Modular DIN rail components
Installation contactors
Technical catalogue
ABB | 1
Overview ...................................................................................................................................... 2
ESB Installation Contactors
20 A / AC-1/AC-7a ESB20 .................................................................................................... 4
24 A / AC-1/AC-7a ESB24 .................................................................................................... 5
40 A / AC-1/AC-7a ESB40 .................................................................................................... 6
63 A / AC-1/AC-7a ESB63 .................................................................................................... 7
Main Technical Data ................................................................................................................... 8
Lighting application .................................................................................................................. 13
EN Installation Contactors - Manually/Automatic Operated
20 A / AC-1/AC-7a EN20 ................................................................................................... 14
24 A / AC-1/AC-7a EN24 .................................................................................................... 15
40 A / AC-1/AC-7a EN40 .................................................................................................... 16
Main Technical Data ................................................................................................................. 17
ESB/EN Installation Contactors
Main Accessories ..................................................................................................................... 19
Index .......................................................................................................................................... 20
1SBC103011S0201
Installation Contactors
Modular DIN rail components
Installation Contactors ESB and EN
Typical segments
All over the world, commercial and industrial buildings such
as hospitals, hotels, shopping and sport centers, domestic
and residential installation are equipped with ABB low voltage
products and systems.
From switchboard to light switch, ABB covers the complete
range of equipment required for controlling and protecting
electrical installations.
1-2 Residential installations | 3 Hotels
21 3
2 | ABB
For controlling and remote switching, ABB offers a complete range
of installation contactors that are mainly used in the following
applications:
s Lighting
s Heating
s Ventilation
s Pumps and motors.
ESB and EN installation contactors are designed to match the
Modular DIN rail components for common use in dedicated panels.
The ESB range includes 4 ratings from 20 A to 63 A with
2 to 4-pole version.
The EN range includes 3 ratings from 20 A to 40 A.
Many contacts variations are available for managing all application.
Products comply with standards IEC60947-4-1 and IEC61095.
Construction:
The ESB20, EN20 operates with an AC solenoid system.
Types ESB24...63, EN24...40 are fitted with a DC solenoid actuator
and are therefore hum-free. The noise during switching is barely
audible making it beneficial for use in buildings such as hospitals,
hotels or houses. An incorporated varistor protects the coil against
remote lightning strikes and overvoltages up to 5 kV.
In addition, it limits the interference voltage peaks of the solenoid
system.
4 Shopping centers | 5 Hospitals | 6 Commercial & industrial buildings
56
The contactors can therefore be combined with programmable
logic controllers. There is no need for a protective circuit. The
solenoid system is provided with radio interference suppression.
Accessories are available, such as auxiliary contacts and sealing
covers.
ESB advantages:
s Powerful for lamp switching
s Operation flag indicator
s DC coil: - Noiseless and hum free
- Low power consumption
- Integrated overvoltage protection.
The EN contactors have a built-in toggle switch for automatic and
manual operation.
EN advantages:
s Facilitate commissioning
s Functional test before start-up
s Ease maintenance operation
s High degree of safety and availability in case of automation
system failure.
4
ABB | 3
4 | ABB
1SBC103001S0201
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 50 Hz 60 Hz pieces kg (1 pce)
3
4
1
2
A1
A2
1 12 V 14 V ESB20-20 GHE3211102R1004 10 0.14
20 V 24 V GHE3211102R1005 10 0.14
24 V 28 V GHE3211102R0001 10 0.14
42 V 48 V GHE3211102R0002 10 0.14
2 N.O. 48 V 55 V GHE3211102R0003 10 0.14
110 V 125...127 V GHE3211102R0004 10 0.14
230 V 264 V GHE3211102R0006 10 0.14
240 V 278 V GHE3211102R0005 10 0.14
400 V - GHE3211102R0007 10 0.14
R3
R4
R1
R2
A1
A2
1 12 V 14 V ESB20-02 GHE3211202R1004 10 0.14
20 V 24 V GHE3211202R1005 10 0.14
24 V 28 V GHE3211202R0001 10 0.14
42 V 48 V GHE3211202R0002 10 0.14
2 N.C. 48 V 55 V GHE3211202R0003 10 0.14
110 V 125...127 V GHE3211202R0004 10 0.14
230 V 264 V GHE3211202R0006 10 0.14
240 V 278 V GHE3211202R0005 10 0.14
400 V - GHE3211202R0007 10 0.14
1
2
A1
A2
R3
R4
1 12 V 14 V ESB20-11 GHE3211302R1004 10 0.14
20 V 24 V GHE3211302R1005 10 0.14
24 V 28 V GHE3211302R0001 10 0.14
42 V 48 V GHE3211302R0002 10 0.14
1 N.O. 48 V 55 V GHE3211302R0003 10 0.14
1 N.C. 110 V 125...127 V GHE3211302R0004 10 0.14
230 V 264 V GHE3211302R0006 10 0.14
240 V 278 V GHE3211302R0005 10 0.14
400 V - GHE3211302R0007 10 0.14
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue250 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 20 A
AC-3 / AC-7b Ratings (for air temperature close to contactor θ ≤ 55°C)
Rated operational power 1 phase 230 V 1.1 kW
Ie Rated operational current 1 phase 230 V 9 A
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 8 VA / 5 W
Average holding coil consumption value 3.2 VA / 1.2 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 10 mm
2 x
1.5 … 4 mm
Coil terminals Rigid 1 x 0.5 … 4 mm
2 x
0.75 … 2.5 mm
ESB20 Installation Contactors
AC Operated
Application
The ESB contactors are used mainly in buildings for
switching and controlling lighting, heating, ventilation and
pumps. They are part of the complete range of Din rail
products and can be integrated easily in dedicated panels.
Description
The ESB20 contactors are used for the control of single phase loads up to 20 A.
They operate with an AC coil.
You can choose between a various N.O. and N.C. contacts combination.
20 A
AC-1/AC-7a
Dimensions: mm, inches
1SBC103001S0201
Certifications and Approvals
UL
CSA
CCC RMRS BV CE
17.5 0.69"
85 3.35"
45 1.77"
6.8 0.68"
1.1 0.43"
59 2.32"
35 mm
EN/IEC 60175
43.5 1.71"
Mounting positions
Pos. 1, 3, 4, 1± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
ABB | 5
36 1.42"
90 3.54"
45 1.77"
59 2.32"
6.8 0.68"
1.1 0.43"
35 mm
EN/IEC 60175
43.5 1.71"
Application
The ESB contactors are used mainly in buildings for switch-
ing and controlling lighting, heating, ventilation and pumps.
They are part of the complete range of Din rail products and
can be integrated easily in dedicated panels.
Description
The ESB24 contactors are used for the control of single and three-phases loads up to 24 A.
Due to their DC solenoid actuator, the ESB24 can be connected to AC or DC voltages.
This provides the following benets:
Hum-free operating system, no vibration, silent in operation, low power consumption, integrated high overvoltage
protection 5 kV. You can choose between a various N.O. and N.C. contacts combination.
Main accessories:
Auxiliary contact blocks EH04.
