83 Series - Modular timers 10 - 16 A Features 83.01 83.02 Multi-function timer range 83.01 - Multi-function & multi-voltage, 1 Pole 83.02 - Multi-function & multi-voltage, 2 Pole (timed + instantaneous options), external time setting potentiometer option 22.5 mm wide Eight time scales from 0.05s to 10 days * High input/output isolation * Wide supply range (24...240)V AC/DC * 35 mm rail (EN 60715) mount * "Blade + cross" - both flat blade and cross head screw drivers can be used to adjust the range and function selectors, the timing trimmer, and to disengage the rail mounting clip * Multi-voltage versions with "PWM clever" technology * * * * Multi-voltage Multi-function * Timing can be regulated using ext. Potentiometer * 2 timed contacts or 1 timed + 1 instantaneous contact Multi-voltage Multi-function * * AI: On-delay DI: Interval GI: Pulse delayed SW: Symmetrical flasher (starting pulse on) BE: Off-delay with control signal CE: On- and off-delay with control signal DE: Interval with control signal on WD: Watchdog (Retriggerable interval with control signal on) Wiring diagram (with control signal) Wiring diagram (without control signal) For outline drawing see page 5 AI: On-delay DI: Interval GI: Pulse delayed SW: Symmetrical flasher (starting pulse on) BE: Off-delay with control signal CE: On- and off-delay with control signal DE: Interval with control signal on WD: Watchdog (Retriggerable interval with control signal on) Wiring diagram (with control signal) Wiring diagram (without control signal) Contact specification Contact configuration Rated current/Maximum peak current A Rated load AC15 (230 V AC) Single phase motor rating (230 V AC) Breaking capacity DC1: 30/110/220 V Minimum switching load 2 CO (DPDT) 16/30 10/30 250/400 250/400 VA 4,000 2,500 VA 750 750 kW 0.5 0.5 16/0.3/0.12 10/0.3/0.12 300 (5/5) 300 (5/5) AgNi AgNi 24...240 24...240 Rated voltage/Maximum switching voltage V AC Rated load AC1 1 CO (SPDT) A mW (V/mA) Standard contact material Supply specification Nominal voltage (UN) V AC (50/60 Hz) 24...240 24...240 Rated power AC/DC VA (50 Hz)/W < 1.5 / < 2 <2/<2 V AC 16.8...265 16.8...265 V DC 16.8...265 16.8...265 V DC Operating range Technical data Specified time range (0.05...1)s, (0.5...10)s, (0.05...1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d Repeatability % 1 1 Recovery time ms 200 200 Minimum control impulse ms 50 50 Setting accuracy-full range Electrical life at rated load in AC1 Ambient temperature range Protection category % cycles C 5 5 70*103 150*103 -20...+60 -20...+60 IP 20 IP 20 Approvals (according to type) 1 83 Series - Modular timers 16 A Features 83.11 83.21 83.41 Mono-function timer range 83.11 - ON-delay, multi-voltage 83.21 - Interval, multi-voltage 83.41 - Off-delay with control signal, multi-voltage 1 Pole 22.5 mm wide * Eight time scales from 0.05s to 10 days * High input/output isolation * Wide supply range (24...240)V AC/DC * 35 mm rail (EN 60715) mount * "Blade + cross" - both flat blade and cross head screw drivers can be used to adjust the range and function selectors, the timing trimmer, and to disengage the rail mounting clip * Multi-voltage versions with "PWM clever" technology * * * * Multi-voltage Mono-function * Multi-voltage Mono-function DI: Interval AI: On-delay For outline drawing see page 5 * * * Multi-voltage Mono-function BE: Off-delay with control signal Wiring diagram (without control signal) Wiring diagram (without control signal) Wiring diagram (with control signal) 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT) 16/30 16/30 16/30 Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 Rated load AC15 (230 V AC) Single phase motor rating (230 V AC) Breaking capacity DC1: 30/110/220 V Minimum switching load 250/400 250/400 250/400 VA 4,000 4,000 4,000 VA 750 750 750 kW 0.5 0.5 0.5 16/0.3/0.12 16/0.3/0.12 16/0.3/0.12 300 (5/5) 300 (5/5) 300 (5/5) AgNi AgNi AgNi 24...240 24...240 24...240 A mW (V/mA) Standard contact material Supply specification Nominal voltage (UN) V AC (50/60 Hz) 24...240 24...240 24...240 Rated power AC/DC VA (50 Hz)/W < 1.5 / < 2 < 1.5 / < 2 < 1.5 / < 2 V AC 16.8...265 16.8...265 16.8...265 V DC 16.8...265 16.8...265 16.8...265 V DC Operating range Technical data (0.05...1)s, (0.5...10)s, (0.05...1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d Specified time range Repeatability % 1 1 1 Recovery time ms 200 200 200 Minimum control impulse ms -- -- 50 % 5 5 5 70*103 70*103 70*103 -20...