ACDC 130 Watts JPS Series xppower.com * High Efficiency up to 90% * Medical Approval (JPS130M Versions) * 3" x 5" Footprint * 100 W Convectioncooled * 130 W Forcedcooled * Single & Multi Outputs * 3 Year Warranty Specification Input * 90-264 VAC (130-370 VDC) * 47-63 Hz * 2.0/1.0 A max at 115/230 VAC (JPS130) 2.6/1.3 A max at 115/230 VAC (JPS130-M) Inrush Current * 30 A at 115 VAC, 60 A at 230 VAC, cold start at 25 C Power Factor * 0.9 typical Earth Leakage Current * 1.5 mA max at 264 VAC/60 Hz (JPS130) 260 A max at 275 VAC/63 Hz (JPS130-M) Input Protection * JPS130 internal T3.15 A/250 VAC fused line, JPS130-M fused line & neutral Input Voltage Input Frequency Input Current Output * See table * 10% on single output models, 5% on multi output models, auxiliary outputs will track by the same percentage Initial Set Accuracy * At 60% rated load 1% single outputs, 3% on V1 for multi outputs Minimum Load * Single output: no minimum load required Multi-outputs: (see note 1) Start Up Rise Time * <20 ms Hold Up Time * 16 ms typical at 115 VAC & rated load (JPS130) 20 ms typical at 115 VAC & rated load (JPS130-M) Drift * <0.2% after 20 mins warm up Line Regulation * 0.5% Vmin to Vmax Load Regulation * 1%, 5% for auxiliary outputs, 20%-100% of rated load Transient Response * 4% max deviation, recovery to within 1% in 500 s for a 25% load change Ripple & Noise * 1% max pk-pk (see note 4) Overvoltage Protection * 110-140% Vnom on V1 only, recycle input to reset Overload Protection * 110-150%, auto recovery Short Circuit Protection * Trip & restart (hiccup mode), auto recovery Temperature * 0.05%/C Coefficient Remote Sense * Single output models only, compensates for up to 0.5 V drop Fan Output * 12 V, 450 mA multi-output models only Output Voltage Output Voltage Trim General Efficiency Isolation Switching Frequency Power Density MTBF * Up to 90% nominal line, full load * 3000 VAC Input to Output (JPS130), 4000 VAC Input to Output (JPS130-M 2 x MOPP), 1500 VAC Input to Ground (JPS130-M 1 x MOPP), 500 VAC Output to Ground * 120 kHz, 10% for both active PFC & PWM * 6.7 W/In3 * 200 kHrs to MIL-HDBK-217F at 50 C, GB Environmental Operating Temperature * 0 C to +70 C, (see derating curves) Cooling * JPS130PS03 83 W convection-cooling, 100 W, with 18 CFM airflow. All others, 100 W with convection cooling,130 W with 18 CFM airflow Operating Humidity * 5-95% RH, non-condensing Storage Temperature * -40 C to +85 C (JPS130) -20 C to +85 C (JPS130-M) Operating Altitude * 3000 m EMC & Safety Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge Conducted Immunity Dips & Interruptions Safety Approvals * EN55022, Class B conducted FCC 20780, level B conducted EN60601-1-2, (JPS130-M) * EN61000-3-2 Class A * EN61000-3-3 * EN61000-4-2, level 3 contact, level 3 air, Perf Criteria A * EN61000-4-3, 10 V/m Perf Criteria A * EN61000-4-4, level 3 Perf Criteria A * EN61000-4-5, Installation Class 3 Perf Criteria A * EN61000-4-6, level 2, Perf Criteria A * EN61000-4-11, 30% 10 ms, 60% 100 ms, 95% 5000 ms Perf Criteria A, B, B * JPS130: EN60950-1, UL60950-1, CSA C22.2 No. 60950-1, CE Mark LVD. JPS130-M: UL60601-1, EN60601-1, CSA C22.2 No. 601.1 CE Mark LVD. Output Power(3) Output Voltage 100 W 3.3 V 5.0 V 12.0 V 15.0 V 24.0 V 28.0 V 48.0 V +5.0 V(1) +12.0 V(2) -12.0 V(2) +3.3 V(1) +5.0 V(2) +12.0 V(2) +5.0 V(1) +12.0 V(2) -12.0 V(2) +5.0 V(1) +15.0 V(2) -15.0 V(2) +5.0 V(1) +24.0 V(2) +12.0 V(2) 130 W 130 W 130 W 130 W 130 W 130 W Output Current Convection-cooled 18 CFM 25.0 20.0 9.0 7.0 4.5 3.8 2.1 11.5 3.0 0.5 10.0 8.0 0.5 10.0 3.0 0.8 10.0 2.5 0.8 2.5 2.8 0.7 A A A A A A A A A A A A A A A A A A A A A A 30.0 26.0 10.8 8.7 5.4 4.6 2.7 15.0 5.0 0.5 15.0 15.0 0.5 15.0 4.1 1.1 15.0 4.1 1.1 4.0 4.0 1.0 Ripple & Noise Pk-Pk(4) A A A A A A A A A A A A A A A A A A A A A A 50 50 120 120 200 200 200 50 100 100 50 50 100 50 120 120 50 150 150 50 240 120 Standard Model Number mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV Medical Model Number JPS130PS03 JPS130PS05 JPS130PS12 JPS130PS15 JPS130PS24 JPS130PS05-M JPS130PS12-M JPS130PS15-M JPS130PS24-M JPS130PS28-M JPS130PS48-M JPS130PS48 JPS130PT31 JPS130PT30 JPS130PT31-M JPS130PT32-M JPS130PT34-M Notes 1. 