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 40... 450 Hz DC pieces kg (1 pce)
3
4
1
2
5
6
7
8
A1
A2
2 12 V 12 V ESB24-40 GHE3291102R1004 5 0.28
24 V 24 V GHE3291102R0001 5 0.28
42 V 42 V GHE3291102R0002 5 0.28
48 V 48 V GHE3291102R0003 5 0.28
4 N.O. 110...120 V 110...120 V GHE3291102R0004 5 0.28
230...240 V 230...240 V GHE3291102R0006 5 0.28
400...415 V 400...415 V GHE3291102R0007 5 0.28
R3
R4
R1
R2
R5
R6
R7
R8
A1
A2
2 12 V 12 V ESB24-04 GHE3291202R1004 5 0.28
24 V 24 V GHE3291202R0001 5 0.28
42 V 42 V GHE3291202R0002 5 0.28
48 V 48 V GHE3291202R0003 5 0.28
4 N.C. 110...120 V 110...120 V GHE3291202R0004 5 0.28
230...240V 230...240V GHE3291202R0006 5 0.28
400...415 V 400...415 V GHE3291202R0007 5 0.28
R3
R4
1
2
A1
A2
7
8
R5
R6
2 12 V 12 V ESB24-22 GHE3291302R1004 5 0.28
24 V 24 V GHE3291302R0001 5 0.28
42 V 42 V GHE3291302R0002 5 0.28
48 V 48 V GHE3291302R0003 5 0.28
2 N.O. 110...120 V 110...120 V GHE3291302R0004 5 0.28
2 N.C. 230...240 V 230...240 V GHE3291302R0006 5 0.28
400...415 V 400...415 V GHE3291302R0007 5 0.28
R3
R4
1
2
A1
A2
5
6
7
8
2 12 V 12 V ESB24-31 GHE3291602R1004 5 0.28
24 V 24 V GHE3291602R0001 5 0.28
42 V 42 V GHE3291602R0002 5 0.28
48 V 48 V GHE3291602R0003 5 0.28
3 N.O. 110...120 V 110...120 V GHE3291602R0004 5 0.28
1 N.C. 230...240 V 230...240 V GHE3291602R0006 5 0.28
400 ...415 V 400 ...415 V GHE3291602R0007 5 0.28
3
4
R1
R2
A1
A2
R5
R6
R7
R8
2 12 V 12 V ESB24-13 GHE3291702R1004 5 0.28
24 V 24 V GHE3291702R0001 5 0.28
42 V 42 V GHE3291702R0002 5 0.28
48 V 48 V GHE3291702R0003 5 0.28
1 N.O. 110...120 V 110...120 V GHE3291702R0004 5 0.28
3 N.C. 230...240 V 230...240 V GHE3291702R0006 5 0.28
400 ... 415 V 400 ... 415 V GHE3291702R0007 5 0.28
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue400 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 24 A
AC-3 / AC-7b Ratings (for air temperature close to contactor θ ≤ 55°C)
Rated operational power 3 phases 400 V 4 kW
Ie Rated operational current 3 phases 400 V 9 A
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 4 VA / 4 W
Average holding coil consumption value 4 VA / 4 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 10 mm
2 x
1.5 … 4 mm
Coil terminals Rigid 1 x 1 … 4 mm
2 x
0.75 … 2.5 mm
ESB24 Installation Contactors
AC / DC Operated
Mounting positions
Pos. 1, 3, 4, 1± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
24 A
AC-1/AC-7a
Dimensions: mm, inches
1SBC103002S0201
Certifications and Approvals
UL
CSA
CCC RMRS BV GL DNV CE
LRS
6 | ABB
Application
The ESB contactors are used mainly in buildings for switch-
ing and controlling lighting, heating, ventilation and pumps.
They are part of the complete range of Din rail products and
can be integrated easily in dedicated panels.
Description
The ESB40 contactors are used for the control of single and three-phases loads up to 40 A.
Due to their DC solenoid actuator, the ESB40 can be connected to AC or DC voltages.
This provides the following benets:
Hum-free operating system, no vibration, silent in operation, low power consumption, integrated high overvoltage
protection 5 kV. You can choose between a various N.O. and N.C. contacts combination.
Main accessories:
Auxiliary contact blocks EH04.
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 40... 450 Hz DC pieces kg (1 pce)
3
4
1
2
5
6
7
8
A1
A2
3 12 V 12 V ESB40-40 GHE3491102R1004 3 0.40
24 V 24 V GHE3491102R0001 3 0.40
42 V 42 V GHE3491102R0002 3 0.40
48 V 48 V GHE3491102R0003 3 0.40
4 N.O. 110...120 V 110...120 V GHE3491102R0004 3 0.40
230...240 V 230...240 V GHE3491102R0006 3 0.40
400...415 V 400...415 V GHE3491102R0007 3 0.40
415 V 415 V GHE3491102R0008 3 0.40
R3
R4
1
2
A1
A2
7
8
R5
R6
3 24 V 24 V ESB40-22 GHE3491302R0001 3 0.40
230 V 230 V GHE3491302R0006 3 0.40
2 N.O.
2 N.C.
R3
R4
1
2
A1
A2
5
6
7
8
3 24 V 24 V ESB40-31 GHE3491602R0001 3 0.40
230 V 230 V GHE3491602R0006 3 0.40
3 N.O.
1 N.C.
3
4
1
2
5
6
A1
A2
3 24 V 24 V ESB40-30 GHE3491502R0001 3 0.39
230 V 230 V GHE3491502R0006 3 0.39
400 V 400 V GHE3491502R0007 3 0.39
3 N.O.
3
4
1
2
A1
A2
3 24 V 24 V ESB40-20 GHE3491402R0001 3 0.38
230 V 230 V GHE3491402R0006 3 0.38
2 N.O.
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue400 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 40 A
AC-3 / AC-7b Ratings (for 1500 r.p.m., 50 Hz or 1800 r.p.m., 60 Hz, 3-phase motors)
(for air temperature close to contactor θ ≤ 55°C)
Rated operational power 3 phases 400 V 11 kW
Ie Max. Rated operational current 3 phases 400 V 22 A
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 5 VA / 5 W
Average holding coil consumption value 5 VA / 5 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 25 mm
2 x
1.5 … 10 mm
Coil terminals Rigid 1 x 1 … 4 mm
2 x
0.75 … 2.5 mm
ESB40 Installation Contactors
AC / DC Operated
Mounting positions
40 A
AC-1/AC-7a
Dimensions: mm, inches
Pos. 1, 3, 4, 1 ± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
1SBC103003S0201
Certifications and Approvals
UL
CSA
CCC RMRS BV GL DNV CE
LRS
54 2.13"
90 3.54"
45 1.77"
59 2.32"
6.8 0.68"
1.1 0.43"
35 mm
EN/IEC 60175
43.5 1.71"
Certifications and Approvals
UL
CSA
CCC RMRS BV GL DNV CE
LRS
ABB | 7
1SBC103004S0201
Application
The ESB contactors are used mainly in buildings for switch-
ing and controlling lighting, heating, ventilation and pumps.
They are part of the complete range of Din rail products and
can be integrated easily in dedicated panels.
Description
The ESB63 contactors are used for the control of single and three-phases loads up to 63 A.
Due to their DC solenoid actuator, the ESB63 can be connected to AC or DC voltages.
This provides the following benets:
Hum-free operating system, no vibration, silent in operation, low power consumption, integrated high overvoltage
protection 5 kV. You can choose between a various N.O. and N.C. contacts combination.
Main accessories:
Auxiliary contact blocks EH04.