+60 -20...+60 -20...+60 IP 20 IP 20 IP 20 Setting accuracy-full range Electrical life at rated load in AC1 Ambient temperature range Protection category Approvals (according to type) 2 cycles C 83 Series - Modular timers 8 - 16 A Features 83.62 83.82 83.91 Mono-function and multi-function timer range 83.62 - Power off-delay, multi-voltage, 2 Pole 83.82 - Star-Delta, multi-voltage, star and delta output contacts 83.91 - Asymmetrical flasher, multi-voltage, 1 Pole 22.5 mm wide Time scales: Type 83.62 - 0.05s to 3 minutes Type 83.82 / 83.91 - 0.05 s to 10 days * Wide supply range (24...240)V AC / DC * 35 mm rail (EN 60715) mount * * Multi-voltage Mono-function * 2 pole Multi-voltage Mono-function * 2 pole * Transfer time can be regulated (0.05...1)s *** * * * * * * BI: Power off-delay (True off-delay) SD: Star-delta Multi-voltage Multi-function LI: Asymmetrical flasher (starting pulse on) LE: Asymmetrical flasher (starting pulse on) with control signal PI: Asymmetrical flasher (starting pulse off) PE: Asymmetrical flasher (starting pulse off) with control signal Wiring diagram (without control signal) * (0.05...2)s, (1...16)s, (8...70)s, (50...180)s ** (0.05...1)s, (0.5...10)s, (0.05...1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d *** 0.05 s, 0.2 s, 0.3 s, 0.45 s, 0.6 s, 0.75 s, 0.85 s, 1 s For outline drawing see page 5 Wiring diagram (with control signal) Wiring diagram (without control signal) Wiring diagram (without control signal) 2 CO (DPDT) 2 NO (DPST-NO) 1 CO (SPDT) 8/15 16/30 16/30 Contact specification Contact configuration Rated current/Maximum peak current A Rated voltage/Maximum switching voltage V AC Rated load AC1 Rated load AC15 (230 V AC) Single phase motor rating (230 V AC) Breaking capacity DC1: 30/110/220 V Minimum switching load 250/400 250/400 250/400 VA 2,000 4,000 4,000 VA 400 750 750 kW 0.3 0.5 0.5 8/0.3/0.12 16/0.3/0.12 16/0.3/0.12 300 (5/5) 300 (5/5) 300 (5/5) AgNi AgNi AgNi 24...240 24...240 24...240 A mW (V/mA) Standard contact material Supply specification Nominal voltage (UN) V AC (50/60 Hz) 24...240 24...240 24...240 Rated power AC/DC VA (50 Hz)/W < 1.5 / < 2 < 1.5 / < 2 < 1.5 / < 2 V AC 16.8...265 16.8...265 16.8...265 V DC 16.8...265 16.8...265 16.8...265 V DC Operating range Technical data Specified time range * ** Repeatability % 1 1 1 Recovery time ms 200 200 200 Minimum control impulse ms 500 ms (A1 - A2) -- 50 % 5 5 5 100*103 70*103 70*103 -20...+60 -20...+60 -20...+60 IP 20 IP 20 IP 20 Setting accuracy-full range Electrical life at rated load in AC1 Ambient temperature range Protection category cycles C Approvals (according to type) 3 83 Series - Modular timers 16 A Ordering information Example: 83 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (24...240)V AC/DC. 8 3 . 0 1 . 0 . 2 4 0 . 0 0 0 0 Versions 0000 = Standard Series Type 0 = Multi-function (AI, DI, GI, SW, BE, CE, DE, WD) 1 = On-delay (AI) 2 = Interval (DI) 4 = Off-delay with control signal (BE) 6 = Power off-delay (True off-delay) (BI) 8 = Star-delta (SD) 9 = Asymmetrical flasher (LI, LE, PI, PE) Supply voltage 240 = (24 ... 