https://www.phoenixcontact.com/us/products/2904912
05/18/2015Page1/6
Temperature measuring transducer-MACX PL-EX-T-UIREL-UP-
SP-2904912
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Programmable temperature transducer with analog output and 3 limit value relays, intrinsically safe signal inputs,
resistance thermometer in 2-, 3-, or 4-wire technology, thermocouples, electrical isolation, wide-range power
supply, spring-cage connection, PLd
The figure shows a version with a
screw connection
Product Features
Key commercial data
Packing unit 1 pc
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 35 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) typ. 5 % ... 95 % (non-condensing)
https://www.phoenixcontact.com/us/products/2904912
05/18/2015Page2/6
Temperature measuring transducer-MACX PL-EX-T-UIREL-UP-
SP-2904912
Technical data
Ambient conditions
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Shock 15g, according to IEC 60068-2-27
Vibration (operation) 5g, accordance to IEC 60068-2-6
Degree of protection IP20
Input data
Sensor types (RTD) that can be used Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range -200 °C ... 850 °C
Input signal range 0 Ω ... 50 kΩ
Potentiometer resistance range 0 Ω ... 50 kΩ
Input signal range -1000 mV ... 1000 mV
Output data
Current output signal 4 mA ... 20 mA
Max. current output signal 22 mA
Load/output load current output ≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor error according to NE 43 or freely configurable
Output name Relay output
Output description 1 SIL/PL
Contact type 2 PDT
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC (250 V DC)
Maximum inrush current 2 A (250 V AC)
2 A (28 V DC)
0.2 A (120 V DC)
Mechanical service life 1 x 105 cycles
Power supply
Supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Typical current consumption < 100 mA (24 V DC)
Power consumption < 2.4 W
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
https://www.phoenixcontact.com/us/products/2904912
05/18/2015Page3/6
Temperature measuring transducer-MACX PL-EX-T-UIREL-UP-
SP-2904912
Technical data
Connection data
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Connection method Push-in connection
General
Maximum transmission error 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
Maximum temperature coefficient 0.01 %/K
Step response (0–99%) typ. 1000 ms (With SIL)
typ. 700 ms (Without SIL)
Status display Green LED (supply voltage, PWR)
Red LED, flashing (line, sensor error, ERR)
Red LED (module error, ERR)
Yellow LED (switching output)
Inflammability class according to UL 94 V0
Pollution degree 2
Surge voltage category II
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Housing material PA 66-FR
Color yellow
Designation Input/output/power supply
Electrical isolation 2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/power supply
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/switching output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output/supply
Electrical isolation 300 Vrms (Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
Conformance CE-compliant
ATEX  II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 G Ex nA nC ic IIC T4 Gc X
IECEx [Ex ia Ga] IIC
https://www.phoenixcontact.com/us/products/2904912
05/18/2015Page4/6
Temperature measuring transducer-MACX PL-EX-T-UIREL-UP-
SP-2904912
Technical data
General
[Ex ia Da] IIIC
Ex nA nC ic IIC T4 Gc X
UL, USA / Canada UL 508 Listed
Functional Safety (SIL) SIL 2
Safety data
Max. internal inductance Linegligible
Max. internal capacitance Ci44 nF
Max. output voltage Uo6 V
Max. output current Io7.4 mA
Max. output power Po11 mW
Group IIC
Max. external inductivity Lo100 mH
Max. external capacity Co1.3 µF
Group IIC
Max. external inductivity Lo10 mH
Max. external capacity Co1.7 µF
Group IIC
Max. external inductivity Lo1 mH
Max. external capacity Co2.6 µF
Group IIC
Max. external inductivity Lo0 mH
Max. external capacity Co10 µF
Group IIB
Max. external inductivity Lo100 mH
Max. external capacity Co6.8 µF
Group IIB
Max. external inductivity Lo10 mH
Max. external capacity Co9.2 µF
Safety-related maximum voltage Um253 V AC/DC
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 2 %
Designation Fast transients (burst)
https://www.phoenixcontact.com/us/products/2904912
05/18/2015Page5/6
Temperature measuring transducer-MACX PL-EX-T-UIREL-UP-
SP-2904912
Technical data
EMC data
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 2 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 2 %
Classifications
eCl@ss
eCl@ss 5.1 27200206
eCl@ss 6.0 27200206
ETIM
ETIM 4.0 EC002653
ETIM 5.0 EC002653
Approvals
Approvals
Approvals
UL Listed / cUL Listed / GL / Functional Safety / cULus Listed
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / EAC Ex / cULus Listed
Approvals submitted
Approval details
UL Listed
https://www.phoenixcontact.com/us/products/2904912
05/18/2015Page6/6
Temperature measuring transducer-MACX PL-EX-T-UIREL-UP-
SP-2904912
Approvals
cUL Listed
GL
Functional Safety
cULus Listed
Drawings
Block diagram
Zone0,1,2
Zone20,21,22 Zone2
IN OUT
Power
24V...230VAC/DC
3.3
3.1
1.2
3.2
1.1
1.3
4.3
4.1
4.2
5.3
5.1
5.2
GND
I
OUT
NC
PLC/DCS
passive
-
+
3.3
3.2
11
21
31
12
22
32
14
24
34
3.6
3.4
3.5
2.6
2.4
2.5
1.6
1.4
1.5
DI
DI
Sensor/Field
4.3
4.1
4.2
ϑ
RTD
4.3
4.1
4.2
5.3
5.1
5.2
ϑ
Poti
TC
-
+
ϑ
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com