https://www.phoenixcontact.com/us/products/2701722
05/03/2021Page3/9
I/O module-AXL F DI16/1 HS 1H-2701722
Technical data
Axioline potentials
Designation AxiolineF local bus supply (UBus)
Supply voltage 5 VDC (via bus base module)
Current consumption max. 120 mA (up to HW01)
max. 60 mA (as of HW02)
Power consumption max. 600 mW (up to HW01)
max. 300 mW (as of HW02)
Designation Supply for digital input modules (UI)
Supply voltage 24 VDC
Supply voltage range 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current consumption max. 30 mA
Power consumption max. 720 mW
Protective circuit Surge protection electronic (35 V, 0.5 s)
Reverse polarity protection parallel diode; with external 5A fuse (only for
commissioning)
Protection max. 8 A (polarity reversal protection up to 5A)
Digital inputs
Input name Digital inputs
Description of the input EN 61131-2 types 1 and 3
Connection method Push-in connection
Connection technology 1-conductor
Number of inputs 16
Protective circuit Polarity reversal protection of the inputs parallel diode (30V, 5s)
Nominal input voltage UIN 24 VDC
Nominal input current at UIN 2.3 mA
Input filter time < 5 µs
Input voltage range "0" signal -3 VDC ... 8.4 VDC
Input voltage range "1" signal 9.4 VDC ... 30 VDC
Electrical isolation
Test section 5V supply of the local bus (UBus) / 24V supply (I/Os) 500 VAC 50 Hz 1
min.
5V supply of the local bus (UBus) / functional ground 500 VAC 50 Hz 1
min.
24V supply (I/O) / functional ground 500 VAC 50 Hz 1 min.
Standards and Regulations
Immunity to ESD
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B, 6 kV contact
discharge, 8 kV air discharge