http://www.tracopower.com Page 1 of 6
Industrial Power Supplies
TSP-3P Series, 240 –960 Watt
Features 200% Peak Power!
3-phase input 3AC 400V or 3AC 500V
200 % boost power for up to 5 seconds
Alternative to AC transformers
Fully regulated 24 VDC output with
10 A, 20 A or 40 A
Rugged metal case design qualified for
harsh industrial environment
High efficiency >92%
Operating temperature range:
25°C to +60°C (full power)
Overload and over temperature protection
Industrial safety approvals
Cost effective design
3-year product warranty
The TRACOPOWER TSP-3P series of high performance DIN-rail power supplies of-
fers an economical solution to generate a regulated DC voltage from three-phase
mains networks. The smart design achieves a very high efficiency at ultra compact
size and very competitive cost. The series provides models with 240, 480 and 960
Watt output power all with additional power reserve of up to 200%.
This high peak power guarantees a reliable start-up of loads with high inrush cur-
rents such as motors, valves and other industrial loads. In many applications these
switching power supplies can also replace mains transformers with rectifiers.
Order Code Output Power
(nom.)
Input Voltage
(nom.)
Output Voltage
(nom.)
*Output Current
(nom.)
TSP 240-124-3PAC400 240 W 3 AC 400 V 24 VDC 10 A
TSP 240-124-3PAC500 3 AC 500 V 24 VDC 10 A
TSP 480-124-3PAC400 480 W 3 AC 400 V 24 VDC 20 A
TSP 480-124-3PAC500 3 AC 500 V 24 VDC 20 A
TSP 960-124-3PAC400 960 W 3 AC 400 V 24 VDC 40 A
TSP 960-124-3PAC500 3 AC 500 V 24 VDC 40 A
Models
* 200% peak current for up to 5 sec.
CB
Scheme
EMC
LVD
IEC 60950-1 UL 60950-1 UL 508 ATEX II3G
EN 60950-1
EN 61558-2-16
EN 60204
http://www.tracopower.com Page 2 of 6
Industrial Power Supplies
TSP-3P Series 240–960 Watt
Input Specifications
Input voltage range star-net configuration (2-phase operation not possible)
400 VAC models: 320 – 440 VAC
500 VAC models: 400 – 550 VAC
(derating below 410 VAC see graph 2)
Input voltage frequency 47 – 63 Hz
Harmonic limits EN 61000-3-2, Class B (for <16 A per phase)
Power factor >0.8 at full load
Recommended circuit breaker, 6.0 A characteristic B
Output Specifications
Output voltage: 24 VDC (fixed)
Regulation – Input / load variation 1 % max. + voltage drop at low input voltage and/or
boost power, see graph 1 & 2
Boost power – max. current 200 % of nominal output current
– duty cycle <10 %
– max. cycle time 5 sec limited by timer (automatic restart after 30 sec.)
– input voltage requirements see graph 1 & 2
Ripple and noise – nominal operation 100 mV pk-pk typ.
(20MHz bandwidth) – boost power operation up to 750 mV pk-pk
Rise time 200 ms typ.
Current limitation at 230 % of nominal output current, constant current
Overvoltage protection 33 V typ.
Overtemperature protection switch off at overtemperature (automatic restart)
Power back immunity 35 VDC continuouse, 40 VDC for one second
320 330 340 350 360 370 430 440
24
23
22
21
25
400 410 420 430 450 460 540 550
24
23
22
21
25
50% load
100% load
100% load
100% load100% load
200% boost
200% boost
Graph 1: 400 VAC input models
VACin VACin
VDCoutVDCout
Graph 2: 500 VAC input models
General Specifications
Temperature range – Full power operation 25°C to +60°C
– Max. operating +70°C, 2.5 %/K derating above +60°C
– Start up –40°C
– In accordance to UL508 25°C to +40°C
Cooling convection cooling, no internal fan
Humidity (non condensing) 95 % rel. H max.