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 40... 450 Hz DC pieces kg (1 pce)
3
4
1
2
5
6
7
8
A1
A2
3 12 V 12 V ESB63-40 GHE3691102R1004 3 0.42
24 V 24 V GHE3691102R0001 3 0.42
42 V 42 V GHE3691102R0002 3 0.42
48 V 48 V GHE3691102R0003 3 0.42
4 N.O. 110...120 V 110...120 V GHE3691102R0004 3 0.42
230...240 V 230...240 V GHE3691102R0006 3 0.42
400...415 V 400...415 V GHE3691102R0007 3 0.42
415 V 415 V GHE3691102R0008 3 0.42
R3
R4
1
2
A1
A2
7
8
R5
R6
3 400 V 400 V ESB63-22 GHE3691302R0007 3 0.42
2 N.O. 2 N.C.
R3
R4
1
2
A1
A2
5
6
7
8
3 110 V 110 V ESB63-31 GHE3691602R0004 3 0.42
230 V 230 V GHE3691602R0006 3 0.42
3 N.O. 1 N.C.
3
4
1
2
5
6
A1
A2
3 230 V 230 V ESB63-30 GHE3691502R0006 3 0.41
400 V 400 V GHE3691502R0007 3 0.41
3 N.O.
3
4
1
2
A1
A2
3 24 V 24 V ESB63-20 GHE3691402R0001 3 0.40
230 V 230 V GHE3691402R0006 3 0.40
2 N.O.
R3
R4
1
2
A1
A2
3 230 V 230 V ESB63-11 GHE3691802R0006 3 0.40
1 N.O. 1 N.C.
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue400 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 63 A
AC-3 / AC-7b Ratings (for 1500 r.p.m., 50 Hz or 1800 r.p.m., 60 Hz, 3-phase motors)
(for air temperature close to contactor θ ≤ 55°C)
Rated operational power 3 phases 400 V 15 kW
Ie Max. rated operational current 3 phases 400 V 30 A
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 65 VA / 65 W
Average holding coil consumption value 4.2 VA / 4.2 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 25 mm
2 x
1.5 … 10 mm
Coil terminals Rigid 1 x 1 … 4 mm
2 x
0.75 … 2.5 mm
ESB63 Installation Contactors
AC / DC Operated
Mounting positions
63 A
AC-1/AC-7a
Dimensions: mm, inches
Pos. 1, 3, 4, 1 ± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
54 2.13"
90 3.54"
45 1.77"
59 2.32"
6.8 0.68"
1.1 0.43"
35 mm
EN/IEC 60175
43.5 1.71"
8 | ABB
1SBC103005S0201
ESB Installation Contactors
Technical Data
Main Pole - Utilization Characteristics according to IEC
Contactor types: AC operated ESB20
AC / DC operated ESB24 ESB40 ESB63
Rated operational voltage Ue max. V AC: 250, DC: 220 AC: 400, DC: 220
Rated frequency limits Hz 50/60, DC
Utilization category AC-1 / AC-7a
for air temperature close to contactor < 55 °C
Max. rated operational current Ie AC-1 / AC-7a
N.O.
A20 24 40 63
N.C.
A20 24 30 30
Utilization category AC-3 / AC-7b
for air temperature close to contactor < 55 °C
Max. rated operational current Ie AC-3/AC-7b
230 V - 1 phase
N.O.
A9 9 22 30
400 V - 3 phases
N.O.
A- 9 22 30
Rated operational power AC-3
230 V - 1 phase kW 1.1 1.3 3.7 5
400 V - 3 phases kW - 4 11 15
Rated making capacity AC-3 10 x Ie / AC-3
Rated breaking capacity AC-3 8 x Ie / AC-3
Short-circuit protection for contactors
gG type fuse A20 35 63 80
Rated short-time withstand current Icw
at 40 °C ambient temp.,
in free air, from a cold state 10 s A72 176 240
Heat dissipation per pole Ie / AC-1/AC-7a W1 346
Max. electrical switching frequency
– for AC-1 / AC-7a cycles/h 300
– for AC-3 / AC-7b cycles/h 600
Electrical durability
– for AC-1 / AC-7a cycles 150000 150000 150000 150000
– for AC-3 / AC-7b cycles 150000 500000 170000 240000
Mechanical durability
– millions of operating cycles 1
Single-phase (AC-1, AC-7a)
Single-phase (AC-7b)
Three-phase (AC-1, AC-7a)
Three-phase (AC-7b, AC-3)
U
UU
W
U
M
L1
L3
V
L2
U
V
U
M
L1
L2
ABB | 9
1SBC103005S0201
Main Pole - Utilization Characteristics according to UL/CSA
Contactor types: AC operated ESB20
AC / DC operated ESB24 ESB40 ESB63
General use rating
Amp rating 240 V A20---
480 V A- 244063
Motor rating
Amp rating
120 V - 1 phase A9.8 - - -
240 V - 1 phase
N.O.
A9.8 9.6 22 28
N.C.
A8 9.6 22 30
440 - 480 V - 3 phases
N.O.
A - 7.6 21 21
N.C.
A3.4 - -
Motor power
120 V - 1 phase hp 1/2 - - -
240 V - 1 phase hp 1 3 7.5 10
440 - 480 V - 3 phases hp - 5 15 15
Short-circuit protection for contactors without thermal
O/L relay - Motor protection excluded
Fuse rating, 480 V A25 25 / K5 40 / K5 75 / K5
Fuse type, 600 V - ---
Max. electrical switching frequency
– for general use cycles/h 300
– for motor use cycles/h 600
General Technical Data
Rated insulation voltage Ui
according to IEC 60947-4-1 V400 500
according to UL/CSA V240 600
Rated impulse withstand voltage Uimp kV 6
Standards IEC 60947-4-1 / EN 60947-4-1 and IEC 61095 / EN 61095, UL 508, CSA C22.2 N°14-05
Air temperature close to contactor
– for operation at 0.85 ... 1.1 Uc°C -25 ... +55 (Type ESB24...63: for ambient temperature > 40°C, add ESB-DIS (1/2 module) at every second contactor)
– for storage °C -40 ... +80
Climatic withstand IEC 60068-2-30, UTE 63-100 execution 1*
Operating altitude m ≤ 2000
Shock withstand 10 g / 4 ms / axes X Y Z
Mounting positions
Pos 1, 3, 4, 1±30°
Pos 5 : not allowed for ESB20
Pos. 1/3/4/1± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
Fixing
on rail acc. to IEC 60715 and EN 60715 35 x 7.5 35 x 15
* ESB20 only
ESB Installation Contactors
Technical Data
10 | ABB
1SBC103005S0201
ESB Installation Contactors
Technical Data
Magnet System Characteristics
Contactor types: AC operated ESB20
AC / DC operated ESB24 ESB40 ESB63
Rated operational voltage Ue max.
- at 50 Hz V12 ... 400 12 ... 415 24 ... 415
- at 60 Hz V14 ... 380 12 ... 415 24 ... 415
- at 400 Hz
V- 12 ... 415 24 ... 415
DC V- 12 ... 415 24 ... 415
Coil operating limits acc. to IEC 60947-4-1 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Drop-out voltage in % of Ucapprox. 20 ... 75 % approx. 10 ... 75 %
Frequency range Hz 50/60 DC, 50 ... 400
Coil consumption
Average pull-in value VA / W 8 / 5 4 / 4 5 / 5 65 / 65
Average holding value VA / W 3.2 / 1.2 4 / 4 5 / 5 4.2 / 4.2
Operating time
between coil energization and:
– N.O. contact closing ms 12 40
between coil de-energization and:
– N.O. contact opening ms 12 40
Connecting Characteristics
Contactor types: AC operated ESB20
AC / DC operated ESB24 ESB40 ESB63
Connecting capacity (min. ... max.)
