision of time interrupts: an attempt was made to call a particular time interrupt OB a second time while or before first call was processed Table 5-5 continued: BCF Operation code error: - substitution error: processed STEP 5 operation cannot be substituted - operation code error: processed STEP 5 operation is incorrect - parameter error: parameter of the processed STEP 5 operation is incorrect FE-6 Not used FE-5 Indicates a serious system error, additional information in RS 80 FE-4 Power down error: processing of a previous power failure (NAU) by the system program did not run correctly; WARM RESTART is therefore not possible FE-3 Interface error (SSF) LZF Runtime error: - called block not loaded - load/transfer error with data blocks - other runtime errors REG-FE Error processing the controller structure R64 in the CYCLE DOPP-FE Double call error: a still active error program processing level (ADF, BCF, LZF, QVZ, REG, ZYK) is activated a second time (COLD RESTART required) CPU 928B Programming Guide C79000-B8576-C898-01 5 - 17 5 Control Bits and Interrupt Stack 5.7.2 ISTACK Content If the CPU is in the stop state, you can display the content of the ISTACK on the screen after the control bit display by pressing the enter key. When the CPU goes into the STOP mode, the system program enters all the information it needs in this ISTACK for a warm restart. You can use the entries in this ISTACK to see what kind of error occurred and where it occurred in the program. If the stop state was caused by a sin gle error, only one level of the ISTACK information is displayed. With several errors, the corresponding number of ISTACK levels are output (DEPTH 01, DEPTH 02, etc.). At all levels, only one error is marked as the CAUSE OF INTERRUPT. If several errors have occurred DEPTH 01 marks the error detected immediately before the change to the stop state. Fig 5-2 is an example of a PG display of the ISTACK content. INTERRUPT STACK DEPTH 02 OP-REG: BLK-STP: C70A 0002 LEVEL: 0004 ACCU1: 0000 C464 SAC: FB-NO.: REL-SAC: ICMK: 00F3 226 0006 0200 DB-ADD: DB-NO.: DBL-REG.: ICRW: 0000 00FF KLAMMERN: KE1 111 KE2 100 KE3 111 CONDITION CODE: CC1 CC0 OVFL OVFLS STATUS X NAU X VKE X PEU BAU STP BCF STUEU WECK ADF X STUEB Fig. 5-2 0000 BA-ADD: OB-NO.: 0000 0000 ACCU2: CAUSE OF INTERR.: ACCU3: 0000 0000 0000 ACCU4: 0000 0000 ODER ERAB MPSTP ZYK QVZ S-6 LZF REG-FE DOPP Example of a screen page "OUTPUT ISTACK" CPU 928B Programming Guide 5 - 18 C79000-B8576-C898-01 Control Bits and Interrupt Stack Explanation of the ISTACK screen DEPTH Information level of the ISTACK when more than one error has occurred: DEPTH 01 = last cause of stop to occur DEPTH 02 = next to last cause of stop to occur ...... DEPTH13 = ...... (maximum depth) Information about the error The following table contains information about the ISTACK IDs with which the statement in the user program can be found which caused the CPU to change to the STOP mode. Table 5-6 Meaning of the ISTACK IDs concerning the point of error Information about the error ISTACK ID Meaning OP-REG Operation register: Contains machine code (first word) of the instruction processed last in an interrupted program processing level (see list of operations, list of machine codes). BLK-STP Block stack pointer: contains the number of elements entered in the block stack at the time when the interruption of this processing level occurred LEVEL Z Specifies the level of program processing that was interrupted Z : 0002: 0004: 0006: 0008: 000A: 000C: 000E: 0010: 0012: 0014: 0016: 0018: COLD RESTART CYCLE TIME INTERRUPT / 5 sec TIME INTERRUPT / 2 sec TIME INTERRUPT / 1 sec TIME INTERRUPT / 500 ms TIME INTERRUPT / 200 ms TIME INTERRUPT / 100 ms TIME INTERRUPT / 50 ms TIME INTERRUPT / 20 ms TIME INTERRUPT / 10 ms TIMED JOB (OB 18) (OB 17) (OB 16) (OB 15) (OB 14) (OB 13) (OB 12) (OB 11) (OB 10) CPU 928B Programming Guide C79000-B8576-C898-01 5 - 19 5 Control Bits and Interrupt Stack Information about the error ISTACK ID Meaning Table 5-6 continued: LEVEL Z (continued) SAC Z: 001A: not used 001C: CL CONTROLLER INTERRUPT 001E: not used 0020: DELAY INTERRUPT 0022: not used 0024: PROCESS INTERRUPT 0026: not used 0028: RETENTIVE MANUAL COLD RESTART 002A: RETENTIVE AUTOMATIC COLD RESTART 002C: transition to stop mode after stop in multiprocessing, stop switch or PG STOP 002E: interface error 0030: collision of time interrupts 0032: CL controller error 0034: cycle error 0036: not used 0038: operation code error 003A: runtime error 003C: addressing error 003E: timeout 0040: not used 0042: not used 0044: MANUAL WARM RESTART 0046: AUTOMATIC WARM RESTART STEP address counter: - contains the absolute address of the last operation of an interrupted program processing level to be processed in the program memory - if an error occurs, SAC indicates the operation that caused it. - before the first operation of a processing level is executed, SAC is set to "0" CPU 928B Programming Guide 5 - 20 C79000-B8576-C898-01 Control Bits and Interrupt Stack Information about the error ISTACK ID ...NO. Meaning Block type and number of the last block processed Table 5-6 continued: REL-SAC Relative STEP address counter: contains the relative address (related to the block start address) of the last operation to be executed in the last block processed (you can display relative addresses on a programmer using the PG mode "input disable"/key-switch or with S5-DOS from stage IV using a function key or you can output the block on a printer) 5 ICMK Interrupt condition code group word: ICMK indicates all the causes of interruptions that have occurred up to now and have not yet been completely processed (see "System Data Memory Assignment", Section 8.3.5) ICRW Interrupt condition code reset word (see "System Data Memory Assignment", (Section 8.3.5) DB-ADD Absolute start address of the data block opened last in the program memory (DW 0) (DB-ADD = 0000, if no DB was opened) DB-NO. Number of the data block opened last DBL-REG Length of the data block opened last BA-ADD Absolute address in the program memory of the operation to be processed next in the block last called ...No. Block type and number of the block last called CPU 928B Programming Guide C79000-B8576-C898-01 5 - 21 Control Bits and Interrupt Stack Information about the error ISTACK ID ACCU 1...4 Meaning Contents of the calculation registers at the time of interruption: in the event of certain errors, the system program writes error identifiers into ACCUs 1 and 2 when the interruption occurs. These identifiers define the cause of the interruption more exactly Table 5-6 continued: BRACKETS Number of bracketed levels: "KEx abc" x = 1 to 7 levels a = OR (OR see condition code bits) b = RLO (result of logic operation, see condition code bits) c = 1: A( c = 0: O( Condition code see Section 3.5 Cause of interrupt The following abbreviations (ISTACK IDs) represent the most important causes of interruptions. Table 5-7 causes ISTACK IDs cause of interrupt The only of interruptions that are marked are those that have occurred in the currently displayed program processing level (see LEVEL). The causes of interruptions represent the contents of the interrupt condition code group word (ICMK, 16 bits, see Section 8.3.5). Some of the entries here are identical to those in the control bits. Cause of interrupt ISTA C K ID Meaning (called error OB) NAU Power supply failure in central controller PEU Peripherals not ready = power failure in expansion unit CPU 928B Programming Guide 5 - 22 C79000-B8576-C898-01 Control Bits and Interrupt Stack Cause of interrupt ISTA C K ID BAU MPSTP Meaning (called error OB) Battery not ready = back-up battery failure (central controller) Multiprocessor STOP: - reset switch on the coordinator in STOP position or - STOP at a different CPU in multiprocessor operation Table 5-7 continued: 5 ZYK Cycle monitoring time exceeded QVZ Timeout during data exchange with I/O peripherals ADF Addressing error for inputs and outputs with process I/O image STP - stop mode caused by setting the stop switch to STOP stop mode caused by command from PG stop mode after processing the STEP 5 operation "STP" stop mode after stop command from system program, if error organization block is not programmed BCF Operation code error: error detected during the operation decoding - substitution error: processed STEP 5 operation cannot be substituted - operation code error: processed STEP 5 operation is incorrect parameter error: parameter of the processed STEP 5 operation is not permitted S-6 Interface error LZF Runtime error: error detected during the execution of an operation: - called block not loaded - load/transfer error with data blocks - other runtime errors CPU 928B Programming Guide C79000-B8576-C898-01 5 - 23 Control Bits and Interrupt Stack Cause of interrupt ISTA C K ID Meaning (called error OB) REG-FE Error processing the controller structure R64 in the CYCLE STUEB Block stack overflow: nesting depth too great; required measure: COLD RESTART) STUEU Interrupt stack overflow: nesting depth too great; required measure: COLD RESTART) Table 5-7 continued: WECK Collision of time interrupts: before or during the processing of a time interrupt OB, an attempt was made to call the same OB a second time DOPP Double call error a still active error program processing level (ADF, BCF, LZF, QVZ, REG, ZYK) is activated a second time (COLD RESTART required) CPU 928B Programming Guide 5 - 24 C79000-B8576-C898-01 Control Bits and Interrupt Stack 5.7.3 Example of Error Diagnosis using the ISTACK Example 1: Fig. 5-3 illustrates the structure of the ISTACK in conjunction with the interruptions that have occurred. - Die Programmbearbeitungsebene ZYKLUS (OB 1) wird unterbrochen durch das Auftreten eines Interrupts. - Following this, the program processing level TIME INTERRUPT is activated and OB 13 is processed. - The TIME INTERRUPT level is exited owing to the occurrence of a process interrupt, the PROCESS INTERRUPT level is activated and OB 2 is processed. - An incorrect addressing operation activates level ADF where OB 25 is processed. In the error handling program, the user has programmed a stop operation (STP); the CPU aborts program execution. STP Depth 01 ADF OB25 Level: 003C STP x Depth 02 Level: 0024 PROCESS INTERRUPT OB2 ADF x Depth 03 Level: 0010 TIME INTERRUPT OB13 Depth 04 Level: 0004 OB1 CYCLE Program processing levels Fig. 5-3 ISTACK Example 1 of evaluating the ISTACK Before the CPU finally goes into the stop mode, a total of four different program processing levels have been interrupted. If you display the ISTACK, you obtain a four level ISTACK, first the ISTACK with depth 01, in which the identifier of the program processing level last interrupted (=ADF) is marked. You can now "page down" through the ISTACK until you reach the ISTACK with depth 04, that represents the CYCLE program processing level, that was interrupted first. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 25 5 Control Bits and Interrupt Stack Example 2: In this example the CPU detects an addressing error when executing the "A I x.y" operation in OB 1. This leads to the processing of OB 25. As a result of an STP operation in PB 5, the CPU goes into the STOP mode (see Fig. 5-4). PB 5 OB 25 0100 1000 0105 JU PB 5 0106 1007 STP ADF OB 1 0010 ADF A Ix.y C DB 16 001A CYCLE Fig. 5-4 Example 2 of evaluating the ISTACK Continued on next page CPU 928B Programming Guide 5 - 26 C79000-B8576-C898-01 Control Bits and Interrupt Stack Continuation 1 of Example 2: Two interrupted program execution levels lead to the creation of a two-level ISTACK (see Figs 5-5 and 5-6): INTERRUPT STACK DEPTH 01 OP-REG: BLK-STP: STP 0003 LEVEL: 003C SAC: PB-NO.: REL-SAC: ICMK: 1007 5 0007 0300 DB-ADD: DB-NO.: DBL-REG.: ICRW: 16 BA-ADD: OB-NO.: 0106 25 0000 ACCU1: 5 CONDITION CODE:... CAUSE OF INTERR.: STP X Fig. 5-5 Example 2 of evaluating the ISTACK: 1st ISTACK level Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 5 - 27 Control Bits and Interrupt Stack Continuation 2 of Example 2: INTERRUPT STACK DEPTH 02 OP-REG: BLK-STP: A Ix.y 0001 LEVEL: 0004 SAC: OB-NO.: REL-SAC: ICMK: 001A 1 000A 0200 DB-ADD: DB-NO.: DBL-REG.: ICRW: BA-ADD: 0000 16 0000 ACCU1: CONDITION CODE:... CAUSE OF INTERR.: ADF X Fig. 5-6 Example 2 of evaluating the ISTACK: 2nd ISTACK level CPU 928B Programming Guide 5 - 28 C79000-B8576-C898-01 Error Handling using Organization Blocks 5.4 Error Handling using Organization Blocks When the system program detects an error, it calls the appropriate organization block to handle it. You can determine how the CPU reacts by programming the relevant organization block. Depending on how you program the organization block, you can achieve the following reactions: * normal program processing is continued * the CPU goes to the STOP mode and/or * a special error handling program is run through. 5 Organization blocks exist for the following causes of errors: Table 5-8 The organization blocks called in case of errors Cause of error Organization block called Reaction of CPU if OB is not 1) programmed Call of a block that is not loaded (LZF) OB 19 STOP Timeout in the user program during access to I/O modules (QVZ) OB 23 none Timeout during update of the process image and during transfer of IPC flags (QVZ) OB 24 none Addressing error (ADF) OB 25 STOP Cycle time exceeded (ZYK) OB 26 STOP Substitution error (SUF) OB 27 STOP Mode selector set to STOP, PG function PC STOP, STOP from S5 bus (multiprocessor operation) OB 28 STOP Operation code error (BCF) OB 29 STOP Parameter error (BCF) OB 30 STOP Other runtime errors (LZF) OB 31 STOP Load/transfer error with data blocks (TRAF) OB 32 STOP Collision of time interrupts (WECK-FE) OB 33 STOP CPU 928B Programming Guide C79000-B8576-C898-01 5 - 29 Error Handling using Organization Blocks Cause of error Organization block called Reaction of CPU if OB is not 1) programmed Error processing the controller structure R64 (REG-FE) OB 34 STOP Communication error on the 2nd serial interface (FE-3) OB 35 none Table 5-8 continued: 1) with DX 0 defaults Response of organization block not loaded If the organization block is not loaded the response depends on the particular error: No interruption of cyclic program execution If a timeout occurs and OB 23, OB 24 or OB 35 is not loaded, cyclic program execution is not interrupted. The CPU does not react. If you want the CPU to go into the STOP mode when a timeout occurs, the organization block must contain a stop statement and be completed with the block end statement BE or DX 0 must have suitable parameters assigned. Program for STOP: : : :STP :BE STOP mode When any other error occurs, the CPU goes into the STOP mode immediately if you did not program the appropriate organization blocks. If, in exceptional circumstances, (e.g. during system installation) you do not want one of these errors to interrupt cyclic program execution, a block end statement in the appropriate organization block is sufficient or assign suitable parameters to DX 0. Program for uninterrupted operation: : : :BE Note Organization block OB 28 is an exception: here, the CPU always goes to the STOP mode regardless of whether you have loaded OB 28 or not. CPU 928B Programming Guide 5 - 30 C79000-B8576-C898-01 Error Handling using Organization Blocks If you do not want to program the corresponding organization block, you can prevent the transition to the STOP mode by assigning appropriate parameters to data block DX 0. Interruptions during processing of error organization blocks After the system program calls the appropriate organization block, the user program in that block is processed. If another error occurs while the first organization block is being processed, the program is interrupted at the next operation boundary and the appropriate second organization block is called, just as in cyclic program execution. The organization blocks are processed in the order in which they are called. The nesting depth for error organization blocks depends on the following: * The type of error 5 No organization blocks belonging to the same program processing level can be nested within each other. (See Chapter 6 for the assignment of error OBs to the program processing level). When processing OB 27 (program processing level BCF) it is, for example, possible to nest OB 32 (program processing level LZF), however, OB 29 or OB 30 (also BCF) cannot be nested in OB 27. If two blocks from the same program processing level are called, the CPU changes immediately to the STOP mode. * The number of program processin g levels currently active at any one time For each activated program processing level, the system program requires extra memory space to set up the ISTACK when an interrupt occurs. If there is not enough memory left, an ISTACK overflow results. If there is an ISTACK overflow, the CPU changes immediately to the STOP mode. * The number of blocks called at any one time If there is a BSTACK overflow, the CPU changes immediately to the STOP mode. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 31 Errors during RESTART 5.5 Errors during RESTART During initialization and during a restart, causes of interruptions and errors can lead to the restart program being aborted and put the CPU into the STOP mode. Interruptions occurring during the restart program (organization blocks OB 20, 21 and 22) are handled just as in the CYCLE. Exception: if a STOP occurs during the restart, no organization block OB 28 is called. Causes of interrupt and causes of error There is no way of responding via a user interface (error OB) to the causes of interrupt and causes of error listed in the table below. Table 5-9 Causes of error and causes of interrupt in RESTART Control bit or ID in ISTA C K Explanation STP Stop command from system program (at FE-STP) or in the user program BAU Failure of the back-up battery on the central controller NAU Failure of the power supply in the central controller PEU Failure of the power supply in an expansion unit STUEU Stack overflow in interrupt stack (ISTACK) STEUB Stack overflow in the block stack (BSTACK) DOPP-FE Double call of an error program processing level RAM-FE Error during initialization: the contents of the operation system RAM or the DB RAM are incorrect MOD-FE Error during initialization: the contents of the user submodule (RAM or EPROM submodule) are not correct DB0-FE 1) Error setting up the block address list (DB 0) DB1-FE 1) Error evaluating DB 1 to set up the address list for updating the process image CPU 928B Programming Guide 5 - 32 C79000-B8576-C898-01 Errors during RESTART Control bit or ID in ISTA C K Table 5-9 continued: 1) 1) 5.5.1 DB0-FE (DB 0 Errors) Explanation DB2-FE Error evaluating DB 2 of the controller structure R64 DX0-FE 1) Error evaluating data block DX 0 or Error evaluating data block DX 2 for further explanations: see the following pages 5 Errors when setting up the block address list (data block DB 0). DB 0 is set up by the system program following POWER ON. If a DB 0 error occurs, you will find error identifiers in the system data words RS 3 and RS 4 that define the error in greater detail. Table 5-10 IDs for DB 0 errors Error identifier RS 3 RS 4 Explanation 8001H yyyyH Wrong block length yyyy = address of the block with the wrong length 8002H yyyyH Calculated end address of the block in the memory is wrong yyyy = block address 8003H yyyyH Invalid block identifier yyyy = address of the block with the incorrect identifier 8004H yyyyH Organization block number too high (permitted: OB 1 to OB 39) yyyy = address of the block with the incorrect number 8005H yyyyH Data block number 0 (permitted: DB 1 to DB 255) yyyy = address of the block with the incorrect number CPU 928B Programming Guide C79000-B8576-C898-01 5 - 33 Errors during RESTART 5.5.2 DB1-FE (DB 1 Errors) Error evaluating DB 1 to set up the address list for updating the process image. * DB 1 does not exist in multiprocessor operation, or * incorrect DB 1 address list during COLD RESTART. Note In multiprocessor operation, the system checks whether DB 1 exists in all types of restart. DB 1 parameters are, however, only evaluated during a COLD RESTART. Table 5-11 IDs for DB 1 errors Error identifier RS 3 RS 4 Explanation 0410H yyyyH Illegal identifier: - header identifier missing or incorrect (correct KC MASK01) - identifier illegal (permitted KH DE00, DA00, CE00, CA00, BB00) - end identifier missing or incorrect (correct KH EEEE) yyyy = illegal identifier 0411H yyyyH "Digital inputs", number of addresses illegal (permitted 0...128) yyyy = illegal number of addresses 0412H yyyyH "Digital outputs", number of addresses illegal (permitted 0...128) yyyy = illegal number of addresses 0413H yyyyH "IPC flag inputs", number of addresses illegal (permitted 0...256) yyyy = illegal number of addresses 0414H yyyyH "IPC flag outputs", number of addresses illegal (permitted 0...256) yyyy = illegal number of addresses 0415H yyyyH Illegal number of timers (permitted: 256) yyyy = illegal number of timers 0419H yyyyH Timeout with digital inputs yyyy = address of the unacknowledged input byte CPU 928B Programming Guide 5 - 34 C79000-B8576-C898-01 Errors during RESTART Error identifier RS 3 RS 4 Explanation Table 5-11 continued: 5.5.3 DB2-FE (DB 2 Errors) 041AH yyyyH Timeout with digital outputs yyyy = address of the unacknowledged output flag byte 041BH yyyyH Timeout with IPC flag input yyyy = address of the unacknowledged IPC flag byte 041CH yyyyH Timeout with IPC flag output yyyy = address of the unacknowledged IPC flag byte 5 Errors in the evaluation of the parameter assignment data block DB 2 for controller structure R64 (controller initialization). If a DB 2 error occurs, system data words RS 3 and RS 4 contain error identifiers that define the error in greater detail. Table 5-12 IDs for DB 2 errors Error identifier RS 3 RS 4 Explanation 0421H DByyH Data block not loaded yy = number of the data block that is not loaded 0422H FByyH Function block not loaded yy = number of the function block that is not loaded 0423H FByyH Function block not recognized yy = number of the unrecognized function block 0424H FByyH Function block loaded with wrong PG software yy =number of the function block 0425H DByyH Wrong controller data block length yy = number of the data block 0426H -- There is not enough memory space in the DB-RAM to shift the controller DBs from the user EPROM to the DB-RAM CPU 928B Programming Guide C79000-B8576-C898-01 5 - 35 Errors during RESTART 5.5.4 DX0-FE (DX 0 or DX 2 Errors) Note DX 0 and DX 2 errors have a common control bit (DX0-FE) in the control bit screen form. Errors evaluating data block DX 0 In the event of a DX 0 error you will find error identifiers in the system data words RS 3 and RS 4 that define the error in more detail. Table 5-13 Errors evaluating data block DX 2 IDs for DX 0 errors Error identifier RS 3 RS 4 Explanation 0431H yyyyH Illegal identifier: - header identifier missing or incorrect (correct KC MASKX0) - field identifier illegal - end identifier missing or incorrect (correct KH EEEE) yyyy = illegal identifier 0432H yyyyH Illegal parameter yyyy = illegal parameter 0434H yyyyH Illegal number of timers (permitted: 0...256) yyyy = incorrect number of timers 0435H yyyyH Illegal cycle time monitoring (permitted: 1 ms to 13000 ms) yyyy = incorrect time value Parameter assignment for the second serial interface. Data block DX 2 is set up by the system program after a COLD RESTART. In the event of a DX 2 error, you will find error identifiers in the system data words RS 3 and RS 4 that define the error in more detail. Table 5-14 IDs for DX 2 errors Error identifier RS 3 RS 4 0451H 0452H -- yyyyH Explanation DX 2 length (without block header) < 4 words is not permitted DX 2 length (without block header) is too short for link type yyyy = length DX 2 CPU 928B Programming Guide 5 - 36 C79000-B8576-C898-01 Errors during RESTART Error identifier RS 3 RS 4 Explanation Table 5-14 continued: 0453H yyyyH Link type illegal yyyy = link type 0454H xx00H Data identifier for stat. parameter set illegal (not equal to 44H, 58H) xx = data identifier 0455H xxyyH Block for static parameter set illegal xx = identifier / yy = DB number 0456H xxyyH Static parameter set does not exist xx = identifier / yy = DB number 0457H yyyyH Static parameter set too short yyyy = number of the non-existent DW 0458H xx00H Data identifier for dynamic parameter invalid (44H, 58H, 00H) xxH = data identifier 0459H yyyyH Block for dynamic parameter set illegal xx = identifier / yy = DB number 045AH xx00H Data identifier for send/job mailbox invalid (not equal to 44H, 58H, 00H) xx = data identifier 045BH xxyyH Block for send/job mailbox illegal xx = identifier / yy = DB number 045CH xx00H Data identifier for receive mailbox invalid (not equal to 44H, 58H, 00H) xx = data identifier 045DH xxyyH Block for receive mailbox illegal xx = identifier / yy = DB number 045EH xx00H Data identifier for coordination bytes invalid (not equal to 44H, 58H, 4DH) xx = identifier 045FH xxyyH Block for coordination bytes illegal xx = identifier / yy = DB number 0460H xxyyH Block for coordination bytes does not exist xx = identifier / yy = DB number 0461H yyyyH DW for coordination bytes does not exist yyyyH = number of the non-existent DW CPU 928B Programming Guide C79000-B8576-C898-01 5 - 37 5 Errors in RUN and in RESTART 5.6 Errors in RUN and in RESTART In the RUN mode, cyclic, time-driven or interrupt-driven program execution or controller processing can be interrupted at operation boundaries by the occurrence of certain errors or faults, e.g. power failure in the central controller or block stack overflow. Interruptions during initialization and in the RESTART mode cause the restart program to be aborted and the CPU goes into the STOP mode or calls the organization block intended for this error. Interruptions occurring during the start-up program are handled in the same way as in the CYCLE. A distinction is made between problems that cause the CPU to go directly to the STOP mode (e.g. STUEU) and problems that cause the system program to call certain organization blocks that you can program instead of the CPU going directly to the STOP mode (e.g. ADF). There is no way of responding via a user interface (error OB) to the causes of interrupt and causes of error listed in the table below. Errors which lead direct to STOP If these errors occur, an ISTACK is created in which the interrupt is displayed. Causes of error and causes of interrupt in RESTART and RUN, which lead direct to STOP Control bit or Explanation ID in ISTA C K Table 5-15 STP STOP caused by the system program (machine error), when an error OB is not loaded, or there is a stop operation in the user program BAU Failure of the back-up battery in the central controller NAU Failure of the power supply to the central controller PEU Failure of the power supply to one or more expansion units STUEU Stack overflow in the interrupt stack (ISTACK), nesting depth too great STUEB Stack overflow in the block stack (BSTACK), nesting depth too great DOPP-FE Double call of an error program processing level CPU 928B Programming Guide 5 - 38 C79000-B8576-C898-01 Errors in RUN and in RESTART Errors- which cause an error OB to be called Table 5-16 Causes of error and causes of interrupt in RESTART and RUN, which lead direct to STOP Control bit or ID in ISTA C K BCF LZF ADF QVZ ZYK WECK-FE REG-FE ABBR S-6 Explanation OB no. Operation code error: - substitution error - operation code error - parameter error OB 27 OB 29 OB 30 Runtime error: - call for a block that is not loaded - transfer error with DBs - other runtime errors OB 19 OB 32 OB 31 Addressing error: - when accessing the process image OB 25 Timeout: - in the user program when accessing I/O modules - when updating the process image OB 23 OB 24 Cycle error - the cycle monitoring time was exceeded OB 26 Collision of two time interrupts: - error processing a time interrupt OB 33 Controller error: - error processing a controller interrupt OB 34 Abort: - (see Section 5.6.8) OB 28 Communication error: - during data exchange via the second serial interface OB 35 The following sections describe each of these causes of errors in more detail. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 39 5 Errors in RUN and in RESTART 5.6.1 BCF (Operation Code Errors) An operation code error occurs when the CPU either cannot interpret or cannot execute a STEP 5 operation in the user program. All permissible operation codes are listed in the list of operations. The operation that caused the operation code error is not executed. If the relevant BCF organization block is loaded, this is called, processed and the user program is then continued starting with the next operation. If the BCF-OB is not loaded, the CPU goes into the STOP mode. The following operation code errors can occur. In each case, the error OB named is called: Substitution error (OB 27) If an operation with a formal operand is to be executed in a function block, the CPU replaces this formal operand with the actual operand contained in the function block call. The CPU recognizes an illegal substitution. The system program interrupts the processing of the user program and calls organization block OB 27, if it is loaded. ACCU 1 contains additional information that defines the error in more detail. Table 5-17 BCF substitution error Error identifier ACCU-1-LACCU-2-L Explanation 1801H -- Substitution error with the DO RS operation 1802H -- Substitution error with the DO DW, DO FW operations 1803H -- Substitution error with the DO=, DI operations 1804H -- Substitution error with the L=, T= operations 1805H -- Substitution error with the A=, AN=, O=, ON=, ==, S= and RB= operations 1806H -- Substitution error with the RD=, LD=, FR=, SFD=, SD=, SSU; and SEC= operations CPU 928B Programming Guide 5 - 40 C79000-B8576-C898-01 Errors in RUN and in RESTART Operation code error (OB 29) An operation code error is detected by the CPU during the execution of a STEP 5 program when an operation is programmed that does not belong to the STEP 5 set of operations for the CPU 928B (e.g. RU and SU operations can be programmed at the programmer but cannot be interpreted by the CPUs 928B, 928, 922 (R processor) and 921 (S processor) in the S5 135U). If the CPU detects an illegal operation code, the execution of the user program is interrupted and organization block OB 29 is called, if it is loaded When OB 29 is called, ACCU 1 contains additional information that defines the error in greater detail. Table 5-18 BCF operation code error Error identifier ACCU-1-LACCU-2-L 5 Explanation 1811H -- Operation with illegal OP code 1812H -- Illegal OP code for an operation in which the high byte of the first operation word contains the value 68H 1813H -- Illegal OP code for an operation in which the high byte of the first operation word contains the value 78H 1814H -- Illegal OP code for an operation in which the high byte of the first operation word contains the value 70H 1815H -- Illegal OP code for an operation in which the high byte of the first operation word contains the value 60H Caution An operation code error should not be acknowledged: the CPU does not recognize whether the incorrect operation is a single word or multiword operation. Once the CPU has processed OB 29, it attempts to continue the program at the next operation word. If this is the second word of a multiword operation, it either detects a further operation code error or executes this word as a valid operation, which can cause a variety of program errors. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 41 Errors in RUN and in RESTART Parameter error (OB 30) An illegal parameter occurs when an operation is programmed with a parameter that is not permitted for the particular CPU (e.g. calling a reserved data block), or when a non-existent special function is called. If the CPU detects an illegal parameter, the system program interrupts the execution of the user program and calls organization block OB 30, if it is loaded. When OB 30 is called, ACCU 1 contains additional information that defines the error in greater detail. Table 5-19 BCF parameter error Error identifier ACCU-1-LACCU-2-L Explanation (illegal p arameter in...) 1821H -- C DB 0, 1, 2 182BH -- JU(C) OB 0 182CH -- JU(C) OB > 39: special function does not exist 182DH -- CX DX 0, CX DX 1, CX DX 2 182EH -- L FW/T FW/L PW/T PW/L OW/T OW/L DD/T DD/DO FW 255 182FH -- L IW/T IW/L QW/T QW 127 1830H -- L FD/T FD 253, 254, 255 1831H -- L ID/T ID/L QD/T QD 125, 126, 127 1832H -- RLD/RRD/SSD/SLD 33-255 1833H -- SLW/SRW/LIR/TIR 16-255 1834H -- SED/SEE 32-255 1835H -- A=/AN=/O=/ON=/S=/RB=/==/ RD=/FR=/SP=/SD=/SEC=/SSU=/ SFD=/L=/LD=/LW=/T= 0, 127-255 1836H -- DO=/LWD= 0, 126-255 1837H -- A S/O S/S S/=S/AN S/ON S/R S byte number > 1023 1838H -- A S/OS/S S/=S/AN S/ON S/RS bit number > 7 1839H -- L SY/T SY parameter>1023 183AH -- L SW/T SW parameter > 1022 CPU 928B Programming Guide 5 - 42 C79000-B8576-C898-01 Errors in RUN and in RESTART Error identifier ACCU-1-LACCU-2-L Explanation (illegal parameter in...) Table 5-19 continued: 5.6.2 LZF (Runtime Errors) 183BH -- L SD/T SD parameter >1020 183CH -- G DB/GX DX parameter 0, 1 or 2 (DB or DX 0, 1, 2 cannot be generated) A runtime error occurs when the CPU detects an error during the execution of a STEP 5 operation.The operation that causes the runtime error is not executed. (Exception: opening a non-existent data block DB/D X). If there is an LZF organization block, this is called. The interrupted user program is then continued from the next operation after the operation that caused the error. If no LZF-OB is loaded, the CPU goes to the STOP mode. The following runtime errors are possible. In each case, the named error OB is called: LZF - calling a block that is not loaded (OB 19) If a block is called or opened in the user program and this block does not exist, the system program automatically detects an error. This applies to all block types and is true for conditional and unconditional calls. If the system program detects the call or opening of a block that is not loaded, it calls organization block OB 19 , if it is loaded. In OB 19, you can specify how the CPU should proceed. If you have programmed OB 19, it is called and processed following which the interrupted STEP 5 program is continued at the next operation unless OB 19 contains a stop operation. If, on the other hand, you have not programmed OB 19, the CPU goes into the STOP mode when a block that is not loaded is called or opened. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 43 5 Errors in RUN and in RESTART When OB 19 is called, ACCU 1 contains additional information that defines the error in greater detail. Table 5-20 LZF - calling a block that is not loaded Error identifier ACCU-1-L ACCU-2-L Explanation 1A01H -- Data block not loaded for C DB 1A02H -- Data block not loaded for CX DX 1A03H -- Block not loaded for JU(C) FB, OB 1 to 39, PB, SB 1A04H -- Block not loaded for DOU(C) FX 1A05H -- Data block not loaded for OB 254 or 255 1A06H -- Data block not loaded for OB 182 1A07H -- Data block not loaded for OB150/OB151/OB 153 Note If you attempt to open a data block that is not loaded, the DBA register (see Chapter 9) is affected. In this case a loaded data block must be opened again before accessing DB/DX data. Load/transfer error (OB 32) When you transfer data to data blocks (DB, DX), the CPU compares the length of the DB that has been opened with the operand in the transfer operation. If the specified parameter exceeds the actual data block length, the CPU does not execute the transfer statement to prevent data in the memory from being overwritten by mistake. The system program also detects a load/transfer error if a single bit of a non-existent data word is to be set/reset or scanned. The system program also detects a load/transfer error if you attempt to access a data word before you call a data block (using C DBn or CX DXn). CPU 928B Programming Guide 5 - 44 C79000-B8576-C898-01 Errors in RUN and in RESTART When the system program detects a load/transfer error, it calls organization block OB 32 , if it is loaded. The operation that caused the transfer error is not executed. When OB 32 is called, ACCU 1 contains additional information that defines the error in greater detail. Table 5-21 LZF-load/transfer error (TRAF) Error identifier ACCU-1-L ACCU-2-L Other runtime errors (OB 31) Explanation 1A11H -- A/AN D, O/ON D, S/R D, =D access to a non-defined data word 1A12H -- Transfer error: T DR to a non-defined data word 1A13H -- Transfer error: T DL to a non-defined data word 1A14H -- Transfer error: T DW to a non-defined data word 1A15H -- Transfer error: T DD to a non-defined data word 1A16H -- Load error: L DR to a non-defined data word 1A17H -- Load error: L DL to a non-defined data word 1A18H -- Load error: L DW to a non-defined data word 1A19H -- Load error: L DD to a non-defined data word These include all runtime errors that cannot be grouped with the previous types of runtime error (transfer errors or calling a block that is not loaded). If the system program detects one of these runtime errors, it calls organization block OB 31 . The operation (or special function) that caused the error is not processed any further. If OB 31 is not loaded, the CPU goes into the STOP mode. If you want program execution to continue when one of the errors listed below occurs, simply write the block end statement BE in OB 31. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 45 5 Errors in RUN and in RESTART When OB 31 is called, ACCU 1 and ACCU 2 contain additional information that defines the error in greater detail. Error identifiers of different operations, OB 254/255 and OB 250 Table 5-22 LZF-other runtime errors/part 1 Error identifier ACCU-1-L ACCU-2-L Explanation 1A21H -- G DB, GX DX: data block already exists 1A22H -- G DB, GX DX: illegal number of data words (< 1 or > 4091) 1A23H -- G DB, GX DX: not enough space in the RAM 1A25H -- DI: 1A29H -- Bracket stack under or overflow following A(, O(, ) 1A2AH -- C DB, CX DX, block length in data block header too short (length < 5 words) 1A2BH -- Function block with incorrect PG software loaded 1A2CH -- ACR: illegal page number in ACCU-1-L (> 255) 1A31H -- OB 254 or OB 255 (shift) or OB 250: destination data block already exists in DB-RAM 1A32H -- OB 254 or OB 255 (duplicate): destination data block already exists in DB-RAM 1A33H -- OB 254 or OB 255 or OB 250: not enough space in the DB-RAM illegal parameter in ACCU 1 (< 1 or > 125) CPU 928B Programming Guide 5 - 46 C79000-B8576-C898-01 Errors in RUN and in RESTART OB 182 error identifiers Table 5-23 LZF-other runtime errors/part 2 (OB 182 identifier) Error identifier ACCU-1-L ACCU-2-L Explanation 1A34H 0001H description of the data field 1A34H 0100H address area type is illegal 1A34H 0101H data block number is illegal 1A34H 0102H "number of the first parameter word" illegal 1A34H 0200H "source data block type" illegal 1A34H 0201H "source data block number" illegal 1A34H 0202H number of first data word in the source to be transmitted illegal 1A34H 0203H length of source data block in the block header, value < 5 words entered 1A34H 0210H "destination data block type" illegal 1A34H 0211H "destination data block" number illegal 1A34H 0212H number of the first data word in the destination to be transmitted illegal 1A34H 0213H length of the destination data block in the block header, value < 5 words entered 1A34H 0220H number of data words to be transmitted illegal (= 0 or > 4091) 1A34H 0221H source data block too short 1A34H 0222H destination data block too short 1A34H 0223H destination data block in EPROM CPU 928B Programming Guide C79000-B8576-C898-01 5 - 47 5 Errors in RUN and in RESTART Error identifiers of the different special function OBs The table below contains identifiers of OB 110, OB 121, OB 122, OB 221, OB 240, OB 241, OB 242 and OB 250. Table 5-24 LZF-other runtime errors/part 3 Error identifier ACCU-1-L ACCU-2-L Explanation 1A35H -- OB 250: number of the transfer block illegal 1A36H -- OB 250: DB x and DB x + 1 or DX x and DX x +1 have different lengths 1A3AH -- OB 221: illegal value for the new cycle time (cycle time < 1 ms or > 13000 ms) 1A3BH -- OB 223: different CPU start-up types in multiprocessor operation 1A41H -- OB 240, OB 241 or OB 242: illegal shift register or data block number (number < 192 or > 255) 1A42H -- OB 241: shift register not initialized 1A43H -- OB 240: not enough space in the DB-RAM 1A44H -- OB 240: data word DW 0 of the data block does not contain '0' 1A45H -- OB 240: illegal shift register length in DW 1 (not between 2 and 256) 1A46H -- OB 240: illegal pointer position or number of pointers > 5 1A47H -- OB 120: illegal value in ACCU 1 or ACCU-2-L 1A48H -- OB 122: illegal value in ACCU 1 1A49H -- OB 110: illegal value in ACCU 1 or ACCU-2-L 1A4AH -- OB 121: illegal value in ACCU 1or ACCU-2-L 1A4BH -- OB 123: illegal value in ACCU 1 CPU 928B Programming Guide 5 - 48 C79000-B8576-C898-01 Errors in RUN and in RESTART OB 150 error identifiers Table 5-25 LZF-other runtime errors/part 4 (OB 150 identifiers) Error identifier ACCU-1-L ACCU-2-L Explanation 1A4CH 0001H illegal function number (=0 or >2) 1A4CH 0100H address area type illegal 1A4CH 0101H data block number illegal 1A4CH 0102H "number of the first data field word" illegal 1A4CH 0103H data block length entered in header < 5 words 1A4CH 0201H year specification in data field illegal 1A4CH 0202H month specification in data field illegal 1A4CH 0203H day of month specification in data field illegal 1A4CH 0204H weekday spec. in data field illegal 1A4CH 0205H hour specification in data field illegal 1A4CH 0206H minute specification in data field illegal 1A4CH 0207H second specification in data field illegal 1A4CH 0208H 1/100 seconds in data field not equal to 0 1A4CH 0209H data field word 3 / bits 0 to 3 not equal to 0 1A4CH 020AH hour format does not match setting in OB 151 CPU 928B Programming Guide C79000-B8576-C898-01 5 - 49 5 Errors in RUN and in RESTART Error identifiers of OB 151, OB 152 and OB 153 Table 5-26 LZF-other runtime errors/part 5 (identifiers of OB 151, OB 152 and OB 153) Error identifier ACCU-1-L ACCU-2-L Explanation OB 151 identifiers 1A4DH 0001H function number illegal (= 0 or > 2) 1A4DH 0100H address area type illegal 1A4DH 0101H data block number illegal 1A4DH 0102H number of the first data field word illegal 1A4DH 0103H data block length entered in header < 5 words 1A4DH 0201H year specification in data field illegal 1A4DH 0202H month specification in data field illegal 1A4DH 0203H day of month spec. in data field illegal 1A4DH 0204H weekday specification in data field illegal 1A4DH 0205H hour specification in data field illegal 1A4DH 0206H minute specification in data field illegal 1A4DH 0207H second specification in data field illegal 1A4DH 0208H 1/100 seconds in data field not equal to 0 1A4DH 0209H job type in data field illegal (> 7) 1A4DH 020AH OB 152 identifiers 1A4EH 0001H function no. illegal (not 0 to 3, or 8 or 15) OB 153 identifiers 1A4FH 0001H function no. illegal (=0 or <1) 1A4FH 0002H illegal delay time CPU 928B Programming Guide 5 - 50 C79000-B8576-C898-01 Errors in RUN and in RESTART Error identifiers of different system operations Table 5-27 LZF-other runtime errors/part 6 (identifiers of different system operations) Error identifier ACCU-1-L ACCU-2-L Explanation 1A50H -- LRW, TRW: the calculated memory address
not in range "0 - EDFFH" 1) 1A51H -- LRD, TRD: the calculated memory address
not in range "0 - EDFEH" 1) 5 1A52H -- TSG, LY GB, LW GW, TY GB, TW GW: the calculated linear address
not in range "0 - EFFFH" 1A53H -- LY GW, LW GD, TY GW, TW GD: the calculated linear address
not in range "0 - EFFEH" 1A54H -- LY GD, TY GD: the calculated linear address
not in range "0 - EFFCH" 1A55H -- TSC, LY CB, LW CW, TY CB, TW CW: the calculated page address
not in range "F400H - FBFFH" 1A56H -- LY CW, LW CD, TY CW, TW CD: the calculated page address
not in range "400H - FBFEH" 1A57H -- LY CD, TY CD: the calculated page address
not in range "F400H - FBFCH" CPU 928B Programming Guide C79000-B8576-C898-01 5 - 51 Errors in RUN and in RESTART Error identifier ACCU-1-L ACCU-2-L Explanation Table 5-27 continued: 1A58H -- TNW, TNB: the source field is not completely in one of the following ranges: 0000 .. 7FFF user memory 1) 8000 .. DD7F data block RAM DD80 .. E3FF DB 0 E400 .. E7FF S flags E800 .. EDFF system data (RI, RJ, RS, RT, C, T) EE00 .. EFFF flags, process image F000 .. FFFF peripherals 1A59H -- TNW, TNB: the destination field is not completely in one of the following ranges: 0000 .. 7FFF user memory 1) 8000 .. DD7F data block RAM DD80 .. E3FF DB 0 E400 .. E7FF S flags E800 .. EDFF system data (RI, RJ, RS, RT, C, T) EE00 .. EFFF flags, process image F000 .. FFFF peripherals 1) see Chap. 9 CPU 928B Programming Guide 5 - 52 C79000-B8576-C898-01 Errors in RUN and in RESTART 5.6.3 ADF (Addressing Error) OB 25 Error identifiers An addressing error occurs when a STEP 5 operation references a process image input or output to which no I/O module was assigned at the time of the last COLD RESTART (e.g. the module is not plugged in, it is defective or it is not defined in DB 1 of the CPU). The system program interrupts the execution of the user program and calls organization block OB 25. After executing the program in OB 25, the CPU continues with the next operation of the interrupted program. The STEP 5 statement that caused ADF was executed but with an undefined input or output value. If OB 25 is not programmed, the CPU goes into the STOP mode when the error occurs, unless you have specified in data block DX 0 that the program should continue. The address error monitoring can also be completely suppressed if you program DX 0 appropriately. The system program transfers the following as error identifiers: ACCU-1-L = 1E40H ACCU-2-L = ADF address 5.6.4 QVZ (Timeout Error) A timeout error occurs when an input or output module is addressed and does not respond with the ready signal (RDY) within a specific time. The cause of the timeout may be a defect on the I/O module or the module may have been unplugged from the PC during operation. The following timeout errors interrupt the user program, and call the appropriate organization blocks: QVZ during direct access via the S5 bus Timeout in the user program during direct access via the S5 bus to CP, IP, coordinator or to a peripheral module (e.g. with load and transfer operations L/T P... or O...): OB 23 The system program calls organization block OB 23, if it is loaded. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 53 5 Errors in RUN and in RESTART Error identifiers ACCUs 1 and 2 contain additional information that defines the error in greater detail. ACCU1-L = 1E23H ACCU2-L = QVZ address QVZ address The QVZ address indicates the first peripheral byte to generate a QVZ. Normally, this is the byte with the lowest address in peripheral operations. An exception to this are QVZ addresses supplied with the commands TNB/TNW in the event of a timeout. Since these operations are decremented, in this case the QVZ address indicates the byte with the highest address that triggered the QVZ during the transfer of data. Timeout error during the update of the process image for inputs/outputs and transfer of IPC flags: QVZ during PII update and transfer of the IPC flags OB 24 The system program calls organization block OB 24. ACCUs 1 and 2 contain additional information that defines the error in greater detail: Table 5-28 QVZ flags when calling OB 24 Error identifier ACCU-1-L ACCU-2-L Explanation 1E25H yyyyH Timeout outputting the process image of the digital outputs yyyy = address of the non-acknowledged output byte 1E26H yyyyH Timeout updating the process image of the digital inputs yyyy = address of the non-acknowledged input byte 1E27H yyyyH Timeout updating the IPC flag outputs yyyy = address of the non-acknowledged IPC flag byte 1E28H yyyyH Timeout updating the IPC flag inputs yyyy = address of the non-acknowledged IPC flag byte CPU 928B Programming Guide 5 - 54 C79000-B8576-C898-01 Errors in RUN and in RESTART Note If the organization blocks called are not programmed , the user program is continued . If a timeout occurs, the CPU reads in the substitute value "00H" and continues to work with this value if the QVZ is acknowledged. A timeout, however, increases the runtime of the STEP 5 operation that caused it. STOP in the case of QVZ If you want a timeout to cause the CPU to stop, you must program the stop operation STP in OB 23 or 24. You can also program DX 0 to cause a system stop in the event of a timeout without programming OB 23/24. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 55 5 Errors in RUN and in RESTART 5.6.5 ZYK (Cycle Time Exceeded Error) The cycle time includes the entire duration of cyclic program execution. The cycle monitoring time can be exceeded owing to a number of reasons: e.g. incorrect programming, a program loop in a function block, failure of the clock pulse generator or by system activities such as process image updating in conjunction with long programs. OB 26 When the cycle time exceeded error occurs, the system program interrupts the user program and calls organization block OB 26, if it is loaded. This retriggers the cycle time monitoring. If the monitoring time elapses again, before OB 26 has been completely processed, the CPU goes into the STOP mode owing to a double call error (DOPP-FE). Cycle monitoring time The cycle monitoring time is variable (1 to 13000 ms) and can be retriggered (see above). Regardless of the cycle time, 100 ms after the cycle time has elapsed, BASP is activated if OB 26 has not yet been completed. You can select the cycle monitoring time by means of an entry in DX 0 or by calling the special function organization block OB 221. In the cyclic program, the cycle time monitoring can be retriggered by calling the special function OB 222. STOP in the case of unloaded OB 26 If you do not program OB 26, the CPU changes to the STOP mode. If you do not want this to happen, you must change the default in DX 0. No error identifiers If a cycle time exceeded error occurs, no error identifiers are transferred to ACCU 1 or ACCU 2. CPU 928B Programming Guide 5 - 56 C79000-B8576-C898-01 Errors in RUN and in RESTART 5.6.6 WECK-FE (Collision of Time If a particular time interrupt OB is requested before its last request has been completely processed, the system program recognizes a collision Interrupts) of time interrupts and calls organization block OB 33 , if it is loaded, or the CPU goes to the STOP mode. See Section 4.5.2. ACCUs 1 and 2 contain additional information that defines the error in greater detail. Table 5-29 WECK-FE identifiers Error identifier ACCU-1-L ACCU-2-L 1001H 0016H Explanation Collision of time interrupts in OB 10 (10 ms) 0014H Collision of time interrupts in OB 11 (20 ms) 0012H Collision of time interrupts in OB 12 (50 ms) 0010H Collision of time interrupts in OB 13 (100 ms) 000EH Collision of time interrupts in OB 14 (200 ms) 000CH Collision of time interrupts in OB 15 (500 ms) 000AH Collision of time interrupts in OB 16 (1 sec) 0008H Collision of time interrupts in OB 17 (2 sec) 0006H Collision of time interrupts in OB 18 (5 sec) Note The identifier in ACCU 2 is the level identifier of the time interrupt that caused the error. If you do not program OB 33, the CPU goes into the stop mode. You can, however, program DX 0 so that the program is continued when a collision of time interrupts occurs although you have not programmed OB 33. A second call for the already active error program processing level "collision of time interrupts" does not lead to a double call error (DOPP). CPU 928B Programming Guide C79000-B8576-C898-01 5 - 57 5 Errors in RUN and in RESTART 5.6.7 REG-FE (Controller Error) An error occurring during the processing of the standard function block for controller structure R64 is detected as a controller error. Note While, for example, a collision of time interrupts is always recognized by the system program, when a particular time interrupt OB is not started and completed within a particular time interval (e.g. OB 13 within 100 ms), incorrect processing of the closed loop control program is only detected when the program processing level CL CONTROL is called . The error is then indicated in the ISTACK. OB 34 If a controller error occurs, the program processing level CL CONTROL is exited and the CONTROLLER ERROR (LEVEL: 001CH) level is called with organization block OB 34. The subsequent reaction of the CPU depends on how you have programmed OB 34: * If you have not programmed OB 34, the CPU goes into the STOP mode. You can see the cause of the error by displaying the ISTACK. * If you have programmed OB 34, the STEP 5 program it contains (e.g. evaluation of ACCU 1 and 2 and then appropriate error handling) is executed. Following this, the controller processing is continued from the point at which it was interrupted. Response to controller errors If you want to ignore all controller errors, simply write the block end statement BE in OB 34. If you want the controller processing to continue when a controller error occurs and you do not program OB 34, change the default in DX 0. CPU 928B Programming Guide 5 - 58 C79000-B8576-C898-01 Errors in RUN and in RESTART When OB 34 is called, ACCUs 1 and 2 contain additional information that defines the error in greater detail. Table 5-30 REG-FE identifiers Error identifier ACCU-1-LACCU-2-L Entry in the control bit screen form Explanation 0801H DByyH Sampling time error yy = number of controller data block involved 0802H DByyH Controller data block not loaded yy = number of the data block that is not loaded 0803H FByyH Controller function block not loaded yy = the number of the function block that is not loaded 0804H FByyH Controller function block not recognized yy = number of the non-recognized function block 0805H FByyH Controller function block loaded with incorrect PC software yy = function block number 0806H DByyH Wrong controller data block length yy = data block number 0880H 00yyH Timeout (QVZ) during the controller processing yy = number of the I/O byte that caused the timeout. In all seven situations, the error identifier R EG-FE is marked in the control bits on the programmer screen. If you operate a PG without the S5-DOS operating system, the last position in the lower line of the control bits screen is not labelled, but is also marked. In the ISTACK screen, the level CL CONTROL, R EG is marked as the cause of the interruption. CPU 928B Programming Guide C79000-B8576-C898-01 5 - 59 5 Errors in RUN and in RESTART Sampling time errors After the selected sampling time has elapsed, the cyclic program is stopped at the next block boundary and the controller processing is inserted. It is possible that the processing of longer blocks takes too long and that the controller processing becomes "out of step": this causes a sampling time error. You can handle a sampling time error just as the other controller errors (as described on the previous page) or you can suppress the error by means of a mask. In this case, program execution is not interrupted when a sampling time error occurs. Refer also to the description "compact closed loop control in the R processor of the S5 135U" in the R64 Controller Structure. You can sometimes prevent a sampling time error by changing the default in DX 0 "processing of controller and process interrupts at block boundaries" to "processing of controller and process interrupts at operation boundaries". 