Reliability, calculated MTBF at +2C acc. to IEC 61709 – TSP 240 & 480 >1 Mio h
– TSP 960 >800‘000 h
Isolation according to IEC/EN 60950-1, UL 60950-1, UL 508
Class of protection safety class I (IEC 536)
Degree of protection IP 20 (IEC/EN 60529)
Output Power Derating
http://www.tracopower.com Page 3 of 6
Industrial Power Supplies
TSP-3P Series 240–960 Watt
General Specifications
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
– Radiated RI suppression EN 55011 class B, EN 55022 class B,
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2
– Electrostatic discharge (ESD) IEC/EN 61000-4-2 8 kV / 15 kV criteria tba
– Radiated RF field immunity IEC/EN 61000-4-3 10 V/m criteria tba
– Electrical fast transient burst immunity input IEC/EN 61000-4-4 4 kV criteria tba
burst immunity output IEC/EN 61000-4-4 2 kV criteria tba
– Surge immunity L – L IEC/EN 61000-4-5 2 kV criteria tba
L – PE IEC/EN 61000-4-5 4 kV criteria tba
+ Output – - Output IEC/EN 61000-4-5 0.5 kV criteria tba
+ Output – PE IEC/EN 61000-4-5 0.5 kV criteria tba
– Output – PE IEC/EN 61000-4-5 0.5 kV criteria tba
– Immunity to conducted RF disturbances IEC/EN 61000-4-6 10 V criteria tba
– Mains voltage dips and interruptions IEC/EN 61000-4-11
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1
– Industrial control equipment UL 508 listed, CSA C22.2 No. 107.1
– Equipment for use in explosive atmospheres ATEX 94/9/EC
– Electrical equipment for machines EN 60204
– Electronic equipment for power installations EN 50178
– Safety of power transformers EN 61558-2-16
Safety approvals and – CB report for IEC 60950-1 www.tracopower.com/products/tsp3p-cb.pdf
– SIQ certificate for EN 60950-1 www.tracopower.com/products/tsp3p-siq.pdf
II3G Ex nA nC llC T3 www.tracopower.com/products/tsp3p-atex.pdf
– UL approvals for UL 508 listed www.tracopower.com/products/tsp3p-ul508.pdf
– Curtis-Straus certificate for UL 60950-1 (2nd) www.tracopower.com/products/tsp3p-ul.pdf
– Bureau Veritas for other standards www.tracopower.com/products/tsp3p-bv.pdf
Environmental compliance – Reach www.tracopower.com/products/tsp3p-reach.pdf
– RoHS RoHS directive 2002/95/EC
Environment – Vibration acc. IEC 60068-2-6; 0.075 mm / 10 – 55 Hz,
– Shock acc. IEC 60068-2-27 11ms / 15 g
Status signals – DC-OK relay contact DC OK = contact closed at >20...22 VDC
rated: 30 VDC/1.0 A for 24 VDC models
– DC-OK indication green LED at >20...22 VDC
– Phase error indication red blinking LED if one or two phases are missing
(function only if earth is connected)
– Overload / Overtemperature red LED on at >100% nominal load (5 sec. count down
for boost power is activated)
red blinking LED at temperature shut down (manual
restart required - mains disconnect for 5 sec.)
– Automatic restart indication red blinking LED during overload recovery periode
Enclosure material aluminium (chassis) / stainless steel (cover)
Mounting – DIN-rail mounting for DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
– Wall mounting (option) with wall mounting bracket - see page 6
Connection screw terminals
Installation instructions www.tracopower.com/products/tsp3p-inst.pdf
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com Page 4 of 6
Industrial Power Supplies
TSP-3P Series 240–960 Watt
240 Watt models
Outline Dimensions
54.0
110.0
(2.13)
(4.33)
110.0
(4.33)
25.0
(0.98)
5.0
(0.20)
14.5
(0.57)
DC-ON DC-OK
L1
38.5
(1.52)
80.0
(3.15)
_+
OVER-LOAD
RESTART
PHASE FAULT
L2 L3
480 Watt models
80.0
125.0
(3.15)
(4.92)
125.0
(4.92)
45.0
(1.77)
86.5
(3.41)
(1.81)
5.0
(0.20)
25.0
(0.98)
25.0
(0.98)
46.0 17.0
(0.67)
DC-OK
DC-ON
OVER-LOAD
RESTART
PHASE FAULT
_+
_+
L1 L2 L3
Weight: 1.05 kg (2.31 lb)
Weight: 575 g (1.27 lb)
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
http://www.tracopower.com Page 5 of 6
Outline Dimensions
960 Watt models
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
Weight: 2.35 kg (5.19 lb)
Industrial Power Supplies
TSP-3P Series 240–960 Watt
165.0
125.0
(6.50)
(4.92)
125.0
(4.92)
25.0
(0.98)
25.0
(0.98)
123.0
(4.84)
21.0
(0.83)
45.0
(1.77)
86.5
(3.41)
DC-OK
DC-ON
OVER-LOAD
RESTART
PHASE FAULT _+
_+
L1 L2 L3
Page 6 of 6
Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com
www.tracopower.com
Order code For models Content of kit
TSP-WMK03
TSP-WMK02
240 W
480 W & 960 W
1 bracket
2 brackets
TSP–WMK Wall Mounting Bracket
Rev. October 7. 2014
Industrial Power Supplies
TSP-3P Series 240–960 Watt
62.5
(2.46)
173.0
(6.81)
TSP 480-124-3PAC400
TSP 480-124-3PAC500
TSP 960-124-3PAC400
TSP 960-124-3PAC500
TSP 240-124-3PAC400
TSP 240-124-3PAC500
Dimensions: [mm] ( ) = Inch
46.0
(1.81)
33.0
(1.30)
25
(0.98)
50.0
(1.97)
2x
ø
4.3
(0.17)
4 x positioning holes
2.0
(0.08)
Material: 2 mm Mild Steel
Tolerance: ±0.1mm (± 0.004)
62.5
(2.46)
96.0
(3.78)
2.0
(0.08)
30.0
(1.18)
15.0
(0.59)
ø
4.3
(0.17)
7.0
(0.28)
15.0
(0.59)
7.0
(0.28)
15.0
(0.59)
Material: 2 mm Mild Steel
Tolerance: ±0.1mm (± 0.004)
55.0
(2.16)
ø
4.25
(0.17)
2.0
(0.08)
2.0
(0.08)
R 2.12
(0.083)
R 2.12
(0.083)
85.0
(3.35)
42.5
(1.67)
34.5
(1.36)
34.5
(1.36)
74.0
(2.91)
37.0
(1.45)
25.0
(0.98)
25.0
(0.98)
4 x positioning holes
2.0
(0.08)
2.0
(0.08)
R 2.12
(0.083)
R 2.12
(0.083)
ø
4.25
(0.17)
ø
4.25
(0.17)
TSP-WMK03
TSP-WMK02