Electrical Characteristics
1.5In2.1In2.75In4In10In
Min Max Min Max Min Max Min Max
Amps min. min. ms s ms s ms ms
<1A 60 30 250 80s 50 5s 5 150
1A-3.15A 60 30 750 80s 95 5s 10 150
4A-6.3A 60 30 750 80s 150 5s 10 150
8A-12A 30 30 750 80s 150 5s 10 150
Agency Information
• UL Recognized Card: Guide JDYX2, File E19180, JDYX8, File E19180
• CSA Component Acceptance: File 53787
• SEMKO: File 816547, 1119019
• VDE: File 40014091, 40024352, 40023140
• BSI: File KM55676
• IMQ: File CA03.00100 and CA03.00529
• PES+JET: File 1641-31003-1009, 1641-31003-1010,
1641-31003-1011, 1641-31003-1012, 1641-31003-2001,
1641-31003-2002
• CCC: File 2002010207011295, CQC11012061930
• KC-Mark: File SU05011-4012A, SU05011-5004A
Ordering
• Specify packaging code (insert packaging code prefix before part number)
e.g., BK- (or BK1-/TR2-) S505-1-R
• Specify option codes if desired (for axial leads, insert “V” between catalog
series and amp rating) e.g., BK-S505-V-1-R
Dimensions - mm
• Ratings above 6.3A have a maximum
0.81mm diameter lead
• With TR2 packaging code, leadwire
length is 19.05mm
5 x 20mm Time-Delay, Ceramic Tube Fuses
S505 Series
1111 BU-SB11758 Page 1 of 2 Data Sheet 2037
5 x 20mm fuse with
optional axial leads
Description
• Time-delay, high breaking capacity
• Available with optional axial leads
• Ceramic tube, silver-plated endcap construction (500mA-800mA),
nickel-plated brass endcap construction (1-12A)
• Optional sleeve is flexible flouropolymer (UL flammability rating VW-1).
Consult factory for details.
• 5 x 20mm physical size
• Designed to IEC 60127-2 (500mA-10A) & extension 12A
Voltage Interrupting Typical DC Cold Typical Typical Agency Information
Product Rating Rating at Rated Resistance Pre-arching Voltage CCC/ PSE/
Code AC Voltage (50Hz) AC1(Ω)2I2t (A2s)AC3Drop (mV)4IMQ5VDE SEMKO cURus CQC5JET CSA5KC5BSI
S505-500-R 250 1500 0.5070 0.188X295 X X X X X X X
S505-800-R 250 1500 0.2370 0.632X189 X X X X X X X
S505-1-R 250 1500 0.1401 1.28 152.5 X X X X X X X X X
S505-1.25-R 250 1500 0.1075 2.22 150 X X X X X X X X X
S505-1.6-R 250 1500 0.0700 6.78 125 X X X X X X X X X
S505-2-R 250 1500 0.0545 9.60 118.5 X X X X X X X X X
S505-2.5-R 250 1500 0.0395 16.60 115 X X X X X X X X X
S505-3.15-R 250 1500 0.0305 36.60 102.5 X X X X X X X X X
S505-4-R 250 1500 0.0185 38.45X86.5 X X X X X X X X X
S505-5-R 250 1500 0.0131 71.30X77.5 X X X X X X X X X
S505-6.3-R 250 1500 0.0102 111X75 X X X X X X X X X
S505-8-R 250 1500 0.0077 228X73 X X X X X6XXXX
S505-10-R 250 1500 0.0061 397 72 X X X X X6XXXX
S505-12-R 250 1000 0.0053 713.7X77 X X
1. Interrupting ratings: 500mA to 10A were measured at 70% to 80% PF on AC,12A was measured
at 100% PF on AC.
2. Typical DC Cold Resistance (measured at <10% of rated current).
3. Typical Pre-Arching I2t (measured at listed interrupting rating and rated voltage if not specified);
With "X" specified, the typical I2t value is measured at 10 times of rated current under DC.
4. Typical Voltage Drop( Voltage Drop was measured at 20°C ambient temperature at rated current).
5. No room for "CSA" & "KC" on the fuse endcap for Non-V Rev. No room for "IMQ", "CQC' or "KC"
on fuse endcap for -V Rev.
6. CQC only.
Specifications