5.6.8 ABBR (Abort) If, during the RUN mode, the stop mode is requested by one of the following: * switching the mode selector on the CPU from RUN to STOP, * PG online function, PLC STOP, * reset switch on coordinator set to STOP (in multiprocessor operation), the system program calls OB 28, it is loaded. After OB 28 has been processed, the CPU goes into the STOP mode. Note The transition to the stop mode takes place regardless of whether you program OB 28 or not. No error identifiers No error identifiers are transferred to ACCU 1 or ACCU 2. CPU 928B Programming Guide 5 - 60 C79000-B8576-C898-01 Errors in RUN and in RESTART 5.6.9 Communication Errors (FE-3) If problems occur on the second serial interface with the computer link RK 517, data transfer with procedure 3964/3964R, data transfer with "open driver" or data transfer with SINEC L1, the system program calls organization block OB 35 and transfers additional information about the problems to ACCU 1. Response in the case of unloaded OB 35 If you do not program OB 35, the system program does not react and the CPU does not go into the stop mode. This is the default reaction. If you want the CPU to go into the stop mode when an interface error occurs and you do not program OB 35, you must change the default in DX 0. 5 Error information in ACCU 1 Every 100 ms the system program checks whether communication errors have occurred on the second serial interface. If an error is detected, the system program transfers the error information to ACCU 1 and ACCU 2. If you program OB 35, the system program calls it and transfers the error information in ACCU 1 and ACCU 2. Error numbers for a maximum of three causes of problems can be transferred when OB 35 is called. If there are more than three causes of problems at the same time, this is indicated by a special overflow identifier. Structure of the error information in ACCU 1 and ACCU 2 31 ACCU 1 0 24 23 0 0 0 F U B 0 18 15 Error number 1 8 7 Error number 2 0 Error number 3 F = '0', when there is no error entered in the error area = '1', when there is an error entered in the error area. U = '0', when there is no error overflow (maximum three entries) = `1`, when there is an error overflow (more than three entries) B = '0', when there is no BREAK on the interface = '1', when there is a BREAK on the interface CPU 928B Programming Guide C79000-B8576-C898-01 5 - 61 Errors in RUN and in RESTART BREAK If there is a BREAK on an interface, OB 35 is only called at the beginning and end of the BREAK status. Error numbers 1 to 3 Here, a maximum of three error numbers belonging to problems detected on the interface are entered in the order in which they are detected by the system. Meaning of the error numbers For the meaning of the error numbers and further information on handling interface errors, refer to the "CPU 928B Communication" Manual (/14/ in Chapter 13). CPU 928B Programming Guide 5 - 62 C79000-B8576-C898-01 Integrated Special Functions 6 Contents of Chapter 6 6.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6 6.2 OB 110: Accessing the Condition Code Byte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 6.3 OB 111: Clear ACCUs 1, 2, 3 and 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13 6.4 OB 112/113: Roll Up ACCU and Roll Down ACCU . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 6.5 OB 120: Enabling/Disabling of Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16 6.6 OB 121: Enable/Disable Individual Time-Driven Interrupts . . . . . . . . . . . . . . . . . . . . . . 6-19 6.7 OB 122: Enable/Disable "Delay of All Interrupts" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-22 6.8 OB 123: Enable/Disable "Delay of Individual Time-Driven Interrupts" . . . . . . . . . . . . . 6-25 6.9 Setting/Reading the System Time (OB 150) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28 6.10 OB 151: Setting/Reading the Time for Clock-Driven Interrupts . . . . . . . . . . . . . . . . . . 6-33 6.11 OB 152: Cycle Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-40 6.12 OB 153: Set/Read Time for Delayed Interrupt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-48 6.13 OB 160 to 163: Loop Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-51 6.14 OB 170: Read Block Stack (BSTACK) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-53 6.15 OB 180: Accessing Variable Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-58 6.16 OB 181: Testing Data Blocks (DB/DX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-62 CPU 928B Programming Guide C79000-B8576-C898-01 6-1 6 Contents 6.17 OB 182: Copying a Data Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-65 6.18 OB 190/OB 192: Transferring Flags to a Data Block . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-68 6.19 OB 191/OB 193: Transferring Data Fields to a Flag Area . . . . . . . . . . . . . . . . . . . . . . . 6-71 6.20 OB 200 to OB 205: Multiprocessor Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-77 6.21 OB 216 to OB 218: Page Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-78 6.21.1 6.21.2 6.21.3 6.21.4 What are pages? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How to access pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Address areas for peripherals on the S5 bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Notes on assigning parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 216: Writing to a Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 217: Reading from a Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 218: Reserving a Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.22 OB 220: Sign Extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-90 6.23 OB 221: Setting the Cycle Monitoring Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-91 6.24 OB 222: Restarting the Cycle Monitoring Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-92 6.25 OB 223: Comparing Restart Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-93 6.26 OB 224: Transferring Blocks of Interprocessor Communication Flags . . . . . . . . . . . . . 6-94 6.27 OB 226: Reading a Word from the System Program . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-95 6.28 OB 227: Reading the Checksum of the System Program . . . . . . . . . . . . . . . . . . . . . . . . 6-96 6.29 OB 228: Reading Status Information of a Program Processing Level . . . . . . . . . . . . . . 6-98 6.30 OB 230 to 237: Functions for Standard Function Blocks . . . . . . . . . . . . . . . . . . . . . . . 6-100 6.31 OB 240 to 242: Special Functions for Shift Registers . . . . . . . . . . . . . . . . . . . . . . . . . . 6-101 6.31.1 6.31.2 6.31.3 6.31.4 Shift Registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 240: Initializing Shift Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 241: Processing Shift Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 242: Deleting a Shift Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-78 6-79 6-80 6-81 6-82 6-84 6-86 6-88 6-101 6-105 6-108 6-109 CPU 928B Programming Guide 6-2 C79000-B8576-C898-01 Contents 6.32 OB 250/251: Closed-loop Control/ PID Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-110 6.32.1 6.32.2 6.32.3 6.32.4 Functional Description of the PID Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PID Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 250: Initializing the PID Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OB 251: Processing the PID Algorithm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Format of controller inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controller parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameter changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Abbreviations for PID controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Normalized fixed point numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.33 OB 254, OB 255: Transferring a Data Block to the DB RAM . . . . . . . . . . . . . . . . . . . 6-125 6-110 6-112 6-118 6-119 6-120 6-121 6-122 6-123 6-123 6-124 6 CPU 928B Programming Guide C79000-B8576-C898-01 6-3 Integrated Special Functions 6 This Chapter tells you which integral special functions the system program contains, where you can use these functions and how you must call and assign parameters to the special function OBs. In addition, you will learn how to detect errors in processing a special function and how do deal with these in the program. 6 CPU 928B Programming Guide C79000-B8576-C898-01 6-5 Introduction 6.1 Introduction The CPU 928B operating system provides you with a number of special functions, that you can call with a conditional (JC OBx) or unconditional (JU OBx) block call. Organization blocks OB 40 to OB 255 are reserved for these special functions. These functions are known as integrated special functions, since they are a fixed part of the system program. You can call these special functions, you cannot, however, read or modify them. The table below gives you an overview of the special functions available. Table 6-1 Overview of the special functions available with the CPU 928B Block Function see section / p age OB 110 OB 111 OB 112 OB 113 Access to the condition code byte Clear ACCU 1, 2, 3 and 4 Roll up ACCU Roll down ACCU 6.2/ 6 - 11 6.3/ 6 - 13 6.6/ 6 - 14 " OB 120 OB 121 OB 122 OB 123 "Disable all interrupts" on/off "Disable single time interrupts" on/off "Delay all interrupts" on/off "Delay single time interrupts" on/off 6.5/ 6 - 16 6.6/ 6 - 19 6.7/ 6 - 22 6.8/ 6 - 25 OB 150 OB 151 Set/read the system time Set/read time for clock-driven time interrupt 6.9/ 6 - 28 6.10/ 6 - 33 OB 152 Read out cycle time 6.11/ 6 - 40 OB 153 Set/read time for delay interrupt (from Version -3UB12) 6.12/ 6 - 48 OB 160 to 163 Loop counter 6.13/ 6 - 51 OB 170 Read block stack (BSTACK) 6.14/ 6 - 53 OB 180 OB 181 OB 182 Variable data block access Test data block (DB/DX) Copy data area 6.15/ 6 - 58 6.16 / 6 - 62 6.17/ 6 - 65 OB 190, 192 OB 191, 193 Transfer flags to data blocks Transfer data fields to flag area 6.18/ 6 - 68 6.19/ 6 - 71 OB 2001), 2021) Functions for multiprocessor communication OB 203, 2041), 205 6.20/ 6 - 77 OB 216 to 218 6.21/ 6 - 78 Accessing pages CPU 928B Programming Guide 6-6 C79000-B8576-C898-01 Introduction Block Function see section / p age OB 220 Sign extension 6.22/6 - 90 OB 221 2) OB 222 OB 223 OB 224 2) OB 226 OB 227 OB 228 Set the cycle monitoring time Restart the cycle monitoring time Compare restart types in multiprocessor operation Transfer a block of IPC flags in multiprocessor operation Read a word from the system program Read the checksum of the system program Read status information of a program processing level 6.23/6 - 91 6.24/6 - 92 6.25/6 - 93 6.26/6 - 94 6.27/6 - 95 6.28/6 - 96 6.29/6 - 98 OB 230 to 2371) Functions for standard function blocks 6.30/6 - 100 OB 240 OB 241 OB 242 Initialize shift register Process shift register Clear shift register 6.31.2/6 - 105 6.31.3/6 - 108 6.31.4/6 - 109 OB 2501) OB 2511) Initialize PID controller Process PID controller 6.32.3/6 - 118 6.32.4/6 - 119 Copy/duplicate a DB or DX data block 6.33/6 - 125 Table 6-1 continued: OB 254, 255 1) 1) Special functions with pseudo operation boundaries (executed in several steps) 2) Instead of these special function organization blocks, assign parameters in data block DX 0 (see Chapter 7). 6 CPU 928B Programming Guide C79000-B8576-C898-01 6-7 Introduction Interfaces The following operations and parameters are available as interfaces when programming the use of special functions: Block call * Conditional/unconditional block call JC ... / JU ... Parameters * Parameters for selecting presets using ACCU 1 and possibly ACCU 2 and/or memory registers. In this description, the term parameters refers to all data that the CPU needs to carry out the special functions correctly. Before you call these special functions in your STEP 5 program, you must load this data into the accumulators or into the memory registers as indicated. ACCU abbreviations The abbreviations used in reference to the parameter assignment of special function OBs are as follows: ACCU 1: ACCU 1, 32 bits ACCU-1-L: ACCU 1, low word, 16 bits ACCU-1-LL: ACCU 1, low word, low byte, 8 bits ACCU-1-LH : ACCU 1, low word, high byte, 8 bits High word High byte 31 Low word Low byte 24 23 High byte 16 15 Low byte 8 7 0 CPU 928B Programming Guide 6-8 C79000-B8576-C898-01 Introduction Errors during special function processing If an error occurs during the processing of the special functions, the system program reacts in a specific manner. In terms of the system program reaction to errors, the special functions can be divided into two groups. Error OB, ACCU identifiers Group 1 includes all the special functions for which an error organization block (error OB) is called in the event of an error. You can program the CPUs reaction in these error OBs. These error OBs are OB 19, OB 30 and OB 31. In ACCU 1 and for some special functions also in ACCU 2 (see Section 5.6.1 and 5.6.2), identifiers are transferred to the error OB that define the error in greater detail. If the CPU encounters for example an incorrect parameter when processing one of these special functions, it detects a runtime error and calls OB 31. On the other hand, if for example the called special function does not exist, the CPU detects an operation code error and attempts to call OB 30. With some of these special functions, if there is a reference to a data block in the call parameters and the data block is not loaded, then the CPU attempts to call OB 19. If the error OBs 30 or 31 are not loaded or contain an STP operation, the CPU goes into the stop mode. LZF or BCF is marked in the control bits in the ISTACK. The accumulators of the error processing levels contain error identifiers that describe the error in greater detail. If OB 19, OB 30 or OB 31 is loaded (and does not contain an STP operation), the user program is continued at the next operation after the OB has been processed. In this case, the accumulators remain unchanged. CPU 928B Programming Guide C79000-B8576-C898-01 6-9 6 Introduction RLO, CC 0/CC 1 In connection with some of the special functions, errors specific to the special function affect the condition codes CC 0/CC 1. If an error occurs during the processing of these special functions, the RLO is normally set (RLO = 1). When using these special functions, you can use a JC operation (conditional jump) in your STEP 5 program to evaluate the RLO and to react to an error. The processing of some special functions also affects the condition codes CC 0 and CC 1. In your STEP 5 program, you can scan these condition codes with comparison operations and once again react to an error. The following descriptions of the individual special function OBs indicate which of these reactions apply to the particular special function OB. Note Calling a special function OB with the operation JC OB > 39 or JU OB > 39 is not a "genuine" block change, but is handled like a STEP 5 operation without a block operand. No interrupts are inserted (when "interrupts at block boundaries" is set). Special functions with pseudo operation boundaries Some of the special functions are carried out in several steps and contain what are known as pseudo operation boundaries. This means that the special function is executed in several steps. If an error (e.g. ZYK) or an interrupt (e.g. time or process interrupt at operation boundaries) occurs during the execution of a step, the appropriate organization block is inserted at the end of this step at the pseudo operation boundary. The special functions containing pseudo operation boundaries are marked in the overview of the integrated special functions. CPU 928B Programming Guide 6 - 10 C79000-B8576-C898-01 OB 110: Accessing the Condition Code Byte 6.2 OB 110: Accessing the Condition Code Byte Function Using the special function organization block OB 110, you can write the contents of ACCU 1 to the condition code register, or mask it with "1" or "0". Assignment of ACCU 1 for access to the condition code register 31 *) 7 6 5 4 3 2 C1 C0 OV OS OR STA W ord displays 1 0 RLO ERAB Bit displays *) Bits 8 to 31 are reserved for extensions and must be "0" when the condition code register is written to. They must also be ignored when reading out the condition code register. Parameters 1. ACCU-2-L: Function number possible values: 2. ACCU 1 1, 2 or 3 : New condition code byte or mask Function no. in ACCU-2-L Contents of ACCU-1-L Function before after 1 New condition code byte New condition code byte The contents of ACCU 1 are loaded in the condition code register. 2 Mask New condition code byte All the bits indicated as "1" in the mask in ACCU 1 are set to "1" in the condition code register. The new condition code byte is loaded in ACCU 1. New condition code byte All the bits indicated as "1" in the mask in ACCU 1 are set to "0" in the condition code register. The new condition code byte is loaded in ACCU 1. 1) 3 Mask 1) 1) Restriction: OB 110 itself affects the condition code bits. It sets: OR = 0, STA = 1 and ERAB = 0, regardless of the value specified for these bits in ACCU 1 before the OB was called. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 11 6 OB 110: Accessing the Condition Code Byte Result After execution of OB 110, the condition code byte will have been changed in accordance with the function and the contents of ACCU-1. Possible errors * Function number in ACCU-2-L not equal to 1, 2 or 3. * One of the bits no. 8 to no. 31 is set in ACCU 1. If an error occurs, OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, the error identifier 1A49H is entered in ACCU-1-L. Example With OB 110, you can test the operations that evaluate or affect the condition code register. Its application is, however, not restricted to the operation test. The following example shows you a further possible application. Call distributor One of four subroutines is to be called depending on the contents of flag byte FY 0. The four subroutines are assigned to bits F 0.0 to F 0.3. Only one of these bits can be set at any one time. M000 M001 M002 M003 :L FY0 :SLW 4 :L KB1 :TAK :JU OB110 :JS =M000 :JO =M001 :JM =M002 :JP =M003 : : : :BEU : : : :BEU : : : : : :BEU : : :BEU ;shift F 0.0 to F 0.3 four bits to the left ;load the function number ;jump ;jump ;jump ;jump if if if if OS OV CC CC = = 0 1 1 1 = 1 = 1 ;if no bit is set ;if F 0.0 = 1 ;if F 0.1 = 1 ;if F 0.2 = 1 ;if F 0.3 = 1 CPU 928B Programming Guide 6 - 12 C79000-B8576-C898-01 OB 111: Clear ACCUs 1, 2, 3 and 4 6.3 OB 111: Clear ACCUs 1, 2, 3 and 4 Function Calling special function organization block OB 111 is a simple way of clearing ACCUs 1 to 4. OB 111 overwrites all four registers with "0". Parameters none Result Accus 1 to 4 (32 bits each) are deleted. Possible errors none 6 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 13 OB 112/113: Roll Up ACCU and Roll Down ACCU 6.4 OB 112/113: Roll Up ACCU and Roll Down ACCU Function OBs 112 and 113 roll the contents of the ACCUs either up or down. * OB 112 (roll up) shifts the contents of ACCU 1 to ACCU 2, the contents of ACCU 2 to ACCU 3 etc. * OB 113 (roll down) shifts the contents of the ACCUs in the opposite direction; the contents of ACCU 1 to ACCU 4, ACCU 4 to ACCU 3 etc. Parameters none Result Figures 6-1 and 6-2 show the contents of the ACCUs before and after calling OB 112 and OB 113. Note You can also shift the contents of the ACCUs using the STEP 5 operations ENT (supplementary operation set) and TAK (system operation) (see Section 3.4.3.). Possible errors none CPU 928B Programming Guide 6 - 14 C79000-B8576-C898-01 OB 112/113: Roll Up ACCU and Roll Down ACCU roll ACCU contents 31 0 31 0 ACCU 4 ACCU 3 OB 112 ACCU 2 ACCU 1 before Fig. 6-1 after 6 Effects of the "roll up" function roll ACCU contents 31 0 31 0 ACCU 4 ACCU 3 OB 113 ACCU 2 ACCU 1 before Fig. 6-2 after Effects of the "roll down" function CPU 928B Programming Guide C79000-B8576-C898-01 6 - 15 OB 120: Enabling/Disabling of Interrupts 6.5 OB 120: Enabling/Disabling of Interrupts A STEP 5 program can be interrupted at block or operation boundaries by programs with a higher priority. These higher priority program processing levels include the process and all time interrupts (cyclic time interrupts, clock-driven time interrupt and delay interrupt). The runtime of the interrupted program is therefore extended by the runtime of the programs inserted by the interrupts. Using special function organization blocks OB 120, you can prevent the insertion of higher priority program processing levels at one or more consecutive block or operation boundaries (depending on the setting in DX 0). Function The special function organization OB 120 affects the reaction to interrupts: Disabling interrupts means that no more interrupts are recognized and the interrupts that have already been detected (e.g. they are waiting for a block boundary) are cleared. If OB 2 (process interrupts) or an OB for time-driven interrupt processing have already started, they are processed to the end. En abling interrupts means that all interrupts are once again recognized immediately, and are inserted and processed at the next block or operation boundary. Parameters 1. Double control word OB 120 records the interrupts to be disabled or delayed in a system-internal double control word . Bit no. 31 3 2 1 0 Double control word CPU 928B Programming Guide 6 - 16 C79000-B8576-C898-01 OB 120: Enabling/Disabling of Interrupts The bits of the double control word are assigned as follows: Control word bit no. Function 0 = '1' all time-driven interrupts in fixed interval delayed 1 = '1' the clock-driven time interrupt is disabled 2 = '1' all process interrupts are disabled 3 = '1' the delay interrupt is disabled 4 to 31 reserved; these bits must be "0"! 2. Accus 2a) ACCU-2-L Function No. Permissible values 6 1,2 or 3 with: 1: The contents of ACCU 1 are loaded in the control word. 2: All the bits in the mask in ACCU 1 marked with a '1' are set to '1' in the control word. The new control word is loaded in ACCU 1. 3: All the bits in the mask in ACCU 1 marked with '1' are set to '0' in the control word. The new control word is loaded in ACCU 1. 2b) ACCU1 New control word or mask, depending on the desired function CPU 928B Programming Guide C79000-B8576-C898-01 6 - 17 OB 120: Enabling/Disabling of Interrupts Result Possible errors Calling OB 120 has the following results: Function no. in ACCU-2-L Contents of ACCU 1 before after 1 Control word Control word 2 Mask New control word 3 Mask New control word * Illegal function number in ACCU-2-L * One of the reserved bits in ACCU 1 (no. 3 to 31) is set to "1". In the event of an error, OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, an error ID is entered in ACCU-1-L. Notes * You can scan the status of a control word with the following program sequence: 1. Load the function number 2 or 3 in ACCU-2-L 2. Load the value '0' in ACCU 1 3. Call special function OB 120 4. Read out ACCU 1 * You can determine the status of interrupt processing by reading out system data word RS 131. - RS 131 Condition codeword "disable all interrupts" * Instead of OB 120, you can use the operations IA and RA to disable and enable process interrupts as follows: IA corresponds to :L :L :JU KB 2 KM 00000000 00000100 OB 120 RA corresponds to :L :L :JU KB 3 KM 00000000 00000100 OB 120 CPU 928B Programming Guide 6 - 18 C79000-B8576-C898-01 OB 121: Enable/Disable Individual Time-Driven Interrupts 6.6 OB 121: Enable/Disable Individual Time-Driven Interrupts Using the special function organization block OB 121, you can prevent the insertion of certain time-driven OBs (time-driven interrupts with a fixed time interv al ) at one or more consecutive block or operation boundaries. You can, for example, prevent a particular program section being interrupted by an OB 18 (5 s) and an OB 17 (2 s). On the other hand, all other programmed time-driven interrupts are processed as usual. Function The special function organization OB 121 affects the reaction to time-driven interrupts: Disabling individual time-driven interrupts means that no more of the specified time-driven interrupts are recognized and the interrupts that have already been detected (e.g. they are waiting for a block boundary) are cleared. If OB 2 (process interrupts) or an OB for time-driven interrupt processing (for processing a time-driven interrupt at a fixed time interval) have already started, they are processed to the end. En abling individual time-driven interrupts means that all interrupts are once again recognized immediately, and are inserted and processed at the next block or operation boundary. Parameters 1. Control word OBs 121 records the time-driven interrupts to be disabled or delayed in a control word: Bit no.: 15 3 2 1 0 Control word CPU 928B Programming Guide C79000-B8576-C898-01 6 - 19 6 OB 121: Enable/Disable Individual Time-Driven Interrupts The bits of the control word are assigned as follows: Bit no. 0 to 2 Interrupt Reserved; these bits must be "0"! 3 = '1' 4 = `1` 5 = '1' 6 = '1' 7 = '1' 8 = '1' 9 = '1' 10 = '1' 11 = '1' Time-driven interrupt with fixed time intervals: 10 ms (OB 10) 20 ms (OB 11) 50 ms (OB 12) 100 ms (OB 13) 200 ms (OB 14) 500 ms (OB 15) 1 sec (OB 16) 2 sec (OB 17) 5 sec (OB 18) 12 to 15 Reserved; these bits must be "0"! 2. Accus 2a) ACCU-2-L Function No. Permissible values: 1, 2 or 3 with: 1: The contents of ACCU 1 are loaded in the control word. 2: All the bits in the mask in ACCU 1 marked with a '1' are set to '1' in the control word. The new control word is loaded in ACCU 1. 3: All the bits in the mask in ACCU 1 marked with '1' are set to '0' in the control word. The new control word is loaded in ACCU 1. 2b) ACCU 1 New control word or mask, depending on the desired function CPU 928B Programming Guide 6 - 20 C79000-B8576-C898-01 OB 121: Enable/Disable Individual Time-Driven Interrupts Possible errors: * Illegal function number in ACCU-2-L * One of the reserved bits in ACCU 1 is set to "1". In the event of an error, OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, an error ID is entered in ACCU-1-L. Notes * You can scan the status of a control word with the following program sequence: 1. Load the function number 2 or 3 in ACCU-2-L 2. Load the value "0" in ACCU 1 3. Call special function OB 121 4. Read out ACCU 1 6 You can determine the status of the time-driven interrupt processing by reading out system data word RS 135. - RS 135 Condition codeword "disable individual interrupts" CPU 928B Programming Guide C79000-B8576-C898-01 6 - 21 OB 122: Enable/Disable "Delay of All Interrupts" 6.7 OB 122: Enable/Disable "Delay of All Interrupts" A STEP 5 program can be interrupted at block or operations boundaries by a higher-priority program. Such higher-priority program processing levels include the process interrupts and all time interrupts (cyclic time interrupts, clock-driven time interrupt and delay interrupt). The runtime of the interrupted program is therefore extended by the runtime of the programs inserted by the interrupts. Using special function block OB 122, you can prevent the insertion of higher priority program processing levels at one or more consecutive block or operation boundaries (depending on the setting in DX 0). Function OB 122 affects the reaction to interrupts as follows: En abling interrupt delay means all interrupts will continue to be registered and already pending interrupts will remain registered. However, registered interrupts will not yet be processed. All operation or block boundaries will be temporarily disabled for the processing interrupts. If OB 2 (process interrupts) or an OB for time-driven interrupt processing have already started, they are processed to the end. Disabling interrupt delay means all registered interrupts will be inserted and processed at the next block or operation boundary. Note If a specific time-driven interrupt OB is called for the second time during the "Delay interrupt" phase, a collision of time interrupts occurs. Parameters 1. Double control word OB 122 records the interrupts to be delayed in a system-internal double control word. Bit no.: 31 3 2 1 0 Double control word CPU 928B Programming Guide 6 - 22 C79000-B8576-C898-01 OB 122: Enable/Disable "Delay of All Interrupts" The bits of the double control word are assigned as follows: Control word bit no. Function 0 = '1' all time-driven interrupts in fixed interval are delayed 1 = '1' the clock-driven time interrupt is delayed 2 = '1' all process interrupts are delayed 3 = '1' the delay interrupt is delayed 4 to 31 reserved; these bits must be "0"! 6 2. Accus 2a) ACCU-2-L Function No. Permissible values: 1, 2 or 3 with: 1: The contents of ACCU 1 are loaded in the control word. 2: All the bits in the mask in ACCU 1 marked with " 1" are set to "1". The new control word is loaded in ACCU 1. 3: All the bits in the mask in ACCU 1 marked with " 0" are set to "1" in the control word. The new control word is loaded in ACCU 1. 2b) ACCU 1 New control word or mask depending on the desired function. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 23 OB 122: Enable/Disable "Delay of All Interrupts" Result Possible errors Calling OB 122 has the following results: Function no. in ACCU-2-L Contents of ACCU 1 before after 1 Control word Control word 2 Mask New control word 3 Mask New control word * Illegal function number in ACCU-2-L * One of the reserved bits in ACCU 1 (no. 4 to 31) is set to "1". In the event of error, OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, the error ID 1A48 H is entered in ACCU-1-L. Notes * You can scan the status of the control work with the following program sequence: 1. Load the function number 2 or 3 in ACCU-2-L 2. Load the value "0" in ACCU 1 3. Call special function OB 122 4. Read out ACCU 1 * You can determine the status of interrupt processing by reading out system data word RS 132. - RS 132 Condition code word "delay all interrupts" CPU 928B Programming Guide 6 - 24 C79000-B8576-C898-01 OB 123: Enable/Disable "Delay of Individual Time-Driven Interrupts" 6.8 OB 123: Enable/Disable "Delay of Individual Time-Driven Interrupts" Using special function organization block OB 123, you can prevent the insertion of certain time-driven OBs (time-driven interrupts with a fixed time interval) at one or more consecutive block or operation boundaries. Function OB 123 affects the reaction to time-driven interrupts as follows: Disabling delay of individual time-driven interrupts means all interrupts will continue to be registered and already pending interrupts will remain registered. However, registered interrupts will not yet be processed. All operation or block boundaries will be temporarily disabled for the processing interrupts. If a time interrupt OB (for processing a time interrupt with a fixed time base) has already been started, it is processed to the end. Disabling delay of individual time-driven interrupts means that with immediate effect, all cyclic time-driven interrupts will again be registered, inserted at the next block or operation boundary (depending on the setting in DX 0) and processed. Note If a specific time-driven interrupt OB is called for the second time during the "Delay interrupt" phase, a collision of time interrupts occurs. Parameters 1. Control word OB 123 records the interrupts to be disabled in a system-internal control word. Bit no.: 15 3 2 1 0 Control word CPU 928B Programming Guide C79000-B8576-C898-01 6 - 25 6 OB 123: Enable/Disable "Delay of Individual Time-Driven Interrupts" The bits of the control word are assigned as follows: Bit no. 0 to 2 Interrupt Reserved; these bits must be "0"! 3 = '1' 4 = `1` 5 = '1' 6 = '1' 7 = '1' 8 = '1' 9 = '1' 10 = '1' 11 = '1' Time-driven interrupt with fixed time intervals: 10 ms (OB 10) 20 ms (OB 11) 50 ms (OB 12) 100 ms (OB 13) 200 ms (OB 14) 500 ms (OB 15) 1 sec (OB 16) 2 sec (OB 17) 5 sec (OB 18) 12 to 15 Reserved; these bits must be "0"! 2. Accus 2a) ACCU-2-L Function No. Permissible values: 1, 2 or 3 with: 1: The contents of ACCU 1 are loaded in the control word 2: All the bits in the mask in ACCU 1 marked with " 1" are set to "1". The new control word is loaded in ACCU 1. 3: All the bits in the mask in ACCU 1 marked with " 0" are set to "1" in the control word. The new control word is loaded in ACCU 1. 2b) ACCU 1 New control word or mask depending on the desired function. CPU 928B Programming Guide 6 - 26 C79000-B8576-C898-01 OB 123: Enable/Disable "Delay of Individual Time-Driven Interrupts" Possible errors * Illegal function number in ACCU-2-L * One of the reserved bits in ACCU 1 (no. 4 to 31) is set to '1' In the event of error, OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, the error ID 1A4B H is entered in ACCU-1-L. Notes * You can scan the status of the control word with the following program sequence: 1. Load the function number 2 or 3 in ACCU-2-L 2. Load the value '0' in ACCU 1 3. Call special function OB 123 4. Read out ACCU 1 * You can determine the status of interrupt processing by reading out system data word RS 137. - RS 137 Condition code word "delay individual time-driven interrupts" CPU 928B Programming Guide C79000-B8576-C898-01 6 - 27 6 Setting/Reading the System Time (OB 150) 6.9 Setting/Reading the System Time (OB 150) Characteristics of the system time * The resolution is 10 ms for reading and 1 sec for setting. * Leap years are taken into account. * You can select between a 24 hour clock and a 12 hour clock, "am" (midnight to twelve o'clock), and "pm" (twelve o'clock to midnight), * The weekday can be specified * Input and output in BCD. * The integral hardware clock for the system time is backed up by the battery in the PLC rack. If you have set the system time, it also remains correct following a power down and WARM RESTART. Function Using OB 150, you can set or read the date and time of the CPU 928B in your user program. The date and time are known as the "system time". Note Before you can read out the system time, it must first be set. Parameters 1. Data Field for the Time Parameters When you set the system time, OB 150 takes the system time from a data field, when you read the system time, OB 150 transfers the current data to the data field. You can set up this data field in a data block or in one of the two fla g areas (F or S flags). The data field consists of four words. 1a) Format of the data field for setting the hardware clock Bit no. 15 1st word 2nd word 12 11 8 7 Seconds Format Day of month 4th word Year 3 0 0 Hours 3rd word 4 Minutes Weekday 0 Month CPU 928B Programming Guide 6 - 28 C79000-B8576-C898-01 Setting/Reading the System Time (OB 150) 1b) Format of the data field when readin g the hardware clock Bit no. 15 11 8 Seconds 1st word 2nd word 12 Format 7 4 3 0 1/100th second Hours 3rd word Day of month 4th word Year Minutes Weekday 0 Month The time parameters have the following meaning, permitted range of values and representation: 1) Data field in the flag area Parameter Permitted range of values Representation Seconds 1/100 seconds Minutes Hours Weekday Day of month1) Month Year 00 to 59 00 to 99 00 to 59 00 to 23 or 01 to 12 depending on selected format 0 to 6 where Mo = 0,..., Su = 6 01 to 31 1) 01 to 12 00 to 99 BCD format Format The format for the hour field is as follows: Bit 15 = 1: 24 hour format (bit 14 = 0) Bit 15 = 0: 12 hour format (select "am" or "pm" in bit 14) Bit 14 = 0: "am" Bit 14 = 1: "pm" -- 6 The value you input is checked to ensure that the date is logically correct taking into account leap years after OB 150 is called. If you set up the data field in a flag area, you must take into account the following assignment of data field words to flag bytes. "x" is the parameter "number of the first data field word" (see following page) that you must enter in ACCU-1-L when OB 150 is called. Bit no. 1st data field word 2nd data field word 3rd data field word 4th data field word 15 8 7 flag byte x flag byte x+1 flag byte x+2 flag byte x+3 0 flag byte x+4 flag byte x+5 flag byte x+6 flag byte x+7 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 29 Setting/Reading the System Time (OB 150) 2. Accus 2a) ACCU-2-L ACCU-2-L contains information on the desired function and the data field used. It must have the following structure: Bit no. 15 Function no. 12 11 Address area type Function number, permitted values: Address area type, permitted values: 8 7 0 Data block no. 1 = set system time 2 = Read system time 1 = DB data block 2 = DX data block 3 = F flag area 4 = S flag area Data block number, permitted values: 3 to 255 (only for address area type 1 or 2; irrelevant for address area types 3 or 4) 2b) ACCU-1-L Number of the 1st data field word, possible value (dependent on the address area type): DB, DX: 0 to 2044 F flags : 0 to 248 (= no. of flag byte 'x') S flags : 0 to 1016 (= no. of flag 'x') Result After OB 150 has been processed correctly, the condition code bits OR, ERAB and OS = 0. All other condition code bits and ACCUs 1 and 2 remain unchanged. Possible errors: In the event of an error, OB 19 or OB 31 is called. If OB 19 or OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU 1 and ACCU 2 (see following table). CPU 928B Programming Guide 6 - 30 C79000-B8576-C898-01 Setting/Reading the System Time (OB 150) Table 6-2 OB 150 error IDs ACCU-1-L ACCU-2-L 1A07H - 1A4CH 0001H 0100H 0101H 0102H 0103H 0201H 0202H 0203H 0204H 0205H 0206H 0207H 0208H 0209H 020AH Cause of error OB called Data block not loaded OB 19 Function no. = 0 or > 2 Address area type illegal Data block number illegal "Number of the first data field word" illegal Data block length in block header < 5 words Year specified in data field illegal Month specified in data field illegal Day of month specified in data field illegal Weekday specified in data field illegal Hour specified in data field illegal Minute specified in data field illegal Second specified in data field illegal 1/100 second in data field not equal to 0 Data field word 3 / bit no. 0 to 3 0 Hour format not the same as setting in OB 151 OB 31 6 Note If you select incorrect parameters when setting the system time, and if the time has been set correctly at least once, the error IDs are transferred, however, the previously set system time is retained. Example "Setting the time" You want to set the system time as follows: "Thurs, 24.11.1991, 11:30, 0 seconds, 24 hour format" It is assumed that the time parameters DB 10 from data word DW 0 onwards. The accurate to the second by triggering a e.g. I 1.0 - button in the vicinity of will be stored in data block system time should be set process interrupt (trigger bit, the PLC). First, program data block DB 10 with the following values and load it in the PLC. You must include the STEP 5 operations for calling OB 150 in OB 1 in such a way that the operations for calling OB 151 are only executed in the case of a rising edge of the trigger bit: Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 6 - 31 Setting/Reading the System Time (OB 150) (continued) "Setting the time": DB 10 0: KH= 0 0 0 0 left byte = seconds (BCD), right byte = 0 1: KH= 9 1 3 0 91 30 2: KH= 2 4 3 0 24 30 3: KH= 9 1 1 0 93 10 = format (=80H) + hour (= 11 BCD) minutes (BCD) = day of the month (BCD) = day of week (3 = Thursday) + bit 0 to bit 3 = 0 = year (BCD) = month (BCD) The STEP 5 operations in OB 1 for calling for OB 150 are as follows: : STELL:L KH1 1 0 A : : : :L KF +0 : :JU OB 150 : Signal edge of the input for setting the system time has occurred Values for ACCU-2-L: Address area type = 1 for "data field in DB" Function number = 1 for "set" ACCU-1-L: Number of the 1st data field word = 0 Call OB 150 "Reading the system time": You want to write the current system time to data block DB 10 from data word DW 4. You must therefore call OB 150 with the following parameters: : :L KH 2 1 0 A : : : : :L KF +4 : :JU OB 150 :C DB 10 : Values for ACCU-2-L: DB no. = 10 Address area type = 1 for "data field in DB" Function no. = 2 for "read" ACCU-1-L Number of 1st data field word = 4 Call OB 150 Open DB 10 Evaluate DB 10 After calling OB 150, the actual system time is stored in the following form in the data block DB 10 ("Thurs, 24.10.93, 11:30, 20 seconds, 13 hundredths, 24 hour format"): DW 4: KH= 2 0 1 3 DW 5: KH= 9 1 3 0 DW 6: KH= 2 4 3 0 DW 7: KH= 9 1 1 0 Seconds = 20 (BCD) 1/100 seconds = 13 (BCD) Format = 24 hour (bits 14/15 = 01), hours = 11 (BCD), Minutes = 30 (BCD) Day of month = 24 (BCD) Day of week = 3 = Thursday Year = 93 (BCD) Month = 10 (BCD) CPU 928B Programming Guide 6 - 32 C79000-B8576-C898-01 OB 151: Setting/Reading the Time for Clock-Driven Interrupts 6.10 OB 151: Setting/Reading the Time for Clock-Driven Interrupts Function By calling OB 151 you can perform the following: * program the CPU 928B, to activate the clock-driven time interrupt ("Time job" - OB 9, see Section 4.5.2) at a preset time : - every minute - every hour - every day - every week - every month - every year - once * read out the current status of a timed job * cancel a previously generated timed job 6 You can call OB 151 in the modes RESTART and RUN. Once generated, a clock-controlled time interrupt is retained following a WARM RESTART (automatic or manual). A COLD RESTART clears an existing timed job. If you generate a new timed job, a currently programmed timed job is automatically cancelled. This means that only one clock-controlled time interrupt can be active. Parameters 1. Data Field for Job Parameters When you generate or cancel a timed job, OB 151 takes the required job parameters from a data field. When you read out the current status of a timed job, OB 151 transfers the current job parameters to a data field. You can set up this data field in a data block or in one of the two flag areas (F or S flags). The data field consists of four words and has the following format for both generating and reading out a timed job: Bit no. 15 1st word 2nd word 12 11 8 7 Seconds Format Day of month 4th word Year 3 0 0 Hours 3rd word 4 Minutes Weekday Job type Month CPU 928B Programming Guide C79000-B8576-C898-01 6 - 33 OB 151: Setting/Reading the Time for Clock-Driven Interrupts The parameters have the following meanings, permissible value ranges and representations: Parameter Permissible range of values Job type 0 to 7 where: 0 = cancel job or no job active 1 = every minute 2 = every hour 3 = every day 4 = every week 5 = every month 6 = every year 7 = once BCD format Seconds 1/100 second Minutes Hours 00 to 59 00 to 99 00 to 59 00 to 23 or 01 to 12 depending on the selected format 0 to 6 where Mo = 0,..., Su = 6 01 to 31 1) BCD format Weekday Day of month1) Month Year Format Data field in the flag area 2) Representation 01 to 12 00 to 99 -- The format of the hour field is as follows: Bit 15 = 1: 24 hour format (bit 14 = 0) Bit 15 = 0: 12 hour format (select "am" or "pm" in bit 14) Bit 14 = 0: "am" Bit 14 = 1: "pm" 1) After calling OB 150, the value specified is checked to ensure it is logically correct taking into account leap years. 2) For the significance of "am" and "pm", see OB 150 in the previous section: "Format" must agree with the format set for the system time in OB 150. When you set up the data field in a flag area, you must take into account the following assignment of the data field words to the flag bytes. "x" is the parameter "number of the first data field word" that you must enter in ACCU-1-L when OB 151 is called. Bit no. 1st data field word 2nd data field word 3rd data field word 4th data field word 15 8 7 flag byte x flag byte x+1 flag byte x+2 flag byte x+3 0 flag byte x+4 flag byte x+5 flag byte x+6 flag byte x+7 CPU 928B Programming Guide 6 - 34 C79000-B8576-C898-01 OB 151: Setting/Reading the Time for Clock-Driven Interrupts 2. Accus 2a) ACCU-2-L ACCU-2-L contains information on the desired function and the data field used. It must have the following structure: Bit no. 15 Function no. 12 11 8 7 Address area type 0 Data block no. Parameters in ACCU-2-L Function number, permitted values: Address area type, permitted values: 1 = generate job 2 = read job 1 = DB data block 2 = DX data block 3 = F flag area 4 = S flag area 6 Data block number, permitted values: 3 to 255 (for address area type = 1 or 2; irrelevant for address area type 3 or 4 2b) ACCU-1-L Number of the 1st data field word, possible values (dependent on the address area type): DB, DX: 0 to 2044 F flags: S flags: 0 to 248 (= no. of flag byte 'x') 0 to 1016 (= no. of flag byte 'x') Note It is pointless to generate a timed job cyclically (e.g. by means of an unconditional OB 151 call with function number 1 in OB 1). Result After OB 150 has been processed correctly, the condition code bits OR, ERAB and OS = 0. All other condition code bits remain unchanged, as do ACCU 1 and ACCU 2. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 35 OB 151: Setting/Reading the Time for Clock-Driven Interrupts Note If the job type "0" is set in the data field and all other parameters are "F" or "FF" (hexadecimal) when you read out a timed job, then no timed job is active. This status can occur as follows: a) following a COLD RESTART, when no timed job is generated, b) when a timed job programmed to be executed only once has been executed or c) when you have cancelled a job. Possible errors: Table 6-3 In the event of an error, OB 19 or OB 31 is called. If OB 19 or OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU 1 and ACCU 2 (see following table). OB 151 error IDs ACCU-1-L ACCU-2-L 1A07H - 1A4DH 0001H 0100H 0101H 0102H 0103H 0201H 0202H 0203H 0204H 0205H 0206H 0207H 0208H 0209H 020AH C ause of error OB called Data block not loaded OB 19 Function no. = 0 or > 2 Address area type illegal Data block number illegal "Number of the first data field word" illegal Data block length in block header < 5 words Year specified in data field illegal Month specified in data field illegal Day of month specified in data field illegal Weekday specified in data field illegal Hour specified in data field illegal Minute specified in data field illegal Second specified in data field illegal 1/100 second in data field not equal to 0 Job type in data field > 7 Hour format not the same as setting in OB 150 OB 31 Note If you assign incorrect parameters and a valid timed job has already been generated, the error identifiers are transferred as indicated above, however, the previously generated timed job is retained. CPU 928B Programming Guide 6 - 36 C79000-B8576-C898-01 OB 151: Setting/Reading the Time for Clock-Driven Interrupts Important points Depending on when you want to trigger a clock-driven time interrupt concerning time parameters (timed job) you must select the individual time parameters in certain combinations. Depending on the time you select for the clock-driven time interrupt, you must specify certain parameters, while others are not evaluated by the system program and can therefore be ignored. The following table indicates which time parameters must be specified for which timed job (XXX = must be specified, --- = irrelevant). Table 6-4 "Time job - Time parameter" assignments Time of interrupt every every every every every every once minute hour day week month year Special features Seconds Minutes Hours W eekd ay Day of month Month Year XXX XXX XXX XXX XXX XXX XXX --XXX XXX XXX XXX XXX XXX ----XXX XXX XXX XXX XXX ------XXX ------- --------XXX XXX XXX ----------XXX XXX ------------XXX * If you select the job type "every year" (= 6) and select " February 29th" as the day of the month and month, then OB 9 will only be called every leap year. * If you select the job type "every month" (= 5) and select the value "29", "30" or "31" then OB 9 will only be called in the months containing these dates. Examples Various timed jobs (24 hour format): 1. "Job at the 29th second of every minute" (12:44:29, 12:45:29 etc): You must specify the following: job type = 1 (Function no. in ACCU-2-L = 1) seconds = 29 2. "Job every hour at xx:14:15": You must specify the following: job type = 2 (Function no. in ACCU-2-L = 1) seconds = 15 minutes = 14 Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 6 - 37 6 OB 151: Setting/Reading the Time for Clock-Driven Interrupts Various timed jobs (24 hour format): (continued) 3. "Job daily at 5:32:47" You must specify the following: job type = seconds = minutes = hours = 3 (Function no. in ACCU-2-L = 1) 47 32 05 4. "Job every week at 10:50:00": You must specify the following: job type = seconds = minutes = hours = weekday= 4 (Function no. in ACCU-2-L = 1) 00 50 10 01 5. "Job every month, on the 14th at 7:30:15": You must specify the following: job type = seconds = minutes = hours = day of month= 5 (Function no. in ACCU-2-L = 1) 15 30 07 14 6. "Job every year, on May 1st at 00:01:45": You must specify the following: job type = seconds = minutes = hours = day of month= month = 6 (Function no. in ACCU-2-L = 1) 45 01 00 01 05 7. "Job on December 31st 1999 at 23:55:00": You must specify the following: job type = seconds = minutes = hours = day of month= month = year = 7 (Function no. in ACCU-2-L = 1) 00 55 23 31 12 99 Continued on the nex page CPU 928B Programming Guide 6 - 38 C79000-B8576-C898-01 OB 151: Setting/Reading the Time for Clock-Driven Interrupts Various timed jobs (24 hour format): (continued) 8. "Cancel job": You must specify the following: job type = 0 (Function no. in ACCU-2-L = 1) 9. "Read out timed job": You must specify the following: function no. in ACCU-2-L = 2 If no job is active, you receive the following result in the data field: Data Data Data Data field field field field word word word word 0: 1: 2: 3: FFFF FFFF FFF0 FFFF H H H H 6 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 39 OB 152: Cycle Statistics 6.11 OB 152: Cycle Statistics A series of statistical data relating to the duration of the cycle can be recorded in the CPU 928B (cycle statistics). Using OB 152, you can initialize the cycle statistics, read out the statistical data and enable and disable the recording of statistical data. Overview The statistical data include the following: * the duration of the previous cycle, * the time elapsed in the currently active cycle since the last cycle boundary, * the minimum and maximum cycle time since the last initialization of the cycle statistics, * the number of cycles since the last initialization of the cycle statistics, * the average cycle time: a maximum of the last 256 cycles recorded in the statistics are used to calculate the average value. Note Only "normal" cycles are recorded in the cycle statistics. If the recording of the duration of the current cycle would falsify the cycle statistics, e.g. by retriggering or restarting the cycle monitoring time, these data are not included in the statistics. This means that "mavericks" do not affect the statistics. This does, however, have the effect that if the cycle monitoring time is repeatedly restarted, then only a few or even no data will be recorded for the statistics (please see in this context the Notes at the end of Section 6.11 "Falsifying the statistical data"). Enabling/disabling the statistics function Following a COLD RESTART (automatic or manual), the statistics function is always disabled and the statistical data are deleted (the cycle statistics are initialized). A WARM RESTART (automatic or manual) does not affect the statistics function or the statistical data. You can activate the statistics function in the RESTART or RUN modes using OB 152. CPU 928B Programming Guide 6 - 40 C79000-B8576-C898-01 OB 152: Cycle Statistics If the statistics function is enabled with OB 152, the statistical data are updated at each cycle boundary and you can read them out by calling OB 152. If you no longer require the statistics function, you can disable the function in the RESTART or RUN modes, once again using OB 152. This reduces the cycle time load caused by the updating of the cycle data at each cycle boundary. You can also initialize the cycle statistics using OB 152 in the RESTART or RUN modes. It may, for example, be useful to initialize the cycle statistics after evaluating the statistical data (possibly also dependent on the value of the cycle counter). Statistical data The statistical data are read out directly as individual values using OB 152 or calculated when OB 152 is called. They are transferred by OB 152 to ACCU-1-L or ACCU-2-L. You can determine the following statistical values by calling OB 152: Table 6-5 Cycle statistics variables - OB 152 Statistical value Format Unit Range of values LASTCYC Duration of the last completed cycle. Fixed point number Milliseconds 0 to 13000 CURCYC Time already elapsed in the current cycle. Fixed point number Milliseconds 0 to 13000 MINCYC Duration of the shortest cycle since the last initialization of the cycle statistics. Fixed point number Milliseconds 0 to 13000 MAXCYC Duration of the longest cycle since the last initialization of the cycle statistics. Fixed point number Milliseconds 0 to 13000 AVERAGE Average of the cycle times of the last (maximum 256) cycles 1) Fixed point number Milliseconds 0 to 13000 CYCLE Number of cycles recorded in the statistics COUNTER since the last initialization of the cycle statistics. Hexadecimal number Number of cycles 0 to 0FFFFH 1) Significance see "calculation of the average value" CPU 928B Programming Guide C79000-B8576-C898-01 6 - 41 6 OB 152: Cycle Statistics Calculation of the average value The average value is calculated by OB 152 using the following algorithm: Each time the statistical data are updated, the value of LASTCYC is entered into an internal system buffer each time the statistical data are updated. This buffer can take a maximum of 256 values. If the buffer is full, the oldest LASTCYC value is lost and the newest value is entered. During the updating of the data, the sum of the LASTCYC values in the buffer is formed so that it always contains the most recent LASTCYC values (maximum 256). When OB 152 is called, the average value is formed by dividing the total by the number of LASTCYC values stored in the buffer. In practical terms, this means that the average value is almost always formed from the LASTCYC values of the last 256 cycles . Functions When OB 152 is called, you can activate the following individual functions by means of a function number: Table 6-6 OB 153 functions Function no. Function 0 Disable cycle statistics 1 Read CURCYC / LASTCYC 2 Read MINCYC / MAXCYC 3 Read AVERAGE VALUE / CYCLE COUNTER 8 Initialize cycle statistics 15 Enable cycle statistics CPU 928B Programming Guide 6 - 42 C79000-B8576-C898-01 OB 152: Cycle Statistics Parameters ACCU-1-L ACCU-1-L contains the function no.; it must have the following structure: Bit no. 15 4 3 0 Function no., permitted values: 0 Function no. see table 6-6 Bit nos. 4 to 15 must always be 0! Result Table 6-7 After OB 152 is called, the condition codes OS, OR and ERAB = '0', the RLO is also 0 except in the cases listed below. In addition to this, the statistical values requested by some functions are transferred to ACCU-1-L and ACCU-2-L with some functions (see table below). Results of the OB 152 functions Function Results of the functions ACCU-1L Disable cycle statistics ACCU-2L Unchanged Significance of "RLO = 1" -- Read CURCYC / LASTCYC CURCYC LAST-CYC CURCYC is incorrect, the data of the current cycle are not used in the statistics 1) Read MINCYC / MAXCYC MINCYC MAXCYC Read AVERAGE VALUE / CYCLE COUNTER AVERAGE -- CYCLE CYCLE COUNTER COUNTER overflow 2) VALUE Initialize cycle statistics Unchanged -- Enable cycle statistics Unchanged -- 1) Due to starting/restarting the cycle monitoring time, cycle error or WARM RESTART 2) If RLO = 1 is set when you read out the cycle counter, then when the condition code is transferred, a system internal flag for cycle overflow is cleared. This flag is then only set again when the cycle counter overflows again. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 43 6 OB 152: Cycle Statistics Possible errors An error occurs if an incorrect function no. is transferred to ACCU-1-L (only the numbers 0 to 3, 8 and 15 are permissible). In the event of an error, OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, the error ID 1A4EH is entered in ACCU-1-L and 0 001H is entered in ACCU-2-L. Special Features This section explains several special features of OB 152 during a COLD RESTART, following a RESTART or when certain events occur and you should take note of these points if you want to use OB 152. Reaction to a COLD RESTART The statistical data are initialized during a COLD RESTART. Calling OB 152 in the first cycle following COLD RESTART reestablishes the initialization data. The following table shows how the statistical data are * initialized following a COLD RESTART and * modified during the first three cycles by the system program. Initialization of stat. data by system program OB 20 1st cycle OB 152: "stat. on." OB 152: "read stat." Update stat. data by system program Update stat. data by system 2nd cycle 3rd cycle COLD RESTART CURCYC --- --- CURCYC (1.) LASTCYC 0 0 0 MINCYC 13 000 13 000 13 000 Cycle time (1.) MAXCYC 0 0 0 AVERAGE 0 0 CYCLE C. 0 0 1) 1) OB 152: "read stat." OB 152: "read stat." --- CURCYC (3.) Cycle time (2.) Cycle time (2.) Cycle time (1.) min. c.t. min. c.t. Cycle time (1.) Cycle time (1.) max. c.t. max. c.t. 0 Cycle time (1.) Cycle time (1.) aver. c.t. aver. c.t. 0 1 1 2 2 --- CURCYC (2.) Cycle time (1.) Cycle time (1.) The value for CURCYC is always read out via OB 152, the cycle monitoring timer. For this reason, it is already available during the first cycle. CPU 928B Programming Guide 6 - 44 C79000-B8576-C898-01 OB 152: Cycle Statistics When the statistical data are initialized, not only the defaults listed in the table, but also the internal system buffer for the average are deleted and an internal flag for cycle counter overflow is reset. Calling OB 152 in a start-up OB Depending on the type of restart, the OB 152 call to read the statistical data provides the following values in ACCU-1-L and ACCU-2-L (columns on a gray background). COLD RESTART Initialization of stat. data by system program WARM RESTART in cycle n OB 20 OB 152: "stat on" OB 21/22 OB 152: "read stat." OB 152: "read stat." CURCYC --- --- 0 LASTCYC 0 0 0 MINCYC 13 000 13 000 13 000 MINCYC MAXCYC 0 0 0 MAXCYC AVERAGE 0 0 0 AVERAGE CYCLE C 0 0 0 CYCLE C. 6 CURCYC 0 Cycle time (n-1) LASTCYC incl. cyc. (n-1) incl. cyc. (n-1) incl. cyc. (n-1) n-1 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 45 OB 152: Cycle Statistics Initializing the statistical data by calling OB 152 Cycle The following table shows how the statistical data are changed when they are initialized by calling OB 152 in the CYCLE. The columns with a gray background contain the values transferred when the statistical data are read. (n) (n+1) (n+1) T Update Update OB 152: "read stat." OB 152: "read stat." OB 152: "init. stat." OB 152: "read stat." OB 152: "read stat." CURCYC CURCYC(n-1) --- CURCYC (n) --- T --- CURCYC (n+1) LASTCYC Cycle time (n-2) Cycle time (n-1) Cycle time (n-1) 0 0 no 0 MINCYC incl. cyc. (n-2) incl. cyc. (n-1) incl. cyc. (n-1) 13 000 13 000 no 13 000 MAXCYC incl. cyc. (n-2) incl. cyc. (n-1) incl. cyc. (n-1) 0 0 no 0 AVERAGE incl. cyc. (n-2) incl. cyc. (n-1) incl. cyc. (n-1) 0 0 no 0 CYCLE C. n-2 n-1 n-1 0 0 no 0 When the statistical data are initialized, not only the defaults listed in the table, but also the system internal buffer for forming the average value is deleted and an internal flag for cycle counter overflow is reset. After the statistical data are initialized by calling OB 152, the data are only updated by the system program at the end of the first cycle after the initialization. Calling OB 152 when the cycle statistics are disabled If you disable the cycle statistics by calling OB 152, the statistical data of the last update are retained. If you then use OB 152 to read the statistical data, it supplies the data from the last update before the statistics were disabled. If you read the statistical data following a COLD RESTART, without enabling the cycle statistics with an OB 152 call, OB 152 supplies the initialization data. CPU 928B Programming Guide 6 - 46 C79000-B8576-C898-01 OB 152: Cycle Statistics Falsifying the statistical data Certain events can cause problems when recording the cycle length of the current cycle and can lead to incorrect values. In these situations, the statistical data for the cycle affected are not updated. These events include the following: * WARM RESTART * Starting the cycle monitoring time by calling OB 221 * Restarting the cycle monitoring time by calling OB 222 * Cycle errors Cycle (n) (n-1) (n+1) Update Interruption by: WARM RESTART OB 221/222 cycle error OB 152: "read stat." CURCYC CURCYC --- LASTCYC Cycle time (n-2) Cycle time (n-1) MINCYC incl. cyc. (n-2) incl. cyc. (n-1) MAXCYC incl. cyc. (n-2) AVERAGE CYCLE C Update OB 152: "read stat." OB 152: "read stat." 1) --- CURCYC (n+1) no Cycle time (n-1) incl. cyc. (n-1) no incl. cyc. (n-1) incl. cyc. (n-1) incl. cyc. (n-1) no incl. cyc. (n-1) incl. cyc. (n-2) incl. cyc. (n-1) incl. cyc. (n-1) no incl. cyc. (n-1) n-2 n-1 n-1 no n-1 Cycle time (n-1) 1) The value of CURCYC corresponds to the time T that has elapsed since the occurrence of the "problem" in the current cycle. This is not the length of the whole cycle. To indicate this situation, the RLO is set to "1" in addition to the values transferred to ACCU-1-L and ACCU-2-L. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 47 6 OB 153: Set/Read Time for Delayed Interrupt 6.12 OB 153: Set/Read Time for Delayed Interrupt Using OB 153, you can transfer so-called "delay jobs" to the system program. After a specified delay time "a delayed interrupt" is then processed (refer to OB 6, Section 4.5.2). Function By calling OB 153, you can do the following: * define and start a delay time, * stop an activated delay time (cancel delay job), * read how long the delay time still has to run. A delay job can be activated in the START UP and RUN modes. Life of a delay job The delayed interrupt triggered by a delay job is only activated by the system program in the R U N mode (OB 6 call). Jobs which become due in a mode other than RUN are discarded by the system program without any message. A currently active (but not yet due) job is also discarded if the CPU changes to the STOP mode or if the power is switched off. Parameters Accus a) ACCU-2-L Delay time in milliseconds (max. 65535) Permitted values:0001H to FFFFH ACCU-2-L only needs to be supplied with the function number '1 ' ("define delay time") when OB 153 is called. The contents of ACCU-2-L are not evaluated in the remaining OB 153 functions. b) ACCU-1-L Function no. Permitted values: 1 = define and start delay time 2 = stop delay time (= cancel job) 3 = read remaining delay time CPU 928B Programming Guide 6 - 48 C79000-B8576-C898-01 OB 153: Set/Read Time for Delayed Interrupt Note If a previously defined delay time is not yet elapsed when a further delay time is defined, the previously defined time is lost and the new delay time started. Result After correct processing of OB 153, the condition code bits OR, ERAB and OS = 0. When OB 153 is called with the function no. '2' or '3', ACCU-1-L contains the remaining time to run in milliseconds. If no delay job is active when OB 153 is called with function no. '2' or '3', ACCU-1-L contains the value '0'. Possible errors The errors listed in the following table can occur. OB 31 (other runtime errors) is called. If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, error IDs are entered in ACCU-1-L and ACCU-2-L (see the table below). Table 6-8 OB 153 error IDs ACCU-1-L 1A4FH ACCU-2-L 0001H 0002H Bedeutung Function no. = 0 or >3 Illegal delay time Examples Define and start delay time: When an AUTOMATIC WARM RESTART is performed, after 5 seconds a certain STEP 5 operation sequence must be run through once. To do this, the delay time is defined and started in start-up organization block OB 22. The STEP 5 operations in OB 22 for calling OB 153: : : :L KF +5000 :L KF +1 : :JU OB 153 : Value for ACCU-2-L: 5000 ms Value for ACCU-1-L: function no. = 1 for "define and start delay time" Call OB 153 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 49 6 OB 153: Set/Read Time for Delayed Interrupt Stop delay time (cancel job) STEP 5 operations for calling OB 153: : : :L KF +2 : :JU OB 153 : Value for ACCU-1-L: function no. = 2 for "stop delay time" Call OB 153 Read out remaining time of a delay job: STEP 5 operations for calling OB 153: : : :L KF +3 : :JU OB 153 : : Value for ACCU-1-L: function no. = 3 for "read out remaining time" Call OB 153 ACCU-1-L contains the time the delay job still has to run. CPU 928B Programming Guide 6 - 50 C79000-B8576-C898-01 OB 160 to 163: Loop Counters 6.13 OB 160 to 163: Loop Counters By using these special function operation blocks, you can implement program loops with a particularly fast runtime. Function A system data word is assigned to each of the four special function OBs as follows: * RS 60: OB 160 * RS 61: OB 161 * RS 62: OB 162 * RS 63: OB 163 6 Programming the program loop You transfer the value for the required number of loop repetitions to one of these system data words. When you then call the appropriate special function OB, the loop counter in the system data word is decremented by 1. The loop is repeated until the loop counter reaches the value zero. Note If the loop counter is already zero before the special function OB is called, it is decremented by 1; the loop is then run through 65,536 times. Parameters System data word RS 60 - 63 Loop counters possible values: 0 - 65 535 decimal (0 to FFFFH) CPU 928B Programming Guide C79000-B8576-C898-01 6 - 51 OB 160 to 163: Loop Counters Result Loop counter in system data word >0: RLO is set (RLO = 1) Loop counter in system data word = 0: RLO is cleared (RLO = 0) The other bit and word condition codes are always cleared. The accumulators are not changed and not evaluated. This means that they are still available at the beginning of the next loop and do not need to be set again. Possible errors none Example Programming a loop counter: The required number of loop repetitions is contained in flag word x. Initialize the loop: "Loop program": Manage loop: Further program : :L :L :!=F :JC :T : : : KB0 FWx =M002 RS 62 Loop counter Transfer loop counter to system data word . M001 : : . : . : . : :JU OB162 Loop counter :JC : : =M001 If RLO = 1 the loop is run through again M002 : : : : . . . . For a further example, refer to Section 9.3 "TNW and TNB: Transferring Memory Fields". CPU 928B Programming Guide 6 - 52 C79000-B8576-C898-01 OB 170: Read Block Stack (BSTACK) 6.14 OB 170: Read Block Stack (BSTACK) Starting with OB 1 or FB 0, the block stack contains all the blocks that have been called in sequence and that have not yet been completely processed. Function Using the special function organization block OB 170, you can read the entries currently in the BSTACK into a data block. In this way, you can find out how many entries are currently in the BSTACK and how much space is still available for further entries. For each entry, you obtain the return address (step address counter = SAC), the absolute start address of the data block valid in this block (DBA) and its length (number of data words = DBL). Note Before you call OB 170, you must first open a data block (DB or DX) with sufficient length. Four data words are required for each BSTACK entry. Parameters Accus a) ACCU-2-L Number of the data word (DW n) from which the entries are to be stored in the open DB (offset) b) ACCU-1-L Required number of BSTACK elements; Possible values: 1 - 62 Example: if ACCU-1-L contains the value "1", you obtain the last BSTACKentry, if it contains "2", you obtain the last and one before last etc. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 53 6 OB 170: Read Block Stack (BSTACK) Result After OB 170 has been called successfully * the offset in the data block is still contained in ACCU-2-L * the actual number of BSTACK elements represented is in ACCU-1-L 1) * The RLO is cleared. * The condition codes CC 0 and CC 1 can be analyzed. * All other bit and word condition codes are cleared. 1) Possible values: 0 - 62, where the represented number is less than or equal to the required number 0 = "no BSTACK entry exists" or "error" (Multiply the contents of ACCU-1-L by four to obtain the number of data words written to the DB). RLO, CC 0 and CC 1 settings Storing the BSTACK elements in open data blocks R LO CC 1 CC 0 Scan with 0 0 1 JM Meanin g Existing number of BSTACK elements < required number 0 0 0 JZ Existing number of BSTACK elements = required number 0 1 0 JP Existing number of BSTACK elements > required number 1 1 1 JC Error The contents of the BSTACK are stored in the data block as follows when OB 170 is called (see also Fig. 6-3): A = BSTACK element number (62 to 1) (As soon as the last BSTACK element is output you can determine the remaining space: A = 17 reserve = A - 1 = 16) B = Depth if the BSTACK element (1 to 62) CPU 928B Programming Guide 6 - 54 C79000-B8576-C898-01 OB 170: Read Block Stack (BSTACK) Block header DW0 Offset DWn A B DWn+1 SAC DWn+2 DBA DWn+3 Length DWn+4 DWn+5 A last entry in the BSTACK (B = 1) 6 B SAC DWn+6 DBA DWN+7 Length second last entry in the BSTACK (B = 2) older BSTACK entries Fig. 6-3 Storing BSTACK entries in a data block CPU 928B Programming Guide C79000-B8576-C898-01 6 - 55 OB 170: Read Block Stack (BSTACK) Possible errors * No data block opened * Opened data block does not exist or is not long enough to take the required number of BSTACK entries * Illegal parameters in ACCU 1 and ACCU 2 If an error occurs, the RLO and the condition codes CC 0 and CC 1 are set (RLO, CC 0 and CC 1 = 1). The remaining bit and word condition codes are cleared. The contents of ACCU-1-L are set to "0". Example You want to read the last three BSTACK entries into data block DX 10. You want the entries to be stored in DX 10 from data word DW 16 onwards (see Figs. 6.4 and 6.5). :CX DX 10 ;open DX 10 :L KY 0,16 ;BSTACK entries to be stored from DW 16 onwards :L KY 0,3 ;you require the last three BSTACK entries 170 :JU OB Six blocks are entered in the BSTACK as follows: BSTACK Element 1 Element 56 Element 57 Depth 1 Element 58 Depth 2 Element 59 Depth 3 (last BSTACK entry) Element 60 Element 61 Element 62 Fig. 6-4 (first BSTACK entry) Contents of the BSTACK in this example Continued on the next page CPU 928B Programming Guide 6 - 56 C79000-B8576-C898-01 OB 170: Read Block Stack (BSTACK) Continuation of the example: After the special function OB is called, DX 10 contains the following: DX 10 Block header DW 0 Offset DW 16 57 1 DW 17 SAC DW 18 DBA DW 19 Length DW 20 58 DW 21 SAC DW 22 DBA DW 23 Length DW 24 59 Depth 1 6 2 Depth 2 3 Depth 3 ACCU-2-L= 16 (Offset) DW 25 SAC ACCU-1-L= 3 (No. of elements in DX 10) Fig. 6-5 DW 26 DBA DW 27 Length RLO = 0 (No errors) CC 0 = 0 CC 1 = 1 (No. of BSTACK elements greater then requested number of elements) Contents of DX 10 in this example after OB 170 is called CPU 928B Programming Guide C79000-B8576-C898-01 6 - 57 OB 180: Accessing Variable Data Blocks 6.15 OB 180: Accessing Variable Data Blocks DBA/DBL register When a data block is opened with the operations C DB and CX DX, the DBA register (data block start address) is loaded with the address of data word DW 0, stored in DB 0. Access to data blocks with operations such as L DR 60 or DO DW 240 etc. are always relative to the data block start address. In addition to the DBA register, the DBL register (data block length) is always loaded when a data block is called. This register contains the length (in words) of the opened DB or DX data block without the block header. Note A maximum of up to 4091 data words can be entered in the DBL register. STEP 5 access to data words is only possible up to a maximum data word number of 255. Example The DBA register the address of the memory word in which DW 0 to DB 17 is stored: DBA = 151BH The number of data words is stored in the DBL register: DBL = 8 (DW 0 to DW 7) Since access to the data words by means of the STEP 5 operations L DW, U D, DO DW etc. is always relative to DBA, 3 is added to 151BH in order to access, e.g. DW 3. Data word DW 3 is stored under the address 151EH. The DBL register is used to check whether a transfer or load operation is pending. T DW 7 is permissible but T DW 8 or L DW 8 are not. Applications of OB 180 Special function OB 180 allows you to access structured data in an opened data block. You can do this by shifting the starting address of the data block entered in the DBA register to the end of the data block with the help of OB 180. Simultaneously to shifting the starting address, OB 180 decrements the block length entered in the DBL register accordingly. It is important that this is done so that the CPU can monitor load and transfer operations in the case of later accesses to the data block. CPU 928B Programming Guide 6 - 58 C79000-B8576-C898-01 OB 180: Accessing Variable Data Blocks * Access to DBs with a length greater than 261 words (five words header) over the whole length of the DB. Using OB 180, you can move an "access window" of 256 data words over the length of the data block. * Handling data structures A data block can be divided into several data records of the same length and with the data arranged in the same order. This is known as structuring the data block. A data block structured in this way might, for example, contain the data of several subprocesses, with a temperature value in the first data word, a pressure in the second and other values for the subprocess in the remaining data words. Using OB 180, you can access the data of each subprocess using the same operations (e.g. L DD, S D, T DR etc.), by loading the DBA register with the start address for the subprocess. In contrast to other substitution mechanisms, (substitution = indexed parameter assignment) you obtain simpler and faster subroutines. 6 Function With OB 180, the starting address of the current data block is shifted by a specified value. In doing so, account is taken of the fact that the remaining available length of the DB has to be reduced (the DBA and DBL registers are loaded in correspondence to the shift). Note Before you call OB 180, a data block (DB or DX) with an adequate length must already be open. Parameters ACCU-1-L offset (number of data words, by which you want to shift the data block start address), possible values: 0 < ACCU-1-L < DBL CPU 928B Programming Guide C79000-B8576-C898-01 6 - 59 OB 180: Accessing Variable Data Blocks Result After OB 180 has been called successfully * the value of the DBA register (= address of DW 0) is raised by the value of ACCU-1-L * the value of the DBL register is reduced by the value of ACCU-1-L * the RLO is cleared (RLO = 0) * all other bit and word condition codes are cleared * Negative length Possible errors * No data block opened * Contents of ACCU-1-L DBL In the event of an error (ACCU-1-L DBL) the DBA and DBL registers remain unchanged. The RLO is set (RLO = 1). The remaining bit and word condition codes are cleared. If the DBL register contains the value "0", OB 180 recognizes that no data block is open. The RLO is set (RLO = 1), signalling an error. Resetting DBA and DBL to the initial value Opening the data block again using the operations C DB or CX DX, re-establishes the initial setting. Example You want to shift the data block start address (DBA = 151B) in DB 17 (DBL = 8) by two data words. :C :L DB KB 17 2 :JU OB 180 open DB 17 shift / offset as constant call OB 180: DBA and DBL are adjusted When you call OB 180, the data word stored at e.g. address 1520 can no longer be addressed as DW 5, but must be addressed as DW 3 etc. (see Fig. 6-6). CPU 928B Programming Guide 6 - 60 C79000-B8576-C898-01 OB 180: Accessing Variable Data Blocks Continuation of the example: Addr. (hex.) DB 17 1516 5 words block header .. . . 1517 DBA old 151B 151C DBA new 151D cccc DW 0 151E dddd DW 1 151F eeee DW 2 DBLold 6 DBLnew 1520 ffff DW 3 1521 gggg DW 4 1522 hhhh DW 5 15 Fig. 6-6 0 Shifting the DB start address Because the DBL register is adjusted at the same time, error monitoring is guaranteed: the operation T DW 5 is permitted, while T DW 6/LW 6 would cause an error. If you call OB 180 again, the DBA can be increased again (and the DBL is further reduced). The operation C DB 17 re-establishes the initial state (DBA = 151B, DBL = 8). If DB 17 has a length of, for example, 258 data words, you cannot access DW 256 and DW 257 using STEP 5 operations. If you shift the DBA register by two, you can address data words 256 and 257 using "DW 254" and "DW 255". For more information about the DBA/DBL registers, refer to Chapter 9. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 61 OB 181: Testing Data Blocks (DB/DX) 6.16 OB 181: Testing Data Blocks (DB/DX) With the special function organization block OB 181 you can check the following: * whether a particular DB or DX data block exists, * the address of the first data word of the data block, * how many data words the data block contains, * the memory type and area (user memory: RAM or EPROM, DB-RAM). Application of OB 181 The "test DB/DX" function is useful before the operations TNB/TNW, G DB/GX DX and before calling the special function organization blocks OB 182, OB 254 and OB 255. You can, for example, call OB 181 before transferring a group of data words, to make sure that the destination data block is both valid and long enough to take all the data words you wish to transfer. Function OB 181 checks that a specified data block exists and returns the characteristic parameters of the data block as a result. Parameters ACCU-1-L a) ACCU-1-LL: block number possible values: 1 to 255 b) ACCU-1-LH: block identifier possible values: 1 = DB 2 = DX CPU 928B Programming Guide 6 - 62 C79000-B8576-C898-01 OB 181: Testing Data Blocks (DB/DX) * If the block does exist in the CPU: Result - ACCU-1-L: contains the address of the first data word (DW 0), - ACCU-2-L: contains the length of the data block in words (without block header), Example: ACCU-2-L contains the value "7": the data block consists of DW 0 to DW 6. - R LO: =0 - CC 0/CC 1: are affected according to the location of the block (see following list), - the remaining bit and word condition codes: are cleared. * If the data block does not exist in the memory or the parameter assignment is incorrect: - ACCU 1 and 2: are not changed - R LO: =1 - CC 0/CC 1: =1 - the remaining bit and word condition codes: are cleared RLO, CC1, CC0 The following condition code bits are set according to the check result. The condition code bits can be evaluated by the operations listed in the "Scan" column of the table: RLO CC 1 CC 0 Scan 0 0 1 JM 0 0 0 1 0 0 JZ JP 1 1 1 JC Meaning DB/DX in user submodule DB/DX in DB RAM DB/DX in EPROM (read-only) DB/DX exists DB/DX in RAM (read/write) DB/DX does not exist or there is an error CPU 928B Programming Guide C79000-B8576-C898-01 6 - 63 6 OB 181: Testing Data Blocks (DB/DX) Possible errors * Incorrect block number (illegal: 0: DB 0/DX 0) * Incorrect block identifier (permitted: 1 = DB, 2 = DX; illegal: 0, 3 to 255) * memory error Examples Refer to Section 8.3.2 / Section 9.2 / Section 9.3. CPU 928B Programming Guide 6 - 64 C79000-B8576-C898-01 OB 182: Copying a Data Area 6.17 OB 182: Copying a Data Area Function OB 182 copies a data field of variable length from one data block to another. You can use DB and DX data blocks as the source and destination blocks. You can select the start of the field in the source and destination data block as required. OB 182 can copy a maximum of 4091 data words. It contains pseudo operation boundaries. Note The source and destination block can be identical; the data areas of the source and destination can overlap. The original d ata of the source area are copied unchanged to the destination area even if there is an overlap. (The area overlappin g in the source is overwritten following the copying.) You can use this feature in certain situations, for example to shift a data area within a block. 6 Parameters 1. Data Field with Parameters for Copyin g Functions Before you call OB 182, supply a data field with all the data required for the copying. This data field can be set up in a DB or DX data block, or in the F or S flag area. The data field defines the source and destination data block, the field start address in both blocks and the number of data words to be transferred. It consists of 5 words. Bit no. 15 1st word 2nd word 3rd word 4th word 8 7 Source DB type 0 Source DB no. No. of 1st data word in source DB to be transferred Dest. DB type Dest. DB no. No. of 1st data word to be written in dest. DB 5th word Number of data words CPU 928B Programming Guide C79000-B8576-C898-01 6 - 65 OB 182: Copying a Data Area The range of values and meaning of the parameters is as follows: Parameters Permissible value range Data block type (source and destination) 1 = DB 2 = DX Data field in the flag area Data block number (source and destination) 3...255 No. of the 1st data word (source and destination) 0...4090 Number of data words 1...4091 If you set up the data field in the flag area, you must take into account the following assignment of data field words to flag bytes. "x" is the parameter "no. of the 1st data field word", that you must store in ACCU-1-L when OB 182 is called. Bit no. 15 8 7 0 1st data field word Flag byte x Flag byte x+1 2nd data field word Flag byte x+2 Flag byte x+3 3rd data field word Flag byte x+4 Flag byte x+5 4th data field word Flag byte x+6 Flag byte x+7 5th data field word Flag byte x+8 Flag byte x+9 2. Accus 2a) ACCU-2-L Der ACCU-2-L enghalt Angaben zum verwendeten Datenfeld. Er mu folgenden Aufbau haben: Bit no. 15 8 7 Address area type 0 Data block no. Parameters in ACCU-2-L Address area type, permitted values: Data block no., permitted values : 1 = DB data block 2 = DX data block 3 = F flag area 4 = S flag area 3 to 255 (in the case of address area type "1" or "2" only; irrelevant in the case of address area type "3" or "4") CPU 928B Programming Guide 6 - 66 C79000-B8576-C898-01 OB 182: Copying a Data Area 2b) ACCU-1-L Number of the 1st data field word, permitted values (depending on the address area type): DB, DX: 0...2043 F flags: 0...246 (= no. of flag byte "x") S flags: 0...1014 (= no. of flag byte "x") Result After OB 182 is correctly executed, the condition code bits OR, ERAB and OS = 0. All other condition code bits and ACCUs 1 and 2 are unchanged. Reactions to errors In the event of an error, OB 19 or OB 31 (other runtime errors) is called. If OB 19 or OB 31 is not loaded the CPU goes to the STOP mode. In both cases, error identifiers are transferred to ACCU 1 and ACCU 2 (see following table). Table 6-9 OB 182 error IDs ACCU-1-L ACCU-2-L 1A06H - 1A34H 0001H 0100H 0101H 0102H 0200H 0201H 0202H 0203H 0210H 0211H 0212H 0213H 0220H 0221H 0222H 0223H Cause of error OB called Data block not loaded OB 19 Data field written to incorrectly Address area type not permitted Data block number not permitted Number of the first data field word not permitted Source data block type not permitted Source data block number not permitted Number of 1st data word in the source DB to be transferred not permitted Length of the source data block in the block header < 5 words Destination data block type not permitted Destination data block number not permitted Number of the 1st data word to be written to in the destination DB not permitted Length of the destination data block in the block header < 5 words Number of data words to be transferred not permitted (= 0 or > 4091) Source data block too short Destination data block too short Destination data block is in an EPROM OB 31 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 67 6 OB 190/OB 192: Transferring Flags to a Data Block 6.18 OB 190/OB 192: Transferring Flags to a Data Block Application With organization blocks OB 190 and OB 192, you can transfer a selected number of flag bytes to a data block. This can, for example, be an advantage before block calls, in error organization blocks or when cyclic program execution is interrupted by a time or process interrupt. Using OB 191 and OB 193, you can then write these flag bytes back from the data block. Note Use OB 190 and OB 191 to save and read back flag bytes, since the time required is extremely short. Before you call OB 190/192, a data block (DB/DX) must already be open. OBs 190/192 only transfer flag bytes from the F flag area to a data block, they cannot transfer flag bytes from the S fla g area. Function After you call OB 190/192, the flag bytes are written to the open data block from the specified data word address. OBs 190/192 take the flag area to be saved from ACCU 2. OBs 190 and 192 are identical except for the way in which they transfer the flag bytes: OB 190 transfers the flags in bytes OB 192 transfers the flags in words. This difference is significant, when the data transferred to the data block are intended for processing and you are not simply using the data block as a buffer. CPU 928B Programming Guide 6 - 68 C79000-B8576-C898-01 OB 190/OB 192: Transferring Flags to a Data Block The following diagram illustrates the difference. OB 190: OB 192: Data block Data block Copy flags with Flags 7 0 15 DL 87 DR 0 15 DL 87 DR FY 0 0 1 0 DW 0 0 1 FY 1 1 3 2 DW 1 2 3 FY 2 2 4 DW 2 4 FY 3 3 0 DW3 4 6 Fig. 6-7 Transferring in bytes (OB 190) and words (OB 192) Note If you transfer an odd number of flag bytes, only h alf the last data word in the data block is used. With OB 190 , the left date in the destination DB is unchanged, with OB 192 the right date is unchanged. Parameters 1. Specifyin g the source: 1a) ACCU-2-LH First flag byte to be transferred, possible values: 0 to 255 1b) ACCU-2-LL Last flag byte to be transferred, possible values: 0 to 255 (The last fla g b yte must be the first flag byte) CPU 928B Programming Guide C79000-B8576-C898-01 6 - 69 OB 190/OB 192: Transferring Flags to a Data Block 2. Specifyin g the destination ACCU-1-L Number of the first data word to be written to in the open data block: The permitted values depend on the length of the data block in the memory. Numbers greater than 255 may occur Result If the special function OBs 190/192 are processed correctly, the RLO is cleared (RLO = 0). The ACCUs remain unchanged. If an error occurs, the RLO is set (RLO = 1), the ACCUs remain unchanged. Possible errors * No DB or DX data block opened * Incorrect flag area (last flag byte < first flag byte) * Data word number does not exist * DB or DX data block not long enough CPU 928B Programming Guide 6 - 70 C79000-B8576-C898-01 OB 191/OB 193: Transferring Data Fields to a Flag Area 6.19 OB 191/OB 193: Transferring Data Fields to a Flag Area Application With the organization blocks OB 191 and OB 193 you can transfer data from a data block to the flag area. With this function, you can, for example, write flag bytes you have saved in a data block back to the flag area. The only difference between OBs 191/193 and OBs 190/192, is that the source and destination are reversed: OB 190/192: Flag area Data block OB 191/193: Flag area Data block Note Before you call OB 191/193, a data block of sufficient len gth (DB/DX) must be opened. 6 OBs 191/193 transfer from the data block only to the F fla g area and not to the S flag area . Function After OB 191/193 is called, data words starting from the data word address specified are read out of the opened data block and transferred to the flag area. OBs 191 and 193 are identical, except for the way in which they transfer data. OB 191 transfers data words in bytes OB 193 transfers data words in words. The figure on the next page illustrates this difference. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 71 OB 191/OB 193: Transferring Data Fields to a Flag Area 15 Data block DL 87 OB 191 Flags DR 0 7 0 DW 0 1 0 (DR 0) 0 FY 0 DW 1 3 2 (DL 0) 1 FY 1 DW 2 5 4 (DR 1) 2 FY 2 6 (DL 1) 3 FY 3 DW 3 15 Data block DL 87 OB 193 Flags DR 0 7 0 DW 0 1 0 (DL 0) 1 FY 0 DW 1 3 2 (DR 0) 0 FY 1 DW 2 5 4 (DL 1) 3 FY 2 6 (DR 1) 2 FY 3 DW 3 Fig. 6-8 Transferring in bytes (OB 191) and words (OB 193) CPU 928B Programming Guide 6 - 72 C79000-B8576-C898-01 OB 191/OB 193: Transferring Data Fields to a Flag Area Parameters 1. Specifyin g the source: 1a) ACCU-2-L Number of the first data word in the open data block to be transferred 2. Specifyin g the destination: 2a) ACCU-1-LH First flag byte to be written to, possible values: 0 to 255 2b) ACCU-1-LL Last flag byte to be written to, possible values: 0 to 255 (The last fla g b yte must be the first flag byte) Result 6 If special function OBs 191/193 are processed correctly, the RLO is cleared (RLO = 0). The ACCUs remain unchanged. In the event of an error, the RLO is set (RLO = 1), the ACCUs remain unchanged. Possible errors * No DB or DX data block open * Incorrect flag area (last flag byte < first flag byte) * Data word number does not exist * DB or DX data block not long enough CPU 928B Programming Guide C79000-B8576-C898-01 6 - 73 OB 191/OB 193: Transferring Data Fields to a Flag Area Example 1 Before program block PB 12 is called, all the flags (FY 0 to FY 255) must be saved in data block DX 37 from address 100 onwards and then written back to the flag area. Saving: :CX :L :L : DX 37 KY 0,255 KB 100 :JU OB 190 Block change: :JU PB 12 Writing back: : :L : :L :JU KB 100 KY 0,255 OB 191 Call the data block Flag area FY0 to FY255 Number of the 1st data word in the destination DB Save flags (Data block already called) Number of the 1st data word in the source DB Flag area FY0 to FY255 Write back flags Example 2 Flags used by the cyclic user program must not be used by a time or process-driven user program. Each program processing level must have a particular section of the flag area assigned to it. e.g.: Cyclic user program: Time-driven user program: FY0 ... . ... FY99 FY100 ... . ... FY199 Process interrupt-driven user program: FY200 ... . ... FY255 If, however, the cyclic user program is already using all 256 flag bytes and the time-driven user program also requires all 256 flag bytes, the flags must be swapped over when the processing level is changed and the old flags stored until the program returns to the original processing level. The quickest way to save and load these flags is with the special function blocks OB 190 and OB 191. Fig. 6-9 illustrates how a flag area FYx to FYy used by both OB 1 and OB 13 (100 ms time interrupt) can be buffered in a data block DBx. Continued on the next page CPU 928B Programming Guide 6 - 74 C79000-B8576-C898-01 OB 191/OB 193: Transferring Data Fields to a Flag Area Continuation of example 2: OB 1 OB 13 DB z OB 190 FY x FY y Save DW a-b the FYs DB z OB191 DW a-b Write the FY x - FYs back FY y 6 Fig. 6-9 Saving the areas when the program processing level changes STEP 5 program in OB 13: :C :L :L :JU :L :L :JU : : :C :L :L :JU :L :L :JU :BE DB KY KB OB KB KY OB 100 0,255 128 190 128 0,255 191 DB KY KB OB KB KY OB 100 0,255 128 190 0 0,255 191 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 75 OB 191/OB 193: Transferring Data Fields to a Flag Area Further applications for organization blocks OB 190 to 193 - In the CPU (A, O, ON, comparable operations 928B, operations involving the processing of single bits AN, S, R, =) that access the flag area are far faster than operations that access data blocks (compare, for example the "A D" or "S F" "S D"). "A F" You can speed up your program if you copy data to the flag area, process them there and then return them to the data block. - A high byte and low byte in a data block can be swapped over without complicated programming by copying the data words to the flag area using the appropriate OBs and then transferring them back as illustrated by Fig. 6-10. Data block 15 Flags 87 7 0 DW x A B DW x+1 C D OB 193 0 15 A FY y B FY y+1 C FY y+2 . . . . D Fig. 6-10 Data block OB 190 87 0 B A DW x D C DW x+1 Swapping the high byte and low byte in a DB using OB 193/OB 190 - You can shift data fields within a data block by specifying a different data word but the same DB number for transferring the data back to the DB. CPU 928B Programming Guide 6 - 76 C79000-B8576-C898-01 OB 200 to OB 205: Multiprocessor Communication 6.20 OB 200 to OB 205: Multiprocessor Communication These special function organization blocks are described in detail in Chapter 10. You can use the special function organization blocks OB 200 and OB 202 to OB 205 to transfer data between CPUs in multiprocessor operation using the coordinator 923C. * OB 200: initialize This special function organization block sets up a memory area in the 923C coordinator. This memory is a buffer for the data fields that are transferred. * OB 202: send This function transfers a data field to the buffer of the 923C coordinator and indicates how many data fields can still be sent. * OB 203: send test The special function OB 203 determines the number of free memory fields in the buffer of the 923C coordinator. * OB 204: receive This function transfers a data field from the buffer of the 923C coordinator and indicates how many data fields can still be received. * OB 205: receive test The special function OB 205 determines the number of occupied memory fields in the buffer of the 923C coordinator. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 77 6 OB 216 to OB 218: Page Access 6.21 OB 216 to OB 218: Page Access What are pages? To implement a large number of communications registers, within the address range of the S5 bus, an address area with a length of 1024 bytes (2048 bytes are reserved) is imaged 256 times on the memory. Because these 256 images are stored beside or behind each other like individual "pages", these memory areas are also referred to as a "page memory". In multiprocessor operation, all modules involved can only access one page of this memory area at any one time, all the remaining pages must be disabled for both reading and writing. A page is addressed via a page address register that exists on all modules operating with pages and that has a fixed address on the S5 bus. You set the numbers (addresses) of the pages on each of these modules using a DIL switch, so that each page can only exists once in the PLC. Before reading or writing to a page, the CPU specifies the page number by writing to the page address register. All the modules that operate according to this procedure of the S5 bus receive this number simultaneously ("broadcast") and store it in their memory. Only the page addressed in this way can be written to or read from in the page memory of the S5 bus, all other pages are disabled. CPU 928B Programming Guide 6 - 78 C79000-B8576-C898-01 OB 216 to OB 218: Page Access How to access pages You can use organization blocks OB 216 to OB 218 and several STEP 5 operations (see Chapter 9) to access the pages. The organization blocks contain the following functions: * OB 216: write a byte/word/double word to a page * OB 217: reads a byte/word/double word from a page * OB 218: the CPU occupies a page (used for coordination in multiprocessor operation) You can use these functions for test purposes and for programming handling blocks or similar functions. Note Whenever possible, only program access to pages by calling OB 216 to OB 218. You should only use the available STEP 5 operations if you have considerable experience of the system. Normally, you can execute all functions using the standard function blocks "handling blocks" and the integrated function organization blocks "multiprocessor communication" (OB 200, OB 202 to OB 205), with which all page access is handled "automatically". CPU 928B Programming Guide C79000-B8576-C898-01 6 - 79 6 OB 216 to OB 218: Page Access Address areas for peripherals on the S5 bus Page length Bit Address area occupied 1024 addresses (byte or word addresses) F400H - F7FFH 2048 addresses (byte or word addresses) F400H - FBFFH 0 7 F000 P area Multiple memory area F100 O area Length: 1024 or 2048 bytes F200 Page no. 255 IPC flags on coordinator F300 System area (semaphores) on the coordinator 3 2 . 1 F400 Page no. 0 Address space of a page FC00 FEFF Distributed peripherals (or free) Page address register FF00 not occupied FFFF Fig. 6-11 Location of the page address area on the S5 bus CPU 928B Programming Guide 6 - 80 C79000-B8576-C898-01 OB 216 to OB 218: Page Access You specify the page to be used when you assign parameters to the special function organization blocks OB 216, OB 217 and OB 218. The number of the "currently active" page is then automatically entered in a memory location with the address 0FEFFH (see Fig. 6-11). All addresses then refer to the page whose number is entered. Note You cannot read the page address register with the address 0FEFF H. At this address, you can, however, read out the bus error register on the coordinator module 923C (see S5-135U/155U System Manual). Notes on assigning parameters When a byte/word/double word is written (OB 216) and read (OB 217) to/from a page, the bytes are referenced in the following order: 7 Address n 6 0 Byte Address n High byte Address n+1 Low byte Byte format Word format Address n H byte in H word Address n+1 L byte in H word Double word format Address n+2 H byte in L word Address n+3 L byte in L word Fig. 6-12 Location of the bytes when writing (OB 216) / reading (OB 217) to/from a page in words or double words CPU 928B Programming Guide C79000-B8576-C898-01 6 - 81 OB 216 to OB 218: Page Access 6.21.1 OB 216: Writing to a Page Function The special function organization block transfers a byte, word or double word from ACCU 1 (right-justified) to a particular page. The addressin g of the page in single or multiprocessor operation and the transfer of the complete data unit (1, 2 or 4 bytes) is one program function and cannot be interrupted. Parameters Accus a) ACCU-3-LH Identifier of the data to be transferred, possible values: 0 = byte 1 = word 2 = double word b) ACCU-3-LL Current page number, possible values: 0 to 255 c) ACCU-2-L Destination address on the page, possible values: 0 to 2047 d) ACCU 1 Data to be written (byte, word, double word: right-justified) CPU 928B Programming Guide 6 - 82 C79000-B8576-C898-01 OB 216 to OB 218: Page Access ACCU contents before writing: High word High byte Low byte ACCU 4 x ACCU 3 Low word High byte Low byte x x x x x Length ID Page number 0: byte (8 bits) 0 to 255 1: word (16 bits) 2: double word (32 bits) Address (relative to start of page) ACCU 2 0 ... 2047 if length ID 0 (byte) x x 0 ... 2046 if length ID 1 (word) 0 ... 2044 if length ID 2 (double word) x data (8 bits) x ACCU 1 6 data (16 bits) data (32 bits) 31 Fig. 6-13 24 23 16 15 8 7 0 ACCU contents before calling OB 216 Result * If the data is written to the page correctly: - ACCU 1 and ACCU 3: remain unchanged. - ACCU-2-L: contains a value incremented by 1, 2 or 4 (depending on the length of the data transferred) - R LO: =1 - the remaining bit and word condition codes: are cleared * If the data cannot be written to the page - all ACCUs: remain unchanged - R LO: =0 - all remaining bit and word condition codes: are cleared. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 83 OB 216 to OB 218: Page Access Possible errors * wrong length ID in ACCU-3-LH * destination address on the page is wrong or does not exist * specified page number does not exist 6.21.2 OB 217: Reading from a Page Function The special function organization block transfers a byte, word or double word from a specific page to ACCU 1 (right-justified). Addressing the page in the single and multiprocessor modes and transferring the complete data (1, 2 or 4 bytes) form a single program unit that must not be interrupted. Parameters Accus a) ACCU-3-LH Identifier of the data to be transferred, permitted values: 0 = byte 1 = word 2 = double word b) ACCU-3-LL Current page no., permitted values: 0 to 255 c) ACCU-2-L Source address of the page, permitted values: 0 to 2047 CPU 928B Programming Guide 6 - 84 C79000-B8576-C898-01 OB 216 to OB 218: Page Access ACCU contents before reading: High word High byte Low byte ACCU 4 x ACCU 3 Low word High byte Low byte x x x x x Length ID Page number 0: byte (8 bits) 0 to 255 1: word (16 bits) 2: double word (32 bits) Address (relative to start of page) 0 + 1... 2047 + 1 for length ID 0 (byte) x ACCU 2 x 0 + 2 ... 2046 + 2 for length ID 1 (word) 6 0 + 4 ... 2044 + 4 for length ID 2 (double word) x data (8 bits) x ACCU 1 data (16 bits) data (32 bit) 31 Fig. 6-14 24 23 16 15 8 7 0 ACCU contents before calling OB 217 Result * If the OB reads from the page successfully, - ACCU 1: (right-justified) contains the value read (the remaining bits up to maximum 32 are cleared), - ACCU 3: remains unchanged, - ACCU-2-L: contains a value incremented by 1, 2 or 4 (depending on the length of the data transferred), - R LO: = 1, - the remaining bit and word condition codes: are cleared. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 85 OB 216 to OB 218: Page Access * If the OB cannot read from the page, - all ACCUs: remain unchanged, - R LO: = 0, - all other bit and word are cleared. condition codes: Possible errors * wrong length ID in ACCU-3-LH * source address on the page is wrong or does not exist * specified page number does not exist 6.21.3 OB 218: Reserving a Page The special function organization block transfers the number of the CPU to a particular page, providing the contents of the memory location addressed on this page are zero. As long as the CPU number is entered in this location, the page is reserved for this CPU and cannot be used by other CPUs. Organization block OB 218 is used to synchronize data transfer and is particularly important when large blocks of d ata must be transmitted as one unit. In the multiprocessor mode, no more than 4 bytes are transferred per bus allocation. Reserving a page is therefore advantageous. Addressin g the page, reading and, if applicable, writin g the slot identifier is one program unit that must not be interrupted. Parameters Accus a) ACCU-2-LL Number of the page to be reserved, permitted values: 0 to 255 b) ACCU-1-L Destination address on the page, permitted values: 0 to 2047 (The contents of ACCU 3 and 4 are irrelevant.) CPU 928B Programming Guide 6 - 86 C79000-B8576-C898-01 OB 216 to OB 218: Page Access Accu assignments before calling OB 218: Low word High word High byte ACCU 2 x x ACCU 1 x x 31 Fig. 6-15 High byte Low byte 24 23 Low byte Page number 0 to 255 x Address (relative to start of page) 0...2047 16 15 8 7 0 ACCU contents before calling OB 218 Result * If the page is reserved successfully: - all ACCUs: remain unchanged - RLO: =1 - the remaining bit and condition codes: are cleared. 6 * If the page cannot be reserved: - all ACCUs: remain unchanged, - R LO: = 0, - all other bit and word condition codes: Possible errors are cleared. * incorrect length ID in ACCU-3-LH * source address on the page is incorrect or does not exist * specified page number does not exist. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 87 OB 216 to OB 218: Page Access 6.21.4 Program Example Task You want to write data words 4 to 11 via the 923C coordinator from the DB 45 of a CPU 928B to the DX 45 (data words 0 to 7) of a second CPU 928B. You want to synchronize the sender and receiver (in the multiprocessor mode) using OB 218. Current page on the coordinator: no. 255 Coordination location on the page (reserved): addr. 53 Data transfer area of the page (reading and writing): addr. 54-69 STEP 5 operations in the SENDER: :L :L :JU :JC KB 255 KB 53 OB218 =M001 :BEU M001 :C DB 45 :L KY 2,255 :L KB 54 :ENT :L DD 4 :JU OB 216 : :TAK : :L DD 6 :JU OB 216 :TAK : :L DD 8 :JU OB 216 :TAK : :L DD 10 :JU OB 216 : :L KY 0,255 :L KB 53 :ENT :L KB 0 :JU OB 216 :BE Page number Address of the coordination cell Transfer the slot ID to the cell on the page If RLO = 1 (transfer successful), jump to label Else block end Open the source data block 2=length ID double word, page number Start address on page Write to ACCU 3 Data words 4 and 5 (= 4 bytes) Transfer the 1st double word Increment address by 4 (ACCU-2-L = 58) Save the destination address Transfer the 2nd double word Transfer the 3rd double word Transfer the 4th double word Address with slot ID ACCU 1 = 0 Clear slot ID, release data transfer area Continued on the next page CPU 928B Programming Guide 6 - 88 C79000-B8576-C898-01 OB 216 to OB 218: Page Access Continuation of the example: STEP 5 operations in the RECEIVER: :L :L KB 255 KB 53 :JU OB 218 :JC :BEU : M002 :CX :L :L :ENT :L : :JU : :T :JU :T : :JU :T : :JU :T : :L :L :ENT :L :JU : :BE =M002 DX 45 KY 2,255 KB 54 KB0 OB 217 DD 0 OB 217 DD 2 Page number Coordination cell Page reserved by 2nd CPU If RLO = 1, jump to label Destination data block Write to ACCU 3 Write to ACCU 2 Read 1st double word Increment the address by 4 (ACCU 2-L = 58) Transfer ACCU 1 to data word 0 and 1 Read 2nd double word 6 OB 217 DD 4 Read 3rd double word OB 217 DD 6 Read 4th double word KY 0,255 KB 53 KB 0 OB 216 Address with slot ID ACCU 1 = 0 Clear slot ID, release data transfer area CPU 928B Programming Guide C79000-B8576-C898-01 6 - 89 OB 220: Sign Extension 6.22 OB 220: Sign Extension Application A sign extension is necessary to extend a negative 16-bit fixed point number to a 32-bit fixed point number before performing a fixed point-floating point conversion (32 bits, operation FDG). Function This special function extends the sign of a 16-bit fixed point number in ACCU-1-L to the more significant word (ACCU-1-H): 15 * If bit 2 = 0 (positive number), the more significant word is loaded with KH = 0000. 15 * If bit 2 = 1 (negative number), the more significant word is loaded with KH = FFFF. Parameters ACCU-1-L 16-bit fixed point number Result ACCU-1-H is loaded into ACCU-1-L according to the sign of the fixed-point number (see above). Possible errors none CPU 928B Programming Guide 6 - 90 C79000-B8576-C898-01 OB 221: Setting the Cycle Monitoring Time 6.23 OB 221: Setting the Cycle Monitoring Time Function By calling this special function, you can modify the cycle monitoring time and change the maximum permitted cycle time. As standard, the cycle monitoring time is set to 150 ms. Along with this call, the timer for the cycle time monitoring is restarted. The maximum permitted cycle time for the cycle in which OB 221 is called, is extended by the newly selected value, calculated from the time when the special function call took place. The cycle monitoring time of all subsequent cycles corresponds to the newly selected value (= the time value that you transfer in ACCU 1). Parameters ACCU 1 a) ACCU-1-L new cycle time (in milliseconds), permitted values 1 ms - 13000 ms, positive fixed point number (KF) 6 b) ACCU 1-H ACCU-1-H must have the v alue " 0" Result The new cycle monitoring time is set after correct processing of OB 221. Possible errors The cycle monitoring time you have specified is not within the range 1 ms - 13000 ms. The function is not executed. The system program recognizes a runtime error and calls OB 31. The other reactions to the error depend on how you have programmed OB 31 (see Section 5.6.2). If OB 31 is not loaded, the CPU goes to the STOP mode. In both cases, the error identifier 1A3AH is entered in ACCU-1-L. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 91 OB 222: Restarting the Cycle Monitoring Time 6.24 OB 222: Restarting the Cycle Monitoring Time Function The special function OB 222 retriggers the cycle monitoring time, i.e. the timer for the monitoring is restarted. After you call this special function, the maximum permitted cycle time for the current cycle is extended by the selected value from the time of the call. Parameters none Possible errors none CPU 928B Programming Guide 6 - 92 C79000-B8576-C898-01 OB 223: Comparing Restart Types 6.25 OB 223: Comparing Restart Types Function If you call OB 223 in multiprocessor operation, the system checks whether the restart types of all CPUs involved are the same. Note OB 223 must only be called when all the CPUs have completed their start up. If start-up synchronization is active (DX 0) this is guaranteed by calling OB 223 in the RUN mode. If start-up synchronization is in active this must be achieved by other means, e.g. delayed OB 223 call. Parameters none 6 Result Error messages in the event of deviating restart types Possible errors If the restart types of all the CPUs participating in multiprocessor mode are not the same, the CPU in which OB 223 is processed detects a runtime error. OB 31 is then called. If OB 31 is not loaded, the CPU goes to the STOP mode with the LZF error message. Its STOP LED flashes slowly. The other CPUs also go to the STOP mode, their LEDs show a steady light. Error IDs When OB 31 is called and the CPU is in the STOP mode, the error ID 1A3B H is entered in ACCU-1-L. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 93 OB 224: Transferring Blocks of Interprocessor Communication Flags 6.26 OB 224: Transferring Blocks of Interprocessor Communication Flags Function The interprocessor communication (IPC) flags are transferred at the end of the program cycle. In the single processor mode, the IPC flags are transferred completely as a block of data to the memory on the coordinator or the CP and/or from this memory to the flags of the CPU. The S5 bus is always available. In multiprocessor operation, on the other hand, each CPU can only use the bus when it is allocated by the coordinator. Each time the CPU has access to the bus, only one byte is transferred. Following this, it is once again the turn of the other CPUs. Sets of data that belong together but that are distributed over several flag bytes are therefore separated. If you call organization block OB 224, you can transfer all the IPC flags specified in DB 1 of the CPU as a block of data. As long as a CPU is transferring IPC flags, it cannot be interrupted by another CPU. Since the next CPU has to wait before it can transfer its data, the cyclic program execution is delayed (cycle time!). OB 224 ensures the consistency of the IPC flag information. It must be called in the start-up program as follows: * in all the CPUs involved in IPC flag transfer and * in each restart type being used. Parameters none Possible errors none CPU 928B Programming Guide 6 - 94 C79000-B8576-C898-01 OB 226: Reading a Word from the System Program 6.27 OB 226: Reading a Word from the System Program Function The system program of the CPU is 128 x 210 words long and is located in a memory area that you cannot access with STEP 5 statements. Using OB 226, however, you can read individual data words from this memory area. Note For using OB 226, please see the description of OB 227 and the relevant programming example. Parameters ACCU 1 Address of the system program memory location to be read permitted values 0 to 0001 FFFF H 6 Result Possible errors - ACCU-1-L: contains the word read from the system program - ACCU-1-H: =0 - ACCU 2 contains the previous contents of ACCU 1 (i.e. the address); the previous contents of ACCU 2 are lost. none CPU 928B Programming Guide C79000-B8576-C898-01 6 - 95 OB 227: Reading the Checksum of the System Program 6.28 OB 227: Reading the Checksum of the System Program Application During cyclic program execution, you can check the contents of the system program as follows: * read the individual memory cells of the system program from address 0H to address 1DFFFH using OB 226, * add all the memory locations using fixed point addition (operation +F), ignoring overflows, * read the checksum using OB 227 and * compare the total obtained by the fixed point addition with the checksum read out by OB 227. Function The special function organization block OB 227 loads the checksum of the system program from the memory area of the system into ACCU 1. The word it reads out corresponds to the total of all memory cells of the system program from address 0H to address 1DFFFH. Parameters none Result - ACCU 1: contains the read out checksum right-justified (1 word); the remaining contents of ACCU 1 are cleared - ACCU 2: contains the previous contents of ACCU 1; the previous contents of ACCU 2 are lost. Possible errors none CPU 928B Programming Guide 6 - 96 C79000-B8576-C898-01 OB 227: Reading the Checksum of the System Program Example Checking the checksum of the system program Function block FB 111 is programmed for checking the checksum of the system program. FB 111 generates the checksum of the contents of all system program memory words and compares this checksum via OB 227 with the system program checksum stored in the system memory. If the checksums are not identical, the FB terminates in a STOP operation. FW 250 = checksum FD 252 = address counter FB111 NAME: CHECKSUM : : :L KH :T FW :T FD : M001 :JU OB :L FD 0000 250 252 222 252 :JU OB 226 :L :+F :T : :L :L :+D :T F : :L :>< :JC : FW 250 FW 250 :JU FD 252 KF+1 clear checksum flags clear address counter restart the cycle monitoring time load the address of the memory cell to be read read word load the checksum flags add store the checksum flags increment the address counter add double word D 252 DH 0001E000 if address counter is not equal to '1E000H' D =M001 jump to label M001 OB : :L FW :!=F :BEC : :STP :BE 227 read checksum if address counter equals '1E000H', 250 load checksum flags if equal, block end if not equal, stop operation CPU 928B Programming Guide C79000-B8576-C898-01 6 - 97 6 OB 228: Reading Status Information of a Program Processing Level 6.29 OB 228: Reading Status Information of a Program Processing Level Function If a particular event occurs, the system program calls the corresponding program processing level. The program processing level is then "activated". Using organization block OB 228, you can find out whether a specific program processing level is active or not at a particular time. Transfer the number of the program processing level whose status you want to scan to ACCU 1. (The numbers are those entered under LEVEL in the ISTACK). When the block is called, it stores the status information of the specified program level in ACCU-1-L. By evaluating this information, you can make your program execution dependent on the status of another program processing level. Parameters ACCU-1-L Number of the program processing level (see ISTACK, LEVEL) possible values (hexadecimal): see following table Level no. in ACCU-1-L 02 04 06 08 0A 0C 0E 10 12 14 16 18 1A 1C 1E 20 22 24 Level name COLD RESTART CYCLE TIME INTERRUPT 5 sec TIME INTERRUPT 2 sec TIME INTERRUPT 1 sec TIME INTERRUPT 500 ms TIME INTERRUPT 200 ms TIME INTERRUPT 100 ms TIME INTERRUPT 50 ms TIME INTERRUPT 20 ms TIME INTERRUPT 10 ms TIMED JOB Not used CONTROLLER INTERRUPT Not used Not used Not used PROCESS INTERRUPT Level no. in ACCU-1-L 26 28 2A 2C 2E 30 32 34 36 38 3A 3C 3E 40 42 44 46 Level name Not used Not used Not used Abort Interface error Collision of time interrupt Controller error Cycle error Not used Operation code error Runtime error Addressing error Timeout Not used Not used MANUAL WARM RESTART AUTOMATIC WARM RESTART CPU 928B Programming Guide 6 - 98 C79000-B8576-C898-01 OB 228: Reading Status Information of a Program Processing Level Result Possible errors - ACCU-1-L: contains the status information: = 0 Program processing level has not been called 0 Program processing level has been activated - ACCU-2-L: contains the previous contents of ACCU-1-L; the previous contents of ACCU-2-L are lost none Example 6 You want to ignore a timeout during the COLD RESTART, however, not in the remaining program processing levels. Call special function organization block OB 228 at the beginning of OB 23 to check whether program processing level COLD RESTART (number 02) is active or not when a QVZ (timeout) occurs. You can make the reactions to the error dependent on the status information you obtain as follows: ACCU 1= 0: COLD RESTART not active ACCU 1 0: COLD RESTART activated QVZ has not occurred in COLD RESTART, but in another program processing level Error handling program must be executed QVZ has occurred in COLD RESTART QVZ can be ignored Using OB 228, you can differentiate between various error situations. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 99 OB 230 to 237: Functions for Standard Function Blocks 6.30 OB 230 to 237: Functions for Standard Function Blocks The special function organization blocks OB 230 to OB 237 are reserved for data handling functions and can only be called in the standard function blocks FB 120 to FB 127. Data handling blocks These standard function blocks, the data handling blocks known simply as "handling blocks", control the data exchange via the page area in the single and multiprocessor modes. They are used when data or parameters and control information are transferred to or from the communications processors (CPs). Assignment aid You can use the table below to find out which handling blocks call the special function organization blocks OB 230 to OB 237. Using the handling blocks Standard function block Special function Organization block Handling block FB 120 SF-OB 230 SEND FB 121 SF-OB 231 RECEIVE FB 122 SF-OB 232 FETCH FB 123 SF-OB 233 CONTROL FB 124 SF-OB 234 RESET FB 125 SF-OB 235 SYNCHRON FB 126 SF-OB 236 SEND ALL FB 127 SF-OB 237 RECEIVE ALL The use of the handling blocks, that can be ordered as a software product on diskette, is described in the manual "S5 135U programmable controller, handling blocks for the R processor and CPU 928/928B" /5/ in Chapter 13). CPU 928B Programming Guide 6 - 100 C79000-B8576-C898-01 OB 240 to 242: Special Functions for Shift Registers 6.31 OB 240 to 242: Special Functions for Shift Registers 6.31.1 Shift Registers Application This introduction tells you what you can use shift registers for and the points to note in doing so. You can use shift registers, e.g. in a manufacturing process, to program a materials follow-up on the programmable controller. On the CPU 928B, you have a maximum of 64 software shift registers available. You can write data to the shift register and read data from it. This is done using "pointers". Pointers are flag bytes that contain the contents of individual cells of a shift register. Structure A software shift register consists of rows of 8-bit wide memory cells and can be between 2 and 256 memory cells long. Location in the DB-RAM The data of a shift register are located in the data block RAM of the CPU. Each shift register is assigned to a specific data block and also has the same number as the data block (permitted: 192 to 255). If you set up a shift register with the number 210, the corresponding data is in data block DB 210. The DB-RAM has a capacity of 46 Kbytes (address KH 8000 to KH DD7F). This area contains the data blocks (starting from KH 8000 in ascending order) copied using OB 254 and 255 and the shift registers you have set up (starting from KH DD7F in descending order). If the memory area of the DB RAM is not sufficient for copying DBs or setting up shift registers, the CPU recognizes a runtime error and calls OB 31. The reactions to the error depend on how you have programmed OB 31 (see Section 5.6.2). The following schematics illustrate the principle of a software shift register with three pointers and twelve memory cells. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 101 6 OB 240 to 242: Special Functions for Shift Registers Pointer 1 Pointer 2 Pointer 3 Flag bit 0 Flag bit 1 Flag bit 2 Flag bit 3 Flag bit 4 Flag bit 5 Flag bit 6 Flag bit 7 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 1 Fig. 6-16 2 3 4 5 6 7 8 9 10 11 12 Schematic showing the principle of a shift register with 3 pointers and 12 memory cells Initializing When you initialize a shift register (see Section 6.31.2), you specify the number of the flag byte for pointer 1 (= base pointer). This is then set permanently on the first memory cell of the shift register. You then position all the other pointers relative to the base pointer (you can use between one and a maximum of six pointers per shift register). Shifting When you shift a shift register (like a hardware shift register), the total contents of all the shift register cells are transferred in bytes from one memory cell to the next (see Fig. 6-17). Each time the shift register function is called, the information is shifted one memory cell (corresponds to one clock pulse), and the pointers are supplied with new contents. As shown by the arrows, the information is shifted through the complete shift register to the last memory cell from where it returns to memory cell 1 (after 12 clock pulses for the shift register illustrated in the schematic). CPU 928B Programming Guide 6 - 102 C79000-B8576-C898-01 OB 240 to 242: Special Functions for Shift Registers Example Figures 6-17 and 6-18 illustrate the shifting of information within a shift register with three pointers and twelve memory cells. Before the special function is called, certain bits are set in the pointers (flags) to identify the pointer information, as follows: Set flag bit 0 of pointer 1 :S F 0.0 Set flag bit 3 of pointer 2 :S F 1.3 Set flag bit 2 of pointer 3 :S F 2.2 The shift register function is then called Pointer 1 Pointer 2 Pointer 3 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 1 Fig. 6-17 1 1 1 1 0 0 0 0 2 0 0 0 0 1 1 1 1 3 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 5 1 1 1 1 1 1 1 1 6 7 0 1 0 1 0 1 0 1 8 0 0 0 0 0 0 0 0 9 10 :JU Flag Flag Flag Flag Flag Flag Flag Flag 0 0 0 0 0 0 0 0 11 bit bit bit bit bit bit bit bit OB 241 0 1 2 3 4 5 6 7 6 Bit Bit Bit Bit Bit Bit Bit Bit 1 0 1 0 1 0 1 0 12 0 1 2 3 4 5 6 7 Schematic showing the principle of a shift register with 3 pointers and 12 memory cells before the first clock pulse After calling the special function, the 8-bit wide information of the memory cells is shifted by one cell, as shown below: Pointer 1 Pointer 2 Pointer 3 1 0 1 0 1 0 1 0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 Fig. 6-18 1 0 0 0 0 0 0 0 2 1 1 1 1 0 0 0 0 3 0 0 0 0 1 1 1 1 4 0 0 0 0 0 0 0 0 5 0 0 0 0 0 0 0 0 6 7 0 0 0 1 0 0 0 0 8 0 1 0 1 0 1 0 1 9 10 Flag Flag Flag Flag Flag Flag Flag Flag 0 0 1 0 0 0 0 0 11 0 0 0 0 0 0 0 0 12 bit bit bit bit bit bit bit bit 0 1 2 3 4 5 6 7 Bit Bit Bit Bit Bit Bit Bit Bit 0 1 2 3 4 5 6 7 Schematic showing the principle of a shift register with 3 pointers and 12 memory cells after the first clock pulse Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 6 - 103 OB 240 to 242: Special Functions for Shift Registers Continuation of the example: You can now evaluate the information in the pointers as follows: :L FY 0 : etc. Flag bits 0, 3 and 2 can be scanned at the base pointer: in this way, you can evaluate all the information from the entries in all pointers at the base pointer (in the example, this requires twelve clock pulses). Organization blocks If you want to use a shift register, there are three special function organization blocks available: * OB 240: This funciton initializes a shift register. * OB 241: This function processes a shift register. * OB 242: This function deletes a shift register. CPU 928B Programming Guide 6 - 104 C79000-B8576-C898-01 OB 240 to 242: Special Functions for Shift Registers 6.31.2 OB 240: Initializing Shift Registers Application Before processing a shift register, you must first initialize it. This is done by calling OB 240 once (ideally in a restart organization block). The parameters that OB 240 requires to create a shift register are contained in a data block with the number of the shift register to be initialized. DB numbers between 192 and 255 are permitted. Function A specific memory area at the end of the DB-RAM is reserved and initialized with the information from the opened data block. Parameters opened data block possible values: 6 DB no. 192 to 255 The data block has a fixed structure which you must not change. It can have a maximum length of 9 data words (DW 0 through DW 8). 0 DW 0 Shift register length (bytes) L DW 1 Number of the 1st flag byte/base pointer Interval n 2 DW 3 Interval n 3 DW 4 Interval n 4 DW 5 Interval n 5 DW 6 Interval n 6 DW 7 0 Fig. 6-19 DW 2 DW 8 or last data word Structure of the data block for initializing a shift register CPU 928B Programming Guide C79000-B8576-C898-01 6 - 105 OB 240 to 242: Special Functions for Shift Registers The individual data words must be assigned as follows: Data word 0 Must always contain the value 0. Data word 1 The shift register length L is the number (in bytes) of memory locations of the shift register. It can be within the range between 2 L 256. Data word 2 The number of the first flag byte determines the base pointer and with it the block of flags assigned to the pointers. The block of flags contains the total number of pointers you have selected. You select pointers by making entries in data words DW 3 to maximum DW 7, using one data word per pointer. If, for example, you want to set up two further pointers, you then have a total of three pointers. Make sure that you have enough flags available for all pointers up to the end of the block of flags. Data word 3 to maximu m 7 You specify the other pointers indirectly. They are defined by their distance (shift register cells = number of bytes) from the base pointer. n2 = distance from pointer 2 to base pointer n3 = distance from pointer 3 to base pointer n4 = distance from pointer 4 to base pointer etc. (1 to maximum 5 entries) Last d ata word (D W 4 to maximum DW 8) (in the example DW 8). This must always contain the value zero. If you only select two additional pointers, the "0" is in data word DW 5 etc. All the information is specified as fixed point numbers. CPU 928B Programming Guide 6 - 106 C79000-B8576-C898-01 OB 240 to 242: Special Functions for Shift Registers Note The number of pointers (6 including the base pointer) must not exceed the length of the shift register. The distance of a pointer to the base pointer must not exceed the length of the shift register. Data word D W 0 and the data word after the last pointer distance must always contain 0 . The data block must be open before OB 240 is called. The data block must have a number in the range DB 192 to DB 255 . Memory requirements n = shift register length/2 + 8 data words are required for every shift register, i.e. the length of the DB RAM is reduced by n data words. The data block RAM end address is shifted to lower addresses. If you attempt to initialize a shift register that already exists, the area already assigned will be initialized again providing the new and old shift registers both have the same length. Otherwise the old area will be declared invalid and a new area will be opened. Possible errors * illegal data block number (<192) * not enough memory space in the DB RAM * formal error in the structure of the data block * illegal length specified for the shift register * errors in the pointer parameters In the event of an error, the CPU recognizes a runtime error and calls OB 31. What happens then depends on how you have programmed OB 31 (see Section 5.6.2). If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L that describe the error in greater detail. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 107 6 OB 240 to 242: Special Functions for Shift Registers 6.31.3 OB 241: Processing Shift Registers The special function organization block OB 241 processes a shift register providing it has been initialized by OB 240. In the CPU 928B, you can call a maximum of 64 shift registers. Application Before you call OB 241, certain flag bits are usually set/reset in the pointers. Each time OB 241 is called, the information is shifted byte by byte from one memory cell to the next higher memory cell. The pointers are then supplied with new contents. By repeatedly calling OB 241, the information can be shifted through the complete shift register to the last memory cell. From here, it is then transferred to memory cell 1. Function Each time OB 241 is processed, the shift register addressed via ACCU-1-L is shifted one position to the right. Parameters ACCU-1-L Number of the shift register to be processed, permissible values: 192 to 255 Result After you call OB 241, the pointers (maximum 6 per shift register) that can be positioned as required with the exception of the base pointers contain the information of the preceding memory cell. You can then evaluate this information. Possible errors * illegal shift register number in ACCU 1 * shift register not initialized. In the event of an error, the CPU recognizes a runtime error and calls OB 31. What happens then depends on how you have programmed OB 31 (see Section 5.6.2). If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L that describe the error in greater detail. CPU 928B Programming Guide 6 - 108 C79000-B8576-C898-01 OB 240 to 242: Special Functions for Shift Registers 6.31.4 OB 242: Deleting a Shift Register Function Parameters With this function, you can delete a shift register in the data block RAM. The entry in the DB 0 address list is cleared and the shift register is declared invalid in the DB RAM (remember: shift registers still occupy memory space after they have been deleted). ACCU-1-L Number of the shift register to be deleted, possible values: 192 to 255 6 Result After you call OB 242, the shift register is deleted and can no longer be used; if you want to work with it again, it must be reinitialized. Possible errors * illegal shift register number in ACCU 1 * shift register not initialized In the event of an error, the CPU recognizes a runtime error and calls OB 31. What happens then depends on how you programmed OB 31 (see Section 5.6.2). If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L that describe the error in greater detail. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 109 OB 250/251: Closed-Loop Control/ PID Algorithm 6.32 OB 250/251: Closed-Loop Control/ PID Algorithm You can work with one or more PID controllers in the CPU 928B of the S5-135U. Each controller must be initialized in the restart organization block. A data block is used to transfer the parameters. The actual control algorithm is integrated in the system program and you can simply call it as an organization block. A data block is used as the data interface between the control algorithm and the user program. 6.32.1 Functional Description of the PID Controller Manual input: Input of YH when S3 set to 0 Input of dYH when S3 set to 1 Z 0 1 S4 0 S2 Auto W dY X XZ XW Y 0 S3 YA (S3 set to 0) LL S1 1 K Fig. 6-20 dYA (S3 set to 1) PID algorithm 0 UL 1 R TI TD Block diagram of the PID controller CPU 928B Programming Guide 6 - 110 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm Index k k times samplin g Switch S1 CONTROL BIT 1 Settin g 0 1 S2 CONTROL BIT 0 S3 CONTROL BIT 3 S4 CONTROL BIT 5 Effect The system error XWk is supplied to the derivative unit. The derivative unit can be supplied with another signal via XZ. 0 Manual operation 1 Automatic 0 Position algorithm 1 Velocity algorithm 0 With feedforward control 1 Without feedforward control 6 STEU control word You obtain a function corresponding to the switch settings of the block diagram by assigning parameters to the PID controller, i.e. by setting the control bits in the control word STEU. The continuous controller is intended for fast control systems, e.g. in process engineering for pressure, temperature or flow rate control. PID algorithm The controller itself is based on a PID algorithm. Its output signal can either be output as a manipulated variable (position algorithm) or as a change of manipulated variable (velocity algorithm). You can disable the individual P, I and D actions by setting their parameters R, TI and TD to zero. This allows you to implement any controller structure you require, e.g. PI, PID or PD controllers. Differentiator You can supply the derivative unit either with the system error XW or a disturbance or the inverted actual value -x can be supplied via the XZ input. Disturbance compensation If you require a precontrol of the actuator without dynamic behaviour to compensate for the influence of a disturbance, then a disturbance Z measured in the process can be fed forward to the control algorithm. In manual operation, this is replaced by the preselected manipulated variable YM. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 111 OB 250/251: Closed-Loop Control/ PID Algorithm Inverted control direction If you require an inverted control direction, preset a negative K value. Limiting the control information If the control information (dY or Y) reaches a limit, the I action is automatically disabled in order to prevent deterioration of the controller response. You can supply the control program with preset fixed values or with adaptive (dynamic) parameters (K, R, TI, TD). These are input via the memory cells assigned to the individual parameters. 6.32.2 PID Algorithm The PID controller is based on a velocity algorithm according to which the control increment dYk is calculated at time t = k * TA, according to the following formula: dYk=K [ (XW k - XW k-1) R + TA (XWk + XWk-1) + 2TN 1 TV (XUk - 2XUk-1 + XUk-2) + dDk-1 ] 2 TA =K ( dPWkR + dIk + dDk ) dXXXk: change in variable XXX at time t. U can be either W or Z, depending on whether XW or XZ is supplied to the derivative unit. The following applies: If XWk is supplied: If XZ is supplied: PWk = Wk - Xk PWk = XWk - XWk-1 PZk = XZk - XZ k-1 QWk = PWk - PWk-1 QZk = PZk - PZ k-1 QWk = XWk - 2XWk-1 + XWk-2 QZk = XZk - 2XZ k-1 + XZ k-2 CPU 928B Programming Guide 6 - 112 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm dPWk = (XWk - XW k-1)R dIk = TI XWk dDk = TI= TA TN 1 (TD QUk + dDk-1) 2 TD = TV TA If you require the manipulated variable Yk at the controller output at time tk, it is calculated according to the following formula: m=k Yk = dYm m=o 6 With most controller structures, it is assumed that R = 1 if a P action is required. Using the variable R, you can adjust the proportional action of the PID controller. Data blocks for the PID controller Controller-specific data are input using a transfer data block (see Sections 6.32.3 and 6.32.4) for initialization and processing of the PID controller. You must specify these data in the transfer data block x: K, R, TI, TD, W, STEU, YH, ULV, LLV The transfer data block must contain data words 0 to 48, i.e. it is 49 data words long. The following table explains the significance of these data words. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 113 OB 250/251: Closed-Loop Control/ PID Algorithm Structure of the transfer data block Table 6-10 Addr. in DB Transferring the data block for PID control Name I/O 1) Numerical format PG format Remarks 3) 2) DW0 -- -- -- -- Reserve DD 1 K I FLP KG Proportional cooefficient K >0: Positive control direction, i.e. change of actual value and manipulated variable in same direction K <0: Negative control direction, floating point number range DD 3 R I FLP KG R parameter, usually equals 1 for controllers with P action DD 5 TI I FLP KG TI = TA/TN DD 7 TD I FLP KG TD = TV/TA DD 9 Wk I FLP KG Setpoint input here, when control bit 6 = 1, otherwise in word no. 19 (-1 Wk <1) DW11 STEU I FLP KM Control word DD 12 YHk I FLP KG Manual input here, when control bit 6 = 1; otherwise in word no. 18 (-1 YHk <1) For velocity algorithms, you must specifiy manipulated variable increments here DD14 ULV I FLP KG 4) Upper limit value -1 ULV 1 (YAk max); !! LLV < ULV !! DD 16 LLV I FLP KG 4) Lower limit value -1 LLV 1 (YAk min) DW18 YHk I NF KF Manual input here, when control bit 6 = 0 (-1 YH < 1). For velocity algorithms, you must specify manipulated variable increments here DW19 Wk I NF KF Setpoint input here, when control bit 6 = 0 (-1 Wk < 1) DW 20 MERK I BP KM Bit 0 = 1: positive limit exceeded; Bit 1 = 1: below negative limit DW 21 Xk I NF KF Actual value input for control bit 7 = 0 (-1 Xk <1) DD 22 Xk I FLP KG Actual value input for control bit 7 = 1 (-1 Xk <1) DW 24 Zk I NF KF Disturbance (-1 Zk <1) DD 25 Zk I FLP KG Disturbance input here, if control bit 7 = 1 (-1 Zk <1) CPU 928B Programming Guide 6 - 114 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm Addr. in DB Name I/O 1) Numerical format PG format Remarks 3) 2) Table 6-10 continued: DD 27 Zk-1 I FLP KG Historical value of the disturbance DW 29 XZk I NF KF Value supplied to the derivative unit via input XZ (-1 XZ k <1); input here, if control bit 7 = 0 DD 30 XZk FLP KG XZ input here, if control bit 7 = 1 (-1 XZ k <1) DD 32 XZk-1 I FLP KG Historical value of XZk DD 34 PZ k-1 I FLP KG XZ k-1 - XZ k-2 DD 36 dDk-1 -- FLP KG Derivative action DD 38 XWk-1 -- FLP KG Historical value of the system error DD 40 PW k-1 -- FLP KG XWk-1 - XWk-2 DW 42 -- -- -- -- Reserve DD 44 Yk-1 -- FLP KG Historical value of the calculated manipulated variable Yk-1 or dYk-1 before the limiter DD 46 YAk FLP KG Output variable DW 48 YAk NF KF Output variable ULV YA LLV 1) I = input, Q = output 2) FLP = floating point number, NF = normalized fixed point number (see page 6 - 103), BP = bit pattern 3) Suggested format (KH, KM also permitted) 4) In normalized fixed point format, the upper and lower limit value must be entered according to the following formulas: DD 14 = BGOG: Value as fixed point number = DD 16 = BGUG: 6 BGOG 32767 BGUG Value as fixed point number = 32767 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 115 OB 250/251: Closed-Loop Control/ PID Algorithm Example of limit values - Limit values Upper limit value = 0.1 Lower limit value = -0.1 - Entries in the DB: DD 14: *1000 000 +00 DD 16: -1000 000 +00 - Output variable is limited: DW 48: +-3276 DD 15: +-0.1 Note: For limit values outside 1, the output variable is limited in floating point format (DD 46). CPU 928B Programming Guide 6 - 116 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm Bit assignment of the control word STEU (data word DW 11 in the transfer DB) Table 6-11 D W 11 Bit no. Control word in the transfer DB Name Meanin g 11.0 AUTO = 1: = 0: Automatic operation Manual operation 11.1 XZ_INP =1: Another variable (not XWk), is supplied to the derivate unit by the input XWk is supplied to the derivate unit. The XZ input is ignored. = =: 11.2 DIS_CTR = 1: = 0: When the controller is called (OB 251) all variables (DW 20 to DW 48) except K, R, TI, TD, BGOG, BGUG, STEU, YHk, W k, Zk and Zk-1 are cleared once in the DB RAM. The controller is disabled. The historical value of the disturbance is updated. control 6 11.3 VELOC = 1: = 0: Velocity algorithm Position algorithm 11.4 1) MANTYPE = 1: If VELOC = 0 (position algorithm) the last manipulated variable to be output is retained. If VELOC is 1 (velocity algorithm) the control increment dYk = 0 is set. If VELOC = 0, then after switching to manual operation, the value of the manipulated variable output YA is brought to the selected manual value exponentially in four sampling steps. Following this, other manual variables are accepted immediately at the controller output. If VELOC = 1, the manual values are switched through to the controller ouptut immediately. In manual operation, the limits are effective. In manual operation the following variables are updated: = 0: Xk, SWk-1 and PW k-1 XZk, XZk-1 and PZ k-1, if control bit 1 = 1 Zk and Zk-1, if control bit 5 = 0 The variable dDk-1 is set to = 0. The algorithm is not calculated. 11.5 NO_Z = 1: = 0: no feedforward control with feedforward control 11.6 PGDG = 1: = 0: Wk, YHk input as floating point number Input as normalized fixed point number 11.7 VAR_FLP = 1: = 0: The variables Xk, XZ k and Z k are input as floating point numbers Input of the variables as normalized fixed point numbers CPU 928B Programming Guide C79000-B8576-C898-01 6 - 117 OB 250/251: Closed-Loop Control/ PID Algorithm D W 11 Bit no. Name Meanin g Table 6-11 continued: 11.8 BUMP 11.9 to 11.15 = 1: = 0: No bumpless changeover from manual to automatic Bumpless changeover from manual to automatic Irrelevant 6.32.3 OB 250: Initializing the PID Algorithm Function OB 250 initializes the PID algorithm and is called in the restart OBs 20/21/22. Parameters The parameters required for the initialization are contained in the transfer data block (DB x). Note The transfer data block must be open before OB 250 is called. For data transfer, each controller requires its own DB x (x 254). From this, the system program automatically generates a further DB x + 1 in the data block RAM, that the controller uses as a data field in cyclic operation. This means that the corresponding DB numbers must still be available. Data blocks DB x + 1 represent the data interfaces between the controller and the user or peripheral I/Os. Possible errors Internally, OB 250 uses OB 254 or OB 255 (duplication of data blocks). In the event of an error, the CPU recognizes a runtime error and calls OB 31. If this is not programmed, the CPU goes to the stop mode. The error IDs entered in ACCU 1 then refer to OB 250. CPU 928B Programming Guide 6 - 118 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm Note If DB x + 1 is not kept free during the initialization, it will be used as a controller data field without any warning if its length is identical to that of a controller DB (49 data words); data words 20 through 48 are cleared. Otherwise the CPU goes to the stop mode. Instead of DB data blocks, you can also use DX data blocks. Initialization is the same as with DB data blocks. 6.32.4 OB 251: Processing the PID Algorithm Application OB 251 is called during cyclic program execution and processes the PID algorithm. Call The controller should be called after the sampling time has elapsed. Keep to the following order: Step Action 1 Call data block DB x + 1 2 Load input data Xk, XZk, Z k and YHk or a subset of these 3 Convert input data to the correct format and transfer it to DB x + 1 4 Call OB 251 (process PID controller) 5 Load the output data YAk from DB x + 1 6 Convert the data and transfer to the process I/Os CPU 928B Programming Guide C79000-B8576-C898-01 6 - 119 6 OB 250/251: Closed-Loop Control/ PID Algorithm Format of controller inputs and outputs Internally, the PID control algorithm uses the floating point format for numerical representation and can be supplied with floating point values. You can also supply the PID controller algorithm using the normalized fixed point format (see bits 6 and 7 in the control word STEU). In this case, the controller automatically converts the words to the floating point format with every call. Adaptation of words from the input and output modules in the STEP 5 program is faster if you use the normalized fixed point format (see table at the end of this section). Inputs You can input W, YH, X, Z and XZ as floating point or normalized fixed point numbers. Different memory cells are reserved for each variable in the data transfer block. Input as normalized fixed point numbers (For an explanation of the normalized fixed point numbers, see the table at the end of this section). Note While keeping within the nominal input ranges of the analog input modules, do not forget that the bit pattern for a certain input value is different from when you use the full input range. This is particularly important when you adjust the setpoint. Otherwise, it is possible that a setpoint input at the PG cannot be reached although the actual value is far higher than the desired value. If your analog-to-digital converter supplies negative numbers as a number and sign, the 2's complement of this number must be formed before it is transferred to the controller DB. Following this, the binary digit 15 must be set to 1. If the number -0 is possible as a number and sign in the following format: 1000000000000000 in your analog-to-digital converter, the 2's complement must not be formed. The number must be transferred to the controller DB as +0: 0000000000000000 Output The controller output YA exists in the DB as a normalized fixed point number and a floating point number. Taking into account the input and output modules used (analog-to-digital converter, digital-to-analog converter) the format must be converted for normalized fixed point inputs and outputs before and after the controller is called in the STEP 5 user program before values are transferred to or from the controller DB. CPU 928B Programming Guide 6 - 120 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm General notes Using BUMP If BUMP (control bit 8) is set to zero, the changeover from manual to automatic operation is bumpless, i.e. the system error, however large it may be, is corrected only by the I action. If, however, you have selected TI = TA/TN = 0 (P or PD controller) the system error does not cause a change of the manipulated variable when the changeover takes place. You can prevent this by setting BUMP = 1. This means that a system error is corrected quickly when there is a manual-to- automatic changeover, irrespective of TI = 0. The manipulated variable jump that results corresponds to the value of the system error, which means that it is not arbitrary in the sense of a disturbance of the controller operation. Displaying MERK, bits 0 and 1 Bits 0 and 1 of MERK can be displayed if required to show that the manipulated variable (for velocity algorithm, the control increment) lies between the upper and lower limits. Since these bits are evaluated by the algorithm for disabling the I action, you cannot overwrite them. Note You must not reload the controller data blocks DB x + 1 during cyclic operation . Cascade control If two or more controllers are cascaded, remember the following points: * If the cascade is split, either all the controllers have to change to manual operation simultaneously to prevent any controller drift due to the I action or at least the controller of the outer loop must be operated manually to ensure that the last manipulated variable corresponding to the setpoint of the inner loop is retained or changed to a safe value. * If you want to close the cascade, both loops should operate at the same time in the automatic mode or at least the inner loop to ensure that the manipulated variable of the outer loop is taken as the setpoint. Switching to manual mode If the control system is disconnected from the controller and directly adjusted at the actuator following the changeover to manual operation, the manipulated variable obtained must be supplied to the controller via the manual input. This ensures that when you change from manual to automatic operation, the controller output will correspond to the manipulated variable set during manual operation. In the case of the velocity algorithm, this will be the change in the manipulated variable. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 121 6 OB 250/251: Closed-Loop Control/ PID Algorithm Controller parameters P controller The parameter for a P controller is K. This is the quotient of the output and input value: K = Xout/Xin. X out X in t=0 t PI controller t=0 t The parameters for a PI controller are the proportional cooefficient K and the reset time TN. The proportional cooefficient K is the quotient of the output and input value and determines the P action. The reset time TN is the time required to respond to achieve the same change in the manipulated variable due to the I action as occurs due to the P action. X out X in t=0 PD controller t TN t=0 t The parameters for a PD controller are the proportional cooefficient K (see above) and the derivative time constant TV. The derivative time constant is the time a P controller would require at a constant rate of change of the input variable to bring about the same change in the output variable that is brought about immediately by the D action of a PD controller. To determine the derivative time constant, a linear change in the input variable is assumed and not a jump function. X out X in t=0 t t=0 TV t CPU 928B Programming Guide 6 - 122 C79000-B8576-C898-01 OB 250/251: Closed-Loop Control/ PID Algorithm PID controller The parameters for a PID controller are the proportional cooefficient K, the reset time TN and the derivative time constant TV. These in turn determine the P, I and D actions. Parameter changes The P action of the manipulated variable is obtained based on the following formula: P action = KP * (XWk - XWk-1) If KP or R are changed during automatic operation, this only affects subsequent changes of the system error XW k. The current value of the manipulated variable is not affected by the parameter change. This response allows for a bumpless change. If, however, you do not want this response, you can eliminate it using the following calculation, (example of a KP change). This calculation is only made once for each parameter change: Yk-1 = Yk-1 + XW k-1(KPnew - KPold) If you use the following program in the case of a parameter change, the controller responds like an analog controller. :L :L :-G :L :xG :L :+G :T Abbreviations for PID controllers dYk dZk FLP k K LL NF R TA TD TI t TN TV UL Wk Xk XWk Yk YAk Zk KPnew KPold load KPnew load KPold DD38 XWk-1 DD44 Yk-1 DD44 = Yk-1 Calculated control increment Disturbance increment Floating point representation k * sampling Proportional cooefficient Lower limit (limiter) Normalized fixed point representation R parameter Sampling time TV/TA TA/TN Sampling instant = k * TA Reset time Derivative time constant Upper limit (limiter) Setpoint Actual value System error Calculated manipulated variable Value of manipulated variable (control increment or manipulated variable) Disturbance CPU 928B Programming Guide C79000-B8576-C898-01 6 - 123 6 OB 250/251: Closed-Loop Control/ PID Algorithm Normalized fixed point numbers One word is required to represent a normalized fixed point number in a data block. The following example illustrates the difference between a fraction represented decimally, in binary and using the KF format on the programmer. Table 6-12 Fraction Fraction in Decimal representation Fixed point number Binary representation -0.999... . 1000000000000001 -32767 -0.75 1010000000000000 -24576 -0.5 1100000000000000 -16384 -0.25 1110000000000000 -8192 0 0000000000000000 0 +0.25 0010000000000000 + 8192 +0.5 0100000000000000 +16384 +0.75 0110000000000000 +24576 +0.999... . 0111111111111111 +32767 Negative normalized fixed point numbers in a binary representation are obtained by forming the 2's complement of the positive normalized fixed point number. Normalized fixed point numbers (NF) can be converted to the values represented in the programmer (KF) as follows: NF * 32767 = KF where -1 < NF <+1 and -32767 KF +32767 CPU 928B Programming Guide 6 - 124 C79000-B8576-C898-01 OB 254, OB 255: Transferring a Data Block to the DB RAM 6.33 OB 254, OB 255: Transferring a Data Block to the DB RAM Special function organization blocks OB 254 and OB 255 allow you to transfer data blocks from the user memory to the DB RAM (data block memory) of the CPU. The special functions OB 254 and 255 are identical; OB 254 is used for D X data blocks and OB 255 for DB data blocks. Application Shifting or duplicating a data block Function Shifting Shifting a data block from the user memory to the DB RAM A data block is shifted from the user memory to the DB RAM and retains its original block number. The new start address of the data block is entered in the address list in DB 0. Duplicating A data block in the user memory or in the DB RAM is duplicated in the DB RAM and assigned a new block number. The start address of the new data block is entered in the address list in DB 0. The start address of the old block is retained in DB 0, i.e. the original data block remains valid. The start address is only entered into DB 0 after the transfer is completed and all identifiers are entered correctly in the block header. The duplicated block is only accepted as valid or existing by the system program after it has been completely transferred. Note Shifting DB0 into the DB-RAM is not possible since it already exists in the DB-RAM. However, you can duplicate DB 0. CPU 928B Programming Guide C79000-B8576-C898-01 6 - 125 6 OB 254, OB 255: Transferring a Data Block to the DB RAM Parameters 1. ACCU-1-L-L Number of the data block to be shifted or duplicated, permitted values: 0 to 255 (0 only for DX or for duplicating DBs) 2. ACCU-1-H-L With the value in ACCU-1-H, you specify whether you want to shift or duplicate a block: ACCU-1-H-L = 0: the data block DB (OB 255 call) or DX with the number specified in ACCU-1-L-L is shifted to the DB RAM ACCU-1-H-L = number for new block, permitted values: 1 to 255 the data block DB (OB 255 call) or DX (OB 254 call) with the number specified in ACCU-1-L-L is duplicated in the DB RAM and entered in DB 0 with the number stored in ACCU-1-H-L. The values for ACCU-1-L-H and ACCU-1-H-H are not considered by OB 254 and OB 255 and are therefore not significant for assigning parameters to the OBs. Possible errors * The data block to be shifted does not exist (OB 19). * The block already exists in the DB RAM (OB 31). (therefore only execute the function once, ideally during the start-up). * Not enough memory space in the DB RAM (OB 31). In the event of an error, the function is not executed. The system program detects a runtime error and calls OB 19 or OB 31 . How the CPU reacts to the error depends on the way in which OB 19 or OB 31 are programmed (see Section 5.6.2). If OB 19 or OB 31 is not programmed, the CPU goes into the stop mode. In both cases, ACCU 1 contains an error identifier that defines the error in greater detail. CPU 928B Programming Guide 6 - 126 C79000-B8576-C898-01 OB 254, OB 255: Transferring a Data Block to the DB RAM Example It is assumed that the data blocks DB3 and DB4 are defined in the user memory. No DB should yet be present in the DB-RAM other than DB0. The following table shows the memory configuration after calling OB 255 several times with the parameters listed in the table. Order of call Function 1 Shift 2 Duplicate 3 Duplicate 4 Shift ACCU -1- DB in memory after call -H-H -H-L -L-H -L-L U ser mem. DB-RAM no 0 no 3 DB 4 DB 3 4 DB 4 DB 3,5 5 DB 4 DB 3,5,6 4 no DB DB 3,4,5,6 sig- 5 sig- 6 nificance 0 nificance 6 CPU 928B Programming Guide C79000-B8576-C898-01 6 - 127 Extended Data Block DX 0 7 Contents of Chapter 7 7.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 4 7.2 Structure of DX 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 5 7.2.1 Example of DX 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 7 7.3 Parameters for DX 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 8 7.4 Examples of Parameter Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 13 7.4.1 7.4.2 STEP 5 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 13 Parameter Assignment using the PG Screen Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 15 CPU 928B Programming Guide C79000-B8576-C898-01 7-1 7 Extended Data Block DX 0 7 The following chapter explains how to use the data block DX 0 and how it is structured. You will find information about the meaning of the various DX 0 patterns and will learn how to create and how to assign parameters via a screen form for a DX 0 data block based on examples. 7 CPU 928B Programming Guide C79000-B8576-C898-01 7-3 Application 7.1 Application You can match some of the activities of the system program to your own particular requirements by selecting settings in DX 0 that differ from the defaults (marked in the following table by "D"). The system program defaults (D) are set automatically at each COLD RESTART. Following this, DX 0 is evaluated. If you do not program and load a DX 0 block, the defaults remain valid; otherwise, the settings you have made in DX 0 become valid. You program DX 0 just as with other data blocks by assigning values using STEP 5 statements, (see Sections 7.2 to 7.4.1) or (with PG system software S5-DOS from Version 3.0 onwards) entering the values as parameters in a special screen form on your PG (see Section 7.4.2). Note Entries or changes to DX 0 only become effective when you perform a COLD RESTART. If a modified DX 0 comes into effect during a COLD RESTART, any parameters you do not modify are retained . CPU 928B Programming Guide 7-4 C79000-B8576-C898-01 Structure of DX 0 7.2 Structure of DX 0 DX 0 is made up of the following three parts: * the start ID for DX 0 (DW 0, 1 and 2) * several fields of varying lengths (depending on the number of parameters) * the end delimiter EEEE. Start ID ASCII characters MASKX0 in DW 0 to DW 2 Field A field in DX 0 consists of 1 to n data words, these contain the following: * the field ID 7 * the field length and * the field parameters. The field ID explains the meaning of the parameters that follow. Each field is assigned to a specific system program part or to a specific system function (e.g. field ID "04" means cyclic program execution). Field length The field length indicates the number of data words needed for the parameters that follow. Parameters Section 7.3 describes the possible parameters. Numerical values are specified in hexadecimal format (KH). End ID This indicates the end of DX 0 with EEEEH in the last data word. CPU 928B Programming Guide C79000-B8576-C898-01 7-5 Structure of DX 0 Formal structure: Bit no. 8 7 15 DW 0 1 2 3 4 5 5 D 3 8 0 4 4 3 1 B 0 M A S K X 0 ASCII chars.: Field length 1 Field ID 1 Parameter Field 1 Parameter Parameter Field ID 2 Field length 2 Field 2 Parameter Field ID n Field length n Parameter Field n Parameter Parameter DW m Fig. 7-1 E E E E End ID Structure of DX 0 CPU 928B Programming Guide 7-6 C79000-B8576-C898-01 Structure of DX 0 7.2.1 Example of DX 0 Start ID DW 0: DW 1: DW 2: KH = 4D41 KH = 534B KH = 5830 Field ID/length Parameters (occupies 1 DW) DW 3: DW 4: KH = 0101 KH = 1001 Field 1 Field ID/length Parameters (occupies 2 DW) DW 5: DW 6: DW 7: KH = 0402 KH = 1000 KH = 0040 Field 2 End ID DW10: KH = EEEE When assigning parameters in DX 0, remember the following points: 7 * You can enter individual fields in any order. * You do not need to specify fields you are not going to use. * If a field exists more than once, the field you enter last is valid. * You can enter individual parameters in any order. * You do not need to specify parameters you are not going to use. * If a particular parameter is specified several times, the parameter last specified is valid. CPU 928B Programming Guide C79000-B8576-C898-01 7-7 Parameters for DX 0 7.3 Parameters for DX 0 Table 7-1 DX 0 parameters and their meaning Field ID/ length Parameters Meanin g 1st/2nd word 1) R ESTART and RUN: 02xx 2) 1000 1001 2000 2001 3000 3001 4000 4001 D AUTOMATIC WARM RESTART after POWER UP AUTOMATIC COLD RESTART after POWER UP D Synchronization of RESTART in multiprocessor operation No synchronization of RESTART in multiprocessor operation D Addressing error monitoring No addressing error monitoring D WARM RESTART RETENTIVE COLD RESTART 6000 D Floating point arithmetic with 16-bit mantissa (optimized for speed) 6001 Floating point arithmetic with 24-bit mantissa (optimized for accuracy) BB00 yyyy Number of timers to be updated 3) Default: yyyy = 256 timers, i.e. timer 0 to 255 permitted: 0...256 C yclic program execution 04xx 1000 yyyy Length of the cycle monitoring time in milliseconds; default: yyyy = 150 ms, permitted: 1 yyyy 32C8 (hex) 1 ms to 13000 ms (dec) 4000 D Update of the process image of the IPC flags without semaphore protection 4001 Upate of the process image of the IPC flags with semaphore protection (in the field, see Section 10.1.3) CPU 928B Programming Guide 7-8 C79000-B8576-C898-01 Parameters for DX 0 Field ID/ length Parameters Meanin g 1st/2nd word 1) Table 7-1 continued: Interrupt-driven program execution 06xx 4) Selection of the processing mode 4) 2000 D Process interrupt signal, level-triggered 2001 Process interrupt signal, edge-triggered Error h andling 10xx Collision of time interrupts 1000 1001 D System stop when the event occurs and OB 33 is not loaded No system stop when the event occurs and OB 33 is not loaded Controller error handling 1200 1201 D System stop when the event occurs and OB 34 is not loaded No system stop when the event occurs and OB 34 is not loaded Cycle error handling 1400 1401 7 D System stop when the event occurs and OB 26 is not loaded No system stop when the event occurs and OB 26 is not loaded Operation code error handling 1800 1801 D System stop when the event occurs and OB 27/29/30 is not loaded No system stop when the event occurs and OB 27/29/30 is not loaded Runtime error handling 1A00 1A01 D System stop when the event occurs and OB 19/31/32 is not loaded No system stop when the event occurs and OB 19/31/32 is not loaded CPU 928B Programming Guide C79000-B8576-C898-01 7-9 Parameters for DX 0 Field ID/ len gth Parameters Meanin g 1st/2nd word 1) Table 7-1 continued: Addressing error handling 1C00 1C01 D System stop when the event occurs and OB 25 is not loaded No system stop when the event occurs and OB 25 is not loaded Timeout error handling 1E00 1E01 System stop when the event occurs and OB 23/24 is not loaded D No system stop when the event occurs and OB 23/24 is not loaded Interface error handling 2000 System stop when the event occurs and OB 35 is not loaded D No system stop when the event occurs and OB 35 is not loaded 2001 EEEE End delimiter 1) D = Default with DX 0 not loaded or block m issing 2) xx = field length (num ber of data words occupied by the parameters) 3) For updating timers, please read the explanation on the following page 4) For parameters and their significance, see the table on page 7-12. Note The current PG software (STEP 5/ST Vers. 6 or STEP 5/MT Vers. 2) for generating DX 0 using a screen form does not transfer the parameters for interface error handling (2000 or 2001) and for the selection "Warm restart or retentive cold restart" (4000 or 4001). You can enter these parameters e.g. with the "output block" PG function (do not forget to change the block length). You can no longer edit a DX 0 modified in this way using the output screen form of the current PG software. CPU 928B Programming Guide 7 - 10 C79000-B8576-C898-01 Parameters for DX 0 Updating the timers * As standard, the timers T 0 to T 255 are updated. * If you enter the value "0" in DX 0, no timers are updated, even if they are included in the program. There is then also no error message output. * Updating is as follows: Entry Updating '0' none '1' and '3' and '5' and '7' and '2' '4' '6' '8' T0 to T1 T0 to T3 T0 to T5 T0 to T7 .... .... Note You can also assign parameters to the number of timers in data block DB 1 (see Section 10.1.6). However, we recommend that you specify this parameter only in DX 0. If you set the number of timers both in DX 0 and in DB 1, the value you specify in DB 1 will be valid! 7 CPU 928B Programming Guide C79000-B8576-C898-01 7 - 11 Parameters for DX 0 Parameters for interrupt processing Parameter/ (old) You can use the table below to find the correct parameter for your interrupt processing and you can program DX 0 with this parameter. Depending on the parameter you select, some (or all) interrupts will be effective at block boundaries and other (or all) interrupts will be effective at operation boundaries, according to the shading in the symbols. T i m e Clock 1) int. 5 s 2 s 1 s 500 ms i n t e r r u p t s 200 ms 100 ms 50 ms 20 ms 10 ms Cont. Delay Proc. int. int int. 122C D (100C) 1224 (100A) 1220 121C (1008) 1216 1214 1212 1210 120E 120C 120A 1208 1206 1204 (1006) D = Default Inter r upts at block boundar ies Inter r upts at oper ation boundar ies Note If you enable interrupt processing at operation boundaries, the operations "TNB" "TNW" may also be interrupted. This also applies to a few of the special function organization blocks, standard function blocks and controller function blocks. 