Top 2000 6 s 12 mm Part number 88226011
Relay output
Mono-voltage
1 timed changeover and 1 instantaneous contact
Elapsed time can be saved mechanically in the event of a break in supply
Progress of cycle displayed
Housing 48 x 48 mm
Connection by screw-terminal base or 8-pin base
Part numbers
Specifications
Type
Functions
Relay outputs
Delay
88 226 013
6 s
12 mm
Multi
-function 2 - 3 - 4
1 time changeover 5 A 1 instantaneous
12 min :
-
Max. timing 6 s
- 60 s -
12 min
-
Dial graduation 0.1 s
- 1 s - 12 s
88 226 019
6 s
12 mm
-
-
-
88 226 012
6 s
12 mm
-
-
-
88 226 011
6 s
12 mm
-
-
-
88 226 501
6 s
12 mm
-
-
-
88 226 502
6 s
12 mm
-
-
-
88 226 503
6 s
12 mm
-
-
-
88 226 504
6 s
12 mm
-
-
-
88 226 016
6 min
12 h
Multi
-function 2 - 3 - 4
1 timed changeover 5 A1 instantaneous
12 min :
-
Max. timing 6 s
- 60 s -
12 min
-
Dial graduation 0.1 s
- 1 s - 12 s
88 226 505
6 min
12 h
-
-
-
88 226 017
6 min
12 h
-
-
-
88 226 506
6 min
12 h
-
-
-
88 226 015
6 min
12 h
-
-
-
88 226 507
6 min
12 h
-
-
-
88 226 014
6 min
12 h
-
-
-
88 226 508
6 min
12 h
-
-
-
Precision limit error
Repetition accuracy
±
1.5 % (
±
4 %/6 s)
Selection precision
See "timing ranges" table for scale graduation
Reset time
0.20 s
Timed two-
pole
Instantaneous single pole
1
Thermal rating
6,3 A
Rating (cos φ
=
0.41) 104 operations
5 A - 230 V
Absorbed power-
motor
Voltage variation at maximum temperature of 55
o
C
according to IEC 255 100
24 V +10 % - 42 V -15 %
48 V +10 % - 110 V -20 %
127 V 0 % - 220 V -20 %
240 V 0 %
Operator factor
100 %
Temperature limits use (°C)
-
10→+55
Temperature limits stored (°C)
-20→70
Environmental protection Tropicalised to IEC 68
-2-10
Vibration withstand on 3 axes (Veritas standard)
4 G
-
55 Hz
Dielectric test voltage according to IEC 255 5 or VDE 0435
1000 V -Un≤60V
2000 V -
Un > 60 V
Insulation according to standard VDE 0110 group C
380 V AC -
440 V DC
Protection Housing
IP 40
Degree of terminal protection
IP 10
Conformity to standards NFC 45250
-
VDE 0110
- 0435 -
0660 or ICE 529
Connection : Screw/saddle
Terminal capacity Single
-wire 1 or 2 leads Multi-wire
0,75 -
2,5 mm
2
Terminal capacity Multi
-wire 1 or 2 leads
0,5 -
1 mm
2
Mounting : Base mounting on 8
-pin socket
Weight (g)
185
Dimensions (mm)
88 226 0
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
N
o
Legend
Panel depth 10 mm max.
M3 screw
Dimensions (mm)
88 226 5
N
o
Legend
Panel depth 10 mm max.
Dimensions (mm)
Panel cut-out
Dimensions (mm)
Solder tag connector
25 622 301 - 8-pin
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Dimensions (mm)
Inverter for DC supply
84 861 501 : 24
48 V DC
84 861 503 : 110
127 V DC
Weight 150 g
48 V DC
84 861 503 : 110
127 V DC
Weight 150 g" class="link_produits thickbox"> Zoom
N
o
Legend
Fixing holes ø 5
Dimensions (mm)
Screw terminal or connector socket
26 622 128 - 8-pin
Curves
Function 2
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Function
*** TRADUCTION MANQUANTE ***
Curves
Function 3
Function
*** TRADUCTION MANQUANTE ***
Curves
Function 4
Function
*** TRADUCTION MANQUANTE ***
Connections
Function 2
Connections
Function 3
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Function 4 : On energisation, chance of contact bounce on instantaneous contact for 250 ms
Function 4 : On energisation, chance of contact bounce on instantaneous contact for 250 ms
Function 4 : On energisation, chance of contact bounce on instantaneous contact for 250 ms
Connections
Function 4
Connections
Internal layout 88 226 0
Connections
Terminal identification 88 226 0
N
o
Legend
Supply
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com
Function 4 : On energisation, chance of contact bounce on instantaneous contact for 250 ms
Function 4 : On energisation, chance of contact bounce on instantaneous contact for 250 ms
Timed contact
Instantaneous contact
Connections
Internal layout 88 226 5
Connections
Terminal identification 88 226 5
N
o 2-3
Legend
Supply
Timed contact
Instantaneous contact
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012 www.crouzet.com