83.01 83.02
1 CO (SPDT) 2 CO (DPDT)
16/30 10/30
250/400 250/400
4,000 2,500
750 750
0.5 0.5
16/0.3/0.12 10/0.3/0.12
300 (5/5) 300 (5/5)
AgNi AgNi
24…240 24...240
24…240 24...240
< 1.5 / < 2 < 2 / < 2
16.8...265 16.8...265
16.8...265 16.8...265
(0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d
± 1 ± 1
200 200
50 50
± 5 ± 5
70·103150·103
–20…+60 –20…+60
IP 20 IP 20
Wiring diagram
(without control signal)
Multi-voltage
Multi-function
Timing can be regulated using ext. Potentiometer
2 timed contacts or 1 timed + 1 instantaneous contact
Multi-voltage
Multi-function
AI: On-delay
DI: Interval
GI: Pulse delayed
SW: Symmetrical flasher (starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
WD: Watchdog (Retriggerable interval with control
signal on)
AI: On-delay
DI: Interval
GI: Pulse delayed
SW: Symmetrical flasher (starting pulse on)
BE: Off-delay with control signal
CE: On- and off-delay with control signal
DE: Interval with control signal on
WD: Watchdog (Retriggerable interval with control
signal on)
Wiring diagram
(with control signal)
Wiring diagram
(with control signal)
Wiring diagram
(without control signal)
83 Series - Modular timers 10 - 16 A
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification
Nominal voltage (UN) V AC (50/60 Hz)
V DC
Rated power AC/DC VA (50 Hz)/W
Operating range V AC
V DC
Technical data
Specified time range
Repeatability %
Recovery time ms
Minimum control impulse ms
Setting accuracy-full range %
Electrical life at rated load in AC1 cycles
Ambient temperature range °C
Protection category
Approvals (according to type)
1
Features
Multi-function timer range
83.01 - Multi-function & multi-voltage, 1 Pole
83.02 - Multi-function & multi-voltage,
2 Pole (timed + instantaneous options),
external time setting potentiometer
option
22.5 mm wide
Eight time scales from 0.05s to 10 days
High input/output isolation
Wide supply range (24...240)V AC/DC
35 mm rail (EN 60715) mount
“Blade + cross” - both flat blade and cross
head screw drivers can be used to adjust the
range and function selectors, the timing
trimmer, and to disengage the rail mounting
clip
Multi-voltage versions with “PWM clever”
technology
For outline drawing see page 5
83.11 83.21 83.41
Multi-voltage
Mono-function
BE: Off-delay with control signal
Wiring diagram
(with control signal)
1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
16/30 16/30 16/30
250/400 250/400 250/400
4,000 4,000 4,000
750 750 750
0.5 0.5 0.5
16/0.3/0.12 16/0.3/0.12 16/0.3/0.12
300 (5/5) 300 (5/5) 300 (5/5)
AgNi AgNi AgNi
24...240 24...240 24...240
24...240 24...240 24...240
< 1.5 / < 2 < 1.5 / < 2 < 1.5 / < 2
16.8...265 16.8...265 16.8...265
16.8...265 16.8...265 16.8...265
(0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d
± 1 ± 1 ± 1
200 200 200
——50
± 5 ± 5 ± 5
70·10370·10370·103
–20…+60 –20…+60 –20…+60
IP 20 IP 20 IP 20
Multi-voltage
Mono-function
AI: On-delay
Wiring diagram
(without control signal)
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification
Nominal voltage (UN) V AC (50/60 Hz)
V DC
Rated power AC/DC VA (50 Hz)/W
Operating range V AC
V DC
Technical data
Specified time range
Repeatability %
Recovery time ms
Minimum control impulse ms
Setting accuracy-full range %
Electrical life at rated load in AC1 cycles
