Instruction Sheet
SL, KL, and Secure SL Series 408-8417
LOC B
1
of 2
E
2007 Tyco Electronics Corporation, Harrisburg, PA
All International Rights Reserved
TE logo, AMP NETCONNECT, and Tyco Electronics are trademarks.
*Trademark. Other products, logos, and company names used are the property of their respective owners.
TOOLING ASSISTANCE CENTER 1-800-722-1111
PRODUCT INFORMATION 1-800-522-6752 This controlled document is subject to change.
For latest revision and Regional Customer Service,
visit our website at
www.tycoelectronics.com
16 OCT 07 Rev L
110Connect Modular Jacks
Figure 1
Universal Wiring
Label
Optional Bend-
Limiting Strain Relief
1375200-1 (Cat 6)
1375200-2 (Cat 5e)
(See Figure 3)
SL Series 110Connect
Modular Jack (shown
)
To obtain information on AMP NETCONNECT products, call
PRODUCT INFORMATION at the number at the bottom of this
page, or visit the AMP NETCONNECT website at
www.ampnetconnect.com
.
1. INTRODUCTION
(Figure 1)
This instruction sheet provides termination
procedures for the SL Series 110Connect (Cat 3,
Cat 5e, and Cat 6) modular jacks; the KL Series
110Connect (Cat 5e and Cat 6) modular jacks; and
Secure SL Series 110Connect (Cat 6) modular jacks.
All dimensions are in millimeters [with inches in
brackets]. Figures and illustrations are for
reference only and are not drawn to scale.
Reasons for reissue of this sheet are provided in
Section 4, REVISION SUMMARY.
2. DESCRIPTION
The jacks accept four pair, twisted–pair cable with 22
through 24 AWG solid conductors and 24 AWG
stranded conductors. The maximum conductor
insulation diameter is 1.45 mm [.057 in.].
3. TERMINATION
1. Strip back only as much cable jacket as
necessary to perform termination. See Figure 2.
Generally, a strip length of 50.8 mm [2.00 in. ]
maximum will meet the needs of most
applications, depending on method of
termination.
If using the optional bend-limiting strain relief,
slide it over cable jacket as shown in Figure 2.
Figure 2
50.8
[2.00]
Optional Bend-Limiting Strain
Relief 1375200-1 or -2 (See
Figure 3)
Keep wire pairs twisted to within 75 mm
[3 in.] of termination for Cat 3 jacks, or
12.7 mm [.50 in.] for CAT 5e Jacks, or 6.0 mm
[.24 in.] for CAT 6 Jacks.
2. Align and lace a color–coded wire pair with the
appropriate slots as indicated by the color coding
on the wiring label (use minimum slack while
maintaining twist, as indicated in Figure 3).
Wire termination requires the use of Impact Tool
1583608-1 or SL Jack Termination Tool
1725150-1. Refer to 408-8858 for SL Jack
Termination Tool instructions.
Set impact setting for low-impact. Orient tool so
cutoff blade is on outside of block and vertical.
3. Use tool to punch wires down into slot and cut
off excess wire. Remove loose wire pieces.
4. Repeat Steps 2 and 3 with all wire pairs.
5. Slide bend–limiting strain relief (if used) onto
jack. Latches on strain relief will engage tabs on
rear of jack as indicated in Figure 3.
4. REVISION SUMMARY
S
New format
S
Deleted old and superceded part numbers in
NOTE in Paragraph 3.2 and Figure 3
NOTE
i
NOTE
i
NOTE
i
NOTE
i
NOTE
i
CAUTION
!
408-8417
SL, KL, and Secure SL Series 110Connect Modular Jacks
Rev
L2
of 2 Tyco Electronics Corporation
Figure 3
Four-Pair Color-Coded Universal Wiring Label
T568B
Color Pattern
Wires Cut Off
Insertion Blade
Cutoff Blade
Impact Tool
1583608-1
Latches on Strain Relief
Engage Tabs on Jack
T568A
Color Pattern
Keep Wires Twisted to
Within 12.7 mm [.50 in.] of
Termination for CAT 5e
Jacks or 6.0 mm [.24 in.] of
Termination for CAT 6
Jacks
Three-Pair Color-Coded Wiring Label
Keep Wires Twisted to
Within 75 mm [3 in.]
of Termination for
CAT 3 Jacks
Wires Cut Off
40.97
[1.613]
Where Space is Limited,
Strain Relief 1375157-1
May be Used as Shown
31.47
[1.239]
SL Series 110Connect
Modular Jack (shown)