1) The PG software for generating DX0 uses the "old" parameters. If you generate a DX0 with new parameters using STEP 5 and want to display it on the PG, an error message is displayed. CPU 928B Programming Guide 7 - 12 C79000-B8576-C898-01 Examples of Parameter Assignment 7.4 Examples of Parameter Assignment 7.4.1 STEP 5 Programming Example A: In multiprocessor operation, you want to use three CPUs: CPU A, B and C. CPU A and B operate closely together, often exchange data and process a complex restart program. CPU C is largely independent and has a short, time-critical program. As standard, all CPUs in multiprocessor operation start cyclic program execution together, i.e. the CPUs wait until all CPUs have completed their restart procedures and then start cyclic program execution at the same time. Since CPU C runs a very short restart program independent of the other CPUs, its restart procedure does not need to be synchronized. By assigning parameters in DX 0, you can arrange for CPU C to start cyclic program execution immediately after its restart, without waiting for CPU A and B. Programming DX 0 for CPU C: DX 0 start ID "MASKX0" DW DW DW 1st field ID/length DW parameter 1 DW end delimiter DW 7 0: 1: 2: 3: 4: 5: KH= KH= KH= KH= KH= KH= 4D41 534B 5830 0201 2001 EEEE Once you have loaded this DX 0 in the program memory, it becomes effective after the next COLD RESTART. Since CPU C processes a very short restart program and does not wait for A and B, its green LED is lit immediately following the restart. The BASP signal (disable command output) is, however, only cancelled when all three CPUs have completed their restart. This means that CPU C cannot access the digital peripherals. CPU 928B Programming Guide C79000-B8576-C898-01 7 - 13 Examples of Parameter Assignment Example B: Assigning the parameters to DX 0 as shown below achieves the following: - the addressing error monitoring is disabled, - the timer updating is disabled, - the cycle time is set to 4 sec. DX 0 start ID "MASKX0 DW 0: DW 1: DW 2: 1st field ID/length DW 3: parameter DW 4: DW 5: parameter 1) DW 6: 2nd field ID/length DW 7: DW 8: parameter 1) DW 9: end delimiter DW10: KH KH KH KH KH KH KH KH KH KF KH = = = = = = = = = = = 4D41 534B 5830 0203 3001 BB00 0000 0402 1000 +4000 EEEE This assignment of parameters to DX 0 has the following effects on program execution: - The part of the process image not assigned to peripheral I/O modules can be used as an additional flag area. - The runtime of the system program is reduced, since no timers are updated. - A cycle error is only detected when the runtime of the user program and the system program together exceeds 4 sec. 1) Parameters occupying two words must be identified with "2" when specifying the field length. CPU 928B Programming Guide 7 - 14 C79000-B8576-C898-01 Examples of Parameter Assignment 7.4.2 Assigning Parameters using the PG Screen Form From stage IV of the PG system software S5-DOS, screen forms are available for assigning parameters to DX 0. The PG software generates the data block DX 0 automatically according to the parameter defaults and the parameters you have specified. Two screen forms are required for this parameter assignment. For the basic steps you require to select and complete PG screen forms, see your STEP 5 manual. Completing the DX 0 screen forms The PG screen form for completing DX 0 is in two parts. The first DX 0 screen contains the first group of parameters (Fig. 7-2): RESTART AFTER POWER UP SYNCHRONIZE MULTIPROCESSOR RESTART BLOCK TRANSFER OF IPC FLAGS ADDRESS ERROR MONITORING CYCLE TIME MONITORING NO. OF TIMER CELLS ACCURACY OF FLOAT. POINT ARITHMETIC DX 0 - PARAM. ASS. (S5 135U: CPU 928, R PROCESSOR) DX 0 RESTART AFTER POWER UP: 1 SYNCHRONIZE MULTIPROCESSOR RESTART YES BLOCK TRANSFER OF IPC FLAGS NO ADDRESSING ERROR MONITORING YES CYCLE TIME MONITORING (X 10 MS) 15 ( R PROC.: 1 - 400 CPU 928: 1 - 600 ) NO. OF TIMER CELLS 256 ( R PROC: 0 - 128 CPU 928: 0 - 256 ) ACCURACY OF FLOAT. POINT ARITHMETIC #24-BIT MANTISSA ONLY BY CPU 928# 16 - BIT MANTISSA F1 F2 F3 F4 F5 SELECT Fig. 7-2 7 ( 1 = WARM RESTART 2 = COLD RESTART ) F6 F7 F8 CONTINUE PG screen form for assigning parameters to DX 0 /part 1 CPU 928B Programming Guide C79000-B8576-C898-01 7 - 15 Examples of Parameter Assignment Once you have selected all the parameters in the first screen form for your application, you can display the second screen form (Fig. 7-3) with the following group of parameters: ADDRESS. ERROR, CYCLE ERROR ACKNOWL. ERROR, TIMER ERR. COMMAND CODE ERROR, CONTROLLER ERROR RUNTIME ERROR PROCESS INT SERVICING INTERRUPTABILITY OF USER PROGRAM BY INTERRUPTS DX 0 DX 0 - PARAM. ASS. (S5 135U: CPU 928, R PROCESSOR) SYSTEM STOP IF EVENT OCCURS AND ERROR OB IS MISSING ADDRESS. ERROR (OB 25) YES CYCLE ERROR (OB 26) YES ACKNOWL. ERROR (OB 23, 24) NO TIMER ERR. (OB 33) YES COMMAND CODE ERR. (OB 27, 29, 30) YES CONTROLLER ERR (OB 34) YES RUNTIME ERROR (OB 19, 31, 32) YES PROCESS INT. SERVICING LEVEL - TRIGGERED INTERRUPTABILITY OF USER PROGRAM BY INTERRUPTS: 1: ALL INTERRUPTS AT BLOCK BOUNDS 2: ALL INTERRUPTS AT OPERATION BOUNDS 3: ONLY PROCESS INTERRUPTS AT OPERATION BOUNDS 4: ONLY PROC: AND CONTROLLER. INT. AT OP. BOUNDS X: (X=10 , . . . 17) TIME INT. FROM OB10 - OBX AND CONTROLLER/PROC INTS. AT OP. BOUNDS #ONLY POSSIBLE WITH CPU 928# F1 F2 F3 F4 F5 SELECT Fig. 7-3 F6 MODE 1 F7 F8 CONTINUE PG screen form for assigning parameters to DX 0 / part 2 The following flowchart explains how to complete the screen forms, store the parameters and load the generated data block DX 0. CPU 928B Programming Guide 7 - 16 C79000-B8576-C898-01 Examples of Parameter Assignment Flowchart for completing the DX 0 screen forms. You want to change parameters in form 1? NO YES Repeat the following procedure until you have made all the required changes in the screen form: - Select input field: Position the cursor before the parameter field. The display field F3 at the bottom edge of the screen indicates whether you can select between alternatives (SELECT displayed) or whether you can change the parameter value (INPUT displayed). - SELECT: Press F3 until the required alternative is displayed. - INPUT: Press F3 once, the cursor jumps to the beginning of the field. You can overwrite the field with a permissible numerical range. You want to change parameters in form 2? NO YES 7 Press F6 (CONTINUE); the 2nd screen is displayed. Change the parameters as described above for the 1st screen form. Press the enter key; the PG software enters all the parameter settings from both screen forms and generates data block DX 0. DX 0 is stored in the PG. You can load it into the CPU using the programmer or you can store it on an EPROM submodule. You will find an example to fill in on the next page. CPU 928B Programming Guide C79000-B8576-C898-01 7 - 17 Examples of Parameter Assignment Example of filling in the DX 0 screen form You want to assign parameters in DX 0 to achieve the following system program response (different from the defaults). - in multiprocessor operation, the CPU for which this DX 0 is programmed does not wait until the other CPUs have completed their restart procedure, - the cycle monitoring time is 100 ms, - arithmetic operations are performed with 24-bit floating point mantissa, - if cycle errors occur, the CPU does not go to the STOP mode if OB 26 is not loaded, - the user program is interrupted at operation boundaries by all interrupts. To obtain these reactions, complete the screen form as follows: First DX 0 screen form: - Select the "synchronize multiprocessor restart" parameter with function key F3 as NO. - For the "cycle time monitoring" parameter, press function key F3 and then type in the number 10 (= 100 ms). - Select the "24-bit mantissa" for the "accuracy of floating point arithmetic" parameter with function key F3. - Press function key F6 (CONTINUE). The second DX 0 screen is then displayed. Second DX 0 screen form: - Select NO for the "cycle error" parameter with function key F3. - Enter the number '2' in the "mode" field of the "interruptability of user program by interrupts" parameter (= all interrupts at operation boundaries). - Confirm your entries by pressing the enter key. Data block DX 0 is now generated by the PG software. Finally, transfer DX 0 to memory or to an EPROM submodule. CPU 928B Programming Guide 7 - 18 C79000-B8576-C898-01 Memory Assignment and Organization 8 Contents of Chapter 8 8.1 Structure of the Memory Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 4 8.2 Address Distribution in the CPU 928B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 5 8.2.1 8.2.2. Address Distribution of the System RAM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 6 Address Distribution of the Peripherals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 7 8.3 User Memory Organization in the CPU 928B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 9 8.3.1 8.3.2 8.3.3 8.3.4 8.3.5 Block Headers in the User Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Block Address Lists in Data Block DB 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RI / RJ Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RS / RT Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bit Assignment of the System Data Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 10 8 - 11 8 - 14 8 - 15 8 - 18 CPU 928B Programming Guide C79000-B8576-C898-01 8-1 8 Memory Assignment and Organization 8 You can use this chapter as a reference section to check the organization of the CPU 928B memory. The chapter also includes important information for the user contained in some of the system data words. 8 CPU 928B Programming Guide C79000-B8576-C898-01 8-3 Structure of the Memory Area 8.1 Structure of the Memory Area The memory area of the CPU 928B is basically divided into the following areas: Table 8-1 Structure of the memory area Memory area User memory: For OBs, FBs, FXs, PBs, SBs, DBs, DXs DB-RAM: For data blocks, shift registers Flags: S Interface data area: System data area: Counters: Timers: RI, RJ RS, RT C T Flags: F Process input and output image: Length W idth max. 32x210 words 16 bits 23x210 words 16 bits 1024 bytes 8 bits each 256 words each 256 words 256 words 256 words 16 bits 16 bits 16 bits 16 bits 256 bytes 8 bits each 128 bytes 8 bits PII, PIQ 8 bits Peripheral I/O area, divided into: P peripherals O peripherals IM 3 IM 4 IPC flags Coordinator module Pages (CP, IP, 923C) Distributed I/Os 256 bytes 256 bytes 256 bytes 256 bytes 256 bytes 256 bytes 2048 bytes 768 bytes Refer to the memory map in the next section for the exact addresses of the areas. Note With STEP 5, you should never access a memory cell within an operand area (e.g. flags) directly using the absolute address of this memory area, but always relative to the base address of the operand area. The base addresses of all operand areas are in the system data area (RS area - see "system data assignment"). CPU 928B Programming Guide 8-4 C79000-B8576-C898-01 Address Distribution in the CPU 928B 8.2 Address Distribution in the CPU 928B Bit no.15 8 7 0 0000 User memory max. 32 x 2 10 RAM or EPROM submodule, can be plugged into the CPU words 7FFF 8000 DB-RAM 23 x 2 10 words DD7F DD80 DB 0 (block address lists) E3FF E400 System RAM, internal to the CPU (see also Fig. 8-2) S flags E7FF E800 System transfer data (RI/RJ areas), system data (RS/RT areas), counters, timers EDFF EE00 15 Flags EEFF EF00 PII/PIQ area EFFF F000 Peripheral I/Os (digital/analog CP/IP) FFFF 7 Fig. 8-1 S5 bus (see also Fig. 8-3) 0 Address distribution in the CPU 928B - overview CPU 928B Programming Guide C79000-B8576-C898-01 8-5 8 Address Distribution in the CPU 928B 8.2.1 Address Distribution of the System RAM Bit no. 15 8 7 0 8000 DB-RAM DD7F DD80 DB0 E3FF E400 S flags E7FF E800 RI: interface data area E8FF E900 RJ: extended interface data area E9FF EA00 RS: system data area EAFF EB00 RT: extended system data area EBFF EC00 Counters (256) ECFF ED00 Timers (256) EDFF EE00 15 Flags EEFF EF00 PII/PIQ area EFFF 7 Fig. 8-2 0 Address distribution - system RAM CPU 928B Programming Guide 8-6 C79000-B8576-C898-01 Address Distribution in the CPU 928B 8.2.2 Address Distribution of the Peripherals Bit no. 7 F000 F07F F080 F08F F100 0 Di g i t a l p e r i p h e r a l s ( wi t h p r o c e s s i m a g e ) , 1024 bits inputs / 1024 bits outputs P area Di g i t a l o r a n a l o g p e r i p h e r a l s ( wi t h o u t p r o c e s s i m a g e ) , 1024 bits inputs / 1024 bits outputs 2048 bits extended peripherals O area F1FF F200 2 0 4 8 b i t s IP C f l a g s ( o n co o r d i n a t o r m o d u l e / CP) F2FF F300 32 semaphores ( o n co o r d i n a t o r m o d u l e ) F3FF F400 Data transfer area f o r CP ( p a g e s ) Page area 8 F BF F F C0 0 IM 3 a r e a F CF F F D0 0 IM 4 a r e a F DF F F E0 0 Di s t r i b u t e d p e r i p h e r a l s , e x t e n d e d a d d r e s s vo l u m e F EF F FF00 Re se r ve d FFFF Fig. 8-3 Address distribution - peripherals (8 bits) on the S5 bus CPU 928B Programming Guide C79000-B8576-C898-01 8-7 Address Distribution in the CPU 928B Address areas for the peripherals and their programming Area (absolute address) EF00 EF7F EF80 EFFF PII (process input image) PIQ (process output image) F07F F080 F0FF Digital peripherals inputs/ outputs Digital or analog peripherals inputs/outputs F1FF L IB / T IB L IW / T IW L ID / T ID A I / AN I / O I / ON I SI / RI/=I 0 0 0 0.0 to to to to 127 126 124 127.7 L QB L QW L QD AQ SQ 0 0 0 0.0 to to to to 127 126 124 127.7 / / / / / T QB T QW T QD AN Q / O Q / ON Q RQ/=Q L PY / T PY L PW / T PW 0 0 to 127 to 126 T PY / T PY T PW / T PW 128 to 255 128 to 254 The inputs and outputs are addressed directly byte or word oriented. P peripherals F100 Parameters When the operation is processed, only the process image is changed. The new status of the process image is only output to the peripherals at the end of the cycle. P peripherals with process ima ge F000 Address with L OY / T OY L OW / T OW Extended peripherals inputs/outputs 0 0 to 255 to 254 The inputs and outputs are addressed directly byte or word oriented. Q peripherals With STEP 5 operations, you can access the peripherals either directly or via the process image. Remember that the process image only exists for input and output bytes of the P peripherals with byte addresses from 0 to 127. Note Using the interface modules IM 304, IM 307 and IM 308, you can access distributed address areas using your program. This allows access to two new address areas similar to the O area. In contrast to the O area, however, access to these areas is only possible using absolute addressing or using FB 196 of the "basic functions" software package (refer to Catalog ST59). CPU 928B Programming Guide 8-8 C79000-B8576-C898-01 User Memory Organization in the CPU 928B 8.3 User Memory Organization in the CPU 928B Depending on the memory submodule you are using, the user memory consists of the memory area from 0000H to 7FFFH. When you load the blocks of the user program, they are stored in any order (addresses in ascending order). "Alternative loading" of the data blocks There are alternative methods of loading DB/DX data blocks depending on the setting in system data word RS 144: The default is that the data blocks are first loaded into the user memory. Only when this has been filled are the data blocks stored in internal DB RAM (8000H to DD7FH). You can reverse this order by setting bit 0 in RS 144 ("alternative loading"). Memory information With the online function MEM CONF (memory configuration) you can obtain the address (hexadecimal) of the memory cell containing the block end operation of the last block in the memory submodule which then tells you the occupation of the RAM submodule. Block management When you correct blocks, the "old" block is declared invalid in the memory and a new block is set up. This also applies when you delete blocks; the blocks are not really deleted in the memory, but simply declared invalid. Gaps created when blocks are deleted are seen as free memory locations and used again when new blocks are loaded. Compress memory Using the COMPRESS MEMORY online function you can create memory space for new blocks. This function optimizes the memory occupation by deleting blocks marked as invalid and shifting valid blocks together. The shifting is separate for the memory submodule and internal RAM module (see Section 11.2.2). CPU 928B Programming Guide C79000-B8576-C898-01 8-9 8 User Memory Organization in the CPU 928B 8.3.1 Block Headers in the User Memory Bit no. Each block in the memory begins with a five word long header. 1st word: block start identifier: 7070H 2nd word: high byte = block type 15 14 13 12 11 01H 02H 04H 05H 08H 0CH 10H 10 9 8 Data block DB Sequence block SB Program block PB Function block FX Function block FB Data block DX Organization block OB 0 0 The block is invalid, not entered in the address list in DB0 0 1 Block in the RAM is valid, and is entered in the address list of DB0 Low byte = block number The block number (0 to 255) is in the low byte of the 2nd header word and is coded in binary: 00 to FFH 3rd word: the high byte of the 3rd word contains the identifiers for the programmer, the low byte contains part of the library number. 4th word: the fourth word contains the rest of the library number. 5th word: the 5th word (low and high byte) contains the length of the block including the block header. This is specified in words. CPU 928B Programming Guide 8 - 10 C79000-B8576-C898-01 User Memory Organization in the CPU 928B 8.3.2 Block Address Lists in Data Block DB 0 Address list start addresses Data block DB 0 contains a list with the start addresses of all blocks in the memory submodule or in the DB RAM of the CPU. The system program generates this list after POWER UP and updates it automatically when you enter or change blocks at the programmer. A 256 words long address list is reserved in DB 0 for each block type i.e. one word is reserved for each block. Blocks that are not loaded or have been deleted have the start address "0". The start addresses of the block address lists are also entered in the system data RS 32 to RS 38. RS 32: Start address of the DX address list RS 33: Start address of the FX address list RS 34: Start address of the DB address list RS 35: Start address of the SB address list RS 36: Start address of the PB address list RS 37: Start address of the FB address list RS 38: Start address of the OB address list (only 48 words long) 8 Block start addresses The start addresses always refer to the first word after the block header: * this is DW 0 of data blocks * this is the first STEP 5 operation of a logic block (in FBs, this is the "JU" operation before the name and the parameter list) CPU 928B Programming Guide C79000-B8576-C898-01 8 - 11 User Memory Organization in the CPU 928B Storing block addresses in DB 0: n = start address of the PB address list (= contents of RS 36) DB0 15 Fig. 8-4 0 n Address PB 0 n+1 Address PB 1 n+2 Address PB 2 n+178 Address PB 178 n+179 Address PB 179 If the value "0" is entered as the address, the block is not loaded Block addresses in DB 0 Examples of how to obtain a block address Start address of FB 40 Solution a): :L RS 37 :L KB 40 :+F : :LIR 1 : : Base address of the FB address list + FB number = Address of the memory cell containing the start address of FB 40 Load the start address of FB 40 in ACCU 1. (If the block is not loaded, the start address = 0) Solution b): :L RS 37 :MAB :LRW +40 Base address of the FB address list Load the BR register with the base address Load the contents of the memory cell "base address + 40" in ACCU 1 CPU 928B Programming Guide 8 - 12 C79000-B8576-C898-01 User Memory Organization in the CPU 928B Determining the start address and length of data block DB 50 a) Using indirect memory access: :L RS 34 :L KB 50 :+F :LIR 1 :L KB 0 :!=F :JC =NIVO :ENT :TAK :L KF -1 :+F :LIR 1 . . NIVO : ....... Load the base address of the DB address list Calculate the address of the entry for DB 50 and load the start address in ACCU 1 If the block does not exist, jump to the NIVO label Load the start address of DB 50 in ACCU 3 and in ACCU 1 Decrement the start address by 1 and load the block length in ACCU 1 Reaction if the block does not exist DB 0 15 User memory: 0 15 0 RS 34 0104 DB 0 0000 DB 1 0000 DB 2 0000 . . . . . . 0009 0109 0000 DW 0 010A DW 1 010B 0000 DW 2 010C .. DW 4 010D DB 49 DB 50 DB 51 .. Fig. 8-5 010A 7070 0105 0106 DB 50 header 8 0107 0108 Example a): start address of DB 50 CPU 928B Programming Guide C79000-B8576-C898-01 8 - 13 User Memory Organization in the CPU 928B Continuation of the example (address and length of DB 50): b) Using the special function organization block OB 181 "test data blocks (DB/DX)": OB 181 (see Section 6.16) executes the same function as described in example 2 / a). In addition to this function, it also determines whether the data block is in the user memory (RAM or EPROM submodule) or in the DB RAM. :L KY1,50 :JU OB 181 :JC =NIVO :JM =PROM :JZ =ANWE :JP =DBRA :JU = FEHL Data block DB 50 "Test data blocks (DB/DX)" Jump if block does not exist Jump if in EPROM submodule Jump if in RAM submodule Jump if in DB RAM Jump to error processing NIVO : : :BEU Data block does not exist PROM : : :BEU Data block is in the user memory (EPROM submodule) ANWE : : :BEU Data block is in the user memory (RAM submodule) DBRA : : :BEU Data block is in the DB RAM FEHL : : :BE Error processing Result: ACCU-1-L: Start address of DB 50 ACCU-2-L: Length of DB 50 RLO = 1 if DB 50 does not exist 8.3.3 RI / RJ Area The RI area is an area 256 words long in the internal system RAM of the CPU. It occupies addresses E800H to E8FFH. The RJ area is an area 256 words long in the internal system RAM of the CPU. It occupies addresses E900H to E9FFH. You can use the entire RI area (RI 0 to RI 255) and the entire RJ area (RJ 0 to RJ 255) for your own purposes. Only an overall reset can clear the RI / RJ areas (zeros entered). CPU 928B Programming Guide 8 - 14 C79000-B8576-C898-01 User Memory Organization in the CPU 928B 8.3.4 RS / RT Area The RS and RT areas contain information for the system programmer and system internal data. The RS area is an area 256 words long in the internal system RAM of the CPU. It occupies the addresses EA00H to EAFFH. Caution You can only write to system data words RS 1, RS 60 to RS 63, RS 133 and RS 140. - You can use RS 60 and RS 63 for your own purposes. RS 1 and RS 133 have a fixed function and influence the processing of the program. You must only write valid identifiers to them. You can only read the other system data - Writing to these system data can affect the functional capability of your CPU and connected programmers. The R T area is an area 256 words long in the internal system RAM of the CPU. It occupies the addresses EB00H to EBFFH. You can use the entire RT area (RT 0 to RT 255) for your own purposes. 8 The RS / RT area can only be cleared by an overall reset. You can obtain the information of some of the system data (the internal configuration of the CPU, the software release, the CP identifier etc.) using the SYSTEM PARAMETERS online function. Following figures 8-6 and 8-7 you will find the bit assignment of some system data that you can evaluate using STEP 5 operations or with the PG (refer to Section 5.3.1 for an explanation of the abbreviations). CPU 928B Programming Guide C79000-B8576-C898-01 8 - 15 User Memory Organization in the CPU 928B Assignment of the system data in the RS area RS 0 Name Addr. Interrupt condition codeword (ICCW) EA00 1 Interrupt condition code reset word (ICRW) EA01 2 Interrupt condition code group word (ICMK) EA02 3 Start-up error identifier condition code 4 5 Stop IDs 6 Cycle IDs Overall reset IDs 7 8 Restart IDs Submodule IDs Error IDs (H) Error IDs (L) Error IDs (F) 9 Current ID number EA03 EA04 EA05 EA06 EA07 EA08 EA09 10 Base address of the input process interface modules EA0A 11 Base address of the output process interface modules EA0B 12 Base address of the process input image EA0C 13 Base address of the process output image EA0D 14 Base address of the flag area 15 16 17 EA0F Base address of the counter area EA10 Base address of the interface area 18 19 EA0E Base address of the timer area EA11 PLC software release End address of the user submodule EA12 EA13 20 Base address of the system area EA14 21 Length of the DB address list EA15 22 Length of the SB address list EA16 23 Length of the PB address list EA17 24 Length of the FB address list EA18 25 Length of the OB address list EA19 26 Length of the FX address list EA1A 27 Length of the DX address list EA1B 28 Length of the address list DB (DB 0) EA1C 29 Slot identifier CPU identifier 2 (type) EA1D : reserved Fig. 8-6 RS area memory map (part 1) CPU 928B Programming Guide 8 - 16 C79000-B8576-C898-01 User Memory Organization in the CPU 928B 30 31 32 33 34 35 36 37 38 39 54 55 56 Length of CPU identifier 1 Base Base Base Base Base Base Base the block header information EA1E PG interface software release EA1F address of the DX address list EA20 address of the FX address list EA21 address of the DB address list EA22 address of the SB address list EA23 address of the PB address list EA24 address of the FB address list EA25 address of the OB address list EA26 EA27 Counter for 1 hour (to 3599 sec, hex) EA36 EA37 EA38 Reserved for handling block 59 60 63 64 79 80 81 Reserved for user purposes Reserved for system program Additional error ID if bit FE-5 is set in RS 8 EA3B EA3C EA3F EA40 EA4E EA50 EA51 Reserved for system program 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 "Closed loop control" ID Condition codeword "disable all interrupts" Condition codeword "delay all interrupts" "Process image updating" ID Condition codeword "disable individual time interrupts" Condition codeword "delay individual time interrupts" Condition codeword "write and delete blocks" EA7F EA80 EA81 EA82 EA83 EA84 EA85 EA86 EA87 EA88 EA89 EA8A EA8B EA8C EA8D 145 EA8F EA90 EA91 255 EAFF 143 144 Fig. 8-7 Alternative loading of data blocks RS area memory map (part 2) CPU 928B Programming Guide C79000-B8576-C898-01 8 - 17 8 User Memory Organization in the CPU 928B 8.3.5 Bit Assignment of the System Data Words Interrupt condition codeword (system data RS 0): RS 0 Interrupt condition codeword Address EA00H Table 8-2 Assignment of RS 0 (Interrupt condition codeword) High b yte Bit no. Assignment 15 NAU 14 PEU 13 BAU 12 MP-STP 11 ZYK 10 QVZ 9 ADF 8 STP Low byte 7 BCF 6 FE-3 5 LZF 4 REG 3 STUEB 2 STUEU 1 WECK 0 DOPP The system data RS 0 corresponds to the CAUSE OF INTERR. in the ISTACK. If, e.g. a runtime error occurs during the program execution, bit number 5 is set. Once the program processing level LZF has been processed completely, bit number 5 is reset. CPU 928B Programming Guide 8 - 18 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 1 Interrupt condition code reset word ICRW Address: EA01H RS 1: Active interface, released for user If you set bit number 9 or bit number 10 of the ICRW the next ADF or QVZ is ignored and does not affect the execution of the program. After a QVZ or ADF occurs, the system program resets the corresponding bit. Table 8-3 Assignment of RS 1 (Interrupt condition code reset word) High b yte Bit no. Assignment 15 14 13 not used 12 11 10 QVZ 9 ADF 8 not used 8 Low byte 7 6 5 4 not used 3 2 1 0 Each program processing level has its own IC RW. CPU 928B Programming Guide C79000-B8576-C898-01 8 - 19 User Memory Organization in the CPU 928B Example of UALW The following example tests whether a module can be addressed at a certain peripheral address. If the module does not exist, ICRW prevents a timeout and a program written for the situation is executed. The example also tests whether a particular peripheral address has been entered in DB 1. If the address does not exist in DB 1, ICRW prevents an addressing error and a special program is executed. FB 201 NAME:L :JU FB 10 NAME:PERITEST Test whether a module can be addressed at PADR : PB 128 peripheral adddress 128 MASK : KM 00000100 00000000 :JN =M001 :.. This program section is processed if the module :.. cannot be addressed :.. M001 : :JU FB 10 NAME:PERITEST Test whether a module with peripheral PADR : QB 4 address 4 is entered in DB 1 MASK : KM 00000010 00000000 :JN =M002 :.. This program section is processed, :.. if the peripheral address :.. is not entered M002 : :BE FB 10 NAME:PERITEST DECL :PADRI/Q/D/B/T/C: I BI/BY/W/D: BY DECL :MASKI/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: :L :T :LW :OW :T :L : :L :LW :AW :L :T :TAK :BE KM RS 1 RS 60 =MASK Load and save ICRW RS 1 =PADR Write ICRW back Single peripheral access or access to the process image Set QVZ or ADF bit RS 1 =MASK Mask QVZ or ADF bit RS 60 RS 1 Write old ICRW back, so that the next QVZ or ADR can be detected CPU 928B Programming Guide 8 - 20 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 2 Interrupt condition code group word ICMK (RS 2): Address: EA02H The 16 bits of the interrupt condition code group word correspond to the possible causes of error listed in the CAUSE OF INTERR. in the ISTACK. If one of these errors occurs, the corresponding bit is set. Table 8-4 Assignment of RS 2 (Interrupt condition code group word) High b yte Bit no. Assignment 15 NAU 14 PEU 13 BAU 12 MP-STP 11 ZYK 10 QVZ 9 ADF 8 STP 8 Low byte 7 BCF 6 FE-3 5 LZF 4 REG 3 STUEB 2 STUEU 1 WECK 0 DOPP You can only read the interrupt code group word (ICMK in the ISTACK). CPU 928B Programming Guide C79000-B8576-C898-01 8 - 21 User Memory Organization in the CPU 928B Example of UAMK If the CPU goes to the stop mode as a result of an addressing error (ADF), ICMK bit number 9 is set. If an operation code error (BCF) occurs when processing the ADF, bit number 7 is also set in the ICMK. Content of the ICMK (binary): Representation (hexadecimal) in the ISTACK: 00000010 10000000 0280 While only the last error to occur is marked under CAUSE OF INTERR. in the ISTACK, all the errors that have occurred are indicated in the ICMK (ISTACK depth 05: in ICMK, 5 bits are set). If you convert the hexadecimal code to the binary code, you can analyze the contents of the ICMK. In this way, you can find out which error led to the stop mode. The error bits are reset as soon as the corresponding error program processing level has been completely processed and is exited. Interrupt codes of errors to which no program processing level is assigned (e.g. NAU, PEU, STUEB, etc.) are cleared during RESTART. CPU 928B Programming Guide 8 - 22 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 5 STO P and RESTART IDs Address: EA05H The IDs correspond to the control bits in lines 1 and 2 of the ISTACK. Table 8-5 Assignment of RS 5 (STOP and RESTART IDs) High byte: STO P IDs Bit no. Assignment 15 PRI-STP 14 not used 13 FE-STP 12 BARB-END 11 PG-STP 10 STP-SCH 9 STP-BEF 8 MP-STP 8 Low b yte: RESTART IDs 7 ANL 6 not used 5 NEUST 4 MWA 3 AWA 2 not used 1 NEU-ZUL 0 MWA-ZUL CPU 928B Programming Guide C79000-B8576-C898-01 8 - 23 User Memory Organization in the CPU 928B RS 6 CYCLE and Submodule/MPL ID s Address: EA06H The IDs correspond to the control bits in lines 3 and 4 of the ISTACK. Table 8-6 Assignment of RS 6 (Cycle and submodule/MPL IDs) High b yte: CYCLE ID s Bit no. Assignment 15 RUN 14 not used 13 EIN-PROZ 12 BARB 11 OB1-GEL 10 FB0-GEL 9 OB-PROZA 8 OB-WECKA Low byte: Submodule/MPL IDs 7 32KW-RAM 6 16KW-RAM 5 8KW-RAM 4 EPROM 3 KM-AUS 2 KM-EIN 1 DIG-EIN 0 DIG-AUS CPU 928B Programming Guide 8 - 24 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 7 R ESET IDs/Initialize error ID s Address: EA07H The IDs correspond to the control bits in lines 5 and 6 of the ISTACK. Table 8-7 Assignment of RS 7 (RESET IDs/Initialize error IDs) High byte: RESET IDs Bit no. Assignment 15 URGELOE 14 URL-IA 13 STP-VER 12 ANL-ABB 11 UA-PG 10 UA-SYS 9 UA-PRFE 8 UA-SCH 8 Low byte: Initialize error IDs 7 DX0-FE 6 not used 5 MOD-FE 4 RAM-FE 3 DB0-FE 2 DB1-FE 1 DB2-FE 0 KOR-FE CPU 928B Programming Guide C79000-B8576-C898-01 8 - 25 User Memory Organization in the CPU 928B RS 8 Error IDs HW/S W Address: EA08H The IDS correspond to the control bits in lines 7 and 8 of the ISTACK. Table 8-8 Assignment of RS 8 (Error IDs HW/SW) Bit no. High b yte: Error IDs H W 15 NAU 14 PEU 13 BAU 12 STUE-FE 11 ZYK 10 QVZ 9 ADF 8 WECK-FE Bit no. Low b yte: Error IDs S W 7 BCF 6 not used 5 FE-5 4 Power-down error 3 FE-3 2 LZF 1 REG-FE 0 DOPP-FE CPU 928B Programming Guide 8 - 26 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 29 Slot ID/CPU/PLC type Address: EA1DH Table 8-9 Assignment of RS 29 (Slot ID/CPU/PLC type) Bit no. High b yte: Error IDs H W 15 14 13 not used 12 11 CPU no. 4 10 CPU no. 3 9 CPU no. 2 8 CPU no. 1 Bit no. Low b yte: Error IDs S W 7 8 6 5 CPU type 4 3 2 1 PLC type 0 RS 29 (HIGH): Active interface, used by the handling blocks and in multiprocessor communication as well as by OB 218 and the SED and SEE operations. RS 29 (LOW): PLC type: 0111 S5-135U CPU type: 1011 CPU 928B CPU 928B Programming Guide C79000-B8576-C898-01 8 - 27 User Memory Organization in the CPU 928B RS 80 Address: EA50H (high and low): This contains additional information to define the cause of the error when bit 5 is set in RS 8 by the system or when control bit FE 5 is marked in the ISTACK output. Identifier in RS 80 Cause of error 2460H RS 130 Ready signal continuously active on the S5 bus Address EA82 (low): The system data RS 130 indicates the following statuses of the program processing level "closed loop control". Bit no. 0 = 0 : program processing level "closed loop control" activated Bit no. 0 = 1 : program processing level "closed loop control" suppressed Before you call a restart organization block (OB 20, 21 or 22) the system program evaluates data block DB 2 (if it exists). Depending on the result of the evaluation, RS 130 is set or reset by the system program. Following this, the system program calls a restart OB. If RS 130 (LOW) is reset, the closed loop controller is processed in cyclic operation according to the controller list in DB 2. CPU 928B Programming Guide 8 - 28 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 131 Condition codeword "disable all interrupts": see OB 120 (Section 6.5) Address EA83 (low) The system data RS 131 indicates the following statuses of the program processing levels "interrupt processing". Table 8-10 Assignment of RS 131 (Disable all interrupts) Bit no. Low byte: Disable all interrupts 7 0 6 0 5 0 4 0 3 Delay interrupt 2 Process interrupts 1 Clock-driven time interrupt 0 Time interrupts at fixed intervals Bit = 1 means: interrupt(s) is (are) disabled. RS 132 8 Condition codeword "delay all interrupts": see OB 122 (Section 6.7) The system data RS 132 indicates the following statuses of the program processing levels "interrupt processing". Table 8-11 Assignment of RS 132 (Delay all interrupts) Bit no. Low byte: Dela y all interrupts 7 0 6 0 5 0 4 0 3 Delay interrupt 2 Process interrupts 1 Clock-driven time interrupt 0 Time interrupts at fixed intervals Bit = 1 means: interrupt(s) is (are) delayed CPU 928B Programming Guide C79000-B8576-C898-01 8 - 29 User Memory Organization in the CPU 928B RS 133 Process image updatin g Address EA85 (low) Table 8-12 Assignment of RS 133 (Process image updating) Bit no. Low b yte: Process image updatin g 7 6 5 not used 4 3 KM-AUS 2 KM-EIN 1 DIGH-EIN 0 DIGH-AUS Bit no. 0 = 0 : Bit no. 0 = 1 : Bit no. 1 = 0 : Bit no. 1 = 1 : Bit no. 2 = 0 : Bit no. 2 = 1 : Bit no. 3 = 0 : Bit no. 3 = 1 : next process image of the digital outputs will be output next process image update of the digital outputs will be suppressed next process image of the digital inputs will be read in next process image update of the digital inputs will be suppressed next process image of the IPC flag inputs will be read in next process image update of the IPC flag inputs will be suppressed next process image of the IPC flag outputs will be output next process image update of the IPC flag outputs will be suppressed Note If a bit is set, it prevents the process image update once, following this it is immediately reset to "0" by the system program. CPU 928B Programming Guide 8 - 30 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 135 Condition codeword "disable individual time interrupts": see OB 121 (Section 6.6) Address EA87 The system data RS 135 indicates the following statuses of the program processing levels "time-driven interrupt processing". Table 8-13 Assignment of RS 135 (Disable individual time interrupts) Bit no. High byte: Disable individual time interrupts 15 0 14 0 13 0 12 0 11 Time interrupt 5 sec (OB 18) 10 Time interrupt 2 sec (OB 17) 9 Time interrupt 1 sec (OB 16) 8 Time interrupt 500 ms (OB 15) Bit no. Low b yte: Disable individual time interrupts 7 Time interrupt 200 ms (OB 14) 6 Time interrupt 100 ms (OB 13) 5 Time interrupt 50 ms (OB 12) 4 Time interrupt 20 ms (OB 11) 3 Time interrupt 10 ms (OB 10) 2 0 1 0 0 0 8 Bit = 1 means: this time interrupt is disabled. CPU 928B Programming Guide C79000-B8576-C898-01 8 - 31 User Memory Organization in the CPU 928B RS 137 Condition codeword "delay individual time interrupts": see OB 123 (Section 6.8.) Address EA89 The system data RS 137 indicates the following statuses of the program processing levels "time interrupt processing": Table 8-14 Assignment of RS 137 (Delay individual time interrupts) Bit no. High byte: Delay individual time interrupts 15 0 14 0 13 0 12 0 11 Time interrupt 5 sec (OB 18) 10 Time interrupt 2 sec (OB 17) 9 Time interrupt 1 sec (OB 16) 8 Time interrupt 500 ms (OB 15) Bit no. Low b yte: Delay individual time interrupts 7 Time interrupt 200 ms (OB 14) 6 Time interrupt 100 ms (OB 13) 5 Time interrupt 50 ms (OB 12) 4 Time interrupt 20 ms (OB 11) 3 Time interrupt 10 ms (OB 10) 2 0 1 0 0 0 Bit = 1 means: this time interrupt is delayed. CPU 928B Programming Guide 8 - 32 C79000-B8576-C898-01 User Memory Organization in the CPU 928B RS 140 Condition codeword "write and read blocks" Address EA8C System data RS 140 indicates whether blocks have been overwritten, newly loaded or deleted since the last OVERALL RESET of the CPU or since the last time system data RS 140 was cleared. The bits for changes and block type are allocated to each block. Before a new monitoring section, system data RS 140 must be cleared. RS 140 is also cleared during an overall reset. Table 8-15 Assignment of RS 140 (Write/read IDs) Bit no. High b yte: W rite/read IDs 15 Block deleted 14 Block newly loaded 13 Block overwritten 12 11 10 not used 9 8 8 Bit no. Low byte: Write/read IDs 7 not used 6 DX 5 DB 4 FX 3 FB 2 SP 1 PB 0 OB CPU 928B Programming Guide C79000-B8576-C898-01 8 - 33 User Memory Organization in the CPU 928B RS 144 "Alternative loading of data blocks into DB RAM" Address EA90 In the CPU 928B, all blocks are first loaded by the programmer into the user memory submodule as standard. Only when there is no more memory space there, are the data blocks (DBs, DXs) and only the data blocks loaded into DB RAM. You can influence the order of loading data blocks via bit no. 0 of system data word RS 144: Bit 0 = 0: Default "Standard behavior": The data blocks are loaded into the user memory submodule first. Only when there is no more space there, are they loaded into DB RAM. Bit 0 = 1: The data blocks are loaded into DB RAM first. Only when there is no more space there, are they loaded into the user memory submodule. The remaining bits of RS 144 are not assigned. Note Code blocks are loaded into the user memory regardless of the setting in RS 144. The setting in RS 144 has no influence on operations and special function OBs for generating and reloading blocks. CPU 928B Programming Guide 8 - 34 C79000-B8576-C898-01 Memory Access using Absolute Addresses 9 Contents of Chapter 9 9.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 4 9.2 Access using the Address in ACCU 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 8 9.2.1 9.2.2 LIR/TIR: Loading to or Transferring from a 16-Bit Memory Area Indirectly . . . . . . . . 9 - 9 Registers 0 to 3 and 9 to 12: ACCU 1, 2, 3 and 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 11 Register 6: Data Block Start Address (DBA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 11 Register 8: DBL = Data Block Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 14 Register 15: SAC = Step Address Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 15 Examples of using the Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 16 9.3 Transferring Fields of Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 18 9.3.1 Example of Transferring Memory Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 21 9.4 Operations with the Base Address Register (BR Register) . . . . . . . . . . . . . . . . . . . . . . 9 - 26 9.4.1 9.4.2 9.4.3 Operations for Transfer between Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessing the Local Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessing the Global Memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Testing and setting a busy location in the global area. . . . . . . . . . . . . . . . . . . . . . . . . Load and transfer operations for the global memory organized in bytes . . . . . . . . . . Load and transfer operations for the global memory organized in words . . . . . . . . . Accessing the Page Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Opening a page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Testing and setting a busy location in the page area . . . . . . . . . . . . . . . . . . . . . . . . . . Load and transfer operations for the pages organized in bytes. . . . . . . . . . . . . . . . . . Load and transfer operations for pages organized in words . . . . . . . . . . . . . . . . . . . . 9.4.4 9 - 27 9 - 28 9 - 29 9 - 29 9 - 31 9 - 32 9 - 33 9 - 34 9 - 34 9 - 35 9 - 37 CPU 928B Programming Guide C79000-B8576-C898-01 9-1 9 Memory Access using Absolute Addresses 9 This chapter explains how to use STEP 5 operations and special STEP 5 registers to address data in certain memory areas using absolute addresses. 9 CPU 928B Programming Guide C79000-B8576-C898-01 9-3 Introduction 9.1 Introduction The STEP 5 programming language contains operations with which you can access the entire memory area. These operations belong to the "system operations". Caution If the operations described in this section are not used properly, STEP 5 blocks and system data can be overwritten. This can result in undesirable operating statuses. Only experienced system programmers should use operations that work with absolute addresses. Local memory Local memory is the memory area available in each CPU (user submodule, DB-RAM, RI, RJ, RS, RT area, counters, timers, flags, process image). Global memory Global memory only exists once for all CPUs and is addressed via the S5 bus. Memory organization Memory areas are organized in b ytes or words as follows: * bytes: each address addresses a byte * words: each address addresses a 16-bit word (= 2 bytes) CPU 928B Programming Guide 9-4 C79000-B8576-C898-01 Introduction The local memory is internal and exists in each CPU 15 7 The global memory is an external memory shared by all CPUs in a PLC via the S5 bus 15 0 0000H 7 0 0000H EDFFH EE00H 255 15 7 0 EFFFH F000H 2 1 F400H FBFF 9 0 FC00H FEFFH Pages 1024 bytes/words 2048 bytes/words FFFFH Select register Fig. 9-1 Global and local memory CPU 928B Programming Guide C79000-B8576-C898-01 9-5 Introduction Memory access With the following operations, you can access local or global memory areas using absolute addresses (see also Fig. 9-2). Access to the local and global area You can acccess both the local and global areas: * local area (0000 to EFFF) and the part of the global memory or- ganized in bytes (F000 to F3FF, FC00 to FFFF): TNB, TNW, LIR, TIR * the part of the local area organized in words (0000 to E3FF and E800 to EDFF): LRW, TRW, LRD, TRD Access only to the global area You can access the following parts of the global area: * the part of the global area organized in bytes (0000 to EFFF): LY GB, LY GW, LY GD, TY GB, TY GW, TY GD, TSG * the part of the global area organized in words (0000 to EFFF): LW GW, LW GD, TW GW, TW GD, TSG Access to the page area You can access the following part of the page area: * the part of the global area organized in bytes (F400 to FBFF, = dual-port RAM area): LY CB, LY CW, LY CD, TY CB, TY CW, TY CD, TSC * the part of the global area organized in words (F400 to FBFF, = dual-port RAM area): LW CW, LW CD, TW CW, TW CD, TSC CPU 928B Programming Guide 9-6 C79000-B8576-C898-01 Introduction no access possible access possible a) LIR, TIR, TNB, TNW b) LRW, TRW, LRD, TRD c) LY GB, LY GW, LY GD TY GB, TY GW, TY GD, (TSG) d) LW GW, LW GD TW GW, TW GD, (TSG) e) LY CB, LY CW, LY CD TY CB, TY CW, TY CD, (TSC) f) LW CW, LW CD, TW CW, TW CD, (TSC) Fig. 9-2 9 Access to local or global memory areas using absolute addresses (see also Fig. 9-1) CPU 928B Programming Guide C79000-B8576-C898-01 9-7 Access using the Address in ACCU 1 9.2 Access using the Address in ACCU 1 Application Registers are memory cells used by the CPU to execute a STEP 5 program. Every register is 16 bits wide. Using the system operations LIR (load a register indirectly) and TIR (transfer a register indirectly) you can access the contents of the registers. Operations Table 9-1 Operations for indirect memory access using registers Operation Operand Function LIR Register no. 0 to 15 Load the specified register with the content of a memory word addressed by ACCU 1 (20-bit address). TIR Register no. 0 to 15 Load the content of the specified register in the memory word addressed by ACCU 1 (20-bit address). The memory word is either in the local area (0000 to EFFF) or in the the part of the global area organized in bytes (F000 to F3FF, FC00 to FFFF). The following pages explain which registers you can use with the operations. Examples explain how to use the operations. CPU 928B Programming Guide 9-8 C79000-B8576-C898-01 Access using the Address in ACCU 1 9.2.1 LIR/TIR: Loading to or Transferring from a 16-Bit Memory Area Indirectly The following table shows which register numbers you can use with the CPU 928B for the LIR and TIR operations and how these are assigned. Table 9-2 16-bit register for LIR/TIR Register no. Register assignment (each 16 bits wide) 1) 0 ACCU-1-H (left word of ACCU1, bits 16 to 31)1) 1 ACCU-1-L (right word of ACCU1, bits 0 to 15)1) 2 ACCU-2-H 3 ACCU-2-L 5 Block stack pointer (offset) 6 DBA (data block start address register) 8 DBL (data block length register) 9 ACCU-3-H 10 ACCU-3-L 11 ACCU-4-H 12 ACCU-4-L Loading the contents of an addressed memory register into register '0'or '1 overwrites the address stored in ACCU 1. 9 Registers 4, 7, 13, 14 and 15 do not exist on the CPU 928B. LIR/TIR operations with these register numbers are treated as no operations (NOP). LIR and TIR with the page area The LIR and TIR operations are not suitable for accessing the page area (addresses F400 to FBFF) in the S5-135U multiprocessor PLC. Use instead the operations from Section 9.4.4 "Accessing the Page Memory" or the special functions from Section 6.21 "Page Accesses". LIR/TIR: with 8-bit memory areas If you use the LIR and TIR operations to access memory areas that are only 8 bits wide i.e., for memory addresses from E400 to E7FF and EE00 remember that * the TIR operation transfers only the low byte of the register. The high byte of the register is lost. and * the LIR operation overwrites the high byte of the registers with FFH . CPU 928B Programming Guide C79000-B8576-C898-01 9-9 Access using the Address in ACCU 1 Figures 9-3 and 9-4 illustrate the difference between LIR/TIR access to word and byte-oriented areas: 15 15 0 0 15 0 addressed memory cell Register n ACCU 1 LIR n 15 0 15 0 addressed memory cell Register n ACCU 1 TIR n Fig. 9-3 LIR/TIR with 16-bit memory areas (word-oriented) 7 15 0 0 15 0 addressed memory cell F Register n F ACCU 1 LIR n 15 0 15 0 addressed memory cell x x Register n ACCU 1 TIR n Fig. 9-4 LIR/TIR with a-bit memory areas (byte-oriented) CPU 928B Programming Guide 9 - 10 C79000-B8576-C898-01 Access using the Address in ACCU 1 Registers 0 to 3 and 9 to 12: During program execution, the CPU uses the accumulators as buffers. Using the TIR operation, you can transfer the contents of the ACCU 1, 2, 3 and 4 accumulators into memory cells with absolute addresses. With the LIR operation, you can load the contents of memory cells with absolute addresses into the accumulators. The absolute address of the memory cell is always in ACCU-1-L. Examples You want to load the contents of the memory cell with the address A000 into flag word FW 100. :L KH A000 :LIR 1 : :T FW 100 :BE load address A000 of the memory cell into ACCU 1 load the contents of the memory cell in ACCU 1 into register 1 = load ACCU 1 store the contents of address A000 in flag word FW 100 You want to transfer the contents of flag word 200 to the memory cell with the address A000. :L FW 200 :L KH A000 : :TIR 3 : :BE load flag word FW 200 into ACCU 1 load address A000, the destination address, in ACCU 1 (flag word FW 200 to ACCU 2) transfer contents of register 3 = ACCU 2 into the memory cell addressed by ACCU 1 Register 6: Data Block Start Address (DBA) 9 When you open a data block with the operations C DB and CX DX, the address of DW 0 of this data block is loaded in register 6. The block address list in DB 0 contains this address. The DBA register is set to "0" before each OB 1 or FB 0 call. The DBA register remains the same if the following occurs: * a jump operation (JU/JC) causes program execution to continue in a different block or * a different program processing level is inserted. CPU 928B Programming Guide C79000-B8576-C898-01 9 - 11 Access using the Address in ACCU 1 It changes if one of the following occurs: * another data block is opened or * the program returns to a higher level block after a new data block was opened in the inserted block (see also Section 2.4.2, Range of Validity of Data Blocks). Note In the ISTACK, the address entered in the DBA register appears under the heading "DB-ADD". You normally access data words with the STEP 5 operations L/T DW, L/T DR, L/T DL, L/T DD, A/O/AN/ON/=/S/R Dx.y. You can only use these operations up to data word DW 255. However, by manipulating the DBA register, you can use them to access data words > 255. This is also possible with special function OB 180 (see Section 6.15). Examples Example 1: Effect of the "CX DX 17" operation on the DBA register: Addresses DX 17 1516H 1517H 1518H 5 words block header 1519H 151AH DBA 151BH KH = 0000 DW 0 151CH KH = 0001 DW 1 151DH Fig. 9-5 . . . DW 2 Using the DBA register When DX 17 is called, the address of the memory word in which DW 0 is stored is entered in the DBA register. In this example, the DBA is 4152H. Note: In the ISTACK, the address entered in the DBA register appears under the heading 'DB-ADD'. CPU 928B Programming Guide 9 - 12 C79000-B8576-C898-01 Access using the Address in ACCU 1 Example 2: By changing register 6, you can load data word DW 300 of data block DB 100. FB 7 NAME : LIR/TIR6 :L :ADD :LIR :ADD :T :L :ADD :LIR : RS 34 BN+100 1 KF+200 RS 62 RS 20 KF+62 6 :L :T :BE DW 100 FW 100 start address of the DB address list plus 100 produces the address list entry of DB 100 start address of DB 100 (DW 0) to ACCU 1 store address of DW 200 in DB 100 in system data word RS 62 load base address of system data load address of RS 62 in ACCU 1 load DBA register with the contents of the address of RS 62, i.e., the data block start is set to DW 200 load DW (200 + 100) = DW 300 store DW 300 in flag word FW 100 Example 3: Changing the DBA and DBL registers. FB7 NAME :OB180 :C :L :JU : :JC : :L :T :BEU ERRO : : :BE DB 100 KF 200 OB 180 =ERRO DW 100 FW 100 DBA and DBL registers are loaded with the values of DB 100 and with the help of OB 180 the DBA register is increased by 200 and the DBL register reduced by 200 error output, in case DB 100 contains less than or equal to 200 data words load DW 300 and store in FW 100 9 program section for error handling Note If you manipulate the DBA register as shown in example 1, the DBL register is not changed. This means that transfer error monitoring can no longer be guaranteed. By using the special function OB 180 "variable data block access" you can also shift the DBA register by a selected number of data words. Since OB 180 also changes the DBL register at the same time, transfer error monitoring remains in effect. CPU 928B Programming Guide C79000-B8576-C898-01 9 - 13 Access using the Address in ACCU 1 Register 8: DBL = Data Block Length In addition to the DBA register, a DBL register is loaded every time a data block is called. This contains the length (in words) of the data block called, without the block header. The DBL register is set to "0" before each OB 1 or FB 0 call. The DBL register remains the same if the following occurs: * a jump operation (JU/JC) causes program execution to continue in a different block or * a different program processing level is inserted. It changes if one of the following occurs: * another data block is opened or * the program returns to a higher level block after a new data block was opened in the inserted block (see also Section 2.4.2). CPU 928B Programming Guide 9 - 14 C79000-B8576-C898-01 Access using the Address in ACCU 1 Example Effect of the "CX DX 17" operation on the DBL: Addresses DX17 1516H 1517H 1518H 5 words block header 1519H 151AH DBA 151BH aaaa DW 0 151CH bbbb DW 1 151DH cccc DW 2 151EH dddd DW 3 151FH eeee DW 4 1520H ffff DW 5 1521H gggg DW 6 1522H hhhh DW 7 DBL Fig. 9-6 9 Using the DBL register When DX 17 is called, the number of existing data words is entered in the DBL register. In this example the DBL is 8 (DW 0 to DW 7) Note: In the ISTACK, the number entered in the DBL register appears under the heading "DBL-REG". Register 15: SAC = Step Address Counter During STEP 5 program execution, register 15 contains the absolute address of the operation in the program memory to be processed next. CPU 928B Programming Guide C79000-B8576-C898-01 9 - 15 Access using the Address in ACCU 1 9.2.2 Examples of using the Registers Example 1: You want all the data words of a data block to contain a constant. The program shown below writes the constant KH=A5A5 to all data words in DB 50. After changing the STEP 5 operations shown in bold face, it can also be used to write any values required to different data blocks (DB or DX). Non-existent data blocks or data blocks with no data words are detected and cause a jump to the NIVO label. The start address (DBA) and length (DBL) of the data block are determined by the special function OB 181 "test data block (DB/DX)". The program uses all four accumulators. In the figure, you can see the occupation of the accumulators during the program as far as the LOOP label. Within the loop, the accumulator occupation does not change. ACCU 1 initially contains the address of the last data word (DBA + DBL - 1) and is reduced by 1 each time the loop is run through. ACCU 2 contains the address of the first data word (DBA). The loop is abandoned as soon as the contents of ACCU 1 are less than the contents of ACCU 2. The operation TIR 10 that stores the contents of ACCU-3-L (the constant) under the address located in ACCU-1-L is used to write to the data words. : :L KY 1,50 constant to be written to all data words type and number of the data block OB 181 =NIVO special function OB "test data blocks" abandon if DB 50 does not exist =NIVO ACCU 1 := address of last data word + 1 ACCU 2 := address of the first data word ACCU 3 := constant abandon if DB 50 contains no data words KHA5A5 : :L :ENT :JU :JC :TAK :ENT :+F : : : :!