ACA-20RM-ALM Series
True-rms-AC Ammeters with Alarm Function
MPM_ACA-20RM-ALM.B01 Page 1 of 5
Murata Power Solutions’ ACA-20RM-ALM Series digital ac ammeters accurately display
the true-rms value of non-sinusoidal ac currents and provide a user-settable, over current
alarm function. When the preset over current level is exceeded, the LED display continu-
ously fl ashes from high to low intensity. All models are totally self-contained—no other
user-supplied components are required. A built-in current transformer greatly simplifi es
most ac ammeter applications: just pass the load conductor through the built-in current
transformer, apply ac power, and the ammeter is fully operational.
Two input ranges are available: 0-30.0 Amps, or 0 to 50.0 Amps, both with 0.1A resolu-
tion. The 50 Amp model features a convenient split-core type current transformer which
can be clamped around insulated live conductors. Two power supply options are available:
85-140V (47-63Hz), and 170-264V (47-63Hz). Power consumption from a nominal 120V or
220V ac supply is less than 50mA. Super-stable components and an rms-to-dc converter
circuit combine to achieve excellent performance when measuring the complex, non-sinu-
soidal, ac currents found in today’s computer/telecom equipment.
All ACA-20RM-ALM Series true-rms ammeters feature full-size, 0.37" (9.4mm) high,
3½ digit, bright red LED-displays and a built-in bezel/fi lter assembly that includes metal
fasteners. They are also panel cutout compatible with MPS’s DMS-20RM Series of rms-
reading ac voltage monitors, making ACA-20RM-ALM ammeters the ideal upgrade for
today’s sophisticated instrumentation.
FEATURES
User–settable, visual alarm function
Flashing display indicates overcurrent faults
Measures the true-rms value of complex ac current
waveforms
Includes built-in current transformers
Ideal for measuring current in sensitive IT applications
Available in two input ranges: 0-30.0A, and 0 to 50A
50A model features convenient split-core CT
Easy-to-read, red LED display with 0.37"/9.4mm high
digits
Two AC power options: 85-140Vac & 170-264Vac
(50/60Hz)
2000V isolation between ac supply and load conductor
Approvals to UL/cUL/IEC/61010-1
C
®
US E156931
CURRENT LIMITED
AC SUPPLY
3½ D IGIT
A/D CONVERTER
+V –V
+
RMS-to-DC
CONVERTER
CAL.
BUILT-IN
CURRENT
TRANSFORMER
LED DISPLAY
POWER
CONVERTER
TB1
AB
(L1)
MEASURED AC
LOAD CURRENT
Figure 1. ACA-20RM-ALM Series simplifi ed schematic
www.murata-ps.com/support
ACA-20RM-ALM Series
True-rms-AC Ammeters with Alarm Function
MPM_ACA-20RM-ALM.B01 Page 2 of 5
TECHNICAL NOTES
IMPORTANT! To ensure safe and reliable operation, ACA-20RM-
ALM ammeters must be installed and serviced by qualifi ed
technical personnel. Contact Murata Power Solutions if there is
any doubt regarding ammeter setup, installation, or operation.
1. Measurement Type: ACA-20RM-ALM ac ammeters employ a
true-rms input circuit to measure current fl owing through L1. Stated
accuracy specifi cations are measured using a sine-wave current
at, or close to, the ammeter’s full-scale input range, at nominal line
frequency of 60Hz.
2. Calibration (Potentiometer R7): Periodic recalibration of ACA-
20RM-ALM ammeters is not required under normal, indoor operating
environments. If user calibration is necessary, it must be performed
by qualifi ed technical personnel. Calibration is performed with poten-
tially lethal voltages applied to the ACA-20RM-ALM and its associated
wiring. A plastic, fully-insulated adjusting tool must be used to access
the calibration potentiometer R7 located on the back of the ammeter
(see ‘Mechanical Specifi cations’ section). Contact MPS if additional
information is required regarding calibration, setup, or any other
technical issue pertaining to ACA-20RM-ALM ammeters.
3. Overcurrent Alarm Setup and Adjustment (Potentiometer R3):
ACA-20RM-ALM ammeters feature a user-settable, overcurrent visual
alarm indication which can be used to alert operators that a load cir-
cuit breaker or fuse is approaching an overload condition. When the
load current sensed by L1 exceeds this preset level, the ammeter’s
LED display will fl ash from normal intensity to dim intensity at rate of
approximately 1.5 times per second.
