Current Transducer LF 1005-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
IPN Primary nominal r.m.s. current 1000 A
IPPrimary current, measuring range 0 .. ± 1500 A
R M Measuring resistance @ TA = 70°C TA = 85°C
RM min RM max RM min RM max
with ± 15 V @ ± 1000 A max 0 18 0 15
@ ± 1200 A max 0 7 0 4
with ± 24 V @ ± 1000 A max 5 60.5 10 57.5
@ ± 1500 A max 5 24 10 21
ISN Secondary nominal r.m.s. current 200 mA
K N Conversion ratio 1 : 5000
VCSupply voltage (± 5 %) ± 15 .. 24 V
ICCurrent consumption 20 (@ ± 24 V) + ISmA
VdR.m.s. voltage for AC isolation test, 50 Hz, 1 mn 3kV
Accuracy - Dynamic performance data
X G Overall accuracy @ IPN , TA = 25°C ± 0.4 %
εLLinearity < 0.1 %
Typ Max
IOOffset current @ IP = 0, TA = 25°C ± 0.4 mA
IOT Thermal drift of IO- 10°C .. + 85°C ± 0.3 ± 0.5 mA
trResponse time 1) @ 90 % of IPN < 1 µs
di/dt di/dt accurately followed > 100 A/µs
fFrequency bandwidth (- 1 dB) DC .. 150 kHz
General data
TAAmbient operating temperature - 10 .. + 85 °C
TSAmbient storage temperature - 25 .. + 100 °C
R S Secondary coil resistance @ TA = 70°C 48
TA = 85°C 51
mMass 500 g
Standards 2) EN 50178
Notes : 1) With a di/dt of 100 A/µs
2) A list of corresponding tests is available.
Features
Closed loop (compensated) current
transducer using the Hall effect
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
IPN =1000 A
020813/5
LEM Components www.lem.com
Remarks
IS is positive when IP flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100°C.
Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Mechanical characteristics
General tolerance ± 0.5 mm
Transducer fastening
Vertical position 2 holes 5.3 mm
2 M5 steel screws
Fastening torque, maxi 4 Nm or 2.52 Lb. - Ft.
or 4 holes 4.2 mm
4 M4 steel screws
Fastening torque, maxi 3.2 Nm or 2.02 Lb. - Ft.
or 4 holes 2.25 mm depth10 mm
4 x PT KA30 screws long 10 mm
Fastening torque, maxi 0.9 Nm or 0.57 Lb. - Ft.
Transducer fastening
Horizontal position 4 holes 5.3 mm
4 M5 steel screws
Fastening torque, maxi 4 Nm or 2.52 Lb. - Ft.
or 4 holes 2.25 mm depth16 mm
4 x PT KA30 screws long 16 mm
Fastening torque, maxi 1 Nm or 0.63 Lb. - Ft.
Primary through-hole 40.5 x 40.5 mm
Connection of secondary Molex 5045-03/AG
Dimensions LF 1005-S (in mm. 1 mm = 0.0394 inch)
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Secondary terminals
Pin +:supply voltage +15 .. 24 V
Pin M:measure
Pin -:supply voltage -15 .. 24 V
Connection
Bottom view
Front view Back view
Top view