=F :JC : LOOP :ADD :TIR : :> L TNB 5 L L TNW 2 Transferring blocks of memory CPU 928B Programming Guide 9 - 20 C79000-B8576-C898-01 Transferring Fields of Memory 9.3.1 Example of Transferring Memory Fields a) Task You want to copy a field of maximum 4095 data words from a DB or DX data block to a different DB or DX data block. The start of the field of data is specified within the source and destination data block by an offset value between 0 and 4095. The program is stored in FB 10. KY (type, no.) STNO FB10 Source DB KF (Offset ) SOFF Source DB BY KY (type, no.) DTNO STAT Status Dest. DB KF (Offset) DOFF Dest. DB KF (block length) Fig. 9-9 LENG 9 Function block for transferring fields of data Before the copying function is started, the input parameters are checked. In the event of an error, bit no. 7 = 1 is set in the output parameter STAT and the type of error specified in bits no. 0 to no. 2 as follows: Bit no. 7 6 5 0 = no error 1 = error 4 3 2 1 0 Type of error 1 = source DB = destination DB 2 = offset or length > 4095 3 = source DB does not exist or illegal 4 = source DB too short 5 = destination DB does not exist or illegal 6 = destination DB in read-only memory (EPROM submodule) 7 = destination DB too short Continued on next page CPU 928B Programming Guide C79000-B8576-C898-01 9 - 21 Transferring Fields of Memory Example 1 continued: b) Program structure: FB 10 is made up of five program sections with the following tasks: - Input parameters a) Check that the source and destination data block are not the same type and same number. b) Check that the input parameters "source offset", "destination offset" and "length of field" are less than 4096. - Source data block: a) Check that the source data block exists and is long enough. b) Calculate the absolute address of the last data word in the destination field. - Destination data block: a) Check that the destination data block exists and is long enough and whether it is in the random access memory (RAM submodule or DB-RAM). b) Calculate the absolute address of the last data word in the destination field. - Transfer: Execute the copy function with the help of the TNW operation. Blocks of data with more than 255 words are transferred in sub-fields of 128 words (operation TNW 128). Any remaining data is transferred by an additional TNW operation. - Condition code: Write the output parameter "status" according to the results of the checks carried out. c) Occupied memory cells FW 242 End address of the data destination FW 244 End address of the data source FW 246 Length of the field of data FW 248 Offset in the destination data block FW 250 Type and number of the destination data block FW 252 Offset in the source data block FW 254 Type and number of the source data block RS 60 Sub-field counter Continued on next page CPU 928B Programming Guide 9 - 22 C79000-B8576-C898-01 Transferring Fields of Memory Example 1 continued: b) Programming function block FB 10 Note:If you want to copy from data word DW 0, the program sections shown in heavy print can be omitted. You do not specify an offset value. FB10 SEGMENT 1 NAME:DB-DB-TR DECL :STNOI/Q/D/B/T/C: D DATA BLOCK-DATA BLOCK TRANSFER KM/KH/KY/KS/KF/KT/KC/KG: KY DECL :SOFFI/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF DECL :DTNOI/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KY DECL :DOFFI/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF DECL :LENGI/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF DECL :STAT I/Q/D/B/T/C: Q BI/BY/W/D: BY : : BEGINNING OF INPUT PARAMETERS :LW =STNO TYPE (DB/DX) AND NUMBER OF :T FW 254 THE SOURCE DATA BLOCK :LW =DTNO TYPE (DB/DX) AND NUMBER OF :T FW 250 THE DESTINATION DATA BLOCK :!=F SOURCE DB = DESTINATION DB ? :JC =F001 JUMP IF YES : : : :LW :T FW :LW :T FW :OW =SOFF 252 =DOFF 248 OFFSET DATA OFFSET DATA IN SOURCE BLOCK IN DESTINATION BLOCK :LW :T : =LAEN FW 246 LENGTH (NUMBER OF DATA WORDS) OF THE FIELD TO BE TRANSFERRED (LENGTH OF FIELD) :OW OR SOURCE OFFSET, DESTINATION OFFSET :L KH F000 :AW :JP =F002 : : : : : : LENGTH >= 4096 ? JUMP, IF YES END OF INPUT PARAMETERS 9 Continued on next page CPU 928B Programming Guide C79000-B8576-C898-01 9 - 23 Transferring Fields of Memory Example 1 continued: : :L FW 254 :JU OB 181 :JC =F003 :TAK :ENT BEGINNING OF SOURCE DATA BLOCK TYPE AND NUMBER OF SOURCE DATA BLOCK TEST DATA BLOCK JUMP, IF BLOCK TEST NEGATIVE A1: NUMBER OF DWs, A2: ADDRESS A3: ADDRESS :L FW 252 :ENT OFFSET IN SOURCE DATA BLOCK A3: NUMBER OF DWs, A4: ADDRESS :L LENGTH OF FIELD FW 246 :+F OFFSET + LENGTH OF FIELD := 256 WORDS ? MULTIPLIED BY 2, NUMBER OF SUBFIELDS EACH WITH 128 WORDS END ADDRESS OF THE DATA SOURCE END ADDRESS OF THE DATA DESTINATION JUMP, IF FIELD LENGTH < 256 WORDS TRANSFER A SUB-FIELD REDUCE SOURCE END ADDRESS BY LENGTH OF THE SUB-FIELD REDUCE DESTINATION END ADDRESS BY LENGTH OF THE SUB-FIELD COUNT LOOP JUMP, IF NOT ALL SUBFIELDS HAVE BEEN TRANSFERRED FIELD LENGTH, LOW BYTE TRANSFER REMAINDER OF FIELD END TRANSFER BEGINNING OF CONDITION CODE ID 00 (HEX): NO ERROR OUTPUT PARAMETER STATUS/ERROR ERROR ID 81 (HEX): SOURCE DB = DESTINATION DB ERROR ID 82 (HEX): OFFSET OR LENGTH >= 4096 ERROR ID 83 (HEX): SOURCE DB ILLEGAL ERROR ID 84 (HEX): SOURCE DB TOO SHORT ERROR ID 85 (HEX): DESTINATION DB ILLEGAL ERROR ID 86 (HEX): DESTINATION DB IN READ-ONLY MEMORY ERROR ID 87 (HEX): DESTINATION DB TOO SHORT END OF CONDITION CODE 9 CPU 928B Programming Guide C79000-B8576-C898-01 9 - 25 Operations with the Base Address Register (BR Register) 9.4 Operations with the Base Address Register (BR Register) Application The BR register (base address register, 32 bits) is used by the load and transfer operations described from Section 9.3.3 onwards to address the memory. The absolute address of the memory cell to be accessed is calculated as the sum of the contents of the BR register and a constant as follows: Absolute address = BR register contents + constant Operations Table 9-5 Load and arithmetic operations with the BR register Operation Operand Function MBR Constant (0H to F FFFFH) Load the BR register with a 20-bit constant 1) ABR Constant (-32 768 to +32 767) Add a 16-bit constant to the contents of the BR register 1) Bits 220 to 231 of the BR register are set to "0". MBR 0 to FFFFF ABR -32768 to +32767 20-bit constant 31 0 BR 31 19 0 BR 0.........0 16-bit constant (fixed point number) 31 0 BR Fig. 9-10 Changing the BR register Loading the BR register * The BR register is retained when the same program processin g level is continued in another block called by the jump operation (JU FB / JC FB). * The BR register is retained after nesting in a different program execution level. When the system program calls another program processing level, the BR register is set to " 0 ". CPU 928B Programming Guide 9 - 26 C79000-B8576-C898-01 Operations with the Base Address Register (BR Register) Operations with the Base Address Register (BR Register) 9.4.1 Operations for Transfer between Registers Application You can use the operations described in this section for the fast exchange of values between the restisters ACCU 1, STEP address counter (SAC) and base address register (BR). Operations Table 9-6 1) Operations for transfer between registers Operation Operand Explanation MAS -- Transfer the contents of ACCU 1 (bit 20 to 214) to the SAC register (STEP address counter) MAB -- Transfer the contents of ACCU 1 (bits 20 to 231) to the BR register (base address register) MSA -- Transfer the contents of the STEP address counter (SAC register) to ACCU 1 1) MSB -- Transfer the contents of the SAC register (STEP address counter) to the BR register (base address register) 1) MBA -- Transfer the contents of the BR register (base address register) to ACCU 1 MBS -- Transfer the contents of the BR register (bits 20 to 214, base address register) to the SAC register (STEP address counter) Bits 215 to 231 are set to "0" The following figure illustrates how the registers are changed by the operations. CPU 928B Programming Guide C79000-B8576-C898-01 9 - 27 9 Operations with the Base Address Register (BR Register) 31 0 16 15 SAC MSA, MSB MAS, MBS 14 31 0 SAC 31 16 0 ACCU 1, BR .............. x x x 14 15 16 15 0 .............. 0 0 0 ACCU 1, BR 0 ACCU 1 MAB, MBA 31 16 15 0 BR Fig. 9-8 Register - register transfer operations 9.4.2 Accessing the Local Memory Application With the following operations, you can access the local memory organized in words using an absolute memory address. The absolute address is the total of the BR register contents and the 16-bit constant contained in the operation (-32768 to +32767). Operations Table 9-7 Operations for accessing the local memory Operation Operand Description 1) LRW Constant (-32768 to +32767) add the specified constant to content of the BR register and load the word addressed in this way in ACCU-1-L LRD Constant (-32768 to +32767) add the specified constant to content 1) of the BR register and load the double word addressed in this way in ACCU 1 TRW Constant (-32768 to +32767) add the specified constant to content of the BR register and transfer the content of ACCU-1-L to the word addressed in this way CPU 928B Programming Guide 9 - 28 C79000-B8576-C898-01 Operations with the Base Address Register (BR Register) Operation Operand Description Table 9-7 continued: TRD 1) Permissible address area Constant (-32768 to +32767) add the specified constant to content of the BR register and transfer the content of ACCU 1 to the double word addressed in this way ACCU 2 new = ACCU 1old The absolute address must be as follows: * for LRW, TRW: between 000H and E3FFH or E800H and EDFFH * for LRD, TRD: between 000H and E3FEH or E800H and EDFEH Error reaction If the calculated address of the memory location is not in the permissible memory area, the CPU detects a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). 9 9.4.3 Accessing the Global Memory Application With the following operations, you can access the global memory organized in bytes or words using an absolute memory address. The absolute address is the total of the BR register contents and the constant contained in the operation (-32768 to 32767). Testing and setting a busy location in the global area You can control the access of individual CPUs to common memory areas using a busy location. Each memory area used by more than one CPU has a busy location assigned to it that must be tested by each CPU before it can access this area. The busy location either contains the value "0" or the slot identifier of the CPU currently using the memory area. This CPU releases the memory area by writing "0" to the busy location again when it is finished. (Note the explanations for the operations "set semaphore/SED" and "enable semaphore/SEE" in Section 3.5.5.). CPU 928B Programming Guide C79000-B8576-C898-01 9 - 29 Operations with the Base Address Register (BR Register) The CPU tests and sets a busy location using the TSG operation. Operation TSG Sequence Operand -32768 to +32767 Explanation Add the specified constant to the content of the BR register and test and set the location addressed in this way. The low byte of the word addressed by the contents of the BR register + the constant is used as the busy location. If the content of the low byte is "0", the TSG operation enters the slot ID (from RS 29) into the busy location. Testing (= reading) and setting (= writing) the busy location is one program unit that cannot be interrupted. Result You can evaluate the result of the test in condition codes CC 0 and CC 1, as follows: CC 1 CC 0 Explanation 0 0 The busy location contains the value "0"; the CPU enters its slot ID. 1 0 The CPU's own slot ID is already entered in the busy location. 0 1 The busy location contains a different slot ID. Note All CPUs that require synchronized access to a com mon global memory area must use the TSG operation. Permissible address area The absolute address must be between 0000H and EFFFH. Error reaction If the calculated address of the memory location is not in the range shown, the CPU detects a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). CPU 928B Programming Guide 9 - 30 C79000-B8576-C898-01 Operations with the Base Address Register (BR Register) Load and transfer operations for the global memory organized in bytes Table 9-8 Operations for access to the global memory organized in bytes Operation Permissible address area Operand Description LY GB -32768 to +32767 add the specified constant to content of the BR register and load the byte addressed in this way in ACCU-1-LL 1) 3) LY GW -32768 to +32767 add the specified constant to content of the BR register and load the word addressed in this way in ACCU-1-L 2) LY GD -32768 to +32767 add the specified constant to content of the BR register and load the double word addressed in this way in ACCU 13) TY GB -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU-1-LL to the byte addressed in this way TY GW -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU-1-L to the word addressed in this way TY GD -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU 1 to the double word addressed in this way 1) ACCU-1-LH and ACCU-1-H are set to '0'. 2) ACCU-1-H is set to '0'. 3) ACCU 2 new : = ACCU 1old 3) The absolute address must be as follows: * between 0 and EFFFH (for LY GB, TY GB) * between 0 and EFFEH (for LY GW, TY GW) * between 0 and EFFCH (for LY GD, TY GD) CPU 928B Programming Guide C79000-B8576-C898-01 9 - 31 9 Operations with the Base Address Register (BR Register) Error reaction If the calculated address of the memory location is not in the range shwon, the CPU detects a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). Load and transfer operations for the global memory organized in words Table 9-9 Operations for access to the global memory organized in words Operation Description LW GW -32768 to +32767 LW GD -32768 to +32767 add the specified constant to content of the BR register and load the double word addressed in this way in ACCU 1 2) -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU-1-L to the word addressed in this way -32768 to +32767 add the specified constant to content of the BR register transfer the content of ACCU 1 to the double word addressed in this way TW GW TW GD Permissible address area Operand add the specified constant to content of the BR register and load the word addressed in this way in ACCU-1-L 1) 2) 1) ACCU-1-H is set to '0'. 2) ACCU 2 new : = ACCU 1old The absolute address must be as follows: * for LW GW, TW GW: between 0 and EFFFH * for LW GD, TW GD: between 0 and EFFEH Error reaction If the calculated address of the memory location is not in the range shown, the CPU detects a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). CPU 928B Programming Guide 9 - 32 C79000-B8576-C898-01 Operations with the Base Address Register (BR Register) 9.4.4 Accessing the Page Memory Application Using the following operations, you can access pages organized in bytes or words via an absolute memory address. The absolute address is the total of the BR register contents and the constant contained in the operation (-32768 to 32767). Procedure of accessing pages The global area includes a "window" in the address area F400H to FBFFH to allow access to one of maximum 256 memory areas (= pages). A page occupies a maximum of 2 K addresses and can be organized in bytes or words. Before each access to the page area, one of the 256 pages must be selected by entering its page number in the select register. Writing to the select register and the subsequent access to the page area cannot be interrupted. Before any access (load/transfer) to the page area, one of the 256 pages must be opened. To do this, you transfer the number of the page to be opened to ACCU-1-L; this number is entered in the CPU internal page register with the ACR operation. All subsequent page operations write the contents of the page register to the select register of the appropriate modules on the S5 bus before the page is accessed. Changing the page register * The page register is retained when the same progra m processing level is continued in another block called by the jump operation (JU FB / JC FB). * When the page register is modified in a block, its value is retained if the program jumps back to the calling block at the end of the block. * After another program processing level has been inserted, the system program loads the same value in the page register as it had before the other level was inserted. * When the system program calls another program processin g level, the page register is set to " 0 ". CPU 928B Programming Guide C79000-B8576-C898-01 9 - 33 9 Operations with the Base Address Register (BR Register) Opening a page Operation Operand ACR Explanation Open the page whose number is located in ACCU-1-L permitted values: 0 to 255 Error reaction The page number must be between 0 and 255. If this is not the case, the CPU recognizes a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). Testing and setting a busy location in the page area You can control the access of individual CPUs to common memory areas using a busy location. Each memory area used by more than one CPU has a busy location assigned to it that must be tested by each CPU before it can access this area. The busy location either contains the value "0" or the slot identifier of the CPU currently using the memory area. This CPU releases the memory area by writing "0" to the busy location again when it is finished. (Note the explanations of the operations "set semaphore/SED" and "enable semaphore/SEE" in Section 3.5.5.). The CPU tests and sets a busy location on the open page using the TSC operation. Operation TSC Sequence Operand -32768 to +32767 Explanation Add the specified constant to the content of the BR register and test and set the location on the opened page addressed in this way. The low byte of the word addressed by the contents of the BR register + the constant is used as the busy location. If the content of the low byte is "0", the TSC operation enters the slot ID (from RS 29) into the busy location. Testing (= reading) and setting (= writing) the busy location is one program unit that cannot be interrupted. CPU 928B Programming Guide 9 - 34 C79000-B8576-C898-01 Operations with the Base Address Register (BR Register) Result You can evaluate the result of the TSC operation in condition codes CC 0 and CC 1, as follows: CC 1 CC 1 Explanation 0 0 The busy location contains the value "0"; the CPU enters its slot ID. 1 0 The CPUs own slot ID is already entered in the busy location. 0 1 The busy location contains a different slot ID. Note All CPU s requiring synchronized access to a common global memory area (page area) must use the TSC operation. Error reaction Load and transfer operations for the pages organized in bytes The location must be on the corresponding module and on the common page between F F400H and F FBFFH. If this is not the case, the CPU recognizes a runtime error and calls OB 32, providing it is loaded. If OB 32 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). Table 9-10 Operation Operations for access to the pages organized in bytes Operand LY CB -32768 to +32767 LY CW -32768 to +32767 LY CD -32768 to +32767 Explanation add the specified constant to content of the BR register and load the byte in the opened page addressed in this way into ACCU-1-LL 1) 3) add the specified constant to content of the BR register and load the word in the opened page addressed in this way into ACCU-1-L 2) 3) add the specified constant to content of the BR register and load the double word in the opened page addressed in this way into ACCU 13) CPU 928B Programming Guide C79000-B8576-C898-01 9 - 35 9 Operations with the Base Address Register (BR Register) Operation Operand Explanation Table 9-10 continued: Permissible address area TY CB -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU-1-LL to the byte addressed in this way in the opened page. TY CW -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU-1-L to the word addressed in this way in the opened page. TY CD -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU 1 to the double word addressed in this way in the opened page. 1) ACCU-1-LH and ACCU-1-H are set to '0'. 2) ACCU-1-H is set to '0'. 3) ACCU 2 new : = ACCU 1old The absolute address must be as follows: * for LY CB, TY CB: between F400H and FBFFH * for LY CW, TY CW: between F400H and FBFEH * for LY CD, TY CD: between F400H and FBFCH Error reaction If the calculated byte address is not in the range shown, the CPU recognizes a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). CPU 928B Programming Guide 9 - 36 C79000-B8576-C898-01 Operations with the Base Address Register (BR Register) Load and transfer operations for pages organized in words Table 9-11 Operation Permissible address area Operations for access to the pages organized in words Operand Explanation LW CW -32768 to +32767 add the specified constant to content of the BR register and load the word addressed in this way in the opened page into ACCU-1-L 1) LW CD -32768 to +32767 add the specified constant to content of the BR register and load the double word addressed in this way in the opened page into ACCU 1 2) TW CW -32768 to +32767 add the specified constant to content of the BR register and transfer the content of ACCU-1-L to the word addressed in this way in the opened page. TW CD -32768 to +32767 add the specified constant to content of the BR register transfer the content of ACCU 1 to the double word addressed in this way in the opened page. 1) ACCU-1-H is set to '0'. 2) ACCU 2 new : = ACCU 1old 9 The absolute address must be as follows: * for LW CW, TW CW: between F400H and FBFFH * for LW CD, TW CD: between F400H and FBFEH Error reaction If the calculated address of the memory cell is not in the range shown, the CPU recognizes a runtime error and calls OB 31, providing it is loaded. If OB 31 is not loaded, the CPU goes to the stop mode. In both cases, error IDs are entered in ACCU-1-L, that define the error in greater detail (see Section 5.6.2). CPU 928B Programming Guide C79000-B8576-C898-01 9 - 37 Multiprocessor Mode and Communication 10 Contents of Chapter 10 10.1 Multiprocessor Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 4 10.1.1 10.1.2 10.1.3 10.1.4 10.1.5 When to use the Multiprocessor Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . What Communications Mechanisms are Available?. . . . . . . . . . . . . . . . . . . . . . . . . . . . Exchanging Data via IPC Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Flag Assignment and IPC Flag Assignment in Multiprocessor Mode (DB 1) . . . . How to Create Data Block DB 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2 Multiprocessor Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 13 10.2.1 10.2.2 10.2.3 10.2.4 10.2.5 10.2.6 10.2.7 10.2.8 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How the Transmitter and Receiver are Identified . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Why Data is Buffered. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How the Buffer is Processed and Managed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calling Communication OBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How to Assign Parameters to Communication OBs. . . . . . . . . . . . . . . . . . . . . . . . . . . How to Evaluate the Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3 Runtimes of the Communication OBs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 29 10.4 INITIALIZE Function (OB 200) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 31 10.4.1 10.4.2 10.4.3 10.4.4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Call Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5 SEND Function (OB 202) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 38 10.5.1 10.5.2 10.5.3 10.5.4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Call Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 4 10 - 4 10 - 5 10 - 9 10 - 9 10 - 13 10 - 14 10 - 15 10 - 16 10 - 19 10 - 20 10 - 21 10 - 22 10 - 31 10 - 33 10 - 33 10 - 36 10 - 38 10 - 38 10 - 38 10 - 40 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 1 10 Contents 10.6 SEND TEST Function (OB 203) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 43 10.6.1 10.6.2 10.6.3 10.6.4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Call Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.7 RECEIVE Function (OB 204) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 45 10.7.1 10.7.2 10.7.3 10.7.4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Call Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.8 RECEIVE TEST Function (OB 205) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 49 10.8.1 10.8.2 10.8.3 10.8.4 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Call Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.9 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 51 10.9.1 Calling the Special Function OB using Function Blocks . . . . . . . . . . . . . . . . . . . . . . . Programming function blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transferring Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming FB 110 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application of FB 110 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Extending the IPC Flag Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Structure of the connection list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Program structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programming function blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Application example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.9.2 10.9.3 10 - 43 10 - 43 10 - 43 10 - 43 10 - 45 10 - 45 10 - 45 10 - 46 10 - 49 10 - 49 10 - 49 10 - 49 10 - 51 10 - 52 10 - 58 10 - 58 10 - 62 10 - 64 10 - 64 10 - 65 10- 65 10 - 66 10 - 68 10 - 70 10 - 75 CPU 928B Programming Guide 10 - 2 C79000-B8576-C898-01 Multiprocessor Mode and Communication 10 At the beginning of this chapter, you will see when you can use the multiprocessor mode and which data exchange is possible in this mode. The chapter provides you with information about programming for multiprocessor operation (Section 10.1). The second part of the chapter provides you with detailed instructions and examples of exchanging larger amounts of data in the multiprocessor mode (multiprocessor communication Sections 10.2 to 10.9). 10 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 3 Multiprocessor Mode 10.1 Multiprocessor Mode Definitions of terms 10.1.1 When to use the Multiprocessor Mode You are in multiprocessor mode as soon as you plug in a coordinator module, regardless of how many CPUs or CP/IPs are plugged in. * If your user program is too large for one CPU and there is not enough memory, distribute your program on several CPUs. * When a particular part of your system has to be processed especially fast, separate the appropriate program part from the total program and run it on its own fast CPU. * When your system consists of several parts that you can separate easily and control independently, let CPU 1 process system part 1, CPU 2 process system part 2, etc. For more information on multiprocessing, read the information in your system manual. This will help you to decide which CPUs are best suited for your problem. 10.1.2 What Communications Mechanisms are Available? * "Interprocessor communication flags" are available for cyclic exchange of binary data between CPUs (CPU 948, CPU 946/947, CPU 928B, CPU 928 and CPU 922) or between CPUs and communications processors (CPs). * For the exchange of large amounts of data (e.g., entire data blocks) between the CPU 948, CPU 946/947, CPU 928B, CPU 928 and CPU 922 you are supported by the "special functions for m ultiprocessing" OB 200 to OB 205 (for more information refer to Section 10.2). CPU 928B Programming Guide 10 - 4 C79000-B8576-C898-01 Multiprocessor Mode 10.1.3 Exchanging Data via IPC Flags Interprocessor communication (IPC) flags are available for cyclic exchange of binary data. They are used mainly for transmitting information byte by b yte. Data is transferred as follows: CPU(s) CPU(s) CPU(s) Communications processor(s) The system program transfers IPC flags once per cycle. For data transfer between CPUs, the IPC flags are buffered physically on the coordinator. IPC flags are bytes that are transferred. You define them in DB 1 for each CPU as IPC input or output flags. If, for example, you have defined flag byte 50 on the CPU 1 as an IPC output flag byte, its signal state is transferred cyclically via the coordinator to the CPU on which the flag byte FY 50 is defined as an IPC input flag byte (see Section 10.1.5). Note There is no error message when the IPC flag byte exists physically but is only written by one CPU and never read out and vice-versa. Memory area Jumper settings With the CPU 948 the memory area for the IPC flags in the coordinator and the CPs covers the addresses F 200H to F F2FFH . On a CPU/communications processor there are 256 available IPC flag bytes. To avoid double assignments you must group the 256 available IPC flag bytes on the COR or CP modules. Fields of 32 bytes can be enabled or disabled (your system manual contains information about setting the jumpers). CPU 928B Programming Guide C79000-B8576-C898-01 10 - 5 10 Multiprocessor Mode Example CPU 1 Coordinator IPC output flags: FY 96 to FY 119 Write IPC input flags: FY 120 to FY 125 Read Enabled area per jumpers: IPC flag bytes FY 96 to FY 127 CPU 2 IPC output flags: FY 120 to FY 125 Write IPC input flags: FY 96 to FY 119 Read Fig. 10-1 Transferring IPC flags in the multiprocessor mode Note - The only flag bytes that you can specify as IPC flags are the ones enabled on the coordinator or on the CP(s). - A flag byte that is defined on one or more CPUs as an IPC input flag byte must be defined as an IPC output flag byte on one other CPU or CP. An IP C output flag byte is only allowed on one C PU , but this may be used as an IPC input flag in all other CPUs in the rack. - If you have flag bytes that you have not defined as IPC flags in a CPU, you can use them as normal flags! You cannot use S flags as IP C flags! CPU 928B Programming Guide 10 - 6 C79000-B8576-C898-01 Multiprocessor Mode Data exchange between CPUs and communication processors If you want to exchange data between one CPU and one CP, you must enable the necessary number of IPC flags on the CP. You have 256 bytes available that you can divide into groups of 32 bytes. If you want to transfer data from one CPU to several CPs, the areas you enable in the CPs and the coordinator must not overlap, otherwise the same address is assigned twice. If you want to use IPC flags simultaneously on the coordinator and in one or more CPs, you must also prevent double addressing as follows: Divide the IPC flags among the coordinator and the CPs in groups of 32 bytes. Remove jumpers on the coordinator to mask the IPC flag bytes that you want to use in the CP (refer to the System Manual). You can define a specific flag byte as an IPC output flag in one CPU only. However, you can define a specific flag byte as in IPC input flag in several CPUs. Example CP 1 CPU 1 IPC output flags: CP 1: FY 96 to FY 119 CP 2: FY 201 to FY 205 CP 1 CP 2 Enabled area: IPC flag bytes FY 96 to FY 127 CP 2 10 Enabled area: IPC input flags: CP 1: FY 120 to FY 125 CP 2: FY 195 to FY 200 Fig. 10-2 CP 1 IPC flag bytes FY 192 to FY 223 CP 2 Example of IPC flag areas on the CPs CPU 928B Programming Guide C79000-B8576-C898-01 10 - 7 Multiprocessor Mode Transmitting IPC flags in multiprocessor operation At the end of each program cycle, along with the updating of the process image, the CPU transmits the IPC flags specified in DB 1 when the coordinator signals the CPU that it can access the S5 bus. The coordinator allocates the bus enable signal to each CPU in sequence. When a CPU has access to the S5 bus, it can transmit only one byte. Because of this interleaved transmission, related (byte groups) IPC flag information can be separated and subsequently processed with old or incorrect values. If you want to transfer information that takes up more than one byte, you can prevent corruption of data by setting a parameter in extended data block DX 0. This parameter uses semaphores to ensure that all IPC flags specified in DB 1 are transferred in groups (see Chapter 7). While one CPU is transmitting IPC flags, another CPU cannot interrupt it. Because the next CPU has to wait to transmit its data, cyclic program processing of this CPU is delayed accordingly. Multiprocessor communication For transferring data blocks or more exactly fields of data with a size of max. 64 byte (= 32 data words), the following special functions are integrated in the CPU: * OB 200: INITIALIZE: preassign * OB 202: SEND: send a data field * OB 203: SEND TEST: test sending capacity * OB 204: RECEIVE: receive a data field * OB 205: RECEIVE TEST: test receiving capacity CPU 928B Programming Guide 10 - 8 C79000-B8576-C898-01 Multiprocessor Mode 10.1.4 The I/O area of the programmable controller is available only once on I/O Flag Assignment and the S5 bus. The I/O area encompasses the addresses F000H to IPC Flag Assignment in Multiprocessor Mode (DB 1) FFFFH. In multiprocessor mode, all CPUs in the programmable controller access this I/O area "simultaneously". To avoid data being overwritten, the I/O area must be divided between the individual CPUs. For this purpose, you must program D B 1 for every CPU . In DB 1 you define the inputs and outputs (byte addresses 0 to 127) and IPC flag inputs and outputs each CPU is to work with. If the CPU does not use any I/O or IPC flags, an (empty) DB 1 must still be available in multiprocessor mode. Note Only the input and output bytes defined in DB 1 will be taken into account during updating of the process I/O image by each CPU. 10.1.5 How to Create Data Block DB 1 Inputting or changing DB 1 * Create/modify DB 1 on the PG using the DB 1 screen form or * by editing DB 1 as a data block on the PG and then transferring it to the CPU. 10 Note The CPU evaluates the entered or changed DB 1 only after a cold restart! Using the DB 1 screen form 1. Select the editor for the DB 1 screen form on your PG (refer to Fig. 10-3). 2. Enter the required values for "digital inputs" etc. as decimal numbers. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 9 Multiprocessor Mode 3. Enter the values by pressing the enter key on the PG. The PG then generates DB 1. 4. Transfer DB 1 to the CPU or load it into an EPROM submodule. Note You can specify the timer field length in DX 0 and/or in the DB 1 screen form. We recommend that you specify this parameter only in DX 0 (see Chapter 7). Example of the DB 1 screen form DB 1 I/O assignment: Digital inputs: , 0, 1, 2, 3, 7, 10, , , , , , , , , , Digital outputs: , 0, 2, 4, 12, , , , , , , , , , , , IPC flag inputs: , 50, 51, 60, , , , , , , , , , , , , IPC flag outputs: , 70, 72,100, , , , , , , , , , , , , Timer field length: , Fig. 10-3 , PG screen form for generating DB 1 Editing DB 1 as a data block 1. Write the DB 1 start ID in data words 0, 1 and 2: DW 0: DW 1: DW 2: KH = 4D41 KH = 534B KH = 3031 ('M' 'A') ('S' 'K') ('0' '1') CPU 928B Programming Guide 10 - 10 C79000-B8576-C898-01 Multiprocessor Mode 2. Type in the individual operand areas (from data word 3 onwards). Before each operand area, you must specify an ID. The possible ID words are as follows: ID word for digital inputs ID word for digital outputs ID word for IPC input flags ID word for IPC output flags KH = DE00 KH = DA00 KH = CE00 KH = CA00 After each ID word, use fixed-point format to list the numbers of the inputs and outputs used. 3. Complete the entries with the DB 1 end ID "KH = EEEE" and transfer DB 1 to the CPU. Note You can make the DB 1 entries in any order. Remember that the process image of the inputs and outputs is updated in the reverse order to which you store the addresses in DB 1 (i.e. the last entry is updated first). Multiple entries of the same bytes (e.g., for test purposes) are possible. The system program makes multiple updates of the process images of bytes that are entered more than once. Example of editing DB 1 DB1 0: 1: 2: 3: 4: 5: 6: 7: 8: 9: 10: 11: 12: 13: 14: 15: 16: 17: 18: 19: 20: 21: 22: 23: 24: FD: CPU948ST.S5D KH KH KH KH KF KF KF KF KF KF KH KF KF KF KF KH KF KF KF KH KF KF KF KH = = = = = = = = = = = = = = = = = = = = = = = = 4D41; 534B; 3031; DE00; +00000; +00001; +00002; +00003; +00007; +00010; DA00; +00000; +00002; +00004; +00012; CE00; +00050; +00051; +00060; CA00; +00070; +00072; +00100; EEEE; DW 0-2: Start ID for DB 1 ID word for digital inputs Input byte 0 Input byte 1 Input byte 2 Input byte 3 . Input byte 10 ID word for digital outputs Output byte 0 Output byte 2 . Output byte 12 ID word for IPC flag inputs Flag byte 50 . Flag byte 60 ID word for IPC flag outputs Flag byte 70 . Flag byte 100 End ID 10 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 11 Multiprocessor Mode Entering DB 1 The system program adopts DB 1 during a cold restart. The system program checks to see if the inputs and outputs or IPC flags indicated in DB 1 exist in their corresponding modules. If they are not present there, a DB 1 error causes the CPU to go into the STOP mode and the STOP LED flashes slowly. The CPU no longer processes your program. After you program DB 1 and the CPU accepts it during a cold restart, the following rules apply: * Only the inputs and outputs indicated in DB 1 can access peripheral modules via the process images (L.../T... ...IB, ...IW, ...ID, ...QB, ...QW, ...QD operations and logic operations with inputs and outputs). Access to process image addresses not entered in DB 1 cause addressing errors. * You can loa d peripheral bytes directly by bypassing the process image using the L PY, L PW, L OY, L OW operations for all acknowledging inputs, regardless of entries in DB 1. * You can transfer directly (T PY, T PW) to bytes 0 to 127 only for the outputs indicated in DB 1. This is because the process image is also written to during direct transfer. Writing to I/O addresses not entered in DB 1 causes an addressing error. * Transfer without a process image : Direct transfer to byte addresses >127 is possible regardless of the entries in DB 1. Direct transfer of byte addresses of the extended I/Os (T OY, T OW) is also possible regardless of the entries in DB 1. CPU 928B Programming Guide 10 - 12 C79000-B8576-C898-01 Multiprocessor Communication 10.2 Multiprocessor Communication Definition 10.2.1 Introduction Multiprocessor communication means the exchange of larger amounts of data (data blocks) between CPUs operating in the multiprocessor mode. The COR 923C coordinator is necessary for multiprocessor communication. To transfer data blocks, or to be more precise, blocks of data with a maximum length of 64 bytes (= 32 data words), you can use the following special functions that are integrated in the CPU: * OB 200: INITIALIZE: preassign * OB 202: SEND: send a field of data * OB 203: SEND TEST: test sending capacity * OB 204: RECEIVE: receive a data field * OB 205: RECEIVE TEST: test receiving capacity The special function OBs, OB 200 and OB 202 to OB 205 are simply called "communication OBs" in the following sections. Required knowledge To use these functions, you only require basic knowledge of the STEP 5 programming language and the way in which SIMATIC S5 programmable controllers operate. You can obtain this basic information from the publications listed in "Further Reading". Basic sequence To transfer data, you must activate the SEND function on the transmitting CPU and the RECEIVE function on the receiving CPU. The data words of a DB or DX data block located in the transmitting CPU are transported via the coordinator 923C to the receiving CPU one after the other and written to the DB or DX data block with the same number and under the same data word address; i.e. this represents a "1:1" copy operation. Length of data fields transferred The amount of data that can be transferred with the SEND and RECEIVE functions is normally 32 words. If the block length (without header) is not a multiple of 32 words, the last field of data to be transferred is an exception and is less than 32 words long. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 13 10 Multiprocessor Communication The data block in the receiving CPU can be longer or shorter than the data block to be sent. It is, however, important that the data words transferred by the SEND function exist in the receiving block; otherwise the RECEIVE function signals an error. Example: Data block: Data to be sent in the transmitting CPU: Data received in the receiving CPU: DB 17 DB 17 Data word address DW 32 to DW 63 DW 32 to DW 63 10.2.2 How the Transmitter and Receiver are Identified Each field of data exchanged between the CPUs is marked with a number to indicate the source and destination CPU. The CPUs are numbered so that the leftmost CPU has the number 1 and each subsequent CPU to the right has a number increased by 1. Example S5-135U/155U: . . C O R C P U C P U C P U C 1 2 3 C P C P I I I Q Q I M . . Fig. 10-4 Sender/receiver identification CPU 928B Programming Guide 10 - 14 C79000-B8576-C898-01 Multiprocessor Communication 10.2.3 Why Data is Buffered Generally, the multiprocessor mode is used to distribute tasks on several CPUs. Since the tasks are not identical and the performance of the CPUs involved can be different, the program execution of the individual CPs in the multiprocessor mode is always asynchronous. This means that the data sent by a CPU cannot always be received immediately by another CPU. For this reason, the data to be transferred is buffered on the coordinator 923 C. The number of the CPU executing the task and the number of the sender when receiving and the receiver when sending define the source or the destination of a data field. Example Data transfer from CPU 3 to CPU 2: 1st step: S E ND, p a r a m e t e r o f r e c e i v i n g CPU = 2 . . C O R C P U C P U C P U C 1 2 3 C P C P I I I Q Q I M . . CPU 3 buffers its data on the coordinator. 10 2nd step: RECEI V E , p a r a m e t e r o f t r a n s m i t t i n g CPU = 3 . . C O R C P U C P U C P U C 1 2 3 C P C P I I I Q Q I M . . When CPU 2 is ready to receive, it copies the data from the coordinator buffer to the destination DB. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 15 Multiprocessor Communication 10.2.4 How the Buffer is Processed and Managed Principle The buffer is based on the FIFO principle (first in - first out, queue principle). The data is received in the order in which it is sent. This applies to each individual link (identified by the transmitting and receiving CPU) and is independent of other links. Data protection The buffer is battery-backed; this means that the "automatic warm restart following a power down" is possible without any restrictions. A loss of power during a data transfer does not cause any loss of data in the programmable controller. Management The coordinator 923 C has a memory capacity of 48 data fields each with a fixed length of 32 words. The INITIALIZE function assigns these fields to individual CPU links. Each memory field can receive exactly one field of data. The length of the data can be from 1 data word to 32 data words. A d ata field is entered in a memory field by a SEND function and read out again by a RECEIVE function. The number of memory fields assigned to a link is directly related to the parameters for the transmitting capacity (SEND, SEND TEST function) and receiving capacity (RECEIVE, RECEIVE TEST function). The transmitting capacity indicates how many of the memory fields reserved for a link are free at any particular time. The receivin g capacity indicates how many of the memory fields reserved for a link are occupied at any particular time. The sum of the transmitting and receiving capacity is always equal to the number of memory fields reserved for a link. CPU 928B Programming Guide 10 - 16 C79000-B8576-C898-01 Multiprocessor Communication Example Occupation of the buffer by a link The link between CPU 3 and CPU 2 is initialized. The link is assigned seven memory fields in the buffer of the coordinator. Following this, the data transfer shown below would be possible. Transmitting capacity (no. of free memory fields) initialize send field A send 4 fields B, C, D, E send 2 fields K, L send 4 fields F, G, H, I 7 6 5 4 Transmitter: CPU 3 3 2 1 0 7 6 2 4 0 5 5 0 1 5 3 7 2 2 7 Time 1 2 3 Receiver: CPU 2 4 5 6 7 Receiving capacity (no. of free memory fields) Fig. 10-5 receive fields A, B receive fields C, D, E, F, G receive fields H, I 10 receive fields K, L Example of the occupation of the COR buffer Sending/receiving n data fields means that the corresponding functions are called n times one after the other. To simplify the representation, at any one time, data can either be sent or received in this example. It is, however, possible and useful to transmit (CPU 3) and receive (CPU 2) simultaneously ("Parallel processing in a multiprocessor programmable controller"). In the example, fields H and I are received while fields K and L are sent. The example illustrates the queue organization of the buffer: the fields of data sent first (A,B,C...) are received first (A,B,C...). CPU 928B Programming Guide C79000-B8576-C898-01 10 - 17 Multiprocessor Communication Summary Buffering data on the coordinator COR 923C allows the asynchronous operation of transmitting and receiving CPUs and compensates for their different processing speeds. Since the capacity of the buffer is limited, the receiver should check "often" and "regularly" whether there are data in the buffer (RECEIVE TEST function, receiving capacity > 0) and should attempt to fetch stored data (RECEIVE function). Ideally, the RECEIVE function should be repeated until the receiving capacity is zero. This means that the transmitted data are not buffered for a longer period of time and that the receiver always has the current data. This also means that memory fields remain free (the transmitting capacity is increased) and prevents the sender from being blocked (i.e. when the transmitting capacity is zero). Note A receiving capacity of zero represents the ideal state (i.e. all transmitted data have been fetched by the receiver), on the other hand a transmitting capacity of zero indicates incorrect planning, as follows: - the SEND function is called too often, - the RECEIVE function is not called often enough or - there are not enough memory fields assigned to the link. The capacity of the buffer is insufficient to compensate temporary imbalances in the frequency with which the CPUs transmit and receive data. CPU 928B Programming Guide 10 - 18 C79000-B8576-C898-01 Multiprocessor Communication 10.2.5 System Start-Up If you require multiprocessor communication, then all CPUs involved must go through the same STOP-RUN transition (= RESTART), i.e. all the CPUs go through a COLD RESTART or all CPUs go through a WARM RESTART. You must make sure that the restart of at least all the CPUs involved in the communication is uniform in the following ways: * direct operation (front switch, programmer), * parameter assignment (DX 0) and/or * programming (using the special function organization block OB 223 "stop if non-uniform restarts occur in the multiprocessor mode") COLD RESTART In organization block OB 20 (COLD RESTART) only one CPU must set up the buffer (in the COR 923C) using the INITIALIZE function. Any existing data is lost. Following this, i.e. during the RESTART, you can call the SEND, SEND TEST, RECEIVE, RECEIVE TEST functions in the individual CPUs. With appropriate programming, you must make sure that this only occurs after the buffer in the coordinator has been correctly initialized. On completion of the RESTART, i.e. in the RUN mode, the user program is processed from the beginnin g, i.e. from the first operation in OB 1 or FB 0. WARM RESTART You must not use the INITIALIZE function in the organization blocks OB 21 (MANUAL WARM RESTART) and OB 22 (AUTOMATIC WARM RESTART). Calling the SEND, SEND TEST, RECEIVE, RECEIVE TEST functions can cause problems (refer to the following sections). On completion of the WARM RESTART, i.e. in the RUN mode, the user program is not processed from the start, but from the point at which it was interrupted . The point of interruption can, for example, be within the SEND function. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 19 10 Multiprocessor Communication 10.2.6 Calling Communication OBs Proceed as follows: 1. Call the INITIALIZE function only in the cold restart organization block OB 20 on one CPU. 2. Call the SEND, SEND TEST, RECEIVE, RECEIVE TEST functions either only within the cyclic program or only within the time-driven program. Double call Depending on the assignment of parameters in DX 0 ("interrupts at operation boundaries"), and the type of program execution (WARM RESTART, interrupt handling, e.g. OB 26 for cycle time error) it is possible that one of the functions INITIALIZE, SEND, SEND TEST, RECEIVE and RECEIVE TEST can be interrupted. If a user interface inserted at the point of interruption also contains one of the functions SEND, SEND TEST, RECEIVE and RECEIVE TEST an illegal call (double call) is recognized and an error is signalled (error number 67, Section 10.2.8). Parallel processing Once you have completed the assignment of the buffer (INITIALIZE function), you can execute the functions SEND, SEND TEST, RECEIVE and RECEIVE TEST in any combination and with any parameter assignment in all the CPUs simultaneously and parallel to each other. Taking a single link (e.g. from CPU 2 to CPU 3) it is possible to execute the SEND function (CPU 2) and the RECEIVE function (CPU 3) simultaneously. While CPU 2 is sending data fields to the coordinator, CPU 3 can already receive (fetch) buffered data fields from the coordinator. Areas occupied The communication OBs do not require a working area (for buffering variables) and do not call data blocks. They do, of course, access areas containing parameters, although only the parameters marked as output parameters are modified. CPU 928B Programming Guide 10 - 20 C79000-B8576-C898-01 Multiprocessor Communication Results bits The results bits (CC 1/CC 0, RLO etc.) are influenced by the communication OBs. For more detailed information refer to Section 10.2.8. Changes in the ACCUs * CPU 922, CPU 928, CPU 928B: The contents of ACCU 1 to ACCU 4 and the contents of the registers are not affected by the communication OBs. * CPU 946/947, CPU 948: 10.2.7 How to Assign Parameters to Communication OBs The contents of all registers and ACCU 1, 2 and 3 remain the same, only the contents of ACCU 4 are affected. The communication OBs have the following types of parameter: * input parameters, * output parameters and * call parameters. Input and output parameters are located in a maximum 10 byte long data field in the F flag area. The data field is divided into an area for input parameters and an area for output parameters. Input parameters The input parameters specify how a function is handled. All or part of the parameters are read out by communication OBs and evaluated, no write access takes place. Output parameters The output parameters contain all the information that the calling program needs about the result of a job, e.g. error bits. Some or all of the output parameters are written to by the communication OBs, this area is not read. Note You can assign a flag area with 10 flag bytes for all communications functions. The functions themselves require different numbers of bytes. Refer to the description of the single functions (Section 10.4ff). CPU 928B Programming Guide C79000-B8576-C898-01 10 - 21 10 Multiprocessor Communication Call parameters For all communication OBs the number of the first flag byte in the data field (= pointer to data field) in ACCU-1-L is transferred as the call parameter. Permitted values are 0 to 246. Example Data field with parameters for the RECEIVE function (OB 204) FY x + 0: transmitting CPU FY x + 1: -- input parameter not used FY x + 2: condition code byte FY x + 3: receiving capacity output parameter output parameter FY x + 4: block ID FY x + 5: block number output parameter output parameter FY x + 6: address of the first FY x + 7: received data word output parameter output parameter FY x + 8: address of the last FY x + 9: received data word output parameter output parameter This example illustrates that the number of the first F flag byte in the data field must not be higher than FY 246, since otherwise the parameter field of up to 10 bytes would exceed the limits of the flag area (FY 255). 10.2.8 How to Evaluate the Output Parameters Condition codes Among other things, the output parameters indicate whether or not a function could be executed and if not they indicate the reason for the termination of the function. The INITIALIZE, SEND, SEND TEST, RECEIVE and RECEIVE TEST functions affect the condition codes (see programming instructions for your CPUs, general notes on the STEP 5 operations): * the OV and OS bits (word condition codes) are always cleared, * the OR, STA, ERAB bits (bit condition codes) are always cleared, * RLO, CC 1 and CC 0 indicate whether a function has been executed correctly and completely. CPU 928B Programming Guide 10 - 22 C79000-B8576-C898-01 Multiprocessor Communication Table 10-1 Condition codes of the communication OBs Condition codes Evaluation Meaning R LO CC 1 CC 0 0 0 0 JC= Function executed completely and correctly 1 0 0 JC= Function aborted, pointer to data field illegal (>246) Function aborted owing to an initialization conflict 1 0 1 JC= and JM= Function aborted owing to an error (error number 1 to 9) 1 1 0 JC= and JP= Function aborted owing to a warning (warning number 1 or 2) In the followin g sections, it is assumed that the pointer to the data field contains a correct value. The first byte of the output parameter provides detailed information about the cause of termination. Condition code byte Bit no. 7 6 5 4 W E I 0 W = 1: Warning E = 1: Error I = 1: Initialization conflict Number: - of a warning - of an error - of an initialization conflict 3 2 1 0 10 Number CPU 928B Programming Guide C79000-B8576-C898-01 10 - 23 Multiprocessor Communication The first byte in the field of the output parameters (condition code byte) also indicates whether or not a function has been correctly and completely executed. This byte contains detailed information about the cause of termination of a function. Assuming that at least the pointer to the data field contains a correct value, this byte is always relevant. If the function has been executed correctly and completely, all the bits are cleared (= 0), and all other output parameters are relevant. If the function is aborted with a warning (bit number 7 = 1), only the condition code for the transmitting/receiving capacity is relevant, other output parameters (if they exist) are unchanged. If the function is aborted owing to an error (bit number 6 = 1) or an initialization conflict (bit number 5 = 1), all other output parameters remain unchanged. Evaluation of the code byte The identifiers 'W', 'E' and 'I' indicate the significance of the numbers. Apart from this bit-by-bit evaluation, it is also possible to interpret the whole condition code byte as a fixed point number without sign. If you interpret the condition code byte as a byte, the groups of numbers have the following significance: Table 10-2 Code byte for the communication OBs/number groups Number group Significance 0 Function executed correctly and completely 33 to 42 Function aborted owing to an initialization conflict 65 to 73 Function aborted owing to an error 129 to 130 Function aborted owing to a warning Errors are detected and indicated in the ascending order of the error numbers. This means that several errors may have occurred although (currently) only one is indicated. The other errors are then indicated by further calls. CPU 928B Programming Guide 10 - 24 C79000-B8576-C898-01 Multiprocessor Communication Example Initialization conflict The SEND function indicates an error and is not executed. If you then make program and/or parameter modifications and the SEND function again indicates an error with a higher number than previously, you can assume that you have corrected one of several errors. An initialization conflict can only occur with the INITIALIZATION function. If a conflict occurs, you must modify the program or the parameters. Initialization conflict numbers (evaluation of the condition code byte as a byte): Table 10-3 Cond. code byte Condition code byte: Initialization conflict numbers Significance 33 The pages required for multiprocessor communication (numbers 252 to 255) are not or not all available. 