20% minimum load required on V1 to maintain stated regulation for auxiliary rails. 2. Load regulation of auxiliary rails is defined over the range of 20%-100% of rated load. 3. Maximum power with 18 CFM of forced air. 4. Ripple and noise measured over 15 MHz bandwidth with a 47 F electrolytic capacitor and 0.47 F ceramic capacitor. 5. Covers available, order part number `JPS130-M COVER' or add suffix `C' to receive the unit with cover fitted. Overall dimensions 89.5 x 143.0 x 40.0 mm. For industrial units order part number `JPS130 COVER' or add suffix `-C' to receive the unit with cover fitted. Overall dimensions 90.6 x 142.9 x 39.8 mm. Fixing screws M3, maximum penetration depth 3mm from cover outer surface. 6. Connector kits and cable harnesses available. Consult sales for options. Mechanical Details 0.16 (4.0) Dia Mounting Hole (4 Places) L TB2 1 N TB1 1 Voltage Trim TB3 2.55 (64.8) [2.60 (66.2) -M] TB2 3.00 (76.2) JPS130-M PIN CONNECTIONS TB2 PS05 PS 12 - 48 PT31 PT32 1 Return Return -12 V -15 V 2 Return Return +12 V +15 V 3 Return Return Return Return 4 Return +V Return Return 5 +V +V Return Return 6 +V +V Return Return 7 +V +5 V +5 V 8 +V +5 V +5 V 9 +5 V +5 V Type *5273-08A *5273-06A *5273-09A 0.22 (5.7) [0.2 (5.0) -M] -M version 1 4.55 (115.6) [4.60 (117.0) -M] 5.00 (127.0) TB2 1 2 3 4 5 6 7 8 9 10 Type 1.18 (30.0) (1) To Chassis Grounding x 2 All dimensions are in inches (mm). Tolerance: 0.02 (0.4) max. Weight: 0.5 lbs (240 g) approx. 0.10 (2.5) TB3 PIN CONNECTIONS Pin Single Multi 1 - Sense 0V 2 + Sense +12 V Fan Notes *5273-08A *5273-06A *5273-09A PT30 +3.3 V +3.3 V Return Return Return Return Return +5 V +5 V +12 V *5273-10A * Note: MOLEX connector type Derating Curves 130 A A JPS130 and `-M' with 18 CFM fan (except JPS130PS03). B JPS130PS12, PS15, PS24 and PS48 and `-M' with convection cooling. JPS130PS03 with 18 CFM fan. C JPS130PS05, PT30, PT31, PT32 and PT34 and `-M' with convection cooling. D JPS130PS03 with convection cooling. 100 Load (W) 1. Single output industrial model shown, add extra 0.08" (2.0 mm) to overall height for multi-output models. Dimensions followed by `-M' apply for medical units (note output connector orientation). 2. AC input connector (TB1): Molex 5277-02A or equivalent. Mates with 5196-N housings/5194/5225 crimps. 3. DC output connector (TB2): Molex 5273 or equivalent, mates with 5195-N housing/5194/5225 crimps and 5239-N housing/5167/5168/2478/2578 crimps. Except JPS130PS03 which has a 6-position terminal screw block: Dinkle part number EHK508V Series accepts 24-12 AWG wire. Terminal screw tightening torque 4 lbs-in (0.45 Nm) maximum. 4. TB3: Molex 5045-02A or equivalent. Mates with KK 51191 housings/50802 crimps and KK 5051 housings/2759/5159 crimps. Single output units - TB3 is remote sense. Multi-output units - TB3 is 12 V, 450 mA fan output. JPS130 PIN CONNECTIONS PS03, 12 - 48 PT31 +V +5 V +V +5 V +V +5 V Return Return Return Return Return Return Return +12 V -12 V PS05 +V +V +V +V Return Return Return Return PT34 +12 V +24 V Return Return Return Return +5 V +5 V +5 V C B D 80 60 40 20 0 -10 0 10 20 30 40 50 60 70 Ambient Temp (C) 17-Sept-12 ACDC JPS130 Models and Ratings