As shown in Figure 3, the alarm circuit consists of jumper JP1, and
adjustment potentiometer R3. As shipped, R3 is factory set to trip
when the load current is approximately 24 Amps for 30A models, and
approximately 45 Amps for 50A models. When R3 is set to its maxi-
mum clockwise position, the alarm indication will not activate until the
load current fl owing through L1 exceeds the maximum rating of the
ammeter, i.e., above 30.0A, or above 50.0A, depending on the model.
Performance/Functional Specifi cations
Typical at TA = +25°C, unless otherwise noted.
Specifi ed full-scale currents are those passing through the ammeter’s built-in
current transformer’s primary load-circuit. See Notes 2 and 3 below for ad-
ditional model-specifi c information.
The overcurrent rating of 1.5 x the rated full-scale current is a continuous rating
and applies to the current passing through the built in current transformer only,
it does not apply to any external circuit-wiring or external loads. Accuracy is
guaranteed up to the rated current level.
Specifi ed accuracy applies to inputs with crest factors (CF) up to 2.0, where CF
= Vpeak/Vrms. Crest factors of 2 to 5 introduce an additional error of ±3% of full
scale. Ammeters are calibrated with a near full-scale 60Hz sine-wave current
owing through the ammeter’s built-in CT.
All specifi ed maximum power supply currents are steady state; larger surge
currents can occur at initial application of line power.
Rated Full-Scale Current Min. Typ. Max. Units
ACA-20RM-4-ACX-RL-ALM 50.0 Amperes
ACA-20RM-5-ACX-RL-ALM 30.0 Amperes
Overcurrent Rating 1.5 x Rated Full-Scale Current
Performance
Sampling Rate 2.5 Samples per second
Accuracy ±0.4%FS ±3 Counts with 60Hz
Sine-Wave Input
Measurement Type rms Responding, Crest Factors of 1-5
Temperature Drift (0 to 60 °C) ±0.2 ±0.4 Counts/ºC
Zero-Current Reading (within
30 sec.)
–001 000 001 Counts
Dielectric Withstanding Voltage 2000 Vdc
UL/IEC61010-1 Measurement category II
Power Supply Voltage
ACA-20RM-X-AC3-RL-ALM 85 120 140 Vac/47-63Hz
ACA-20RM-X-AC4-RL-ALM 170 220 264 Vac/47-63Hz
Power Supply Current
ACA-20RM-X-AC3-RL-ALM 30 50 mA/47-63Hz
ACA-20RM-X-AC4-RL-ALM 30 50 mA/47-63Hz
Alarm Function
Display indication Flashing Display with actual current
reading and display intensity change
Settable range
ACA-20RM-4-ACX-RL-ALM 13 45 50 Amps
ACA-20RM-5-ACX-RL-ALM 8 24 30 Amps
Power Supply Terminal Block
Wire Size 16-22AWG, Solid or stranded
Insulation Strip Length 0.250 inches
Screw Tightening Torque 3.6 pounds-inches (0.4Nm)
Rated Voltage 310Vac
Display
Display Type and Size 3½ Digit Red LED, 0.37”/9.4mm High
Overrange Indication 1___”
Decimal Point Fixed, model dependent
(see full-scale input current)
Physical/Environmental
Operating Temperature 0 +60 °C
Storage Temperature –40 +75 °C
Humidity (non-condensing) 0 85 %
Dimensions Model dependent, see page 4 & 5
Weight
ACA-20RM-4-XXX-XX-ALM 1.5 Ounces (43 grams) nominal
ACA-20RM-5-XXX-XX-ALM 2.1 Ounces (60 grams) nominal
Ordering Information
ACA-20RM-4-AC3-RL-ALM-C 50.0A Range (split-core CT), 85-140Vac power
ACA-20RM-4-AC4-RL-ALM-C 50.0A Range (split core CT), 170-264Vac power
ACA-20RM-5-AC3-RL-ALM-C 30.0A Range, 85-140Vac power
ACA-20RM-5-AC4-RL-ALM-C 30.0A Range, 170-264Vac power
See www.murata-ps.com/dpm-availability for model-specifi c availability.
www.murata-ps.com/support
ACA-20RM-ALM Series
True-rms-AC Ammeters with Alarm Function
MPM_ACA-20RM-ALM.B01 Page 3 of 5
7. Isolation: The built-in current transformer L1 provides a minimum
of 2000Vdc isolation between the load conductor and the ammeter’s
supply voltage connected to TB1.