34 The pages required for multiprocessor communication (numbers 252 to 255) are defective. 35 The parameter "automatic/manual" is illegal. The following errors are possible: - the "automatic/manual" ID is less than 1, - the "automatic/manual" ID is greater than 2. 36 The parameter "number of CPUs" is illegal. The following errors are possible: - the number of CPUs is less than 2, - the number of CPUs is greater than 4. 37 The parameter "block ID" is illegal. The following errors are possible: - the block ID is less than 1, - the block ID is greater than 2. 38 The parameter "block number" is incorrect, since it is a data block with a special significance. The following errors are possible: - if block ID = 1 DB 0, DB 1, DB 2 - if block ID = 2 : DX 0, DX 1, DX 2 39 The parameter "block number " is incorrect, since the data block does not exist. 40 The parameter "start address of the assignment list" is too high or the data block is too short. 10 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 25 Multiprocessor Communication Cond. code byte Significance Table 10-3 continued: Errors 41 The assignment list in the data block is not correctly structured. 42 The sum of the assigned memory fields is greater than 48. If an error occurs, you must change the program/parameters. Error numbers (evaluation of the condition code byte as a byte): Table 10-4 Cond. code byte Condition code byte: Error numbers Significance 65 The parameter "receiving CPU" (SEND, SEND TEST) is illegal. The following errors are possible: - The number of the receiving CPU is greater than 4, - the number of the receiving CPU is less than 1, - the number of the receiving CPU is the same as the CPU's own number. 66 The parameter "transmitting CPU" (RECEIVE, RECEIVE TEST) is illegal. The following errors are possible: - The number of the transmitting CPU is greater than 4, - the number of the transmitting CPU is less than 1, - the number of the transmitting CPU is the same as the CPU's own number. 67 The special function organization block call is wrong (SEND, RECEIVE, SEND TEST, RECEIVE TEST). The following errors are possible: - Secondary error, since the INITIALIZE function could not be called or was terminated by an initialization conflict. - Double call: the call for this function (SEND, SEND TEST, RECEIVE or RECEIVE TEST) is illegal, since one of these functions INITIALIZE, SEND, SEND TEST, RECEIVE or RECEIVE TEST has already been called in this CPU in a lower processing level (i.e. cyclic program execution). - The CPU's own number is incorrect (system data corrupted); following power down/power up the CPU number is generated again by the system program. CPU 928B Programming Guide 10 - 26 C79000-B8576-C898-01 Multiprocessor Communication Cond. code byte Significance Table 10-4 continued: 68 The management data (queue management) of the selected links are incorrect; set up the buffer in the coordinator 923C again using the INITIALIZE function (SEND, RECEIVE, SEND TEST, RECEIVE TEST). 69 The parameter "block ID" (SEND) or the block ID provided by the sender (RECEIVE) is illegal. The following errors are possible: - The block ID is less than 1, - the block ID is greater than 2. 70 The parameter "block number" (SEND) or the block number supplied by the sender (RECEIVE) is illegal, since it is a data block with a special significance. The following errors are possible: - If the block ID = 1 : DB 0, DB 1, DB 2 - if the block ID = 2 : DX 0, DX 1, DX 2 71 The parameter "block number" (SEND) or the block number provided by the sender (RECEIVE) is incorrect. The specified data block does not exist. 72 The parameter "field number" (SEND) is incorrect. The data block is too short or the field number too high. 73 The data block is not large enough to receive the data field transmitted by the sender (RECEIVE). 10 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 27 Multiprocessor Communication Warning The function could not be executed; the function call must be repeated, e.g. in the next cycle. Warning numbers (evaluation of the condition code byte as a byte): Table 10-5 Cond. code byte Condition code bytes: Warning numbers Significance 129 The SEND function cannot transfer data, since the transmitting capacity was already zero when the function was called. 130 The RECEIVE function cannot accept data, since the receiving capacity was already zero when the function was called. CPU 928B Programming Guide 10 - 28 C79000-B8576-C898-01 Runtimes of the Communication OBs 10.3 Runtimes of the Communication OBs The "runtime" is the processing time of the special function organization blocks; the time from calling a block to its termination can be much greater if it is interrupted by higher priority activities (e.g. updating timers, etc.). Table 10-6 Runtimes of the communication OBs Special function OB Block name OB 200/ initialize OB 202/ send C PU 928 C PU 928 B CPU 946/ 94 7 C PU 948 230 ms 130 ms 130 ms 128 ms 90 ms 806 s (294 s 666 s (250 s 696 s (280 s 762 s (426 s 542 s (220 s basic time basic time basic time basic time basic time + 16 s/word); + 13 s/word); + 13 s/word); + 21 s/ + 19 s/ double word); double word); 118 s if a 115 s if a 145 s if a warning occurs warning occurs warning occurs 243 s if a 110 s if a warning occurs warning occurs 72 s OB 203/ send test OB 204/ receive C PU 922 50 s 80 s 207s 115 s 825 s (281 s 660 s (244 s 690 s (274 s 772 s (421 s 506 s (218 s basic time basic time basic time basic time basic time + 17 s/word); + 13 s/word); + 13 s/word); + 22 s/ + 18 s/ double word); double word); 115 s if a 98 s if a 128 s if a 132 s if a warning occurs warning occurs warning occurs 243 s if a warning occurs warning occurs OB 205/ receive test 70 s 48 s 78 s 223 s 120 s The runtimes listed in Table 10-6 assume that of four CPUs inserted in a rack, only the CPU whose runtimes are being measured accesses the SIMATIC S5 bus. If other CPUs use the bus intensively, the runtime increases particularly for the send/receive functions. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 29 10 Runtimes of the Communication OBs Transfer time An important factor of a link (e.g. from CPU 1 to CPU 2) is the total data transfer time. This is made up of the following components: * time required to send (see runtime), * length of time the data are buffered (on the COR 923C coordinator) and * the time required to receive data (see runtime) The length of time that the d ata are "in transit" is largely dependent on the length of time that the data is buffered and therefore on the structure of the user program (see " Buffering Data"). CPU 928B Programming Guide 10 - 30 C79000-B8576-C898-01 INITIALIZE Function (OB 200) 10.4 INITIALIZE Function (OB 200) 10.4.1 Function To transfer data from one CPU to another CPU, the data must be temporarily buffered. The INITIALIZE function sets up a buffer on the COR 923C coordinator. The memory is initialized in fields with a fixed length of 32 words. Each memory field accepts one data field with a length between 1 data word and 32 data words. A data field is entered in a memory field by a SEND function and read out by a RECEIVE function. If you are using two CPUs, there are two links (transfer directions, "channels"): CPU 1 CPU 2 If you are using three CPUs, there are six links: 10 CPU 1 CPU 2 CPU 3 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 31 INITIALIZE Function (OB 200) If you are using four CPUs, there are twelve links: CPU 1 CPU 2 CPU 3 CPU 4 The INITIALIZE function specifies how the total of 48 available memory fields are assigned to the maximum twelve links. This means that each possible link, specified by the parameters "transmitting CPU" and "receiving CPU" has a certain memory capacity available. Note Before you can call the SEND / RECEIVE / SEND TEST / RECEIVE TEST functions, one CPU must have already called the INITIALIZE function and executed it completely and without errors. If the INITIALIZE function is called several times, one after the other, the last assignment made is valid. While a CPU is processing the INITIALIZE function, no other multiprocessor communication functions including the INITIALIZE function can be called on other CPUs. CPU 928B Programming Guide 10 - 32 C79000-B8576-C898-01 INITIALIZE Function (OB 200) 10.4.2 Call Parameters Structure of the (parameter) data field Before calling OB 200, you must supply the input parameters in the data field. OB 200 requires eight F flag bytes in the data field for input and output parameters: FY x + 0: ACCU-1-L FY x + 1: FY x + 2: FY x + 3: FY x + 4: FY x + 5: Mode (automatic/ manual ) Number of CPUs Block ID Block number Start address of the assignment list input parameter input parameter input parameter input parameter input parameter FY x + 6: FY x + 7: Condition code byte Total capacity output parameter output parameter When OB 200 is called, you transfer the flag byte number at which the parameter data field begins to ACCU-1-L: ACCU-1-LH: ACCU-1-LL: 0 0 to 246 10.4.3 Input Parameters Mode (automatic/manual) Number of CPUs Mode = 1: Mode = 2: Mode = 0 or 3 to 255: automatic manual illegal, causes an initialization conflict 10 This parameter is only relevant when you have selected the "automatic" mode. With the "automatic" setting, the memory fields are divided evenly according to the number of CPUs. Number of CPUs Number of links Memory fields per link 2 2 24 3 6 8 4 12 4 0; 1; 5 to 255 Illegal, causes an initialization conflict CPU 928B Programming Guide C79000-B8576-C898-01 10 - 33 INITIALIZE Function (OB 200) Block ID, block number, address assignment list The parameters are only relevant if you select the "manual" mode. You must then create an assignment list in a data block in which the 48 available memory fields (or less) are assigned to the maximum 12 links. This function is particularly useful when some CPUs transfer more data than others. The CPUs not involved in the multiprocessor communication do not need and should not have memory fields assigned to them. The parameters * block ID, * block number and * start address of the assignment list specify where the assignment list is stored. Block ID ID = 1: ID = 2: ID = 0 or 3 to 255 : Block number For the block number, you specify the number of the DB or DX data block in which the assignment list is stored. Start address of the assignment list Along with the block ID and number, this specifies the area (or more precisely, the start address of the area) in the data block in which the assignment list is stored. As the address of the assignment list, specify the data word number at which the assignment list begins in flag bytes FY x+4 (high byte) and FY x+5 (low byte). DB data block DX data block illegal, causes an initialization conflict CPU 928B Programming Guide 10 - 34 C79000-B8576-C898-01 INITIALIZE Function (OB 200) Assignment list With the assignment list, you specify how many of the existing 48 memory fields are to be assigned to the links. The list is not ch anged by the system program. It has the following structure. Table 10-7 Assignment list for OB 200 (initialize) Data word Format Value Significance DW DW DW DW n+ n+ n+ n+ 0 1 2 3 KS KY KY KY S1 2,a 3,b 4,c Transmitter = CPU 1 Receiver = CPU 2 Receiver = CPU 3 Receiver = CPU 4 DW DW DW DW n+ n+ n+ n+ 4 5 6 7 KS KY KY KY S2 1,d 3,e 4,f Transmitter = CPU 2 Receiver = CPU 1 Receiver = CPU 3 Receiver = CPU 4 DW DW DW DW n+ 8 n+ 9 n + 10 n + 11 KS KY KY KY S3 1,g 2,h 4,i Transmitter = CPU 3 Receiver = CPU 1 Receiver = CPU 2 Receiver = CPU 4 DW DW DW DW n + 12 n + 13 n + 14 n + 15 KS KY KY KY S4 1,k 2,l 3,m Transmitter = CPU 4 Receiver = CPU 1 Receiver = CPU 2 Receiver = CPU 3 Instead of the lower case letters a to m (in bold face) numbers between 0 and 48 must be inserted depending on the number of assigned memory fields. The sum of these numbers must not exceed 48. 10 Note You must keep to the structure shown in Table 10-7 even if you have less than four CPUs. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 35 INITIALIZE Function (OB 200) Example You have three CPUs in your rack, CPU 2 sends a lot of data to the other two CPUs. The other two CPUs, however, only send a small amount of data back to CPU 2 as acknowledgements in a logical handshake. There is no data exchange between CPU 1 and CPU 3. The assignment list is stored in data block DB 40 from DW 0 onwards and has the following parameters: DB40 0: 1: 2: 3: 4: 5: 6: 7: 8: 9: 10: 11: 12: 13: 14: 15: 16: FD: KS KY KY KY KS KY KY KY KS KY KY KY KS KY KY KY CPU928ST.S5D = = = = = = = = = = = = = = = = S1; 2,2; 3,0; 4,0; S2; 1,22; 3,22; 4,0; S3; 1,0; 2,2 ; 4,0; S4; 1,0; 2,0; 3,0; Transmitter: Receiver: Receiver: Receiver: Transmitter: Receiver: Receiver: Receiver: Transmitter: Receiver: Receiver: Receiver: Transmitter: Receiver: Receiver: Receiver: CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU CPU 1 2/2 fields 3/no field 4 (does not 2 1/22 fields 3/22 fields 4 (does not 3 1/no field 2/2 fields 4 (does not 4 (does not 1/no field 2/no field 3/no field exist)/no field exist)/no field exist)/no field exist) 10.4.4 Output Parameters Condition code byte This byte informs you whether the INITIALIZE function was executed correctly and completely. Initialization conflict The initialization conflicts listed are recognized and indicated by the function in the ascending order of their numbers. If an initialization conflict occurs, you must change the program/parameters. All the numbers listed in the following table can occur in the condition code byte. CPU 928B Programming Guide 10 - 36 C79000-B8576-C898-01 INITIALIZE Function (OB 200) Cond. code byte Significance 33 The pages required for multiprocessor communication (numbers 252 to 255) are not or not all available. 34 The pages required for multiprocessor communication (numbers 252 to 255) are defective. 35 The parameter "automatic/manual" is illegal. The following errors are possible: - the "automatic/manual" ID is less than 1, - the "automatic/manual" ID is greater than 2. 36 The parameter "number of CPUs" is illegal. The following errors are possible: - the number of CPUs is less than 2, - the number of CPUs is greater than 4. 37 The parameter "block ID" is illegal. The following errors are possible: - the block ID is less than 1, - the block ID is greater than 2. 38 The parameter "block number" is incorrect, since it is a data block with a special significance. The following errors are possible: - if block ID = 1 DB 0, DB 1, DB 2 - if block ID = 2 : DX 0, DX 1, DX 2 39 The parameter "block number " is incorrect, since the data block does not exist. 40 The parameter "start address of the assignment list" is too high or the data block is too short. 41 The assignment list in the data block is not correctly structured. 42 The sum of the assigned memory fields is greater than 48. Errors The "error" number group cannot occur with the INITIALIZE function. Warning The "warning" number group cannot occur with the INITIALIZE function. Total capacity This parameter specifies how many of the 48 available memory fields are assigned to links. In the "automatic" mode, this parameter always has the value 48. In the "manual" mode, it can have a value less than 48. This means that existing memory capacity is not used. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 37 10 SEND Function (OB 202) 10.5 SEND Function (OB 202) 10.5.1 Function The SEND function transfers a data field to the buffer of the COR 923C coordinator. It also indicates how many data fields can still be sent or buffered. 10.5.2 Call Parameters Structure of the (parameter) data field ACCU-1-L Before calling OB 202 you must specify the input parameters in the data field. OB 202 requires six F flag bytes in the data field for input and output parameters: FY x + 0: FY x + 1: FY x + 2: FY x + 3: receiving CPU block ID block number field number input parameter input parameter input parameter input parameter FY x + 4: FY x + 5: condition code byte transmitting capacity output parameter output parameter When OB 202 is called, transfer the flag byte at which the parameter data field begins to ACCU-1-L: ACCU-1-LH: ACCU-1-LL: 0 0 to 246 10.5.3 Input Parameters Receiving CPU CPU number of the receiver (destination); the permitted value is between 1 and 4 but must be different from the CPU's own number. CPU 928B Programming Guide 10 - 38 C79000-B8576-C898-01 SEND Function (OB 202) Block ID ID = 1: ID = 2: ID = 0 or 3 to 255: Block number The block number, along with the block ID and the field number specifies the area from which the data to be sent is taken (and where it is to be stored in the receiving CPU). DB data block DX data block illegal, causes an error message Remember that certain data blocks have a special significance, for example, DB 0, DB 1 or DX 0 (see programming instructions for your CPUs). These data blocks must therefore not be used for the data transfer described here! If you attempt to use these block numbers, the function is aborted with an error message. Field number The field number indicates the area in which the data to be sent is located. Field number Data area First data word Last data word 0 1 DW 0 DW 32 DW 31 DW 63 2 3 DW 64 DW 96 DW 95 DW 127 4 5 DW 128 DW 160 DW 159 DW 191 6 7 DW 192 DW 224 DW 223 DW 255 8 9 : : DW 256 DW 288 : : DW 287 DW 319 : : 10 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 39 SEND Function (OB 202) The following situations are possible: * DB is longer than source area: If the data block is sufficiently long, you obtain a 32-word long area per field as shown in the table above. * DB is too short : If the end of the data block is within the selected field, in the last field an area with a length between 1 and 32 words will be transferred. * Field is outside the D B: If the first data word address of a field is not within the length of the data block, the SEND function detects and indicates an error. Example Data block with a length of 80 words: DW 0 to DW 74, 5 words are required for the block header. Field no.: First data word: Last data word: Length: 0 1 DW 0 DW 32 DW 31 DW 63 32 words 32 words 2 DW 64 DW 74 11 words 3 and higher Incorrect parameter assignment 10.5.4 Output Parameters Condition code byte This byte informs you whether the SEND function was executed correctly and completely. Initialization conflict Has no significance with the SEND function. CPU 928B Programming Guide 10 - 40 C79000-B8576-C898-01 SEND Function (OB 202) Errors When the SEND function is called, the following error numbers (evaluation of the condition code byte) can occur: Condition code byte Significance 65 The parameter "receiving CPU" is illegal. The following errors are possible: - The number of the receiving CPU is greater than 4 - The number of the receiving CPU is less than 1 - The number of the receiving CPU is the same as the CPU's own number. 67 The special function organization block call is wrong. The following errors are possible: - Secondary error, since the INITIALIZE function could not be called or was terminated by an initialization conflict. - Double call: the call for this function, SEND, SEND TEST, RECEIVE or RECEIVE TEST is illegal, since one of the functions INITIALIZE, SEND, SEND TEST, RECEIVE or RECEIVE TEST has already been called in this CPU in a lower processing level (e.g. cyclic program processing). - The CPU's own number is incorrect (system data corrupted) following power down/power up the CPU number is generated again by the system program. 68 The management data (queue management) of the selected links are incorrect; set up the buffer in the coordinator 923C again using the INITIALIZE function. 69 The parameter "block ID" is illegal. The following errors are possible: - The block ID is less than 1, - the block ID is greater than 2. 10 70 The parameter "block number" is illegal, since it is a data block with a special significance. The following errors are possible: - If the block ID = 1 : DB 0, DB 1, DB 2 - If the block ID = 2 : DX 0, DX 1, DX 2 71 The parameter "block number" is incorrect. The specified data block does not exist. 72 The parameter "field number" is incorrect. The data block is too short or the field number too high. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 41 SEND Function (OB 202) Warning The function could be executed; the function call must be repeated, e.g. in the next cycle. The following warning numbers (evaluation of the condition code byte) can occur: Condition code byte 129 Transmitting capacity Significance The SEND function cannot transfer data, since the transmitting capacity was already zero when the function was called. The "transmitting capacity" indicates how many data fields can still be sent and buffered. CPU 928B Programming Guide 10 - 42 C79000-B8576-C898-01 SEND TEST Function (OB 203) 10.6 SEND TEST Function (OB 203) 10.6.1 Function The SEND TEST function determines the number of free memory fields in the buffer of the COR 923C coordinator. Depending on this number m, the SEND function can be called m times to transfer m data fields. 10.6.2 Call Parameters Structure of the (parameter) data field ACCU-1-L Before calling OB 203, you must specify the input parameters in the data field. OB 203 requires 4 F flag bytes in the data field for input and output parameters: FY x + 0: FY x + 1: receiving CPU -- input parameter not used FY x + 2: FY x + 3: condition code byte transmitting capacity output parameter output parameter When OB 203 is called, transfer the flag byte number at which the parameter data field begins to ACCU-1-L: ACCU-1-LH: ACCU-1-LL: 0 0 to 246 10.6.3 Input Parameters Receiving CPU 10 The CPU's own number and the number of the receiving CPU identify the link for which the transmitting capacity is determined. 10.6.4 Output Parameters Condition code byte This byte indicates whether the SEND TEST function was executed correctly and completely. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 43 SEND TEST Function (OB 203) Initialization conflict Has no significance for the SEND TEST function. Errors When calling the SEND TEST function, the following error numbers (evaluation of the condition code byte) can occur: Condition code byte Significance 65 The parameter "receiving CPU" is illegal. The following errors are possible: - The number of the receiving CPU is greater than 4, - The number of the receiving CPU is less than 1, - The number of the receiving CPU is the same as the CPU's own number. 67 The special function organization block call is wrong. The following errors are possible: - Secondary error, since the INITIALIZE function could not be called or was terminated by an initialization conflict. - Double call: the call for this function, SEND, SEND TEST, RECEIVE or RECEIVE TEST is illegal, since one of the functions INITIALIZE, SEND, SEND TEST, RECEIVE or RECEIVE TEST has already been called in this CPU in a lower processing level (e.g. cyclic program processing). - The CPU's own number is incorrect (system data corrupted); following power down/power up the CPU number is generated again by the system program. 68 The management data (queue management) of the selected links are incorrect; set up the buffer in the coordinator 923C again using the INITIALIZE function. Warning The "warning" number group cannot occur with the SEND TEST function. Transmitting capacity The "transmitting capacity" parameter indicates how many data fields can be sent and buffered. CPU 928B Programming Guide 10 - 44 C79000-B8576-C898-01 RECEIVE Function (OB 204) 10.7 RECEIVE Function (OB 204) 10.7.1 Function The RECEIVE function takes a data field from the buffer of the COR 923C coordinator. It also indicates how many data fields are still buffered and can still be received. The RECEIVE function should be called in a loop until all the buffered data fields have been received. 10.7.2 Call Parameters Structure of the (parameter) data field ACCU-1-L Before calling OB 204, you must specify the input parameters in the data field. OB 204 requires 10 F flag bytes in the data field for input and output parameters: FY x + 0: FY x + 1: transmitting CPU -- input parameter not used FY x + 2: FY x + 3: FY x + 4: FY x + 5: FY x + 6: FY x + 7: FY x + 8: FY x + 9: condition code byte receiving capacity block ID block number address of the first received data word address of the last received data word output parameter output parameter output parameter output parameter output parameter output parameter output parameter When calling OB 204, transfer the flag byte number at which the parameter data field begins to ACCU-1-L: ACCU-1-LH: ACCU-1-LL: 0 0 to 246 10.7.3 Input Parameters Transmitting CPU The receive block receives data supplied by the transmitting CPU. Specify the number of the transmitting CPU. The permitted value is between 1 and 4, but must be different from the CPU's own number. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 45 10 RECEIVE Function (OB 204) 10.7.4 Output Parameters Condition code byte This byte informs you whether the RECEIVE function was executed correctly and completely. Initialization conflict Has no significance with the RECEIVE function. Errors When calling the RECEIVE function the following error numbers (evaluation of the condition code byte) can occur: Condition code byte Significance 66 The parameter "transmitting CPU" is illegal. The following errors are possible: - The number of the transmitting CPU is greater than 4, - The number of the transmitting CPU is less than 1, - The number of the transmitting CPU is the same as the CPU's own number. 67 The special function organization block call is wrong. The following errors are possible: - Secondary error, since the INITIALIZE function could not be called or was terminated by an initialization conflict. - Double call: the call for this function, SEND, SEND TEST, RECEIVE or RECEIVE TEST is illegal, since one of the functions INITIALIZE, SEND, SEND TEST, RECEIVE or RECEIVE TEST has already been called in this CPU in a lower processing level (e.g. cyclic program processing). - The CPU's own number is incorrect (system data corrupted) following power down/power up the CPU number is generated again by the system program. 68 The management data (queue management) of the selected links are incorrect; set up the buffer in the coordinator 923C again using the INITIALIZE function. 69 The block identifiers supplied by the transmitter are illegal. The following errors are possible: - The block ID is less than 1, - The block ID is greater than 2. CPU 928B Programming Guide 10 - 46 C79000-B8576-C898-01 RECEIVE Function (OB 204) Condition code byte Significance Error numbers continued: Warning 70 The block number supplied by the transmitter is illegal, since it is a data block with a special significance. The following errors are possible: - If the block ID = 1 : DB 0, DB 1, DB 2 - If the block ID = 2 : DX 0, DX 1, DX 2 71 The block number provided by the transmitter is incorrect. The specified data block does not exist. 73 The data block is too small to receive the data field supplied by the transmitter. The function could not be executed; the function call must be repeated, e.g. in the next cycle. The following warning number (evaluation of the condition code byte) can occur: Condition code byte 130 Receiving capacity Significance The RECEIVE function cannot receive data, since the receiving capacity was already zero when the function was called. The "receiving capacity" parameter indicates how many data fields are still buffered and can still be received. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 47 10 RECEIVE Function (OB 204) Block ID: ID = 1: ID = 2: ID = 0 or 3 to 255: Block number Block number of the DB/DX in which the received data are stored (and from which they are taken by the SEND function in the transmitting CPU). DB data block DX data block illegal, causes an error message Remember that the receive data blocks must be in a random access memory, using read-only memories (EPROM) might possibly serve a practical purpose for transmit data blocks only. Address of the first received data word Data word number within the DB/DX in which the first transferred/received data word was stored. Address of the last received data word Data word number within the DB/DX in which the last transferred/received data word was stored. Note The difference between the addresses of the first and last data word transferred is a maximum of 31, since a maximum of 32 data words can be transferred per function call. CPU 928B Programming Guide 10 - 48 C79000-B8576-C898-01 RECEIVE TEST Function (OB 205) 10.8 RECEIVE TEST Function (OB 205) 10.8.1 Function The RECEIVE TEST function determines the number of occupied memory fields in the buffer of the COR 923C coordinator. Depending on this number m, the RECEIVE function can be called m times to receive m data fields. 10.8.2 Call Parameters Structure of the (parameter) data field ACCU-1-L Before calling OB 205, you must specify the input parameters in the data field. OB 205 requires 4 F flag bytes in the data field for input and output parameters: FY x + 0: FY x + 1: transmitting CPU -- input parameter not used FY x + 2: FY x + 3: condition code byte receiving capacity output parameter output parameter When calling OB 204, transfer the flag byte number at which the parameter data field begins to ACCU-1-L: ACCU-1-LH: ACCU-1-LL: 0 0 to 246 10.8.3 Input Parameters 10 Transmitting CPU The CPU's own number and the number of the transmitting CPU identify the link for which the receiving capacity is determined. 10.8.4 Output Parameters Condition code byte This byte indicates whether the RECEIVE TEST function was executed correctly and completely. Initialization conflict Has no significance with the RECEIVE TEST function. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 49 RECEIVE TEST Function (OB 205) Errors When calling the RECEIVE TEST function, the following error numbers (evaluation of the condition code byte) can occur: Condition code byte Significance 66 The parameter "transmitting CPU" is illegal. The following errors are possible: - The number of the transmitting CPU is greater than 4, - The number of the transmitting CPU is less than 1, - The number of the transmitting CPU is the same as the CPU's own number. 67 The special function organization block call is wrong. The following errors are possible: - Secondary error, since the INITIALIZE function could not be called or was terminated by an initialization conflict. - Double call: the call for this function, SEND, SEND TEST, RECEIVE or RECEIVE TEST is illegal, since one of the functions INITIALIZE, SEND, SEND TEST, RECEIVE or RECEIVE TEST has already been called in this CPU in a lower processing level (e.g. cyclic program processing). - The CPU's own number is incorrect (system data corrupted); following power down/power up the CPU number is generated again by the system program. 68 The management data (queue management) of the selected links are incorrect; set up the buffer in the coordinator COR 923C again using the INITIALIZE function. Warning The "warning" number group cannot occur with the RECEIVE TEST function. Receiving capacity The "receiving capacity" parameter indicates how many data fields can be received and buffered. CPU 928B Programming Guide 10 - 50 C79000-B8576-C898-01 Applications 10.9 Applications Based on examples, this section explains how to program multiprocessor communication. Note If you use the function blocks listed below and service interrupts on your CPU (e.g. with OB 2) remember to save the "scratchpad flags" at the start of interrupt servicing and to write them back when the interrupt is completed. This also applies to the setting "interrupts at block boundaries", since the call of the special function organization blocks represents a block boundary. 10.9.1 Calling the Special Function OB using Function Blocks The following five function blocks (FB 200 and FB 202 to FB 205) contain the call for the corresponding special function organization block for multiprocessor communication (OB 200 and OB 202 to OB 205). The numbers of the function blocks are not fixed and can be changed. The parameters of the special function OBs are transferred as actual parameters when the function blocks are called. The direct call of the special function organization blocks is faster, however, is more difficult to read owing to the absence of formal parameters FB no. FB name Function FB 200 INITIAL Set up buffer FB 202 SEND Send a data field FB 203 SEND-TST Test sending capacity FB 204 RECEIVE Receive a data field FB 205 RECV-TST Test receiving capacity 10 The flag area from FY 246 to maximum FY 255 is used by the function blocks as a parameter field for the special function organization blocks. The exact significance of the input and output parameters is explained in the description of the special function organization blocks. CPU 928B Programming Guide C79000-B8576-C898-01 10 - 51 Applications Note The following examples of applications involve finished applications that you can program by copying them. Programming function blocks FB 200: initializing the links FB 200 INITIAL Parameter n ame (1) AUMA INIC (5) (2) NUMC TCAP (6) (3) TNAS (4) STAS Significance Parameter type D ata type Parameter field AUMA A utomatic/ma nual I BY FY 246 NUMC Number of C PUs I BY FY 247 TNAS T ype (H byte) and n umber (L byte) I W FW 248 of the data block containing the assignment list STAS Start address of the assignment list I W FW 250 INIC Initialization conflict Q BY FY 252 TCAP T otal cap acity Q BY FY 253 Continued on the next page CPU 928B Programming Guide 10 - 52 C79000-B8576-C898-01 Applications FB 200 continued FB 200 SEGMENT 1 NAME:INITIAL DECL :AUMA DECL :NUMC DECL :TNAS DECL :STAS DECL :INIC DECL :TCAP 0017 0018 0019 001A 001B 001C 001D 001E 001F 0020 0021 0022 0023 0024 0025 0026 0027 :L :T :L :T :L :T :L :T : :L :JU : :L :T :L :T :BE LEN=45 0000 I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I I I I Q Q BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:W BI/BY/W/D:W BI/BY/W/D:BY BI/BY/W/D:BY =AUMA FY 246 =NUMC FY 247 =TNAS FY 248 =STAS FW 250 Automatic/manual KB 246 OB 200 SF OB: "Initialize" FY 252 =INIC FY 253 =TCAP Initialization conflict Number of CPUs DB type, DB no. Start address of the assignment list Total capacity 10 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 53 Applications FB 202: Sending a data field FB 202 SEND (1) RCPU ERWA (4) (2) TNDB TCAP (5) (3) FINO Parameter n ame Significance Parameter type D ata type Parameter field RCPU R eceiving CPU I BY FY 246 TNDB T ype (H byte) and n umber (L byte) of the source d ata block I W FW 247 FINO Field number I BY FY 249 ERWA Error/wa rning Q BY FY 250 TCAP T ransmitting cap acity Q BY FY 251 FB 202 LEN=40 SEGMENT 1 NAME:SEND DECL :RCPU DECL :TNDB DECL :FINO DECL :ERWA DECL :TCAP 0014 0015 0016 0017 0018 0019 001A 001B 001C 001D 001E 001F 0020 0021 :L :T :L :T :L :T : :L :JU : :L :T :L :T 0000 I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I I I Q Q BI/BY/W/D:BY BI/BY/W/D:W BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY =RCPU FY 246 =TNDB FW 247 =FINO FY 249 Receiving CPU KB 246 OB 202 SF OB: "Send a data field" FY 250 =ERWA FY 251 =TCAP Error/warning DB type, DB no. Field number Transmitting capacity CPU 928B Programming Guide 10 - 54 C79000-B8576-C898-01 Applications FB 203: Testing the transmitting capacity FB 203 SEND-TST (1) Parameter name RCPU Significance ERRO (2) TCAP (3) Parameter type Data type Parameter field RCPU R eceiving CPU I BY FY 246 ERRO Error Q BY FY 248 TCAP T ransmitting cap acity Q BY FY 249 FB 203 LEN=30 SEGMENT 1 0000 NAME:SEND-TST DECL :RCPU I/Q/D/B/T/C: I DECL :ERRO I/Q/D/B/T/C: Q DECL :TCAP I/Q/D/B/T/C: Q 000E 000F 0010 0011 0012 0013 0014 0015 0016 0017 0018 :L :T : :L :JU : :L :T :L :T :BE BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY =RCPU FY 246 Receiving CPU KB 246 OB 203 SF OB: "Test transmitting capacity" FY 248 =ERRO FY 249 =TCAP Error 10 Transmitting capacity CPU 928B Programming Guide C79000-B8576-C898-01 10 - 55 Applications FB 204: Receiving a data field FB 204 RECEIVE (1) TCPU Parameter name Significance ERWA (2) RCAP (3) TNDB (4) STAA (5) ENDA (6) Parameter type Data type Parameter field TCPU T ransmitting C PU I BY FY 246 ERWA Error/wa rning Q BY FY 248 RCAP R eceiving capacity Q BY FY 249 TNDB T ype (H byte) and n umber (L byte) of the destination d ata block Q W FW 250 STAA Address of the first received data word (start address) Q W FW 252 ENDA Address of the last received data word (end address) Q W FW 254 Continued on the next page CPU 928B Programming Guide 10 - 56 C79000-B8576-C898-01 Applications FB 204 continued: FB 204 LEN=45 SEGMENT 1 NAME:RECEIVE DECL :TCPU DECL :ERWA DECL :RCAP DECL :TNDB DECL :STAA DECL :ENDA 0017 0018 0019 001A 001B 001C 001D 001E 001F 0020 0021 0022 0023 0024 0025 0026 0027 0000 I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: I/Q/D/B/T/C: :L :T : :L :JU : :L :T :L :T :L :T :L :T :L :T :BE I Q Q Q Q Q BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:W BI/BY/W/D:W BI/BY/W/D:W =TCPU FY 246 Transmitting CPU KB 246 OB 204 SF OB: "Receive a data field" FY 248 =ERWA FY 249 =RCAP FW 250 =TNDB FW 252 =STAA FW 254 =ENDA Error/warning Receiving capacity DB type, DB no. Start address End address FB 205: Testing the receiving capacity FB 205 10 RECV-TST (1) Parameter name TCPU Significance ERRO (2) RCAP (3) Parameter type Data type Parameter field TCPU T ransmitting C PU I BY FY 246 ERRO Error Q BY FY 248 RCAP R eceiving capacity Q BY FY 249 CPU 928B Programming Guide C79000-B8576-C898-01 10 - 57 Applications FB 205 continued: FB 205 LEN=30 SEGMENT 1 0000 NAME:RECV-TST DECL :TCPU I/Q/D/B/T/C: I DECL :ERRO I/Q/D/B/T/C: Q DECL :RCAP I/Q/D/B/T/C: Q 000E 000F 0010 0011 0012 0013 0014 0015 0016 0017 0018 :L :T : :L :JU : :L :T :L :T :BE BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY =TCPU FY 246 Transmitting CPU KB 246 OB 205 SF OB: "Test receiving capacity" FY 248 =ERRO FY 249 =RCAP Error 10.9.2 Transferring Data Blocks Receiving capacity In this example, the function block TRAN DAT (FB 110) transfers a selectable number of data fields from a data block in one CPU to the data block of the same type and same number in a different CPU. The FB number (FB 110) has been selected at random and you can use other numbers. Programming FB 110 is described first followed by the application of FB 110. Programming FB 110 FB 110: Transferring a data block Task The data area to be transferred is stipulated by the input parameter FIRB (= number of the first data field to be transferred) and NUMB (= number of data fields to be transferred). A data field normally consists of 32 data words. Depending on the data block length, the last data field may be less than 32 data words. The transfer is triggered by a positive-going edge at the start input STAR. If the output parameter REST is zero after the transfer, this means that the function block TRANDAT was able to send all the data fields (according to the NUMB parameter). Continued on the next page CPU 928B Programming Guide 10 - 58 C79000-B8576-C898-01 Applications FB 110 continued: If, however, the REST output parameter has a value greater than zero, this means that the function block must be called again, for example in the next cycle. This means that you or the user program can only change the set parameters (i.e. the values of all parameters) when the REST parameter indicates zero showing that the data transfer is complete. You can call the function block TRANDAT several times with different parameters. In this case, various data areas are transferred simultaneously (interleaved in each other). The special function organization blocks for multiprocessor communication OB 202 to OB 205 can also be used "directly". This possibly is illustrated in the application example. If the SEND function (OB 202) is not correctly executed with the TRANDAT function block, the error number is entered in the output parameter ERRO, the RLO = '1' and the output parameter REST is set to '0'. The TRANDAT function block uses flag bytes FY 246 to FY 251 as scratchpad flags. All other variables whose value is significant as long as the output parameter REST = '0' continue to have memory assigned to them using the mechanism of formal/actual parameters. This is necessary to allow various data blocks to be transferred simultaneously. Implementation FB 110 TRAN-DAT (1) STAR ERRO (6) (2) RCPU REST (7) (3) TNDB CUBN (8) (4) NUMB EDGF (9) (5) FIRB 10 Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 10 - 59 Applications FB 110 continued: Parameter n ame Significance Parameter type Data type STAR Start the transfer of the data block on a positive-going edge I BI RCPU R eceiving CPU I BY TNDB T ype (H byte) and n umber (L byte) of the data block to be I W Number of data fields to be transferred. I BY FIRB Number of the first data field to be transferred. I BY ERRO Erro r Q BY REST Number of data fields still to be transferred. Q BY CUBN 1) C urrent field number Q BY EDGF 1) Ed ge f lag Q BI transferred. NUMB 1) Internal scratchpad flag, not intended for evaluation FB 110 LEN=89 SEGMENT 1 0000 NAME:TRAN-DAT DECL :STAR I/Q/D/B/T/C: DECL :RCPU I/Q/D/B/T/C: DECL :TNDB I/Q/D/B/T/C: DECL :NUMB I/Q/D/B/T/C: DECL :FIRB I/Q/D/B/T/C: DECL :ERRO I/Q/D/B/T/C: DECL :REST I/Q/D/B/T/C: DECL :CUBN I/Q/D/B/T/C: DECL :EDGF I/Q/D/B/T/C: 0020 0021 0022 0023 0024 :L :T :L :T : =RCPU FY 246 =TNDB FW 247 I I I I I Q Q Q Q BI/BY/W/D:BI BI/BY/W/D:BY BI/BY/W/D:W BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BY BI/BY/W/D:BI Assign parameter field for SF OB 202 Continued on the next page CPU 928B Programming Guide 10 - 60 C79000-B8576-C898-01 Applications FB 110 continued: 0025 0026 0027 0028 0029 002A 002B 002C 002D 002E 002F 0030 0031 0032 0033 0034 0035 0036 0038 0039 003A 003B 003C 003D 003E 003F 0040 0041 0042 0043 0044 0045 0046 0047 0048 0049 004A 004B 004C 004D 004E 004F 0050 0051 0052 0053 :L :L :><0, continue to attempt to send data fields =GOOD =CUBN FY 249 KB 246 OB 202 FY 250 =ERRO =GOOD =CUBN 1 =CUBN =REST 1 =REST =LOOP SF OB: "Send a data field" Abort if error Abort if trans-cap. = 0 Increment field number Decrement number of remaining data fields F 0.0 F 0.0 KB 0 =ERRO Regular end of program: =ERRO KB 0 =REST Program end if error: 10 RLO = 0, ERRO = 0 RLO = 1, ERRO contains error number CPU 928B Programming Guide C79000-B8576-C898-01 10 - 61 Applications Application of FB 110 Application of FB 110 Task You want CPU 1 to transfer data blocks DB 3 (data fields 2 to 5) and DB 4 (data fields 1 to 3) to CPU 2 during the cyclic user program. The RECEIVE function (OB 204) is also called in the cyclic user program. Implementation Function CPU 1 CPU 2 called in: called in: Initialization (OB 200) OB 20 - Send organization (FB 1) OB 1 - - OB 1 exists: exists: DB 3; DB 4 - - DB 3; DB 4 Receive organization (FB 2) Send DB Receive DB The user program in function block FB 1 of CPU 1 contains two calls for the function block TRANDAT in each case with different sets of parameters. The transfer of the first data block DB 3 begins after a positive edge after input I 2.0. A positive edge at input I 2.1 starts the transfer of the second data block. FB 1 SEGMENT 1 NAME:S-ORG 0000 :L 0001 :T 0002 :L 0003 :T 0004 :L 0005 :T 0006 :L 0007 :T 0008 : LEN=yy 0000 KB FY KY FW KB FY KB FY 2 0 1,3 1 4 3 2 4 To CPU 2 .. .. from data block DB 3 .. four data fields .. send from 2nd data field Continued on the next page CPU 928B Programming Guide 10 - 62 C79000-B8576-C898-01 Applications Application example continued: 0009 000A 000B 000C 000D 000E 000F 0010 0011 0012 0013 0014 0015 0016 0017 0018 0019 001A 001B 001C 001D 001E 001F 0020 0021 0023 0024 0025 0026 0027 0028 0029 002A 002B 002C 002D 002E 002F 0030 0031 0032 0033 0034 0035 0036 00xx :JU FB 110 NAME :TRAN-DAT STAR : I 2.0 RCPU : FY 0 TNDB : FW 1 NUMB : FY 3 FIRB : FY 4 ERRO : FY 5 REST : FY 6 CUBN : FY 7 EDGF : F 8.0 : : :JC =HALT : :L KB 2 :T FY 10 :L KY 1,4 :T FW 11 :L KB 3 :T FY 13 :L KB 1 :T FY 14 : :JU FB 110 NAME :TRAN-DAT STAR : I 2.1 RCPU : FY 10 TNDB : FW 11 NUMB : FY 13 FIRB : FY 14 ERRO : FY 5 REST : FY16 CUBN : FY17 EDGF : F 8.1 : : :JC =HALT :BEU : HALT : : : : : Abort after error To CPU 2 .. .. from data block DB 4 .. three data fields .. send from 2nd data field 10 Abort after error The error handling takes place here (e.g. stop, message output on the printer, ...) :BE Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 10 - 63 Applications Application example continued: In CPU 2, the RECEIVE function (OB 204) called by FB 2 enters each transmitted data field into the appropriate data block. It may take several cycles before a data block has been completely received. FB 2 LEN=yy SEGMENT 1 NAME:RECV-DAT 0000 :L 0001 :T 0002 : 0003 SCHL :L 0004 :JU 0005 :JM 0006 :L 0007 :L 0008 :>F :JC :TAK D KM/KH/KY/KS/KF/KT/KC/KG:KF Q BI/BY/W/D: BY =CPUN KB 1 CPUN = CPUN - 1 Error if: =ERWA KB 3 CPU no. <1 =ERWA CPU no. >4 Continued on the next page CPU 928B Programming Guide 10 - 70 C79000-B8576-C898-01 Applications FB 100 continued: 0013 : 0014 :SLW 0015 :T 0016 : 0017 :L 0018 :T 0019 : 001A LOOP :L 001B :L 001C :+F 001D :T 001E :ADD 001F :T 0020 : 0021 :DO 0022 :L 0023 :T 0024 :L 0025 :!=F 0026 :JC 0027 : 0028 :B 0029 :L 002A :T 002B :L 002C :JU 002D :L 002E :JC 002F : 0030 :L 0031 :L 0032 :>< no. of reserved fields? =EMPT KB 0 FY 249 FY 240 DW 0 FW 247 Field counter 10 Type and number of the source DB KB 246 OB 202 FY 250 =OBER SF OB: Send a data field Abort if error/warning FY 249 1 FY 249 FY 239 Field no. = field no. + 1 All data fields transferred ? =TRAN Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 10 - 71 Applications FB 100 continued: 0048 EMPT :L 0049 :I 004A :T 004B :L 004C :F 0012 :JC 0013 : 0014 :L 0015 :T 0016 : 0017 :L 0018 :T 0019 : 001A SRCH :L 001B :I 001C :T 001D :DO 001E :L 001F :LW 0020 :>4 KB 1 FY 242 Link counter KB 16 FW 244 FW 244 1 FW 244 FW 244 DL 0 =CPUN Pointer to sub-list 2 Search sub-list 2 until the next entry for the receiving CPU with the number'CPUN' is found. =SRCH FW DR FY KB 244 0 243 0 Number of reserved memory fields = 0 ? 10 =EMPT FW 244 KM 00000000 00001100 Determine the number of the transmitting CPU from the pointer to sub-list 2. 1 FY 246 KB 246 OB 205 FY 248 OBER SF OB: "Test receiving capacity" Abort if error Continued on the next page CPU 928B Programming Guide C79000-B8576-C898-01 10 - 73 Applications FB 101 continued: 0037 0038 0039 003A 003B 003C 003D 003E 003F 0040 0041 0042 0043 0044 0045 0046 0047 0048 0049 004A 004B 004C 004D 004E 004F 0050 0051 :L :L :> 128: 36 s + n * 2.38 s CPU 928B Programming Guide 12 - 4 C79000-A8576-C898-01 Appendix 1: Technical Data of the CPUs in the S5-135U Operation / processin g C PU 922 C PU 928 C PU 928 B Interrupt-driven program processing Extension of the cycle time by inserting an empty OB 2 (without STEP 5 operations) at an operation boundary 367 s 330 s 492 s Response time 300 s 280 s 297 s 340 s for the first time interrupt OB 440 s for the first time interrupt OB 180 s for each further interrupt OB due at the same time 200 s for each further interrupt OB due at the same time 100 ms 10, 20, 50, 100, 200, 500 ms, 1, 2, 5 sec 10, 20, 50, 100, 200, 500 ms, 1, 2, 5 sec - - every minute, every hour, every day, every month, every year, once - - 1 ms 150 ms 1 ... 4000 ms 150 ms 1 ... 6000 ms 150 ms 1 ... 13000 ms yes yes yes Time-driven program processing Extension of the cycle time by inserting an empty OB 13 (without STEP 5 operations) at an operation boundary 375 s Clock pulse for calling the time-driven program (Time interrupt OB 10 to OB 18) Resolution times for clock-driven time interrupt (OB 9) 12 Resolution time for delay interrupt (OB 6) Cycle time monitoring default selectable between triggerable CPU 928B Programming Guide C79000-A8576-C898-01 12 - 5 Appendix 1: Technical Data of the CPUs in the S5-135U Operation / processing C PU 922 CPU 92 8 CPU 928B 64 64 64 approx. 22.2 approx. 46.6 approx. 46.6 128 each 256 each 256 each 2048 flags 2048 flags 2048 flags + 8192 S flags Size of the memory Size of the user memory (in Kbytes) per submodule Size of the memory for data blocks (DB-RAM, in Kbytes) Timers and counters, flags Number of timers and counters Number of flags Definition of terms Basic time The basic time is the part of the cyclic system runtime required without updating the process image, without transferring IPC flags and without interrupts or errors. Response time The response time is the time from activating the program processing level PROCESS INTERRUPT for processing the first operation in OB 2. It is a prerequisite that OB 2 can be called immediately after recognizing the process interrupt. The response time is extended if the program waits until the next operation or block boundary CPU 928B Programming Guide 12 - 6 C79000-A8576-C898-01 Appendix 2: Error Identifiers Appendix 2: Error Identifiers Error IDs in System Data RS 3 and RS 4 RS 3 RS 4 Explanation Structure of the block address lists (Ev aluation of D B 0) 8001H yyyyH 8002H yyyyH 8003H yyyyH 8004H yyyyH 8005H yyyyH Wrong block length yyyy = addressof the block with the wrong length Calculated end address of the block in the memory is wrong yyyy = block address Illegal block ID yyyy = addressof the block with wrong ID Organization block number too high (permitted: OB 1 to OB 39) yyyy = address of the block with wrong number Data block number 0 (permitted: DB 1 to DB 255) yyyy = address of the block with the wrong number Structure of the address lists for updating the process image (Ev aluation of D B 1) 0410H yyyyH 0411H yyyyH 0412H yyyyH 0413H yyyyH 0414H yyyyH 0415H yyyyH 0419H yyyyH 041AH yyyyH 041BH yyyyH 041CH yyyyH Illegal iD: - header ID missing or incorrect (correct KS MASK01) - ID illegal (permitted KH DE00, DA00, CE00, CA00, BB00) - end ID missing or incorrect (correct KH EEEE) yyyy = illegal ID "Digital iputs" , number of addresses illegal (permitted 0 ... 128) yyyy = illegal number of addresses "Digital outputs" , number of addresses illegal (permitted 0 ... 128) yyyy = illegal number of addresses "IPC input flags" , number of addresses illegal (permitted 0 ... 256) yyyy = illegal number of addresses "IPC output flags", number of addresses illegal (permitted 0 ... 