Main pole terminals
Rigid 1 x mm² 1.5 ... 10 1.5 ... 25
2 x mm² 1.5 ... 4 1.5 ... 10
Capacity acc. to UL/CSA AWG 14-8 16-8 16-4
Coil terminals
Rigid 1 x mm² 0.5 ... 4 1 ... 4
2 x mm² 0.75 ... 2.5
Capacity acc. to UL/CSA AWG 18-14 16-10
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Protection against direct contact in acc. with EN 50274
All terminals IP20
Screwdriver type
Main poles Flat Ø 5 / Pozidriv 1 Flat Ø 7.5 / Pozidriv 2
Coil terminals Flat Ø 5 / Pozidriv 1 Flat Ø 5 / Pozidriv 1
Stripping length
Main poles mm 10 13
Coil terminals mm 7
Tightening torque
Main poles Nm 1.2 1 2.5
Coil terminals Nm 0.9
ABB | 11
1SBC103005S0201
ESB Installation Contactors
Technical Data
EH04... Auxiliary Contact Block - Utilization Characteristics according to IEC
Contactor types: AC operated ESB20
AC / DC operated ESB24 ESB40 ESB63
Rated operational voltage Ue max. V - 500
Conventional free air thermal current Ith
θ < 40 °C A-6
Rated frequency limits Hz - 50/60
Rated operational current Ie / AC-15
acc. to IEC 60947-5-1 240 V 50/60 Hz A-4
415 V 50/60 Hz A-3
500 V 50/60 Hz A-2
Making capacity acc. to IEC 60947-5-1 - 11 x Ie AC-15
Breaking capacity acc. to IEC 60947-5-1 - 11 x Ie AC-15
Short-circuit protection gI type fuse A-10
Minimum switching capacity
with failure rate acc. to IEC 60947-5-4 V/mA -17 / 5
Heat dissipation per pole at 6 A W - 0.1
Electrical durability
AC-1 / 400 V / 3-phase for ESB20...63
80101 6350403024161,5 2 3 4 5 6 8
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
Millions of operating cycles
Breaking current [A]
ESB24
ESB40
ESB63
ESB20
20
AC-3 / 400 V / 3-phase for ESB24...63
801016350403024161.5
2.21.1 3 4 7.5 11 15
234568
0.01
0.1
1
2
0.02
0.03
0.04
0.05
0.06
0.08
0.2
0.3
0.4
0.5
0.6
0.8
Millions of operating cycles
Breaking current [A]
Switching capacity [kW]
ESB24
ESB40
ESB63
12 | ABB
1SBC103005S0201
DC-1/DC-3 switching DC with N.O. contacts (N.O.)
DC-1 (L/R ≤ 1 ms) DC-3 (L/R ≤ 2 ms)
Type Rated operating
voltage Ue
1 current path 2 current paths
in series
3 current paths
in series
1 current path 2 current paths
in series
3 current paths
in series
ESB20-20 24 V DC 20 A 20 A - 15 A 20 A -
48 V DC 15 A 20 A - 7 A 15 A -
60 V DC 15 A 20 A - 5 A 10 A -
110 V DC 5 A 15 A - 1.5 A 5 A -
220 V DC 0.5 A 5 A - 0.2 A 1.5 A -
ESB24 24 V DC 24.0 A 24.0 A 24.0 A 16.0 A 24.0 A 24.0 A
48 V DC 21.0 A 24.0 A 24.0 A 8.0 A 18.0 A 24.0 A
60 V DC 17.0 A 24.0 A 24.0 A 4.0 A 14.0 A 24.0 A
110 V DC 7.0 A 16.0 A 24.0 A 1.6 A 6.5 A 16.0 A
220 V DC 0.9 A 4.5 A 13.0 A 0.2 A 1.0 A 4.0 A
ESB40 24 V DC 40.0 A 40.0 A 40.0 A 19.0 A 40.0 A 40.0 A
48 V DC 23.0 A 40.0 A 40.0 A 10.0 A 20.0 A 40.0 A
60 V DC 18.0 A 32.0 A 40.0 A 5.0 A 16.0 A 34.0 A
110 V DC 8.0 A 17.0 A 30.0 A 1.8 A 7.0 A 18.0 A
220 V DC 1.0 A 5.0 A 15.0 A 0.3 A 1.1 A 4.5 A
ESB63 24 V DC 50.0 A 63.0 A 63.0 A 21.0 A 44.0 A 63.0 A
48 V DC 25.0 A 43.0 A 63.0 A 11.0 A 22.0 A 47.0 A
60 V DC 20.0 A 35.0 A 60.0 A 5.5 A 18.0 A 38.0 A
110 V DC 9.0 A 19.0 A 33.0 A 2.0 A 8.0 A 21.0 A
220 V DC 1.1 A 5.5 A 17.0 A 0.3 A 1.2 A 5.0 A
DC-1/DC-3 switching DC with N.C. contacts (N.C.)
DC-1 (L/R ≤ 1 ms) DC-3 (L/R ≤ 2 ms)
Type Rated operating
voltage Ue
1 current path 2 current paths
in series
3 current paths
in series
1 current path 2 current paths
in series
3 current paths
in series
ESB20-02 24 V DC 14 A 20 A - 6 A 10 A -
48 V DC 7 A 14 A -3 A6 A-
60 V DC 4.5 A 10 A - 2 A 4 A -
110 V DC 1.5 A 4.4 A - 0.6 A 1.8 A -
220 V DC 0.2 A 1.5 A - 0.1 A 0.6 A -
ESB24 24 V DC 14.5 A 24.0 A 24.0 A 6.3 A 11.0 A 19.0 A
48 V DC 7.5 A 12.5 A 22.0 A 3.1 A 5.4 A 9.4 A
60 V DC 4.5 A 10.0 A 17.5 A 2.0 A 4.3 A 7.5 A
110 V DC 1.6 A 4.4 A 9.5 A 0.7 A 1.9 A 4.1 A
220 V DC 0.2 A 1.4 A 3.8 A 0.1 A 0.6 A 1.6 A
ESB Installation Contactors
Technical Data
ABB | 13
1SBC103007S0201
ESB Installation Contactors - Lighting Application
Technical Data
Switching of lamp load
The following table shows the number of lamps which can be connected per phase at 230 V, 50 Hz. Air temperature, near the contactor, must be
limited to 55°C.
Please, note that the given capacitor load must not be exceeded, otherwise inadmissible high inrush current peaks could occur.
These are inuenced by the length and cross section of the wire used, the type of power supply unit and specications of the lamp brand.
For these reasons, values in the table are for information only.
Numbers are given for a 230V voltage distributed between phase and neutral: single phase (phase + neutral) or three-phases (3 phases + neutral),
lamps are wired in star connection.
In the case of three-phase supply without neutral, 230V phase-to-phase, the permissible number of lamps per phase will be that given in the table
multiplied by 0.58.