8. Split-Core CT (Clamp-on) Models: Both 50A models feature a split-
core current transformer that can be clamped around a properly insu-
lated live conductor without having to disconnect or remove power
from the load circuit. This live-connection capability can only be used
if the load’s power source is electrically isolated (see technical note
7) from the ammeter’s own power source that’s connected to TB1.
The ammeter’s ac power supply must always be denergized before
making connections to TB1. Refer to the ‘Panel Installation’ section of
this data sheet for additional information.
L1
TO AC LOAD
TB1
BACK VIEW
A
B
FUSED AC POWER
Figure 2. Typical wiring diagram
To adjust the overcurrent alarm set-point level:
A. Turn off power to the ACA-20RM-ALM (i.e., the power source con-
nected to TB1).
B. Carefully remove the shorting jumper across JP1 from its ‘normal
operation position’ across terminals 2 and 3 and place it across JP1
terminals 1 and 2.
C. Re-apply power to TB1 and, using a plastic insulated adjusting tool,
adjust R3 so the ammeter’s display shows the desired overcurrent
trip level in Amps.
D. Turn off power to the ACA-20RM-ALM and return JP1’a shorting
jumper back to its ‘normal operation position’ across terminals 2
and 3. Re-apply power to TB1 to resume normal operation. If pos-
sible, after the ammeter is re-confi gured for normal operation, the
load current should be slowly increased to verify the visual alarm
operates when the load current exceeds the preset level.
Please note, the load circuit does not need to be turned off to adjust the
overcurrent alarm set point. Current fl owing through L1 while JP1 is
across terminals 1 and 2 will not be measured. Once tripped, the alarm
set point function has a hysteresis of approximately 0.5A.
The overcurrent alarm function can also be adjusted with JP1 in its
normal operation position if the desired alarm overcurrent-level is
actually fl owing through L1 (i.e., with a live load). For example, with
a 20 Amp load current fl owing through L1, and with JP1 in its normal
operation position, slowly adjust R3 until the display starts fl ashing on
and off. Using this “live load” adjustment method eliminates the need
to turn off power to TB1 or reconfi guring JP1.
4. Wire Gauges and Fusing: Wires specifi ed in the Functional Specifi ca-
tions section must be used for making connections to ACA-20RM-ALM
series ammeters. All power-supply and load wiring must be rated for
the supply voltages and currents they will conduct and must comply
with any code or application-mandated requirements pertaining to the
user’s specifi c installation.
ACA-20RM-ALM ammeters are not internally fused. Terminal block TB1
is to be used only for powering the ammeter’s internal circuitry; it must
not be used to supply power to external loads. The supply wires feed-
ing these power meters must be fused with a 0.25A/250V time delay/
time lag fuse, in accordance with applicable regulatory codes.
Wire insulation must be stripped to within ±10% of the stated dimen-
sions, and wires should be inserted into TB1 such that their insulation
is not pinched by the screw terminal.
5. AC Supply Polarity and Grounding: The two supply inputs, TB1-A and
TB1-B, on ACA-20RM-ALM ammeters are not in themselves polarity
sensitive, that is, they have no internal “AC LO” or “AC HI” designa-
tions. ACA-20RM-ALM ammeters do not include or require a connec-
tion to earth/chassis ground.
6. Connector Torque Ratings: It is important to tighten TB1’s, screw-ter-
minals to their rated torque specifi cation of 3.6 pound-inches (0.4Nm).
Proper tightening will minimize connector losses and ensure safe,
reliable operation.
Figure 3. Alarm circuit component location
TB1 R7
CAL
JP1
BACK VIEW
R3
ALARM
JP1
Normal Operation
3
2
1
JP1
Overcurrent
Alarm Adjustment
3
2
1
3
2
1
F R O N T V I E W
1 . 2 8 0
( 3 2 . 5 1 )
0 . 1 8 7
( 4 . 7 5 )
R E C O M M E N D E D D R I L L A N D
P A N E L C U T O U T D I M E N S I O N S
1 . 8 2 6 ( 4 6 . 3 8 )
0 . 8 3 8
( 2 1 . 2 9 )
1 . 6 2 6 ( 4 1 . 3 0 )
1 . 0 7
( 2 7 . 1 8 )
I N T E R N A L C O R N E R R A D I I :
0 . 0 3 2 ( 0 . 8 1 ) M A X .