240)V AC/DC Supply version 0 = AC (50/60 Hz)/DC No. of poles 1 = 1 CO (SPDT) 2 = 2 CO (DPDT) for 83.02 and 83.62 2 = 2 NO (DPST-NO) for 83.82 Technical data Insulation Dielectric strength between input and output circuit V AC 4,000 between open contacts V AC 1,000 Insulation (1.2/50 s) between input and output kV 6 EMC specifications Type of test Reference standard Electrostatic discharge Radio-frequency electromagnetic field contact discharge EN 61000-4-2 4 kV air discharge EN 61000-4-2 8 kV (80 / 1,000 MHz) EN 61000-4-3 10 V/m (1,000 / 2,700 MHz) EN 61000-4-3 3 V/m Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals Surges (1.2/50 s) on Supply terminals on control signal terminal (B1) Radio-frequency common mode EN 61000-4-4 6 kV on control signal terminal (B1) EN 61000-4-4 6 kV common mode EN 61000-4-5 6 kV differential mode EN 61000-4-5 4 kV common mode EN 61000-4-5 6 kV differential mode EN 61000-4-5 4 kV (0.15 / 80 MHz) on Supply terminals EN 61000-4-6 (80 / 230 MHz) Radiated and conducted emission 10 V EN 61000-4-6 10 V EN 55022 class B Other data Current absorption on control signal (B1) < 1 mA - max cable length (capacity of 10 nF / 100 m) 150 m - when applying a control signal to B1, which is B1 is isolated from A1 and A2 by an opto-coupler, and can different from the supply voltage at A1/A2 therefore be operated at a voltage other than the supply voltage. If using a control signal of between (24... 48)V DC and a supply voltage of (24...240)V AC, ensure that the signal - is connected to A2 and the + is applied to B1, and that L is applied to B1 and N to A2. Use a 10 k/ 0,25 W linear potentiometer. Maximum cable length 10 m. When using an external potentiometer, the timer automatically use its setting in place of the internal setting. Consider the voltage potential at the potentiometer to be the External potentiometer for 83.02 same as the timer supply voltage. Power lost to the environment without contact current with rated current Screw torque Max. wire size 4 W 1.4 W 3.2 Nm 0.8 solid cable stranded cable mm2 1x6 / 2x4 1x4 / 2x2.5 AWG 1x10 / 2x12 1x12 / 2x14 83 Series - Modular timers 16 A Outline drawings 83.01 Screw terminal 83.02 Screw terminal 83.11 Screw terminal 83.21 Screw terminal 83.41 Screw terminal 83.62 Screw terminal 83.82 Screw terminal 83.91 Screw terminal 5 83 Series - Modular timers 16 A Accessories Sheet of marker tags, for types 83.01/11/21/41/62/82, plastic, 72 tags, 6x12 mm 060.72 060.72 Potentiometer usable as external potentiometer for type 83.02 10 k / 0.25 W linear 087.02.2 087.02.2 Z2 Z1 Functions LED* Supply NO output voltage contact Open Closed OFF Open 15 - 18 25 - 28 15 - 16 25 - 26 ON Open 15 - 18 25 - 28 15 - 16 25 - 26 ON Open (Timing in Progress) 15 - 18 25 - 28 15 - 16 25 - 26 ON Closed 15 - 16 25 - 26 15 - 18 25 - 28 Contacts * The LED on type 83.62 is illuminated when supply voltage is supplied to timer. * Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1. * ** 6 * With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1). ** A voltage other than the supply voltage can be applied to the control signal (B1), example: A1 - A2 = 230 V AC B1 - A2 = 12 V DC 83 Series - Modular timers 16 A Functions U = Supply voltage Wiring diagram Multi-function without control signal S = Signal switch = Output contact (AI) On-delay. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs when power is removed. Type 83.01 83.02 (DI) Interval. Apply power to timer. Output contacts transfer immediately. After the preset time has elapsed, contacts reset. 83.01 (GI) Pulse delayed. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs after a fixed time of 0.5s. (SW) Symmetrical flasher (starting pulse on). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ratio is 1:1 (time on = time off). 83.02 *** with control signal (BE) Off-delay with control signal. Power is permenently applied to the timer. The output contacts transfer immediately on closure of the control signal (S). Opening the control signal initiates the preset delay, after which time the output contacts reset. (CE) On- and off-delay with control signal. Power is permenently applied to the timer. Closing the control signal (S) initiates the preset delay, after which time the output contacts transfer. Opening the control signal initiates the same preset delay, after which time the output contacts reset. 