Lamp type Lamp data Permissible number
of lamps per phase
(230 V, 50 Hz )
Capacitor
Watt In
A
ESB20 ESB24 ESB40 ESB63 µF
Incandescent
lamps
60 0.26 21 25 54 83
100 0.43 13 15 32 50
200 0.87 7 7 16 25
300 1.30 4 5 11 16
500 2.17 33610
1000 4.35 1135
Fluorescent lamps
Uncompensated
and series
compensation
15 0.33 40 30 100 155
20 0.37 37 26 85 135
40 0.43 32 20 65 105
42 0.54 26 16 52 85
58 0.64 21 12 40 65
65 0.67 21 12 40 65
115 1.3 9 5 18 28
140 1.5 9 5 18 28
Two-lamp circuit 2 x 20 2 x 0.13 2 x 22 2 x 26 2 x 85 2 x 140
2 x 40 2 x 0.22 2 x 17 2 x 20 2 x 65 2 x 105
2 x 42 2 x 0.24 2 x 13 2 x 16 2 x 52 2 x 65
2 x 58 2 x 0.34 2 x 10 2 x 12 2 x 40 2 x 65
2 x 65 2 x 0.34 2 x 10 2 x 12 2 x 40 2 x 65
2 x 115 2 x 0.65 2 x 4 2 x 5 2 x 18 2 x 28
2 x 140 2 x 0.75 2 x 4 2 x 5 2 x 18 2 x 28
Parallel
compensation
15 0.11 16 8 16 67 4.5
20 0.13 16 8 16 67 4.5
40 0.22 16 8 16 67 4.5
42 0.24 13 6 12 50 6
58 0.34 11 5 10 43 7
65 0.34 11 5 10 43 7
115 0.65 4241718
140 0.75 4241718
High pressure
mercury-vapor
lamps
Uncompensated
50 0.61 30 14 36 50
80 0.8 15 10 27 38
125 1.15 10 7 19 26
250 2.15 6 4 10 14
400 3.25 22710
700 5.40 2146
1000 7.5 1134
2000/ 8 1 3 4
400 V
Parallel
compensation
50 0.28 4 5 10 43 7
80 0.41 348378
125 0.65 2362610
250 1.22 1231518
400 1.95 1 3 10 25
700 3.45 1 5 45
1000 4.8 1 4 60
2000/ 5.45 12335
400 V
Lamps with
electronic power
supply units
1 x 18 15 24 55 76
2 x 18 8 18 34 48
1 x 36 12 16 34 47
2 x 36 7 11 20 29
1 x 58 11 14 32 46
2 x 58 6 8 17 24
Lamp type Lamp data Permissible number
of lamps per phase
(230 V, 50 Hz )
Capacitor
Watt In
A
ESB20 ESB24 ESB40 ESB63 µF
Halogen
metal-vapor lamps
Uncompensated
35 0.53 9 10 28 38
701451420
1501.833811
25031257
4003.51146
1000 9.5 1 2
2000 16.5 1 1
2000/ 10.5 2 2
3500/ 18 1 1
400 V
Parallel
compensation
35 0.25 5 11 30 6
70 0.45 3 5 18 12
150 0.75 13920
2501.512733
400 2.5 2 6 35
1000 5.8 –––295
2000 11.5 –––1148
2000/ 6.6 1 2 58
3500/ 11.6 –––1100
400 V
Low pressure
sodium-vapor
lamps
Uncompensated
35 1.5 10 8 22 30
55 1.5 10 8 22 30
90 2.4 5 5 13 19
135 3.5 3 3 10 13
150 3.3 3 3 10 14
180 3.3 3 3 10 14
200 2.3 3 5 14 20
Parallel
compensation
35 0.31 - 1 4 15 20
55 0.42 - 1 4 15 20
90 0.63 - 1 3 10 30
135 0.94 - - 2 7 45
150 1.0 - - 2 8 40
180 1.16 - - 2 8 40
200 1.32 - 1 3 12 25
High pressure
sodium-vapor
lamps
Uncompensated
150 1.8 3 4 15 20
2503.023915
3303.712810
400 4.7 - 1 6 8
1000 10.3 - - 3 4
Parallel
compensation
150 0.83 - 1 3 15 20
2501.5- 12933
330 2.0 - - 2 7 40
400 2.4 - - 1 6 48
1000 6.3 ---2106
Transformers
for halogen
low voltage lamps
(12 or 24 V AC)
Transformers
for Watt
Permissible number of transformers per circuit
(230 V, 50 Hz)
20 40 50 110 174
50 20 24 50 80
75 13 16 35 54
100 10 12 27 43
150 7 9 19 29
200 5 6 14 23
300 3 4 9 14
Single-phase Three-phase Three-phase with neutral 400 V
230 V
L1
N
230 V230 V
L1
L2
L3
230 V
230 V
230 V
L1
L2
L3
N
230 V
Certifications and Approvals
UL
CSA
CCC CE
14 | ABB
1SBC103008S0201
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 50 Hz 60 Hz pieces kg (1 pce)
3
4
1
2
A1
A2
1 24 V 28 V EN20-20 GHE3221101R0001 10 0.14
230 V 264 V GHE3221101R0006 10 0.14
2 N.O.
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue250 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 20 A
Pe AC-1 Rated operational power 230 V 4 kW
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 8 VA / 5 W
Average holding coil consumption value 3.2 VA / 1.2 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 10 mm
2 x
1.5 … 4 mm
Coil terminals Rigid 1 x 0.5 … 4 mm
2 x
0.75 … 2.5 mm
EN20
Installation Contactors - Manually / Automatic Operated
AC Operated
20 A
AC-1/AC-7a
Dimensions: mm, inches
1SBC103008S0201
Application
The EN contactors are used mainly in buildings for switching
and controlling lighting, heating, ventilation and pumps.
They are part of the complete range of Din rail products and
can be integrated easily in dedicated panels.
Description
The EN20 contactors are used for the control of single phase loads up to 20 A. They operate with an AC coil.
EN contactors have a built-in toggle switch to select between three function modes:
Off position, automatic run (normal contactor function), manual override with a return to Auto the next time the coil is
energized.
This offers many advantages as:
You can make functional test before installation start-up. It can be used for maintenance operation, to change lamps
and test it. It provides higher safety and drop out as you can switch the application manually.
The toggle switch is also used for household application like water heating where double tariff of kWh is used.
0 = Off
I = ON
Automatic
run
1 3
A1
2 4
2
0
1
A
U
T
O
S
T
0
P
M
A
N
17.5 0.69"
85 3.35"
45 1.77"
58 2.28"
6.8 0.68"
1.1 0.43"
35 mm
EN/IEC 60175
43.5 1.71"
Mounting positions
Pos. 1, 3, 4, 1± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Certifications and Approvals
UL
CSA
CCC CE
ABB | 15
1SBC103009S0201
Application
The EN contactors are used mainly in buildings for switching
and controlling lighting, heating, ventilation and pumps.
They are part of the complete range of Din rail products and
can be integrated easily in dedicated panels.
Description
The EN24 contactors are used for the control of single and three-phase loads up to 24 A.
They operate with a
DC coil.
EN contactors have a built-in toggle switch to select between three function modes:
Off position, automatic run (normal contactor function), manual Override with a return to Auto the next time the coil is
energized.
This offers many advantages as:
You can make functional test before installation start-up, it can be used for maintenance operation, to change lamps
and test it, it provide higher safety and drop out as you can switch the application manually.
The toggle switch is also used for household application like water heating where double tariff of kWh is used.