Ambient temperature range °C
Protection category
Approvals (according to type)
Features
Mono-function timer range
83.11 - ON-delay, multi-voltage
83.21 - Interval, multi-voltage
83.41 - Off-delay with control signal,
multi-voltage
1 Pole
22.5 mm wide
Eight time scales from 0.05s to 10 days
High input/output isolation
Wide supply range (24...240)V AC/DC
35 mm rail (EN 60715) mount
“Blade + cross” - both flat blade and cross
head screw drivers can be used to adjust the
range and function selectors, the timing
trimmer, and to disengage the rail mounting
clip
Multi-voltage versions with “PWM clever”
technology
Wiring diagram
(without control signal)
Multi-voltage
Mono-function
DI: Interval
2
83 Series - Modular timers 16 A
For outline drawing see page 5
3
83.62 83.82 83.91
Multi-voltage
Multi-function
LI: Asymmetrical flasher
(starting pulse on)
LE: Asymmetrical flasher (starting
pulse on) with control signal
PI: Asymmetrical flasher
(starting pulse off)
PE: Asymmetrical flasher (starting
pulse off) with control signal
Wiring diagram
(with control signal)
2 CO (DPDT) 2 NO (DPST-NO) 1 CO (SPDT)
8/15 16/30 16/30
250/400 250/400 250/400
2,000 4,000 4,000
400 750 750
0.3 0.5 0.5
8/0.3/0.12 16/0.3/0.12 16/0.3/0.12
300 (5/5) 300 (5/5) 300 (5/5)
AgNi AgNi AgNi
24...240 24...240 24...240
24...240 24...240 24...240
< 1.5 / < 2 < 1.5 / < 2 < 1.5 / < 2
16.8...265 16.8...265 16.8...265
16.8...265 16.8...265 16.8...265
***
± 1 ± 1 ± 1
200 200 200
500 ms (A1 - A2) 50
± 5 ± 5 ± 5
100·10370·10370·103
–20…+60 –20…+60 –20…+60
IP 20 IP 20 IP 20
Multi-voltage
Mono-function
2 pole
BI: Power off-delay (True off-delay)
Wiring diagram
(without control signal)
Contact specification
Contact configuration
Rated current/Maximum peak current A
Rated voltage/Maximum switching voltage V AC
Rated load AC1 VA
Rated load AC15 (230 V AC) VA
Single phase motor rating (230 V AC) kW
Breaking capacity DC1: 30/110/220 V A
Minimum switching load mW (V/mA)
Standard contact material
Supply specification
Nominal voltage (UN) V AC (50/60 Hz)
V DC
Rated power AC/DC VA (50 Hz)/W
Operating range V AC
V DC
Technical data
Specified time range
Repeatability %
Recovery time ms
Minimum control impulse ms
Setting accuracy-full range %
Electrical life at rated load in AC1 cycles
Ambient temperature range °C
Protection category
Approvals (according to type)
Features
Mono-function and multi-function timer range
83.62 - Power off-delay, multi-voltage, 2 Pole
83.82 - Star-Delta, multi-voltage,
star and delta output contacts
83.91 - Asymmetrical flasher, multi-voltage,
1 Pole
22.5 mm wide
Time scales:
Type 83.62 - 0.05s to 3 minutes
Type 83.82 / 83.91 - 0.05 s to 10 days
Wide supply range (24…240)V AC / DC
35 mm rail (EN 60715) mount
Wiring diagram
(without control signal)
Wiring diagram
(without control signal)
Multi-voltage
Mono-function
2 pole
Transfer time can be
regulated (0.05…1)s ***
SD: Star-delta
83 Series - Modular timers 8 - 16 A
* (0.05…2)s, (1…16)s, (8…70)s, (50…180)s
** (0.05…1)s, (0.5…10)s, (0.05…1)min,
(0.5...10)min, (0.05...1)h, (0.5...10)h,
(0.05...1)d, (0.5...10)d
*** 0.05 s, 0.2 s, 0.3 s, 0.45 s, 0.6 s, 0.75 s,
0.85 s, 1 s
For outline drawing see page 5
Example: 83 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (24…240)V AC/DC.
