Rev. 06.14.12_85
ADN-C Series
1 of 3
313
process
yellow
3405
1797
1375
116
2607
652
242
2985
375
240
Embedded Power for
Business-Critical Continuity
ADN-C Series
120 - 480 Watts
• Slim form factor
• Five year warranty
• High Efficiency > 90% Typ.
• Full Power at 60 °C
• Power Boost ™
• Industrial Grade Design
• Metal mounting clip
• Metal case
• MTBF > 450,000h demonstrated
at 40 °C
• Active PFC > 0.92
• Adjustable output
• Overvoltage protection with
autorecovery
• Continuous short circuit and
overload protection
• SEMI F47 Sag Immunity
• New visual diagnostic LED
• 3 Status LEDs
• Input
• Output
• Alarm
• DC OK Relay
• Parallel Operation Capability
• Screw terminal connections
• RoHS Compliant
• No tools required for mounting
Total Power: 120-480 Watts
Input Voltage: 85-264 Vac,
90-375 Vdc
# of Outputs: Single
Electrical Specifications
Safety
Input
AC Input ra nge: Nominal: 115 - 230 Vac
85 - 264 Vac
DC Input range: 90-375 Vdc
Frequency: 47-67 Hz, 400 Hz
Efficiency: > 90%
Inrush current (typical): < 15A or < 30A depending on model
PFC: Active, better than 0.92
Output
Nominal voltage: ADN5-24-1PM-C & ADN10-24-1PM-C: 24 Vdc (22.5 - 28.5 Vdc Adj)
ADN20-24-1PM-C: 24 Vdc (24-28 Vdc Adj)
Initial Voltage Setting: 24.5 V ± 1%
Hold-up time: > 20 ms at full load (100 Vac Input @ Tamb = +25 °C)
Voltage regulation: < ± 2% (combination line, load, time and temperature related
changes)
Ripple: ADN5-24-1PM-C & ADN10-24-1PM-C: < 50 mVpp
ADN20-24-1PM-C: < 100 mVpp
Back EMF immunity: < 35 Vdc
Power Boost™: 1.5 x Nominal current for 2 or 4 seconds depending on model
Short circuit current: 1.5 x Nominal current at near zero volts at short circuit condition
Parallel operation: Switch selectable single unit or parallel unit operation. Units will not be dam-
aged by parallel operation (regardless of switch position
setting)
Ouput Noise suppression: Radiated EMI values below EN61000-6-2
Overvoltage protection: > 30.5 Vdc but < 33 Vdc, auto recovery
Line and Load regulation: < 0.5%
Time and Temperature Drift: < 1%
• UL508, cULus Listed
• UL 60950-1, cURus
• IEC60950-1
• Class I, Div 2 Hazardous Locations
• ATEX Certified on selected models
• IP20
• CE
Special Features
New Slim
Form Factor