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 40...450 Hz DC pieces kg (1 pce)
3
4
1
2
5
6
7
8
A1
A2
2 24 V 24 V EN24-40 GHE3261101R0001 5 0.24
230/240 V 230/240 V GHE3261101R0006 5 0.24
4 N.O.
R3
R4
1
2
A1
A2
5
6
7
8
2 24 V 24 V EN24-31 GHE3261601R0001 5 0.24
230/240 V 230/240 V GHE3261601R0006 5 0.24
3 N.O.
1 N.C.
3
4
1
2
5
6
A1
A2
2 230/240 V 230/240 V EN24-30 GHE3261501R0006 5 0.23
3 N.O.
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue400 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 24 A
Pe AC-1 Rated operational power 230 V 5.3 kW
400 V 16 kW
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 4 VA / 4 W
Average holding coil consumption value 4 VA / 4 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 10 mm
2 x
1.5 … 4 mm
Coil terminals Rigid 1 x 1 … 4 mm
2 x
0.75 … 2.5 mm
EN24
Installation Contactors - Manually / Automatic Operated
AC / DC Operated
Mounting positions
Pos. 1, 3, 4, 1 ± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
24 A
AC-1/AC-7a
Dimensions: mm, inches
1SBC103009S0201
0 = Off
I = ON
Automatic
run
1 3
A1
2 4
2
0
1
A
U
T
O
S
T
0
P
M
A
N
85 3.35"
45 1.77"
58 2.28" 36 1.42"
6.8 0.68"
1.1 0.43"
35 mm
EN/IEC 60175
43.5 1.71"
Certifications and Approvals
UL
CSA
CCC CE
16 | ABB
1SBC103012S0201
Application
The EN contactors are used mainly in buildings for switch-
ing and controlling lighting, heating, ventilation and pumps.
They are part of the complete range of Din rail products
and can be integrated easily in dedicated panels.
Description
The EN40 contactors are used for the control of single and three-phase loads up to 40 A.
They operate with a
DC coil.
EN contactors have a built-in toggle switch to select between three function modes:
Off position, automatic run (normal contactor function), manual Override with a return to Auto the next time the coil is
energized.
This offers many advantages as:
You can make functional test before installation start-up, it can be used for maintenance operation, to change lamps
and test it, it provide higher safety and drop out as you can switch the application manually.
The toggle switch is also used for household application like water heating where double tariff of kWh is used.
Ordering Details
Main poles Nb of Control coil voltage
Type Order code
Pack(ing) Weight
modules 40...450 Hz DC pieces kg (1 pce)
3
4
1
2
5
6
7
8
A1
A2
3 24 V 24 V EN40-40 GHE3421101R0001 3 0.41
110 V 110 V GHE3421101R0004 3 0.41
230/240 V 230/240 V GHE3421101R0006 3 0.41
4 N.O.
R3
R4
1
2
A1
A2
5
6
7
8
3 24 V 24 V EN40-31 GHE3421601R0001 3 0.41
230/240 V 230/240 V GHE3421601R0006 3 0.41
3 N.O.
1 N.C.
3
4
1
2
5
6
A1
A2
3 230/240 V 230/240 V EN40-30 GHE3421501R0006 3 0.40
3 N.O.
3
4
1
2
A1
A2
3 230/240 V 230/240 V EN40-20 GHE3421401R0006 3 0.30
2 N.O.
Main Technical Data For complete technical data see 1SBC103005S0201.pdf
Main poles
Rated operational voltage Ue400 V
acc to. IEC 60947-4-1
and IEC 61095
Ie AC-1 / AC-7a Rated operational current (for air temperature close to contactor θ ≤ 55°C) 40 A
Pe AC-1 Rated operational power 230 V 8.8 kW
400 V 26 kW
Magnet system
Coil operating limits (acc. to IEC 60947-4-1) 0.85 … 1.1 Uc (at θ ≤ 55°C)
Average pull-in coil consumption value 5 VA / 5 W
Average holding coil consumption value 5 VA / 5 W
Connecting
capacity
Main pole terminals Rigid 1 x 1.5 … 25 mm
2 x
1.5 … 10 mm
Coil terminals Rigid 1 x 1 … 4 mm
2 x
0.75 … 2.5 mm
EN40
Installation Contactors - Manually / Automatic Operated
AC / DC Operated
Mounting positions
Pos. 1, 3, 4, 1± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
40 A
AC-1/AC-7a
Dimensions: mm, inches
1SBC103012S0201
0 = Off
I = ON
Automatic
run
1 3
A1
2 4
2
0
1
A
U
T
O
S
T
0
P
M
A
N
85 3.35"
54 2.13"
45 1.77"
58 2.28"
6.8 0.68"
1.1 0.43"
35 mm
EN/IEC 60175
43.5 1.71"
ABB | 17
1SBC103014S0201
EN
Installation Contactors - Manually / Automatic Operated
Technical Data
Main Pole - Utilization Characteristics according to IEC
Contactor types: AC operated EN20
AC / DC operated EN24 EN40
Rated operational voltage Ue max. V 250 400
Rated frequency limits Hz 50/60
Utilization category AC-1 / AC-7a
for air temperature close to contactor < 55 °C
Max. rated operational current Ie AC-1 / AC-7a
N.O.
A20 24 40
N.C.
A-2430
Short-circuit protection
for contactors gG type fuse A20 35 63
Rated short-time withstand current Icw
at 40 °C ambient temp.,
in free air, from a cold state 10 s A72 176
Heat dissipation per pole Ie / AC-1 / AC-7a W14
Max. electrical switching frequency
– for AC-1 / AC-7a cycles/h 300
Electrical Durability
– for AC-1 / AC-7a cycles 150000
Mechanical durability
– millions of operating cycles 1
General Technical Data
Contactor types: AC operated EN20
AC / DC operated EN24 EN40
Rated insulation voltage Ui
according to IEC 60947-4-1 V400 500
Rated impulse withstand voltage Uimp. kV 6
Standards IEC 60947-4-1 / EN 60947-4-1 and IEC 61095 / EN 61095
Air temperature close to contactor
– for operation at 0.85 ... 1.1 Uc°C -25 ... +55 (Type EN24...40: for ambient temperature > 40°C, add ESB-DIS (1/2 module) at every second contactor)
– for storage °C -40 ... +80
Climatic withstand IEC 60068-2-30, UTE 63-100 execution 1*
Operating altitude m ≤ 2000
Shock withstand 10 g / 4 ms / axes X Y Z
Mounting positions
Pos 1, 3, 4, 1±30°
Pos 5 : not allowed for EN20
Pos. 1/3/4/1± 30°
+30° -30°
Pos. 3
Pos. 2
Pos. 1
Pos. 4
Pos. 5
Fixing
on rail acc. to IEC 60715 and EN 60715 35 mm
* EN20 only
18 | ABB
1SBC103014S0201
EN
Installation Contactors - Manually / Automatic Operated
Technical Data
Magnet System Characteristics
Contactor types: AC operated EN20
AC / DC operated EN24 EN40
Rated operational voltage Ue max.