0 . 0 9 3 ( 2 . 3 6 2 ) D I A M E T E R ( 4 R E Q U I R E D )
0 . 1 1 6 ( 2 . 9 5 )
1 . 3 3 6 ( 3 3 . 9 3 ) 0 . 1 4 5 ( 3 . 6 8 )
0 . 69
(17.5)
www.murata-ps.com/support
ACA-20RM-ALM Series
True-rms-AC Ammeters with Alarm Function
MPM_ACA-20RM-ALM.B01 Page 4 of 5
PANEL INSTALLATION
BEZEL AND PANEL CUTOUT
All connections to ACA-20RM-ALM Series ammeters must be made after
the ammeter is securely attached to the panel and with all associated
load and supply voltages de-energized (off), using extreme caution and
observing all safety measures applicable to the user’s installation.
Care should be exercised when passing conductors through the amme-
ter’s built-in current transformer L1. The installed wire-positions should
be such that minimal mechanical forces are applied to L1, TB1, or to the
ammeter itself. In high-vibration environments, it is strongly recom-
mended that adequate strain reliefs be used for all wiring.
Using Figure 4 as a guide, carefully insert the bezel/color fi lter assembly
into the panel opening. From the rear of the panel, install the four round
Figure 4. Panel Installation
plastic standoffs over the bezel’s threaded studs. Install the ACA-20RM-
ALM pc-board assembly as shown and then attach and securely tighten
each of the four hex nuts to 15-20 ozf-in (0.106 to 0.140 N-m). Use only
the factory-supplied hardware as the use of substitute hardware could
result in an unsafe installation and/or adversely affect the reliability of
the ammeter.
The recommended range of panel thickness that can be used with the
supplied hardware is 0.040 inches (1.0mm) to 0.125 inches (3.2mm).
Panel thickness outside of this range will require additional user-supplied
hardware or modifi cations.
SIDE VIEW
Bezel
Gasket Standoff
Nut
ACA-20RM
AC Ammeter
Board-Cutout
PANEL
Gasket Standoff
0.190 (4.83)
0.032 (0.8) Thick
www.murata-ps.com/support
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifi cations are subject to change without
notice. © 2015 Murata Power Solutions, Inc.
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfi eld, MA 02048-1151 U.S.A.
ISO 9001 and 14001 REGISTERED
This product is subject to the following operating requirements
and the Life and Safety Critical Application Sales Policy:
Refer to: http://www.murata-ps.com/requirements/
ACA-20RM-ALM Series
True-rms-AC Ammeters with Alarm Function
MPM_ACA-20RM-ALM.B01 Page 5 of 5
MECHANICAL SPECIFICATIONS
MECHANICAL DIMENSIONS: Inches (mm)
TOLERANCES: 2 PL DEC ±0.02 (±0.51)
3 PL DEC ±0.010 (±0.254)
FRONT VIEW
BACK VIEW
SIDE VIEW
100-10
M9
100-10
M9
2.100
(53.34)
1.400
(35.56)
0.250
(6.35)
30 AMP MODELS
0.480
(12.19)
Lead Length
2.0 (50.5) min.
A
B
B1
0.35
(8.9)
Diameter
FRONT VIEW
BACK VIEW
SIDE VIEW
100-10
M9
100-10
M9
2.100
(53.34)
1.400
(35.56)
0.250
(6.35)
50 AMP SPLIT-CORE CT MODELS
1.024
(26.01)
0.551
(14.00)
0.984
(24.99)
1.575
(40.00)
0.480
(12.19)
0.40
(10.2)
Diameter
Lead Length
5.0 (127.0) min.
A
B
TB1
1. Description of safety marks:
Caution, risk of electrical shock
Caution, risk of danger
Equipment is protected throughout by double or reinforced insulation
2. Cleaning Instructions: Gently clean with dry cloth only.
3. Caution: if the equipment is used in a manner not specifi ed by Murata Power Solutions, the protection provided by the equipment may be impaired.