83.01 (DE) Interval with control signal on. Power is permenently applied to the timer. On momentary or maintained closure of control signal (S), the output contacts transfer, and remain so for the duration of the preset delay, after which they reset. 83.02 *** (WD) Watchdog (Retriggerable interval with control signal on). Power is permanently applied to the timer. On momentary or maintained closure of control signal (S), the output contacts transfer, and remain so for the duration of the preset delay, after which they reset; subsequent closures of control signal during the delay will extend the time. If the closure of the control signal (S) is longer than the preset time (T) then the output contacts reset. *** Type 83.02: regulated using an external potentiometer (10 k - 0.25 W). NOTE: The timing function must be set when the timer is de-energised. Or for the 83.02, when the contact mode selector is in the OFF position. 83.02 type Contact mode selector Functions without control signal (example: AI) Functions with control signal (example: BE) Both output contacts (15-18 and 25-28) follow the timing function Both output contacts (15-18 and 25-28) follow the timing function Both output contacts [15-18 and 25(21)-28(24)] stay permanently open Both output contacts [15-18 and 25(21)-28(24)] stay permanently open The output contact 15-18 follows the timing function The output contact 21-24 follows the power supply (U) The output contact 15-18 follows the timing function The output contact 21-24 follows the control signal (S) 2 timed contacts 1 timed + 1 instantaneous contact 7 83 Series - Modular timers 16 A Functions Wiring diagram U = Supply voltage Mono-function without control signal S = Signal switch = Output contact Type 83.11 (AI) On-delay. Apply power to timer. Output contacts transfer after preset time has elapsed. Reset occurs when power is removed. 83.21 (DI) Interval. Apply power to timer. Output contacts transfer immediately. After the preset time has elapsed, contacts reset. 83.62 (BI) Power off-delay (True off-delay). Apply power to timer (minimum 500 ms). Output contacts transfer immediately. Removal of power initiates the preset delay, after which time the output contacts reset. 83.82 (SD) Star-delta. Apply power to timer. The star contact ( ) closes immediately. After preset delay has elapsed the star contact ( ) resets. After a further time (settable from 0.05s to 1s) the delta contact ( ) closes and remains in that position, until reset on power off. 83.41 (BE) Off-delay with control signal. Power is permenently applied to the timer. The output contacts transfer immediately on closure of the control signal (S). Opening the control signal initiates the preset delay, after which time the output contacts reset. 83.91 (LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open). Apply power to timer. Output contacts transfer immediately and cycle between ON and OFF for as long as power is applied. The ON and OFF times are independently adjustable. 83.11 83.21 83.62 83.82 with control signal (S) 83.41 Asymmetrical recycler without control signal 83.91 Z1-Z2 open: (LI) function Z1-Z2 linked: (PI) function with control signal 83.91 Z1-Z2 open: (LE) function Z1-Z2 linked: (PE) function 8 (PI) Asymmetrical flasher (starting pulse off) - (Z1-Z2 linked). Apply power to timer. Output contacts transfer after time T1 has elapsed and cycle between OFF and ON for as long as power is applied. The ON and OFF times are independently adjustable. (LE) Asymmetrical flasher (starting pulse on) with control signal - (Z1-Z2 open). Power is permenently applied to the timer. Closing control signal (S) causes the output contacts to transfer immediately and cycle between ON and OFF, until opened. (PE) Asymmetrical flasher (starting pulse off) with control signal - (Z1-Z2 linked). Power is permenently applied to the timer. Closing the control signal (S) initiates delay T1 after which the output contacts transfer and continue to cycle between OFF and ON, until the control signal is opened.