- at 50 Hz V12 ... 400 12 ... 415 24 ... 415
- at 60 Hz V14 ... 380 12 ... 415 24 ... 415
V DC - 12 ... 415 24 ... 415
Coil operating limits acc. to IEC 60947-4-1 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Drop-out voltage in % of Ucapprox. 20 ... 75 % approx. 10 ... 75 %
Frequency range Hz 50/60 40 ... 450
Coil consumption
Average pull-in value VA / W 8 / 5 4 / 4 5 / 5
Average holding value VA / W 3.2 / 1.2 4 / 4 5 / 5
Operating time
between coil energization and:
– N.O. contact closing ms 12 40
between coil de-energization and:
– N.O. contact opening ms 12 40
Connecting Characteristics
Contactor types:
EN20
EN24 EN40
Connecting capacity (min. ... max.)
Main pole terminals
Rigid 1 x mm² 1.5 ... 10 1.5 ... 25
2 x mm² 1.5 ... 4 1.5 ... 10
Capacity acc. to UL/CSA AWG 14 ... 8 16 ... 8 16 ... 4
Coil terminals
Rigid 1 x mm² 0.5 ... 4 1 ... 4
2 x mm² 0.75 ... 2.5
Capacity acc. to UL/CSA AWG 18 ... 14 16 ... 10
Degree of protection
acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529
Protection against direct contact in acc. with EN 50274
All terminals IP20
Screwdriver type
Main poles Flat Ø 5 / Pozidriv 1 Flat Ø 7.5 / Pozidriv 2
Coil terminals Flat Ø 5 / Pozidriv 1 Flat Ø 5 / Pozidriv 1
Stripping length
Main poles mm 10 13
Coil terminals mm 7
Tightening torque
Main poles Nm 1.2 1 2.5
Coil terminals Nm 0.9
ABB | 19
EH04-20
Contact Blocks
EH04-20 EH04-11
ESB24-40
ESB-PLK24
ESB-DIS
SZ-KZS...
ESB-PLK40/63
1SBC103006S0201
Ordering Details
Auxiliary Contact Blocks
Contactor
type
Contact blocks Type Order code
Pack(ing)
pieces
Weight
kg (1 pce)
ESB24...63
2-
EH04-20 GHE3401321R0001 10 0.004
EN24...40
1 1 EH04-11 GHE3401321R0002 10 0.004
Sealing cover
Contactor
type
Type Order code
Pack(ing)
pieces
Weight
kg (1 pce)
ESB24, EN24
ESB-PLK24 GHE3201903R0001 10 0.002
ESB40...63, EN40
ESB-PLK40/63
GHE3401903R0002 10 0.009
Distance piece
Contactor
type
Type Order code
Pack(ing)
pieces
Weight
kg (1 pce)
ESB24...63, EN24...40
ESB-DIS GHE3201902R0001 10 0.002
Labelling material
Contactor type
ESB20...63, EN20...40
Type Order code
Pack(ing)
pieces
Weight
kg (1 pce)
Label - unlabelled* SZ-KZS GHS2101946R0004 30 0.008
Label - numbering 1-40
SZ-KZS/1
GHS2101946R0005 30 0.008
Label - numbering 2 * 1-20
SZ-KZS/6 GHS2101946R0010 30 0.008
Label - numbering 4 * 1-10
SZ-KZS/9 GHS2101946R0013 30 0.008
Label - numbering 4 * 11-20
SZ-KZS/10 GHS2101946R0014 30 0.008
Label - labelled L1
SZ-KZS/11 GHS2101946R0015 30 0.008
Label - labelled L2
SZ-KZS/12 GHS2101946R0016 30 0.008
Label - labelled L3
SZ-KZS/13 GHS2101946R0017 30 0.008
Note: * The unlabelled can be labelled by water-resistant and permanent marker or by means of computer-controlled
labelling system (plotter).
Special labels on request: minimum quantities 50
ESB, EN Installation Contactors
Main Accessories
Auxiliary Contact Blocks
Sealing cover
Distance piece
Labelling material
20 | ABB
GHE3201902R0001 ESB-DIS 19
GHE3201903R0001 ESB-PLK24 19
GHE3211102R0001 ESB20-20 4
GHE3211102R0002 ESB20-20 4
GHE3211102R0003 ESB20-20 4
GHE3211102R0004 ESB20-20 4
GHE3211102R0005 ESB20-20 4
GHE3211102R0006 ESB20-20 4
GHE3211102R0007 ESB20-20 4
GHE3211102R1004 ESB20-20 4
GHE3211102R1005 ESB20-20 4
GHE3211202R0001 ESB20-02 4
GHE3211202R0002 ESB20-02 4
GHE3211202R0003 ESB20-02 4
GHE3211202R0004 ESB20-02 4
GHE3211202R0005 ESB20-02 4
GHE3211202R0006 ESB20-02 4
GHE3211202R0007 ESB20-02 4
GHE3211202R1004 ESB20-02 4
GHE3211202R1005 ESB20-02 4
GHE3211302R0001 ESB20-11 4
GHE3211302R0002 ESB20-11 4
GHE3211302R0003 ESB20-11 4
GHE3211302R0004 ESB20-11 4
GHE3211302R0005 ESB20-11 4
GHE3211302R0006 ESB20-11 4
GHE3211302R0007 ESB20-11 4
GHE3211302R1004 ESB20-11 4
GHE3211302R1005 ESB20-11 4
GHE3221101R0001 EN20-20 14
GHE3221101R0006 EN20-20 14
GHE3261101R0001 EN24-40 15
GHE3261101R0006 EN24-40 15
GHE3261501R0006 EN24-30 15
GHE3261601R0001 EN24-31 15
GHE3261601R0006 EN24-31 15
GHE3291102R0001 ESB24-40 5
GHE3291102R0002 ESB24-40 5
GHE3291102R0003 ESB24-40 5
GHE3291102R0004 ESB24-40 5
GHE3291102R0006 ESB24-40 5
GHE3291102R0007 ESB24-40 5
GHE3291102R1004 ESB24-40 5
GHE3291202R0001 ESB24-04 5
GHE3291202R0002 ESB24-04 5
GHE3291202R0003 ESB24-04 5
GHE3291202R0004 ESB24-04 5
GHE3291202R0006 ESB24-04 5
GHE3291202R0007 ESB24-04 5
GHE3291202R1004 ESB24-04 5
GHE3291302R0001 ESB24-22 5
GHE3291302R0002 ESB24-22 5
GHE3291302R0003 ESB24-22 5
GHE3291302R0004 ESB24-22 5
GHE3291302R0006 ESB24-22 5
GHE3291302R0007 ESB24-22 5
GHE3291302R1004 ESB24-22 5
GHE3291602R0001 ESB24-31 5
GHE3291602R0002 ESB24-31 5
GHE3291602R0003 ESB24-31 5
GHE3291602R0004 ESB24-31 5
GHE3291602R0006 ESB24-31 5
GHE3291602R0007 ESB24-31 5
GHE3291602R1004 ESB24-31 5
GHE3291702R0001 ESB24-13 5
GHE3291702R0002 ESB24-13 5
GHE3291702R0003 ESB24-13 5
GHE3291702R0004 ESB24-13 5
GHE3291702R0006 ESB24-13 5
GHE3291702R0007 ESB24-13 5
GHE3291702R1004 ESB24-13 5
GHE3401321R0001 EH04-20 19
