Axioline digital input module, 32inputs, 24VDC, single-wire connection method (including bus base module and
connectors)
Product description
The module is designed for use within an AxiolineF station.
It is used to acquire digital signals.
The filter times of the inputs can be adjusted to increase noise immunity.
Filter times of 100μs enable the user to implement a counter function with a maximum input frequency of 5kHz in the application. 
Product Features
32 digital inputs according to EN61131-2 type1 and type3
24VDC, 2.4mA
Connection of sensors in single-wire technology
Minimum update time of < 100 μs
Filter times can be adjusted in three increments: <100µs, 1000µs or 3000µs
Maximum input frequency: 5 kHz
Device rating plate stored
Diagnostic and status indicators
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 220.0 GRM
Custom tariff number 85389091
Country of origin Germany
Technical data
Dimensions
Width 53.6 mm
Height 126.1 mm
Depth 54 mm
https://www.phoenixcontact.com/us/products/2688035
09/03/2014Page2/6
I/O module-AXL DI 32/1-2688035
Technical data
Dimensions
Note on dimensions The depth is valid when a TH35-7.5 DIN rail is used (according to
EN60715).
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Connection data
Designation AxiolineF connector
Connection method Push-in technology
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 1.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 16
Stripping length 8 mm
General
Weight 167 g
Note on weight specifications with connectors and bus base module
Mounting type DIN rail
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000‑4‑2/IEC61000‑4‑2 Criterion B; 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN61000‑4‑3/IEC61000‑4‑3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN61000‑4‑4/IEC61000‑4‑4 Criterion B, 2kV
Noise immunity test in accordance with EN 61000-6-2 Transient surge
voltage (surge) EN61000‑4‑5/IEC61000‑4‑5 Criterion B; DC supply lines:
±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
https://www.phoenixcontact.com/us/products/2688035
09/03/2014Page3/6
I/O module-AXL DI 32/1-2688035
Technical data
General
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN61000‑4‑6/IEC61000‑4‑6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 25g, 11 ms period, half-
sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Diagnostics messages I/O supply failure Yes
Interfaces
Designation AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Axioline potentials
Communications power UBus 5 V DC (via bus base module)
Current consumption from UBus max. 120 mA
Supply of digital input modules UI24 V DC
Current consumption from UImax. 50 mA
Digital inputs
Input name Digital inputs
Description of the input EN 61131-2 types 1 and 3
Connection method Push-in technology
1-wire
Number of inputs 32
Protective circuit Polarity reversal protection of the inputs Parallel diode (30V, 5s)
Input filter time 3000 µs (default)
Input voltage range "0" signal -3 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Nominal input current at UIN 2.4 mA
Classifications
eCl@ss
eCl@ss 4.0 27240404
eCl@ss 4.1 27240404
eCl@ss 5.0 27242204
eCl@ss 5.1 27242604
https://www.phoenixcontact.com/us/products/2688035
09/03/2014Page4/6
I/O module-AXL DI 32/1-2688035
Classifications
eCl@ss
eCl@ss 6.0 27242604
eCl@ss 7.0 27242604
eCl@ss 8.0 27242604
ETIM
ETIM 3.0 EC001599
ETIM 4.0 EC001599
ETIM 5.0 EC001599
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 39121311
UNSPSC 12.01 39121311
UNSPSC 13.2 39121311
Approvals
Approvals
Approvals
UL Listed / cUL Listed / BSH / RINA / DNV / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
https://www.phoenixcontact.com/us/products/2688035
09/03/2014Page5/6
I/O module-AXL DI 32/1-2688035
Approvals
BSH
RINA
DNV
cULus Listed
Drawings
Dimensioned drawing
53,6 54
122,4
126,1
Connection diagram
+24V
IN25
+24V
IN1
+24V
IN2
+24V
IN26
+24V
00
10
20
30
01
11
21
31
Block diagram
µ
C
D
UI
4x
DI 1...32
U
24 V
I
UBus
Local bus
Input circuit
013637 00
00
36 0137
00
10
20
30
01
11
21
31
Internal wiring of the terminal points
https://www.phoenixcontact.com/us/products/2688035