Versions
0000 = Standard
Supply voltage
240 = (24 ... 240)V AC/DC
Supply version
0 = AC (50/60 Hz)/DC
No. of poles
1 = 1 CO (SPDT)
2 = 2 CO (DPDT) for 83.02 and 83.62
2 = 2 NO (DPST-NO) for 83.82
Series
Type
0 = Multi-function (AI, DI, GI, SW, BE, CE, DE, WD)
1 = On-delay (AI)
2 = Interval (DI)
4 = Off-delay with control signal (BE)
6 = Power off-delay (True off-delay) (BI)
8 = Star-delta (SD)
9 = Asymmetrical flasher (LI, LE, PI, PE)
0 1 0
Ordering information
... .
24083
Insulation
Dielectric strength between input and output circuit V AC 4,000
between open contacts V AC 1,000
Insulation (1.2/50 μs) between input and output kV 6
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radio-frequency electromagnetic field (80 ÷ 1,000 MHz) EN 61000-4-3 10 V/m
(1,000 ÷ 2,700 MHz) EN 61000-4-3 3 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals EN 61000-4-4 6 kV
on control signal terminal (B1) EN 61000-4-4 6 kV
Surges (1.2/50 μs) on Supply terminals common mode EN 61000-4-5 6 kV
differential mode EN 61000-4-5 4 kV
on control signal terminal (B1) common mode EN 61000-4-5 6 kV
differential mode EN 61000-4-5 4 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) EN 61000-4-6 10 V
on Supply terminals (80 ÷ 230 MHz) EN 61000-4-6 10 V
Radiated and conducted emission EN 55022 class B
Other data
Current absorption on control signal (B1) < 1 mA
- max cable length (capacity of 10 nF / 100 m) 150 m
- when applying a control signal to B1, which is B1 is isolated from A1 and A2 by an opto-coupler, and can
different from the supply voltage at A1/A2 therefore be operated at a voltage other than the supply
voltage.
If using a control signal of between (24... 48)V DC
and
a supply voltage of (24...240)V AC, ensure that the signal – is
connected to A2 and the + is applied to B1, and that L is
applied to B1 and N to A2.
External potentiometer for 83.02 Use a 10 kΩ/0,25 W linear potentiometer. Maximum cable
length 10 m. When using an external potentiometer, the timer
automatically use its setting in place of the internal setting.
Consider the voltage potential at the potentiometer to be the
same as the timer supply voltage.
Power lost to the environment without contact current W 1.4
with rated current W 3.2
Screw torque Nm 0.8
Max. wire size solid cable stranded cable
mm2 1x6 / 2x4 1x4 / 2x2.5
AWG 1x10 / 2x12 1x12 / 2x14
Technical data
83 Series - Modular timers 16 A
4
0 0 0 0
83 Series - Modular timers 16 A
5
Outline drawings
83.01
Screw terminal
83.02
Screw terminal
83.11
Screw terminal
83.21
Screw terminal
83.41
Screw terminal
83.62
Screw terminal
83.82
Screw terminal
83.91
Screw terminal
6
NO output
contact
Supply
voltage
LED*
OFF
ON
ON
ON
Open
Open
Open
(Timing in Progress)
Closed
Open
Contacts
Closed
15 - 18 15 - 16
25 - 28 25 - 26
15 - 18 15 - 16
25 - 28 25 - 26
15 - 18 15 - 16
25 - 28 25 - 26
15 - 16 15 - 18
25 - 26 25 - 28
Functions
83 Series - Modular timers 16 A
* The LED on type 83.62 is illuminated when supply voltage is supplied to timer.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
* With DC supply, positive polarity has to be connected to B1 terminal (according to EN 60204-1).
** A voltage other than the supply voltage can be applied to the control signal (B1), example:
A1 - A2 = 230 V AC
B1 - A2 = 12 V DC
*
**
060.72
Accessories
Sheet of marker tags, for types 83.01/11/21/41/62/82, plastic, 72 tags, 6x12 mm 060.72
087.02.2
Z1 Z2
Potentiometer usable as external potentiometer for type 83.02 087.02.2
10 kΩ / 0.25 W linear
7
with control signal
Multi-function
without control signal Type
83.01
83.02
*** Type 83.02: regulated
using an external
potentiometer
(10 kΩ- 0.25 W).
***
***
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
(GI) Pulse delayed.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs after a fixed time of 0.5s.
(SW) Symmetrical flasher (starting pulse on).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ratio is 1:1 (time on = time off).