GHE3401321R0002 EH04-11 19
GHE3401903R0002 ESB-PLK40/63 19
GHE3421101R0001 EN40-40 16
GHE3421101R0004 EN40-40 16
GHE3421101R0006 EN40-40 16
GHE3421401R0006 EN40-20 16
GHE3421501R0006 EN40-30 16
GHE3421601R0001 EN40-31 16
GHE3421601R0006 EN40-31 16
GHE3491102R0001 ESB40-40 6
GHE3491102R0002 ESB40-40 6
GHE3491102R0003 ESB40-40 6
GHE3491102R0004 ESB40-40 6
GHE3491102R0006 ESB40-40 6
GHE3491102R0007 ESB40-40 6
GHE3491102R0008 ESB40-40 6
GHE3491102R1004 ESB40-40 6
GHE3491302R0001 ESB40-22 6
GHE3491302R0006 ESB40-22 6
GHE3491402R0001 ESB40-20 6
GHE3491402R0006 ESB40-20 6
GHE3491502R0001 ESB40-30 6
GHE3491502R0006 ESB40-30 6
GHE3491502R0007 ESB40-30 6
GHE3491602R0001 ESB40-31 6
GHE3491602R0006 ESB40-31 6
GHE3691102R0001 ESB63-40 7
GHE3691102R0002 ESB63-40 7
GHE3691102R0003 ESB63-40 7
GHE3691102R0004 ESB63-40 7
GHE3691102R0006 ESB63-40 7
GHE3691102R0007 ESB63-40 7
GHE3691102R0008 ESB63-40 7
GHE3691102R1004 ESB63-40 7
GHE3691302R0007 ESB63-22 7
GHE3691402R0001 ESB63-20 7
GHE3691402R0006 ESB63-20 7
GHE3691502R0006 ESB63-30 7
GHE3691502R0007 ESB63-30 7
GHE3691602R0004 ESB63-31 7
GHE3691602R0006 ESB63-31 7
GHE3691802R0006 ESB63-11 7
GHS2101946R0004 SZ-KZS 19
GHS2101946R0005 SZ-KZS/1 19
GHS2101946R0010 SZ-KZS/6 19
GHS2101946R0013 SZ-KZS/9 19
GHS2101946R0014 SZ-KZS/10 19
GHS2101946R0015 SZ-KZS/11 19
GHS2101946R0016 SZ-KZS/12 19
GHS2101946R0017 SZ-KZS/13 19
Order code Type Page Order code Type Page Order code Type Page
Index
Order codes
ABB | 21
EH04-11 GHE3401321R0002 19
EH04-20 GHE3401321R0001 19
EN20-20 GHE3221101R0001 14
GHE3221101R0006 14
EN24-30 GHE3261501R0006 15
EN24-31 GHE3261601R0001 15
GHE3261601R0006 15
EN24-40 GHE3261101R0001 15
GHE3261101R0006 15
EN40-20 GHE3421401R0006 16
EN40-30 GHE3421501R0006 16
EN40-31 GHE3421601R0001 16
GHE3421601R0006 16
EN40-40 GHE3421101R0001 16
GHE3421101R0004 16
GHE3421101R0006 16
ESB20-02 GHE3211202R0001 4
GHE3211202R0002 4
GHE3211202R0003 4
GHE3211202R0004 4
GHE3211202R0005 4
GHE3211202R0006 4
GHE3211202R0007 4
GHE3211202R1004 4
GHE3211202R1005 4
ESB20-11 GHE3211302R0001 4
GHE3211302R0002 4
GHE3211302R0003 4
GHE3211302R0004 4
GHE3211302R0005 4
GHE3211302R0006 4
GHE3211302R0007 4
GHE3211302R1004 4
GHE3211302R1005 4
ESB20-20 GHE3211102R0001 4
G H E3 21110 2 R0 0 0 2 4
G H E3 21110 2 R0 0 0 3 4
G H E3 21110 2 R0 0 0 4 4
G H E3 21110 2 R0 0 0 5 4
G H E3 21110 2 R0 0 0 6 4
G H E3 21110 2 R0 0 07 4
G H E3 21110 2 R10 0 4 4
G H E3 21110 2 R10 0 5 4
ESB24-04 GHE3291202R0001 5
GHE3291202R0002 5
GHE3291202R0003 5
GHE3291202R0004 5
GHE3291202R0006 5
GHE3291202R0007 5
GHE3291202R1004 5
ESB24-13 GHE3291702R0001 5
GHE3291702R0002 5
GHE3291702R0003 5
GHE3291702R0004 5
GHE3291702R0006 5
GHE3291702R0007 5
GHE3291702R1004 5
ESB24-22 GHE3291302R0001 5
GHE3291302R0002 5
GHE3291302R0003 5
GHE3291302R0004 5
GHE3291302R0006 5
GHE3291302R0007 5
GHE3291302R1004 5
ESB24-31 GHE3291602R0001 5
GHE3291602R0002 5
GHE3291602R0003 5
GHE3291602R0004 5
GHE3291602R0006 5
GHE3291602R0007 5
GHE3291602R1004 5
ESB24-40 GHE3291102R0001 5
GHE3291102R0002 5
GHE3291102R0003 5
GHE3291102R0004 5
GHE3291102R0006 5
GHE3291102R0007 5
GHE3291102R1004 5
ESB40-20 GHE3491402R0001 6
GHE3491402R0006 6
ESB40-22 GHE3491302R0001 6
GHE3491302R0006 6
ESB40-30 GHE3491502R0001 6
GHE3491502R0006 6
GHE3491502R0007 6
ESB40-31 GHE3491602R0001 6
GHE3491602R0006 6
ESB40-40 GHE3491102R0001 6
GHE3491102R0002 6
GHE3491102R0003 6
GHE3491102R0004 6
GHE3491102R0006 6
GHE3491102R0007 6
GHE3491102R0008 6
GHE3491102R1004 6
ESB63-11 GHE3691802R0006 7
ESB63-20 GHE3691402R0001 7
GHE3691402R0006 7
ESB63-22 GHE3691302R0007 7
ESB63-30 GHE3691502R0006 7
GHE3691502R0007 7
ESB63-31 GHE3691602R0004 7
GHE3691602R0006 7
ESB63-40 GHE3691102R0001 7
GHE3691102R0002 7
GHE3691102R0003 7
GHE3691102R0004 7
GHE3691102R0006 7
GHE3691102R0007 7
GHE3691102R0008 7
GHE3691102R1004 7
ESB-DIS GHE3201902R0001 19
ESB-PLK24 GHE3201903R0001 19
ESB-PLK40/63 GHE3401903R0002 19
SZ-KZS GHS2101946R0004 19
SZ-KZS/1 GHS2101946R0005 19
SZ-KZS/6 GHS2101946R0010 19
SZ-KZS/9 GHS2101946R0013 19
SZ-KZS/10 GHS2101946R0014 19
SZ-KZS/11 GHS2101946R0015 19
SZ-KZS/12 GHS2101946R0016 19
SZ-KZS/13 GHS2101946R0017 19
Type Order code Page Type Order code Page Type Order code Page
Index
Types
1SBC 103 001 C0202 - Printed in France (W 10.2011 Ferréol)
Contact us
ABB France
Low Voltage Products Division
10, rue Ampère Z.I. - B.P. 114
F-69685 Chassieu cedex / France
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82
D-69123 Heidelberg / Germany
You can find the address of your local sales organisation
on the ABB home page
http://www.abb.com/contacts -> Low Voltage products
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or pos-
sible lack of information in this document.
We reserve all rights in this document and in the
subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB.
Copyright© 2011 ABB
All rights reserved
www.abb.com/lowvoltage