Example: 83 series, modular timers, 1 CO (SPDT) - 16 A, supply rated at (24…240)V AC/DC.
Versions
0000 = Standard
Supply voltage
240 = (24 ... 240)V AC/DC
Supply version
0 = AC (50/60 Hz)/DC
No. of poles
1 = 1 CO (SPDT)
2 = 2 CO (DPDT) for 83.02 and 83.62
2 = 2 NO (DPST-NO) for 83.82
Series
Type
0 = Multi-function (AI, DI, GI, SW, BE, CE, DE, WD)
1 = On-delay (AI)
2 = Interval (DI)
4 = Off-delay with control signal (BE)
6 = Power off-delay (True off-delay) (BI)
8 = Star-delta (SD)
9 = Asymmetrical flasher (LI, LE, PI, PE)
0 1 0
Ordering information
... .
24083
Insulation
Dielectric strength between input and output circuit V AC 4,000
between open contacts V AC 1,000
Insulation (1.2/50 μs) between input and output kV 6
EMC specifications
Type of test Reference standard
Electrostatic discharge contact discharge EN 61000-4-2 4 kV
air discharge EN 61000-4-2 8 kV
Radio-frequency electromagnetic field (80 ÷ 1,000 MHz) EN 61000-4-3 10 V/m
(1,000 ÷ 2,700 MHz) EN 61000-4-3 3 V/m
Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals EN 61000-4-4 6 kV
on control signal terminal (B1) EN 61000-4-4 6 kV
Surges (1.2/50 μs) on Supply terminals common mode EN 61000-4-5 6 kV
differential mode EN 61000-4-5 4 kV
on control signal terminal (B1) common mode EN 61000-4-5 6 kV
differential mode EN 61000-4-5 4 kV
Radio-frequency common mode (0.15 ÷ 80 MHz) EN 61000-4-6 10 V
on Supply terminals (80 ÷ 230 MHz) EN 61000-4-6 10 V
Radiated and conducted emission EN 55022 class B
Other data
Current absorption on control signal (B1) < 1 mA
- max cable length (capacity of ≤ 10 nF / 100 m) 150 m
- when applying a control signal to B1, which is B1 is isolated from A1 and A2 by an opto-coupler, and can
different from the supply voltage at A1/A2 therefore be operated at a voltage other than the supply
voltage.
If using a control signal of between (24... 48)V DC
and
a supply voltage of (24...240)V AC, ensure that the signal – is
connected to A2 and the + is applied to B1, and that L is
applied to B1 and N to A2.
External potentiometer for 83.02 Use a 10 kΩ/≥ 0,25 W linear potentiometer. Maximum cable
length 10 m. When using an external potentiometer, the timer
automatically use its setting in place of the internal setting.
Consider the voltage potential at the potentiometer to be the
same as the timer supply voltage.
Power lost to the environment without contact current W 1.4
with rated current W 3.2
Screw torque Nm 0.8
Max. wire size solid cable stranded cable
mm2 1x6 / 2x4 1x4 / 2x2.5
AWG 1x10 / 2x12 1x12 / 2x14
Technical data
83 Series - Modular timers 16 A
4
0 0 0 0