(BE) Off-delay with control signal.
Power is permenently applied to the timer. The output contacts
transfer immediately on closure of the control signal (S).
Opening the control signal initiates the preset delay, after which
time the output contacts reset.
(CE) On- and off-delay with control signal.
Power is permenently applied to the timer.
Closing the control signal (S) initiates the preset delay, after
which time the output contacts transfer. Opening the control sig-
nal initiates the same preset delay, after which time the
output contacts reset.
(DE) Interval with control signal on.
Power is permenently applied to the timer.
On momentary or maintained closure of control signal (S),
the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset.
(WD) Watchdog (Retriggerable interval with control signal on).
Power is permanently applied to the timer.
On momentary or maintained closure of control signal (S),
the output contacts transfer, and remain so for the duration
of the preset delay, after which they reset; subsequent closures of
control signal during the delay will extend the time. If the closure
of the control signal (S) is longer than the preset time (T) then the
output contacts reset.
Both output contacts (15-18 and 25-28)
follow the timing function
2 timed contacts
1 timed +
1 instantaneous contact
Both output contacts (15-18 and 25-28)
follow the timing function
Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open
Both output contacts [15-18 and 25(21)-28(24)]
stay permanently open
The output contact 15-18 follows the timing function
The output contact 21-24 follows the power supply (U)
The output contact 15-18 follows the timing function
The output contact 21-24 follows the control signal (S)
Wiring diagram
83.01
83.01
83.02
83.02
83 Series - Modular timers 16 A
83.02 type
NOTE: The timing function must be set when the timer is de-energised. Or for the 83.02, when the contact mode selector is in the OFF position.
Contact mode selector Functions without control signal (example: AI) Functions with control signal (example: BE)
Functions
U= Supply voltage S= Signal switch = Output contact
83.91
without control signal
Asymmetrical recycler
without control signal
Mono-function
with control signal (S)
Type
83.11
(AI) On-delay.
Apply power to timer. Output contacts transfer after preset
time has elapsed. Reset occurs when power is removed.
(DI) Interval.
Apply power to timer. Output contacts transfer immediately.
After the preset time has elapsed, contacts reset.
(BI) Power off-delay (True off-delay).
Apply power to timer (minimum 500 ms). Output contacts
transfer immediately. Removal of power initiates the preset
delay, after which time the output contacts reset.
(SD) Star-delta.
Apply power to timer. The star contact ( ) closes immediately.
After preset delay has elapsed the star contact ( ) resets.
After a further time (settable from 0.05s to 1s) the delta
contact ( Δ) closes and remains in that position, until reset on
power off.
(BE) Off-delay with control signal.
Power is permenently applied to the timer.
The output contacts transfer immediately on closure of the
control signal (S). Opening the control signal initiates the
preset delay, after which time the output contacts reset.
(LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
Apply power to timer. Output contacts transfer immediately
and cycle between ON and OFF for as long as power is
applied. The ON and OFF times are independently
adjustable.
(PI) Asymmetrical flasher (starting pulse off) - (Z1-Z2 linked).
Apply power to timer. Output contacts transfer after time T1
has elapsed and cycle between OFF and ON for as long as
power is applied. The ON and OFF times are independently
adjustable.
(LE) Asymmetrical flasher (starting pulse on) with control
signal - (Z1-Z2 open).
Power is permenently applied to the timer.
Closing control signal (S) causes the output contacts to
transfer immediately and cycle between ON and OFF,
until opened.
(PE) Asymmetrical flasher (starting pulse off) with control
signal - (Z1-Z2 linked).
Power is permenently applied to the timer.
Closing the control signal (S) initiates delay T1 after which the
output contacts transfer and continue to cycle between OFF
and ON, until the control signal is opened.
83.11
83.21
83.82
83.41
83.91
Z1-Z2 open: (LI) function
Z1-Z2 linked: (PI) function
Z1-Z2 open: (LE) function
Z1-Z2 linked: (PE) function
83.91
Wiring diagram
Functions
83 Series - Modular timers 16 A
83.62
83.21
83.82
83.41
83.62
8
with control signal
U= Supply voltage S= Signal switch = Output contact