https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page1/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB(selective
fuse breaking) technology, and NFC interface, input: 1-phase,output:12VDC/15 A
Product Description
The fourth generation of the high-performance QUINTPOWER power supplies ensures superior system availability by means of new functions.
Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINTPOWER power supply increase theavailability of your application.
Your advantages
Preventive function monitoring indicates critical operating states before errors occur
Signaling thresholds and characteristic curves that can be adjusted via NFC maximize system availability
Power reserve for easy system extension thanks to static boost with sustained power of up to 125% and ability to start difficult loads thanks to
dynamic boost with up to 200% for 5 seconds
High degree of immunity, thanks to integrated gas-filled surge arrester and mains failure bridging time of more than 20 milliseconds
Robust design thanks to metal housing and wide temperature range from -40°C to +70°C
Worldwide use thanks to the wide range input and international approval package
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4055626355054
Weight per Piece (excluding packing) 1,100.000 g
Custom tariff number 85044030
Country of origin Thailand
Technical data
Dimensions
Width 50 mm
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page2/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Technical data
Dimensions
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 53 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 5000 m (> 2000 m, observe derating)
Input data
Nominal input voltage range 100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range 100 V AC ... 240 V AC -15% ... +10%
110 V DC ... 250 V DC -18% ... +40%
Dielectric strength maximum 300 V AC 60 s
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Discharge current to PE < 3.5 mA
Current consumption 2.4 A (100VAC)
120 V AC
230 V AC
1.1 A (240 V AC)
Nominal power consumption 221 VA
Inrush surge current typ. 15 A (at 25°C)
Mains buffering typ. 55 ms (120 V AC)
typ. 56 ms (230 VAC)
Input fuse 8 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester
Output data
Nominal output voltage 12 V DC
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page3/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Technical data
Output data
Setting range of the output voltage (USet)12 V DC ... 15 V DC (constant capacity)
Nominal output current (IN)15 A
Static Boost (IStat.Boost)17.5 A
Dynamic Boost (IDyn.Boost)20 A (5 s)
Selective Fuse Breaking (ISFB)60 A (15 ms)
Derating > 60 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance ≤ 25 V DC
Control deviation < 0.5 % (Static load change 10% ... 90%)
< 4 % (Dynamic load change 10% ... 90%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Output power 180 W
Typical response time 300 ms (from SLEEP MODE)
Maximum power dissipation in no-load condition < 4 W (120 V AC)
< 4 W (230 V AC)
Power loss nominal load max. < 18 W (120 V AC)
< 16 W (230 V AC)
General
Net weight 1.3 kg
Efficiency typ. 91.2 % (120 V AC)
typ. 92 % (230 V AC)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE 0.5 kV DC (type test)
0.5 kV DC (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1196000 h (25°C)
> 749000 h (40 °C)
> 355000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: PN ≥50%, 5mm horizontally, 15mm next to active components,
50mm vertically
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page4/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Technical data
General
alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm
vertically bottom
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 6.5 mm
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 6.5 mm
Connection data for signaling
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Standard - Safety of transformers EN 61558-2-16 (air clearances and creepage distances only)
Standard - Electrical safety IEC60950-1/VDE0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC60950-1 (SELV)
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page5/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Technical data
Standards and Regulations
EN 60204-1 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN61000-3-2
Shipbuilding approval DNV GL, PRS, BV, LR, ABS
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) 5Hz ... 100Hz resonance search 2.3g, 90min., resonance frequency
2.3g, 90min. (according to DNV GL Class C)
Approval - requirement of the semiconductor industry with regard to mains
voltage dips SEMI F47-0706; EN 61000-4-11
Rail applications EN50121-3-2
Overvoltage category (EN 60950-1) II (≤ 5000m)
Overvoltage category (EN 61010-1) II(≤5000m)
Overvoltage category (EN 62477-1) III(≤2000m)
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
NFC
POut
OVP
"C
+
+
-
-
13
14
Rem
SGnd
Out 1
Out 2
!
active
PFC
-
L
N
(+)
(-)
Diagram
H [m]
[%]
0
25
50
75
100
125
150
175
POut
!
"
#
= P 125 % 40 °C
Stat. $
= PDyn. 150 % 60 °C$
= PN100 % 60 °C$
0 1000 2000 3000 4000 5000
!
"
#
Classifications
eCl@ss
eCl@ss 6.0 27049000
eCl@ss 7.0 27049002
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page6/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Classifications
eCl@ss
eCl@ss 8.0 27049002
eCl@ss 9.0 27040701
ETIM
ETIM 5.0 EC002540
ETIM 6.0 EC002540
Approvals
Approvals
Approvals
UL Listed / UL Recognized / cUL Recognized / cUL Listed / cULus Recognized / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
UL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Recognized http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 211944
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 123528
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page7/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Approvals
cULus Recognized
cULus Listed
Accessories
Accessories
Assembly adapter
Assembly adapters-UWA 182/52-2938235
Universal wall adapter for securely mounting the power supply in the event of strong vibrations. The power supply is
screwed directly onto the mounting surface. The universal wall adapter is attached at the top/bottom.
Assembly adapters-UWA 130-2901664
2-piece universal wall adapter for securely mounting the power supply in the event of strong vibrations. The profiles that
are screwed onto the side of the power supply are screwed directly onto the mounting surface. The universal wall adapter
is attached on the left/right.
Assembly adapters-QUINT-PS-ADAPTERS7/1-2938196
Assembly adapter for QUINT-PS... power supply on S7-300 rail
Device protection
https://www.phoenixcontact.com/us/products/2904608
01/23/2019Page8/8
Power supply unit-QUINT4-PS/1AC/12DC/15-2904608
Accessories
Type 3 surge protection device-PLT-SEC-T3-230-FM-UT-2907919
Type 2/3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage 230VAC/DC.
Type 3 surge protection device-PLT-SEC-T3-24-FM-UT-2907916
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage 24VAC/DC.
Programming adapter
Programming adapter-TWN4 MIFARE NFC USB ADAPTER-2909681
Near Field Communication (NFC) programming adapter with USB interface for the wireless configuration of NFC-capable
products from PHOENIX CONTACT with software. No separate USB driver is required.
Phoenix Contact 2019 © - all rights reserved