INPUT SPECIFICATIONS (1)
Description No Suffix -120 -240
Control Voltage Range 4-32 VDC 90-140 V 180-260 V
Must Turn On Voltage 4.0 VDC 90 VAC 180 VAC
Must Turn Off Voltage 1.0 VDC 10 VAC 10 VAC
Typical Input Current (5)(6) 9 mAdc 15 11
Maximum Turn-On Time [msec] (4) 1/2 Cycle 10.0 10.0
Maximum Turn-Off Time [msec] 1/2 Cycle 40.0 40.0
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) 2500 Vrms
Minimum Insulation Resistance (@ 500 VDC) 109 Ohm
Maximum Capacitance, Input/Output 8.0 pF
Ambient Operating Temperature Range -30 to 80°C
Ambient Storage Temperature Range -30 to 125°C
Weight (typical) 0.5 oz. (14.4g)
Encapsulation Thermally Conductive Epoxy
GENERAL NOTES
1) All parameters at 25°C and per section unless otherwise specified.
2) Dielectric and insulation resistance are measured between input and output
3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
4) Turn-on time for random Switching models is 0.1 ms.
5) DC Input circuitry incorporates active current limiter.
6) Use suffix-120 for 120 VAC control and -240 for 240VAC control