256) yyyy = illegal number of addresses Illegal number of timers (permitted: 256) yyyy = illegal number of timers Timeout in the digital inputs yyyy = address of the non-acknowledged input byte Timeout in the digital ioutputs yyyy = address of the non-acknowledged output byte Timeout in IPC input flags yyyy = address of the non-acknowledged IPC flag byte Timeout in IPC output flags yyyy = address of the non-acknowledged IPC flag byte 12 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 7 Appendix 2: Error Identifiers RS 3 RS 4 Explanation Ev aluation of D B 2 0421H 0422H 0423H 0424H 0425H 0426H DByyH Data yy = number of the non-loaded data block FByyH Function block not loaded yy = number of the non-loaded function block FByyH Function block not recognized yy = number of the non-recognized function block FByyH Function block loaded with wrong PG software yy = number of the function block DByyH Wrong closed loop controller data block length yy = number of the data block There is not enough space in the DB RAM to shift the closed loop controller DB from the user EPROM to the DB RAM Ev aluation of DX 0 0431H yyyyH 0432H yyyyH 0434H yyyyH 0435H yyyyH Illegal ID -header ID missing or incorrect (correct KS MASKX0) -field ID illegal -end ID missing or incorrect (correct KH EEEE) yyyy = illegal ID Illegal parameter yyyy = illegal parameter Illegal number of timers (permitted: 0...256) yyyy = wrong number of timers Illegal cycle monitoring time (permitted: 1ms to 13000ms) yyyy = incorrect time Ev aluation of DX 2 0451H 0452H yyyyH 0453H yyyyH 0454H xx00H 0455H xxyyH 0456H xxyyH 0457H yyyyH 0458H xx00H 0459H xxyyH 0045AH xx00H DX 2 length (without block header)< 4 words is not permitted DX 2 length (without block header) is too short for the link type yyyy = length of DX 2 Type of link illegal yyyy = link type Data iD for static parameter set illegal (not 44H, 58H) xx = data ID Block for static parameter set illegal xx = ID / yy = DB number Static parameter set does not exist xx = ID / yy = DB number Static parameter set too short yyyy = number of the non-existent DW Data ID for dynamic parameter set illegal (not 44H, 58H, 00H) xx = data ID Block for dynamic parameter set illegal xx = ID / yy = DB number Data ID for send mail box / job mail box illegal (not 44H, 58H,00H) xx = data ID CPU 928B Programming Guide 12 - 8 C79000-A8576-C898-01 Appendix 2: Error Identifiers RS 3 RS 4 Explanation Evaluation of DX 2 (continued) 045BH xxyyH 045CH xx00H 045DH xxyyH 045EH xx00H 045FH xxyyH 0460H xxyyH 0461H yyyyH Block for send mail box 7 job mail box illegal xx = ID / yy = DB number Data ID for receive mail box illegal (not 44H, 58H, 00H) xx = data ID Block for receive mail box illegal xx = ID / yy = DB number Data ID for coordination byte illegal (not 44H, 58H, 4DH) xx = ID Block for coordination byte illegal xx = ID / yy = DB number Block for coordination byte does not exist xx = ID / yy = DB number Data word for coordination byte does not exist yyyy = number of non-existent DW 12 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 9 Appendix 2: Error Identifiers Error IDs in ACCU 1 and ACCU 2 ACCU1-L ACCU2-L OB called Explanation REG-FE (closed loop controller error) 0801H 0802H 0803H 0804H 0805H 0806H 0880H DByyH Sampling time error yy = number of the affected controller data block DByyH Controller data block not loaded yy = number of the data block not loaded FByyH Controller function block not loaded yy = number of the function block not loaded FByyH Controller function block not regcognized yy = number of the function block not recognized FByyH Controller function block loaded with wrong PG software yy = function block number DByyH Wrong controller data block length yy = data block number 00yyH Timeout (QVZ) during controller processing yy = number of the I/O byte that caused the QVZ OB 34 W EC K-FE (collision of timed interrupts) 1001H 0016H 0014H 0012H 0010H 000EH 000CH 000AH 0008H 0006H Collision of timed interrupts - OB 10 Collision of timed interrupts - OB 11 Collision of timed interrupts - OB 12 Collision of timed interrupts - OB 13 Collision of timed interrupts - OB 14 Collision of timed interrupts - OB 15 Collision of timed interrupts - OB 16 Collision of timed interrupts - OB 17 Collision of timed interrupts - OB 18 ( 10 ms) ( 20 ms) ( 50 ms) (100 ms) (200 ms) (500 ms) ( 1 sec) ( 2 sec) ( 5 sec) OB 33 BCF (operation code error)/substitution error 1801H 1802H 1803H 1804H 1805H - - - - - 1806H - Substitution error with the DO RS operation Substitution error with the DO DW, DO FW operations Substitution error with the DO= , DI= operations Substitution error with the L= , = T operations Substitution error with the A=, AN=, O=, ON=, S= und RB= operations Substitution error with the RD=, LD=, FR=, SFD=, SR=, SP=, SSU= and SEC= operations OB 27 CPU 928B Programming Guide 12 - 10 C79000-A8576-C898-01 Appendix 2: Error Identifiers ACCU1-L ACCU2-L Explanation OB called BCF (operation code error) 1811H 1812H - - 1813H - 1814H - 1815H - Operation with illegal opcode Illegal opcode for an operation in which the high byte of the first operation word contains the value 68H Illegal opcode for an operation in which the high byte of the first operation word contains the value 78H Illegal opcode for an operation in which the high byte of the first operation word contains the value 70H Illegal opcode for an operation in which the high byte of the first operation word contains the value 60H OB 29 BCF (operation code error)/parameter error Illegal parameter with the following: 1821H 182BH 182CH 182DH 182EH 182FH 1830H 1831H 1832H 1833H 1834H 1835H - - - - - - - - - - - - 1836H 1837H 1838H 1839H 183AH 183BH 183CH - - - - - - - OB 30 C DB 0, 1, 2 JU(C) OB 0 JU(C) OB >39: special function does not exist CX DX 0, CX DX 1 and CX DX 2 L FW /T FW / L PW /T PW /L OW / T OW / L DD / T DD / DO FW : 255 L IW/T IW/L QW/T QW 127 L FD / T FD 253, 254, 255 L ID/T ID/L QD/T QD 125, 126, 127 RLD/RRD/SSD/SLD 33-255 SLW/SRW/LIR/TIR 16-255 SED/SEE 32-255 A=/AN=/O=/ON=/S=/RB=/==/RD=/FR=/SP=/SR=/ SEC=/SSU=/SFD=/L=/LD=/LW=/T= 0, 127-255 DO=/LDW= 0, 126-255 A S/O S/S S/= S/AN S/ON S/R S byte number > 1023 A S/O S/S S/= S/AN S/ON S/R S bit number > 7 L SY/T SY parameter > 1023 L SW/T SW parameter > 1022 L SD/T SD parameter >1020 G DB/GX DX Parameter 0, 1 or 2 (DB or DX 0, 1, 2 cannot be generated) 12 LZF (runtime errors)/block not loaded 1A01H 1A02H 1A03H - - - 1A04H 1A05H 1A06H 1A07H - - - - Block not loaded for C DB operation Block not loaded for CX DXoperation Block not loaded for JU(C) FB, OB 1 to OB 39, PB, SB operation Block not loaded for DOU/DOC FX operation Block not loaded for OB 254 or 255 operation Block not loaded for OB 182 operation Block not loaded for OB 150/OB 151 operation OB 19 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 11 Appendix 2: Error Identifiers ACCU1-L ACCU2-L OB called Explanation LZF (runtime rror)/load or transfer error 1A11H - 1A12H 1A13H 1A14H 1A15H 1A16H 1A17H 1A18H 1A19H - - - - - - - - Access to a non-defined data word with A/AN D, O/ON D, S/R D, =D Transfer error with TDR to a non-defined data word Transfer error with TDL to a non-defined data word Trans error with TDW to a non-defined data word Transfer error with TDD to a non-defined data word Load error with LDR to a non-defined data word Load error with LDL to a non-defined data word Load error with LDW to a non-defined data word Load error with LDD to a non-defined data word OB 32 LZF (runtime error)/other runtime errors Error indicated for .../by ... : 1A21H 1A22H - - 1A23H 1A25H 1A29H 1A2AH - - - - 1A2BH 1A2CH 1A31H - - - 1A32H - 1A33H - 1A34H 1A34H 1A34H 1A34H 1A34H 1A34H 1A34H 0001H 0100H 0101H 0102H 0200H 0201H 0202H 1A34H 0203H 1A34H 1A34H 1A34H 0210H 0211H 0212H 1A34H 0213H G DB, GX DX: data block already exists G DB, GX DX: illegal number of data words (< 1 or > 4091) G DB, GX DX: not enough space in the RAM DI: illegal parameter in ACCU 1 (< 1 or > 125) Bracket stack under of overflow after 'A(', 'O(, ')' C DB, CX DX: block length in data block header too short (length <5 words) Function block loaded with wrong PG software ACR: illegal page number in ACCU-1-L (> 255) OB 254 or OB 255 (shift) or OB 250: destination data block already exists in DB RAM OB 254 or OB 255 (duplicate): destination data block already exists in DB RAM OB 254 or OB 255 or OB250: not enough space in the DB RAM OB 182: data field written to illegally OB 182: address area type illegal OB 182: data block number illegal OB 182: "number of the first parameter word" illegal OB 182: "source data block type" illegal OB 182: "source data block number" illegal OB 182: "number of the first data word in the source to be transferred" illegal OB 182: a value < 5 words is entered in the block header as the length of the source data block OB 182: "destination data block type" illegal OB 182: "destination data block number" illegal OB 182: "number of the first destination data word to be transferred" illegal OB 182: a value < 5 words is entered in the block header as the length of the destination data block OB 31 CPU 928B Programming Guide 12 - 12 C79000-A8576-C898-01 Appendix 2: Error Identifiers ACCU1-L ACCU2-L Explanation OB called LZF (runtime error)/other runtime errors (continued) Error indicated for .../by ... : 1A34H 0220H 1A34H 1A34H 1A34H 1A35H 1A36H 0221H 0222H 0223H - - 1A3AH - 1A3BH - 1A41H - 1A42H 1A43H 1A44H 1A45H - - - - 1A46H 1A47H 1A48H 1A49H 1A4AH 1A4BH 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH - - - - - - 0001H 0100H 0101H 0102H 0103H 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH 1A4CH 1A4DH 1A4DH 1A4DH 0201H 0202H 0203H 0204H 0205H 0206H 0207H 0208H 0209H 020AH 0001H 0100H 0101H OB 182: "number of data words to be transferred" illegal (=0 or > 4091) OB 182: source data block too short OB 182: destination data block too short OB 182: destination data block in EPROM OB 250: number of the transfer block illegal OB 250: different length in DB x and DB x+1 or DX x and DX x+1 OB 221: illegal value for the new cycle time (cycle time <1 ms or > 13 000 ms) OB 223: different start-up types for the CPUs involved in multiprocessor operation OB 240, OB 241 or OB 242: illegal shift register or data block number (no. < 192 or > 255) OB 241: shift register not initialized OB 240: not enough space in the DB RAM OB 240: Data word DW 0 dof the data block does not contain the value '0' OB 240: illegal shift register length in DW 1 (not between 2 and 256) OB 240: illegal pointer position or number of pointers > 5 OB 120: illegal value in ACCU 1 or ACCU-2-L OB 122: illegal value in ACCU 1 OB 110: illegal value in ACCU 1 or ACCU-2-L OB 121: illegal value in ACCU 1 or ACCU-2-L OB 123: illegal value in ACCU 1 OB 150: function number illegal (= 0 or > 2) OB 150: address area type illegal OB 150: data block number illegal OB 150: "number of the first data field word" illegal OB 150: a value < 5 words is entered in the block header as the length of the data block OB 150: year specified in data field illegal OB 150: month specified in data field illegal OB 150: day of month specified in data field illegal OB 150: weekday specified in data field illegal OB 150: hour specified in data field illegal OB 150: minute specified in data field illegal OB 150: second specified in data field illegal OB 150: "1/100 second" specified in data field not equal to 0 OB 150: data field word 3 /bits 0 to 3 not equal to 0 OB 150: hour format does not match setting in OB 151 OB 151: function number illegal (= 0 or > 2) OB 151: address area type illegal OB 151: data block number illegal OB 31 12 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 13 Appendix 2: Error Identifiers ACCU1-L ACCU2-L OB called Explanation LZF (runtime error)/other runtime errors (continued) Error indicated for .../by ... : 1A4DH 1A4DH 0102H 0103H 1A4DH 1A4DH 1A4DH 1A4DH 1A4DH 1A4DH 1A4DH 1A4DH 1A4DH 1A4DH 0201H 0202H 0203H 0204H 0205H 0206H 0207H 0208H 0209H 020AH 1A4EH 0001H OB 152: function number illegal (not 0 to 3 or 8 to 15) 1A4FH 1A4FH 0001H 0002H OB 153: function number illegal (=0 or <0) OB 153: delay time illegal 1A50H - 1A51H - 1A52H - 1A53H - 1A54H - 1A55H - 1A56H - 1A57H - OB 151: "number of the first data field word" illegal OB 151: a value < 5 words is entered in the block header as the length of the data block OB 151: year specified in the data field illegal OB 151: month specified in the data field illegal OB 151: day of month specified in the data field illegal OB 151: weekday specified in the data field illegal OB 151: hour specified in the data field illegal OB 151: minute specified in the data field illegal OB 151: secondspecified in the data field illegal OB 151: "1/100 second" specified in data field is not equal to 0 OB 151: job type in data field illegal (> 7) OB 151: hour format does not match setting in OB 150 OB 31 LRW, TRW: the calculated memory address < BR + constant> is not in the range "0 .. EDFFH" (see Chap 9) LRD, TRD: the calculated memory address < BR + constant> is not in the range "0 .. EDFEH" (see Chap. 9) TSG, LY GB, LW GW, TY GB, TW GW: the calculated linear address < BR + constant> is not in the range "0 .. EFFFH" LY GW, LW GD, TY GW, TW GD: the calculated linear address < BR + constant> is not in the range "0 .. EFFEH" LY GD, TY GD: the calculated linear address < BR + constant> is not in the range "0 .. EFFCH" TSC, LY CB, LW CD, TY CW, TW CD: the calculated page address < BR + constant> is not in the range "F400H .. EBFFH" LY CW, LW CD, TY CW, TW CD: the calculated page address < BR + constant> is not in the range "F400H .. FFFEH" LY CD, TY CD: the calculated page address < BR + constant> is not in the range "F400H .. FBFCH" CPU 928B Programming Guide 12 - 14 C79000-A8576-C898-01 Appendix 2: Error Identifiers ACCU1-L ACCU2-L Explanation OB called LZF (runtime error)/other runtime errors (continued) Error indicated for .../by ... : 1A58H - 1A59H - TNW/TNB: the source block is not completely in one of the following areas: 0000 .. 7FFF user memory (see Chapter 9) 8000 .. DD7F data blockRAM DD80.. E3FF DB 0 E400 .. E7FF S flags E800 .. EDFF system data (RI, RJ, RS, RT, C, T) EE00 .. EFFF flags, process image F000 .. FFFF peripherals TNW/TNB: the destination block is not completely in one of the following areas: 0000 .. 7FFF user memory (see Chapter 9) 8000 .. DD7F data block RAM DD80.. E3FF DB 0 E400 .. E7FF S flags E800 .. EDFF system data (RI, RJ, RS, RT, C, T) EE00 .. EFFF flags, process image F000 .. FFFF peripherals OB 31 QV Z (timeout) 1E23H yyyyH 1E25H yyyyH 1E26H yyyyH 1E27H yyyyH 1E28H yyyyH Timeout (QVZ) in the user program when accessing the peripherals yyyy = QVZ address OB 23 Timeout outputting the process image of the digital outputs yyyy = address of the non-acknowledged output byte Timeout updating the process image of the digital inputs yyyy = address of the non-acknowledged input byte Timeout updating the IPC input flags yyyy = address of the non-acknowledged IPC flag byte Timeout updating the IPC output flags yyyy = address of the non-acknowledged IPC flag byte OB 24 12 ADF (adressin g error) 1E40H yyyyH Adressing error (ADF) in the user program yyyy = ADF address OB 25 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 15 Appendix 3: STEP 5 Operations not Contained in the CPU 928B Appendix 3: STEP 5 Operations not Contained in the CPU 928B Please note that the following STEP 5 operations belonging to the CPU 946/947 and CPU 948 cannot be processed in the CPU 928B. Operation Function Block command output Release command output BAS BAF I, Q, F, C, T, D, RI, RJ, RS, RT Test bit for signal status '1' TB N I, Q, F, C, T, D, RI, RJ, Test bit for signal stauts '0' TB RS, RT SU I, Q, F, C, T, D, RI, RJ, RS, RT Set bit unconditionally RU I, Q, F, C, T, D, RI, RJ, RS, RT Reset bit unconditionally LI M Load interrupt mask SIM Set interrupt mask UBE Interrupt block end STW Stop operation in time-driven interrupt processing Disable addressing errpr interrupt Enable addressing error interrupt enable requested interrupt processing Disable requested interrupt processing IA E RAE RAI IAI CPU 928B Programming Guide 12 - 16 C79000-A8576-C898-01 Appendix 4: Identifiers for the Program Processing Levels Appendix 4: Identifiers for the Program Processing Levels The identfiers correspond to the identifiers entered in the ISTACK under LEVEL (hexadecimal). Identifier Level 0002H 0004H 0006H 0008H 000AH 000CH 000EH Cold restart Cycle Time-driven interrupt 5 sec Time-driven interrupt 2 sec Time-driven interrupt 1 sec Time-driven interrupt 500 ms Time-driven interrupt 200 ms 0010H 0012H 0014H 0016H 0018H 001AH 001CH 001EH Time-driven interrupt 100 ms Time-driven interrupt 50 ms Time-driven interrupt 20 ms Time-driven interrupt 10 ms Timed job Not used Closed loop control Not used 0020H 0022H 0024H Delay interrupt Not used Process interrupt 0026H 0028H 002AH 002CH 002EH Not used Retentive manual cold restart Retentive automatic cold restart Abort Interface error 0030H 0032H 0034H 0036H 0038H 003AH 003CH 003EH Collision of timed interrupts Closed loop controller error Cycle error Not used Operation code error Runtime error Addressing error Timeout 0040H 0042H 0044H 0046H Not used Not used Manual warm restart Automatic warm restart 12 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 17 Appendix 5: Example "ISTACK Evaluation" Appendix 5: Example "ISTACK Evaluation" This (simplified) example illustrates how to evaluate the ISTACK. For more detailed information, you should also refer to Section 5.3 "Control Bits and the Interrupt Stack". Ready to start? The CPU has interrupted cyclic program processing and has changed to the stop mode. Error analysis To find the cause of the interruption, select the programmer online function "output ISTACK". The control bits then appear on the PG screen as shown below: C O N T R O L B I T S >>STP<< X STP-6 FE-STP BARBEND PG-STP STP-SCH STP-BEF X MP-STP >>ANL<< ANL-6 M W A AW A ANL-2 >>RUN<< RUN-6 NEUSTA X EINPROZ X BARB OB1GEL X FB0GEL NEUZU X OBPROZA MWA-ZUL X OBWECKA 8KWRAM EPROM KM-AUS KM-EIN STP-VER ANL-ABB UA-PG UA-SYS DIG-EIN X UA-PRFE DIG-AUS X UA-SCH 32KWRAM 16KWRAM X URGELOE URL-IA DX0-FE FE-22 MOF-FE RAM-FE DB0-FE DB1-FE DB2-FE KOR-FE N AU P E U B AU STUE-FE Z Y K Q V Z AD F WECK-FE B C F FE-6 FE-5 FE-4 FE-3 LZ F X REG-FE DOPP-FE The "X"s in the control bits indicate the current operating status of the CPU (>>STP<< ), and certain characteristics of the CPU are marked (OB 1 loaded, single processor mode, 16 KW user memory etc.). In the top line the cause of the stoppage is indicated as STP-BEF . It is assumed that you have not programmed an STP operation in your STEP 5 user program. This means that the stoppage was caused by a stop operation from the system program because an error OB was not loaded. The identifier LZF is marked in the bottom line. CPU 928B Programming Guide 12 - 18 C79000-A8576-C898-01 Appendix 5: Example "ISTACK Evaluation" It is possible that the system program has detected a runtime error and that the corresponding error organization block is not programmed. Since there are various runtime errors, and you cannot possibly know which of them has occurred, the information shown in the control bits is not yet sufficient for reliable diagnosis. You can now display the actual ISTACK: INTERRUPT STACK DEPTH: 01 OP REG: BST-STP: 0000 0001 LEVEL: 003A ACCU1: 0000 0A01 CONDITION CODE: CAUSE OF INTERR.: SAC: SAC-NO.: REL-SAC: UAMK: 0000 226 0006 0120 ACCU2: 0000 0000 CC1 CC0 STATUS RLO NAU ADF STUEB 0000 DB-ADD: DB-NO.: DBL-REG.: ICRW: ACCU3: 0000 BA-ADD: -NO.: 0000 0000 0000 0000 ACCU4: 0000 0000 OVFL OVFLS OR ERAB PEU BAU MPSTP ZYK QVZ STP X STUEU BCF S-6 LZF REG-FE WECK DOPP The ISTACK at depth 01 represents the program processing level that was last active before the transition to the stop mode. From the identifier 0 03 A (after LEVEL) you can see that this is the ISTACK of the program processing level RUNTI ME ERROR. The error identifier 0 0001A01 is entered in ACCU 1. This tells you that the runtime error was caused by calling a data block that was not loaded using the operation "C DB". Since the corresponding error, OB 19, does not exist in our user program, the system program aborted program execution (STP). The interrupt display mask word IC MK also contains the cause of interrupt. The identifier 0120 corresponds to the bit pattern "0000 0001 0010 0000 ". Bit 25 (LZF) and Bit 28 (STP) are set. You must now find out which block and which operation caused the runtime error. CPU 928B Programming Guide C79000-A8576-C898-01 12 - 19 12 Appendix 5: Example "ISTACK Evaluation" You can now move on in the ISTACK to depth 02 : INTERRUPT STACK DEPTH 02 OP REG: BST-STP: 2006 0001 LEVEL: 0004 ACCU1: 0001 1001 CONDITION CODE: CAUSE OF INTERR.: SAC: OB-NO.: REL-SAC: ICMK: 0037 ACCU2: 0000 0101 CC1 CC0 STATUS VKE NAU 0000 DB-ADD: DB-NO.: DBL-REG.: ICRW: 1 0004 0020 ACCU3: 0000 BA-ADD: -NO.: 0000 0000 0000 0000 ACCU4: 0000 0000 OVFL OVFLS OR ERAB PEU BAU MPSTP ZYK QVZ ADF STP BCF S-6 LZF X REG-FE STUEB STUEU WECK DOPP The identifier 0004 (after LEVEL) tells you that this is the ISTACK of the interrupted program processing level CYCLE . The STEP address counter (SAC) indicates the address 0037H . The operation that caused the error is stored at this absolute address in the user memory. Its code is specified as 2006 (OP-REG). From the listing of the machine codes in the operations list, you can see that this is the STEP 5 operation 'ADB 6' . The interrupt occurred in organization block OB 1. Within OB 1, the operation that caused the error is at the relative address 0 00 4 (REL-SAC). As you have already established, this operation led to a runtime error (see ICMK, bit 25, and CAUSE OF INTERR.). You can now display the incorrect operation on the screen using the SEARCH online function. Enter the appropriate block (OB 1) and the relative address of the operation. CPU 928B Programming Guide 12 - 20 C79000-A8576-C898-01 Appendix 5: Example "ISTACK Evaluation" ! F1 ! F2 ! F3 ! ! DISP SYMB! ! OUTPUT DEVICE: PC BLOCK: F4 ! ! ! OB1 F5 ! F6 ! F7 !LIB.NO. ! ! ! F8 ! ! SEARCH: 4H REL-SAC Following the search, you can see the operation "C D B 6" , that caused the interruption; there is no data block with the number 6 in the user memory. OB 1 SEGMENT 1 0000 0004 :C DB 6 0005 : 0006 : 0007 : 0008 :BE operation that caused the error 12 CPU 928B Programming Guide C79000-A8576-C898-01 12 - 21 Further Reading 13 13 CPU 928B Programming Guide C79000-A8576-C898-01 13 - 1 Further Reading Further Reading /1/ S5-135U/155U CPU 922/CPU 928/CPU 928B/CPU 948 Pocket Guide Order no. 6ES5 997-3UA22 /2/ S5-135U/155U System Manual Order no. 6ES5 998-0SH21 /3/ STEP 5 Manual Order no. C79000-G8576-C140 /4/ GRAPH 5: Graphic programming of sequential controls under the S5-DOS SIMATIC S5 operating system Order no. 6ES5 998-1SA01 /5/ Standard Function Blocks Data Handling Blocks CPU 922, CPU 928, CPU 928B S5-135U, S5-155U Programmable Controllers /6/ SINEC Manual CP 143 with COM 143 Order no. 6GK1970-1AB43-0AB0 /7/ 13 Hans Berger: Automating with the SIMATIC S5-135U SIEMENS AG Order no. A19100-L531-F505-X-7600 CPU 928B Programming Guide C79000-A8576-C898-01 13 - 3 Further Reading /8/ Programmable Controllers Basic Concepts SIEMENS AG Order no. E80850-C293-X-A2 /9/ Catalog ST 59: Programmers SIMATIC S5 /10/ Catalog ST 54.1: Programmable Controllers S5-135U, S5-155U and S5-155H /11/ Catalog ST 57: Standard Function Blocks and Driver Programs for Programmable Controllers of the U Series SIMATIC S5 /12/ SCL Manual Order no. C79000-G8576-C162 /13/ R64 Controller Structure /14/ S5-135U Communication CPU 928B Order No.: 6ES5 998-0CN21 CPU 928B Programming Guide 13 - 4 C79000-A8576-C898-01 Index and Lists 14 Contents of Chapter 14 List of Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 3 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 5 List of Tables and Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 11 List of Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 11 List of Figures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 - 17 14 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 1 List of Abbreviations List of Abbreviations Abbreviations (An explanation of the ISTACK abbreviations can be found in Section 5.4) ACCU-1 (2, 3, 4)-L ACCU-1 (2, 3, 4)-H ACCU-1 (2 ,3, 4)-LL ACCU-1 (2, 3, 4)-LH ADF ANZW low word in accumulator 1 (2, 3, 4), 16 bit high word in accumulator 1 (2, 3, 4), 16 bit low byte of low word in accumulator 1 (2, 3, 4), 8 bit high byte of low word in accumulator 1 (2, 3, 4), 8 bit addressing error condition code word BASP BCD BR BSTACK disable command output (signal on S5 bus) binary coded decimal base address register block stack CC 1, CC 0 COR CP CPU CSF condition code bits for digital operations coordinator module communications processor central processing unit control system flowchart DB DBA DBL DX data block data block start address (in register 6) data block length (in register 8) extended data block EPROM ERAB EU erasable programmable read only memory first scan (bit code) expansion unit FB FX function block extended function block IM INT IP ISTACK interface module (system)interrupt intelligent peripheral module interrupt stack 14 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 3 List of Abbreviations KB KDB call for a non-existent logic block opening a non-existent DB/DX data block LAD LED ladder diagram light-emitting diode NAU power failure OB OR OS OV organization block or (bit code) overflow latching (word code) overflow (word code) PAFE PARE PB PEU PG PI PII PIQ PLC parameter assignment error byte parity error program block power failure on expansion unit programmer process image process image of the inputs process image of the outputs programmable controller QVZ timeout RAM RLO random-access memory result of logic operation SAC SB SPU STA STL STS SUF STUEB STUEU step address counter sequence block operating system processor status (bit code) statement list stop statement substitution error BSTACK overflow ISTACK overflow TRAF transfer or load error ZYK cycle error CPU 928B Programming Guide 14 - 4 C79000-T8576-C898-01 Index Index A Accumulators (ACCUs) Actual operands of function blocks Addressing ADF (addressing error) Arithmetic operations Assignment list AUTOMATIC COLD RESTART See COLD RESTART AUTOMATIC WARM RESTART See WARM RESTART 3-15, 6-15 2-31 1-16 5-29, 5-53 3-56 2-7, 2-26 B Basic levels 4-8, 4-10 Basic operations 2-4, 3-19 BASP LED 4-6 BASP signal 4-27 BCF (operation code error) operation code error 5-29, 5-39, 5-41 parameter error 5-29, 5-39, 5-42 substitution error 5-29, 5-39 - 5-40 Binary numbers 2-8 Block address list 3-8, 8-12 block ID 2-38 body 2-14, 2-26, 2-38 calls 2-17, 3-8, 3-32 formal operands (block parameters) 2-29 header 2-14, 2-38 number 2-13, 2-38, 3-33 preheader 2-15, 2-37 Block operations 3-32 Blocks nesting blocks 3-8 BR register 9-26 BSTACK (block stack) evaluate 5-9 output 5-8 read 6-53 C CC 1 and CC 0 See results codes CPU 928B Programming Guide C79000-T8576-C898-01 Clock-driven time interrupts interruptions 4-34 special features 4-34 Closed loop controller structure R64 4-38 Closed-loop control 6-110 - 6-124 Communication OBs 10-20 condition code byte 10-23 parameters 10-21 runtimes 10-29 Communication processors (CPs) 10-7 Comparison operations 3-32 COMPRESS MEMORY 2-16 Control bits 5-5, 5-10 - 5-28 Controller processing closed loop controller interrupts 4-38 CONTROLLER INTERRUPT 4-8, 4-10, 4-28, 4-38 interrupt points 4-39 Conversion operations 3-62 Correcting blocks 2-16 Counter value 3-28 Counters C 1-15 CSF (control system flowchart) 2-4 Current data block 1-16 CYCLE 3-11, 4-28 cyclic processing 3-4, 3-11 interrupt points 4-30 user interface OB 1 4-29 Cycle boundary 6-40 Cycle statistics 6-42 Cycle time 6-40 Cycle statistics 6-40 Cyclic processing 1-6, 1-18, 4-28 D Data area 6-68 Data block DB 0 2-43, 3-8 Data block DB 1 2-43 Data block DB 2 2-43 Data block DB1 create 10-9 Data block DX 0 2-43 Data block DX 1 2-43 Data block RAM (DB RAM) 1-12, 3-10, 6-101 Data blocks general 1-15 Data blocks (DB/DX) accessing data blocks 6-58 - 6-61 general 2-14, 2-37 generating 3-33 programming 2-39 14 - 5 14 Index structure 2-37 validity 2-40 Data word 1-15, 2-37, 2-41 DBA (data block start address) 9-11 DBL (data block length) 9-14 Decimal numbers 2-8 Decrementing 3-65 Default system reaction 1-9 Defaults, modifying 1-9 Definition of the "9th track" 4-22 DELAY INTERRUPT interruptions 4-32 special features 4-32 Delay time 4-28 Delayed interrupt 6-48 Display generation operation 3-33 E EPROM submodule ERAB See results codes Error handling using organization blocks Error IDs Error information Error levels Error OBs Executive operations 3-10 5-29 - 5-31 5-7 5-5 - 5-9 4-8, 4-10 2-21 3-58 - 3-70 F F flags Fixed point numbers Floating point numbers Formal operands Function block FB 0 Function blocks (FB/FX) general programming standard function blocks structure 1-14, 10-21 2-9 2-8 2-27, 3-51 2-36 2-14, 2-25 2-27 2-25, 2-35 2-26 G Global memory access general GRAPH 5 14 - 6 9-29 9-4 2-5 H Handling blocks 6-100 I I/Os address distribution 8-7 modules 1-13 O area 1-13 P area 1-13 ICMK 8-21 ICRW 8-19 Incrementing 3-65 Interface second serial interface 5-36 to system program 1-9, 1-12, 2-19 Interprocessor communication flags data exchange via IPCs 10-5 general 3-13, 10-5 jumper settings 10-5 Interrupt condition codeword 8-18 Interrupt events 3-14 Interrupt-driven processing 1-7 IPC flags transferring blocks of IPC flags 6-94 ISTACK (interrupt stack) code bits 5-19 contents 5-18 error information 5-5 - 5-9 information in ISTACK 5-19 output 5-6, 5-10 J Jump operations 3-58 L LAD (ladder diagram) LED RUN LED STOP Library number Load operations Local memory access general Logic operations binary 2-4 4-5 4-5 2-38 3-21, 3-54 9-28 9-4 3-50 3-19 CPU 928B Programming Guide C79000-T8576-C898-01 Index digital LZF (runtime errors) 3-50 5-43, 5-45 M Mantissa See floating point number MANUAL WARM RESTART See WARM RESTART Memory access general 9-4 via the BR register 9-26 Memory organization 9-4 Mode of operation of a CPU 1-6 - 1-7-6 Multiprocessor communication application examples 10-51 assignment list 10-35 buffering data 10-15 data amount 10-13 initializing 10-31 modes 10-33 receive data 10-45 send data 10-38 sequence 10-13 Multiprocessor mode data exchange between CPUs and CPs 10-7 Multiprocessor operation communications mechanisms 10-4 I/O assignment 10-9 restart types 6-93 N Nesting program processing levels Nesting depth No operation Normalized fixed point numbers 4-9 3-9 3-33 6-120, 6-124 O O area See I/Os Operand areas Operand substitution Operating modes Operation code OR See results codes CPU 928B Programming Guide C79000-T8576-C898-01 1-13 3-67 4-4, 11-6 2-6 Organization block (OB) general Organization blocks (OB) as user interfaces Organization blocks (OBs) control of the start-up procedure error OBs general special functions OBs OS (overflow latching) See results codes OV (overflow) See results codes 2-17 2-19 2-21 2-21 2-13 2-23 P P area See I/Os Page area/page memory 9-9, 9-33 busy location 9-34 Pages accessing pages 9-33 Parallel operation of serial PG interfaces 11-20 - 11-28 cyclic functions 11-25 long-running functions 11-22, 11-25 short-running functions 11-22, 11-24 Parameter 2-6 Parameters for DX 0 1-9, 7-4, 7-8 - 7-12 PG functions 11-4 PG interface module 11-20 PG screen form for generating DB1 10-10 PID controller 6-110 Priority 1-7, 4-10 Process image outputs (PIQ) 1-6, 1-13 inputs (PII) 1-6, 1-13 general 1-13, 3-13 updating 4-27 Process interrupt 4-8, 4-10, 4-28 Process interrupt signals level-triggered 4-40 Process interrupts disabling 3-71, 4-42 edge-triggered 4-41 enabling 3-71, 4-42 interrupts 4-40 multiple interrupts 4-40 processing 4-39 Processing operations 3-65 Program program organization 3-5 - 3-9 14 - 7 14 Index system program user program Program blocks (PB) Program processing levels general level number Programming general programming language GRAPH 5 SCL STEP 5 Programming language SCL Programming tools 1-8, 6-95 - 6-97 1-10 2-13, 2-17 6-16, 6-22 6-98 1-17 1-20 1-20 1-20 1-20 1-20 Q QVZ (timeout error) 5-29, 5-53 R RAM submodule REG-FE (controller error) Response time RESTART errors during restart errors in restart restart types Results codes ERAB CC 1 and CC 0 OR OS OV RLO STA RLO See results codes RS/RT area RUN errors in RUN general 3-10 5-30, 5-58 4-44 5-32 5-38 - 5-62 6-93 3-16, 3-20 3-18, 3-60 3-17 3-17 3-17 2-7, 3-17, 3-20 3-17, 3-20 8-15 5-38 - 5-62 4-4, 4-27 - 4-44 S S flags Scratchpad flags Semaphores Sequence blocks Sequence blocks (SB) Serial link PG - PLC 14 - 8 1-14 10-51 3-71 - 3-78 2-17 - 2-24 2-13 11-19 Set/reset operations Shift operations Shift register Special functions errors during special function processing general interfaces Special functions OBs STA (status) See results codes Standard function blocks See also function blocks START-UP general STEP 5 operations STEP 5 programming language STL (statement list) STOP Stop operations Structure of the memory area Structured programming Suitability of the CPU 928B Supplementary operations System checkpoint System data System data words bit assignment System data words RS 3 and RS 4 System operations System program System program defaults System RAM System time 3-20, 3-51 3-60 6-101 6-9 6-6 6-8 6-6 3-11 3-11 3-15 2-4 - 2-16 2-4 4-4 3-33 8-4, 8-6 2-5 1-4 2-4 11-5 8-15 8-18 5-6, 5-33 2-4, 3-58 1-8 1-9 8-6 6-28 T TIME INTERRUPT 4-8, 4-10, 4-28 Time interrupts at fixed intervals 4-28 clock-controlled 4-27 interrupt points 4-36 interruptions 4-36 Time-controlled processing 1-7 Time-driven program execution clock-controlled (time interrupt) 4-27 clock-driven time interrupt 4-31 delay interrupt 4-31 in fixed time bases (time interrupts) 4-28, 4-35 time interrupts 4-31 Timed job, generate 6-33 Timer and counter operations 3-26, 3-52 CPU 928B Programming Guide C79000-T8576-C898-01 Index Timer value Timers T Transfer operations Transferring fields of memory 3-27 1-15 3-21, 3-54 9-18 - 9-25 U User checkpoints 11-5 User interface for clock-driven time interrupt 4-34 for closed loop controller interrupt 4-38 for cyclic program execution 4-29 for delay interrupt 4-31 for process interrupt 4-39 for restart 4-22 for time interrupts 4-35 User memory 1-12 organization 8-9 - 8-14 User program 1-8, 1-10 processing 3-4, 3-11 See program storing 1-12 tasks 1-10 W WECK-FE (collision of time interrupts) 4-34, 4-36, 5-29, 5-57 Z ZYK-FE (cycle time exceeded) 5-56 14 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 9 List of Tables and Figures List of Tables and Figures List of Tables Table 2-1 Overview of the organization blocks for program execution . . . . . . . . . . . . . . . . . . . . . 2 - 20 Table 2-2 Overview of the organization blocks for start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 21 Table 2-3 Overview of the organization blocks for error handling . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 21 Table 2-4 Overview of organization blocks for special functions . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 23 Table 2-5 Permitted formal operands for function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 29 Table 2-6 Permitted actual operands for function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 31 Table 2-7 Data formats permitted in a data block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 39 Table 3-1 Result condition codes of STEP 5 operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 18 Table 3-2 Binary logic operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 19 Table 3-3 Set/reset operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 20 Table 3-4 Load and transfer operations/part 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 21 Table 3-5 Load and transfer operations/part 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 22 Table 3-6 Timer and counter operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 26 Table 3-7 Arithmetic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 31 Table 3-8 Comparison operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 32 Table 3-9 Block operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 32 Table 3-10 NOP/display/stop operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 33 Table 3-11 Binary logic operations with formal operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 50 Table 3-12 Digital logic operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 50 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 11 14 List of Tables and Figures Table 3-13 Set/reset operations with formal operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 51 Table 3-14 Timer and counter operations with formal operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 52 Table 3-15 Load and transfer operations with formal operands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 54 Table 3-16 Load and transfer operations with special operands . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 55 Table 3-17 Arithmetic operation ENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 56 Table 3-18 Supplementary arithmetic operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 57 Table 3-19 Jump operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 58 Table 3-20 Shift operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 60 Table 3-21 Conversion operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 62 Table 3-22 Decrement/increment operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 65 Table 3-23 Processing operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 65 Table 3-24 Disabling/enabling process interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 71 Table 3-25 Disable/enable semaphore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 72 Table 4-1 Meaning of the LEDs "RUN" and "STOP" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 5 Table 4-2 Comparison of the different restart types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 21 Table 4-3 Assignment "Time interrupt time - called OB" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 35 Table 4-4 Collision of time interrupt identifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 37 Table 5-1 Meaning of the control bits in the >>STP<< line. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 12 Table 5-2 Meaning of the control bits in the >>ANL<< line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 13 Table 5-3 Meaning of the control bits in the >>RUN<< line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 14 Table 5-4 Meaning of the control bits in lines 4 and 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 14 Table 5-5 Meaning of the control bits in lines 6 to 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 16 Table 5-6 Meaning of the ISTACK IDs concerning the point of error . . . . . . . . . . . . . . . . . . . . . . 5 - 19 CPU 928B Programming Guide 14 - 12 C79000-T8576-C898-01 List of Tables and Figures Table 5-7 ISTACK IDs CAUSE OF INTERRUPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 22 Table 5-8 The organization blocks called in case of errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 29 Table 5-9 Causes of error and causes of interrupt in RESTART . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 32 Table 5-10 IDs for DB 0 errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 33 Table 5-11 IDs for DB 1 errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 34 Table 5-12 IDs for DB 2 errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 35 Table 5-13 IDs for DX 0 errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 36 Table 5-14 IDs for DX 2 errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 36 Table 5-15 Causes of error and causes of interrupt in RESTART and RUN, which lead direct to STOP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 38 Table 5-16 Causes of error and causes of interrupt in RESTART and RUN, which lead direct to STOP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 39 Table 5-17 BCF substitution error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 40 Table 5-18 BCF operation code error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 41 Table 5-19 BCF parameter error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 42 Table 5-20 LZF - calling a block that is not loaded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 44 Table 5-21 LZF-load/transfer error (TRAF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 45 Table 5-22 LZF-other runtime errors/part 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 46 Table 5-23 LZF-other runtime errors/part 2 (OB 182 identifier) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 47 Table 5-24 LZF-other runtime errors/part 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 48 Table 5-25 LZF-other runtime errors/part 4 (OB 150 identifiers) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 49 Table 5-26 LZF-other runtime errors/part 5 (identifiers of OB 151, OB 152 and OB 153) . . . . . . . 5 - 50 Table 5-27 LZF-other runtime errors/part 6 (identifiers of different system operations) . . . . . . . . . 5 - 51 Table 5-28 QVZ flags when calling OB 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 54 Table 5-29 WECK-FE identifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 57 Table 5-30 REG-FE identifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 59 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 13 14 List of Tables and Figures Table 6-1 Overview of the special functions available with the CPU 928B . . . . . . . . . . . . . . . . . . . 6 - 6 Table 6-2 OB 150 error IDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 31 Table 6-3 OB 151 error IDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 36 Table 6-4 "Time job - Time parameter" assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 37 Table 6-5 Cycle statistics variables - OB 152. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 41 Table 6-6 OB 153 functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 42 Table 6-7 Results of the OB 152 functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 43 Table 6-8 OB 153 error IDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 49 Table 6-9 OB 182 error IDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 67 Table 6-10 Transferring the data block for PID control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 114 Table 6-11 Control word in the transfer DB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 117 Table 6-12 Normalized fixed point number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 124 Table 7-1 DX 0 parameters and their meaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 8 Table 8-1 Structure of the memory area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 4 Table 8-2 Assignment of RS 0 (Interrupt condition codeword) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 18 Table 8-3 Assignment of RS 1 (Interrupt condition code reset word) . . . . . . . . . . . . . . . . . . . . . . . 8 - 19 Table 8-4 Assignment of RS 2 (Interrupt condition code group word) . . . . . . . . . . . . . . . . . . . . . . 8 - 21 Table 8-5 Assignment of RS 5 (STOP and RESTART IDs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 23 Table 8-6 Assignment of RS 6 (Cycle and submodule/MPL IDs) . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 24 Table 8-7 Assignment of RS 7 (RESET IDs/Initialize error IDs) . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 25 Table 8-8 Assignment of RS 8 (Error IDs HW/SW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 26 Table 8-9 Assignment of RS 29 (Slot ID/CPU/PLC type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 27 Table 8-10 Assignment of RS 131 (Disable all interrupts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 29 CPU 928B Programming Guide 14 - 14 C79000-T8576-C898-01 List of Tables and Figures Table 8-11 Assignment of RS 132 (Delay all interrupts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 29 Table 8-12 Assignment of RS 133 (Process image updating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 30 Table 8-13 Assignment of RS 135 (Disable individual time interrupts) . . . . . . . . . . . . . . . . . . . . . . 8 - 31 Table 8-14 Assignment of RS 137 (Delay individual time interrupts). . . . . . . . . . . . . . . . . . . . . . . . 8 - 32 Table 8-15 Assignment of RS 140 (Write/read IDs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 33 Table 9-1 Operations for indirect memory access using registers . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 8 Table 9-2 16-bit register for LIR/TIR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 9 Table 9-3 Operations for field transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 18 Table 9-4 Memory areas permitted for TNW, TXB and TXW . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 18 Table 9-5 Load and arithmetic operations with the BR register. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 26 Table 9-6 Operations for transfer between registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 27 Table 9-7 Operations for accessing the local memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 28 Table 9-8 Operations for access to the global memory organized in bytes . . . . . . . . . . . . . . . . . . . 9 - 31 Table 9-9 Operations for access to the global memory organized in words . . . . . . . . . . . . . . . . . . 9 - 32 Table 9-10 Operations for access to the pages organized in bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 35 Table 9-11 Operations for access to the pages organized in words . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 37 Table 10-1 Condition codes of the communication OBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 23 Table 10-2 Code byte for the communication OBs/number groups. . . . . . . . . . . . . . . . . . . . . . . . 10 - 24 Table 10-3 Condition code byte: Initialization conflict numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 25 Table 10-4 Condition code byte: Error numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 26 Table 10-5 Condition code bytes: Warning numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 28 Table 10-6 Runtimes of the communication OBs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 29 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 15 14 List of Tables and Figures Table 10-7 Assignment list for OB 200 (initialize) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 35 Table 10-8 Link list for extending the IPC flag area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 66 Table 11-1 Functions for installation and testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 4 Table 11-2 Activities at checkpoints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 18 Table 11-3 Functions which cannot run simultaneously on both PGs . . . . . . . . . . . . . . . . . . . . . . 11 - 23 CPU 928B Programming Guide 14 - 16 C79000-T8576-C898-01 List of Tables and Figures List of Figures Fig. 1-1 Tasks of the system program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 8 Fig. 1-2 Structure of a STEP 5 user program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 11 Fig. 2-1 Methods of representation in the STEP 5 programming language . . . . . . . . . . . . . . . . . . 2 - 5 Fig. 2-2 Example of block storage in the user memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 16 Fig. 2-3 Block calls that enable processing of a program block . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 18 Fig. 2-4 Structure of a function block (FB/FX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 26 Fig. 2-5 Range of validity of an opened data block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 42 Fig. 3-1 Principle of cyclic program execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4 Fig. 3-2 Example of the organization of the user program according to the program structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 6 Fig. 3-3 Example of the organization of the user program according to the structure of the controlled system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 7 Fig. 3-4 Nested logic block calls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 8 Fig. 3-5 Example of block nesting depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 9 Fig. 3-6 Load and transfer operations in a byte-oriented memory area. . . . . . . . . . . . . . . . . . . . . 3 - 23 Fig. 3-7 Load and transfer operations in a word-oriented memory area . . . . . . . . . . . . . . . . . . . . 3 - 24 Fig. 3-8 Coordination of access to the global memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 73 Fig. 4-1 Front panel of the CPU 928B with display and operating elements . . . . . . . . . . . . . . . . . 4 - 4 Fig. 4-2 Operating states and program processing levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 7 Fig. 4-3: Principle of level change and ISTACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 9 Fig. 4-4 Change of level as a result of a double call error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 11 Fig. 4-5 Double call of error level BCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 12 Fig. 4-6 Cyclic program execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 29 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 17 14 List of Tables and Figures Fig. 4-7 Process interrupt, level triggered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 41 Fig. 4-8 Process interrupt, edge-triggered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 41 Fig. 4-9 Interrupt-driven program execution at block boundaries. . . . . . . . . . . . . . . . . . . . . . . . . 4 - 43 Fig. 5-1 Example of the first screen form page "OUTPUT ISTACK": control bits . . . . . . . . . . . 5 - 11 Fig. 5-2 Example of a screen page "OUTPUT ISTACK" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 18 Fig. 5-3 Example 1 of evaluating the ISTACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 25 Fig 5-4 Example 2 of evaluating the ISTACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 26 Fig. 5-5 Example 2 of evaluating the ISTACK: 1st ISTACK level . . . . . . . . . . . . . . . . . . . . . . . 5 - 27 Fig. 5-6 Example 2 of evaluating the ISTACK: 2nd ISTACK level. . . . . . . . . . . . . . . . . . . . . . . 5 - 28 Fig. 6-1 Effects of the "roll up" function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 15 Fig. 6-2 Effects of the "roll down" function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 15 Fig. 6-3 Storing BSTACK entries in a data block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 55 Fig. 6-4 Contents of the BSTACK in this example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 56 Fig. 6-5 Contents of DX 10 in this example after OB 170 is called . . . . . . . . . . . . . . . . . . . . . . . 6 - 57 Fig. 6-6 Shifting the DB start address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 61 Fig. 6-7 Transferring in bytes (OB 190) and words (OB 192) . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 69 Fig. 6-8 Transferring in bytes (OB 191) and words (OB 193) . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 72 Fig. 6-9 Saving the areas when the program processing level changes. . . . . . . . . . . . . . . . . . . . . 6 - 75 Fig. 6-10 Swapping the high byte and low byte in a DB using OB 193/OB 190 . . . . . . . . . . . . . . 6 - 76 Fig. 6-11 Location of the page address area on the S5 bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 80 Fig. 6-12 Location of the bytes when writing (OB 216) / reading (OB 217) to/from a page in words or double words . . . . . . . . . . . . . . . . . . . . . 6 - 81 Fig. 6-13 ACCU contents before calling OB 216 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 83 Fig. 6-14 ACCU contents before calling OB 217 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 85 CPU 928B Programming Guide 14 - 18 C79000-T8576-C898-01 List of Tables and Figures Fig. 6-15 ACCU contents before calling OB 218 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 87 Fig. 6-16 Schematic showing the principle of a shift register with 3 pointers and 12 memory cells . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 102 Fig. 6-17 Schematic showing the principle of a shift register with 3 pointers and 12 memory cells before the first clock pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 103 Fig. 6-18 Schematic showing the principle of a shift register with 3 pointers and 12 memory cells after the first clock pulse. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 103 Fig. 6-19 Structure of the data block for initializing a shift register . . . . . . . . . . . . . . . . . . . . . . 6 - 105 Fig. 6-20 Block diagram of the PID controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 - 110 Fig. 7-1 Structure of DX 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 - 6 Fig. 7-2 PG screen form for assigning parameters to DX 0 /part 1 . . . . . . . . . . . . . . . . . . . . . . . . 7 - 15 Fig. 7-3 PG screen form for assigning parameters to DX 0 /part 2 . . . . . . . . . . . . . . . . . . . . . . . . 7 - 16 Fig. 8-1 Address distribution in the CPU 928B - overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 5 Fig. 8-2 Address distribution - system RAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 6 Fig. 8-3 Address distribution - peripherals (8 bits) on the S5 bus . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 7 Fig. 8-4 Block addresses in DB 0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 12 Fig. 8-5 Example a): start address of DB 50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 13 Fig. 8-6 RS area memory map (part 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 16 Fig. 8-7 RS area memory map (part 2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 - 17 Fig. 9-1 Global and local memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 5 Fig. 9-2 Access to local or global memory areas using absolute addresses (see also Fig. 9-1) . . . 9 - 7 Fig. 9-3 LIR/TIR with 16-bit memory areas (word-oriented) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 10 Fig. 9-4 LIR/TIR with a-bit memory areas (byte-oriented). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 10 Fig. 9-5 Using the DBA register. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 12 Fig. 9-6 Using the DBL register. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 15 CPU 928B Programming Guide C79000-T8576-C898-01 14 - 19 14 List of Tables and Figures Fig. 9-7 Occupation of the accumulators during the program . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 17 Fig. 9-8 Transferring blocks of memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 20 Fig. 9-9 Function block for transferring blocks of data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 21 Fig. 9-10 Loading the BR register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 26 Fig. 9-11 Register - register transfer operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 28 Fig. 10-1 Transferring IPC flags in the multiprocessor mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 6 Fig. 10-2 Example of IPC flag areas on the CPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 7 Fig. 10-3 PG screen form for generating DB 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 10 Fig. 10-4 Sender/receiver identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 14 Fig. 10-5 Example of the occupation of the COR buffer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 17 Fig. 10-6 Overview of the blocks required in each CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 69 Fig. 10-7 Data exchange between 3 CPUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 75 Fig. 11-1 Sequence of "program test" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 14 Fig. 11-2 Using the second interface as a PG interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 20 Fig. 11-3 First example of a configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 21 Fig. 11-4 Second example of a configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 21 Fig. 11-5 Handling simultaneous jobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 24 Fig. 11-6 Typical sequence of a cyclic function and parallel short-running function. . . . . . . . . 11 - 25 Fig. 11-7 Sequence of two parallel cyclic functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 27 Fig. 11-8 Sequence when a function blocks the CPU 928B . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 - 28 CPU 928B Programming Guide 14 - 20 C79000-T8576-C898-01 Siemens AG AUT E 1163 Ostliche Rheinbruckenstrae 50 D-76181 Karlsruhe Federal Republic of Germany - From: Your Name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Your Title: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Company Name: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Street: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . City, Zip Code: . . . . . . . . . . . . . . . . . . . . . . . . . . . Country: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Phone: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Please check any industry that applies to you: Automotive Pharmaceutical Chemical Plastic Electrical Machinery Pulp and Paper Food Textiles Instrument and Control Transportation Nonelectrical Machinery Petrochemical Other 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remarks Form Your comments and recommendations will help us to improve the quality and usefulness of our publications. Please take the first available opportunity to fill out this questionnaire and return it to Siemens. Please do not forget to state the title, order number and release of your manual. Title of Your Manual: ................................................................................................................ Order No. of Your Manual: .......................................................................... Release: .......... Please give each of the following questions your own personal mark within the range from 1 (very good) to 5 (poor). 1. Do the contents meet your requirements? 2. Is the information you need easy to find? 3. Is the text easy to understand? 4. Does the level of technical detail meet your requirements? 5. Please rate the quality of the graphics/tables: Additional comments: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C79000-V8576-C067-01 1