© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
PRODUCT OVERVIEW
Overview
The GE Innity S™ DC energy system is a
compact power plant that supports dual
voltage (+24V/-48V) operation through the
use of a comprehensive range of advanced
rectiers and DC-DC converters. Primary
voltage is supported by rectiers and battery
reserve, while secondary voltage is supported
by DC-DC converter modules. Primary voltage
can be -48V or +24V.
The Innity S Power System has primary
voltage capacity for +24V and -48V power up
to 800A; secondary voltage capacity is up to
120A per expansion module.
Shelf / Bay Options
Innity S systems features mounting rails for
eld install applications and may be equipped
in a 7 ft 23” relay rack; or a half height rack for
mounting on battery stands. The distribution
module is 4U tall and accommodates up to
26 single voltage or selectable voltage bullet
breaker positions. Universal shelves are 1U tall
with four slots that accept any Innity series
rectier or converter interchangeably in any
power slot. This allows the available slots to be
lled with the mix of power modules desired.
The only restriction is whether AC power
is applied to the shelf. This gives extreme
exibility in the provisioning of power modules
within the system.
Innity Rectier and
Converter Family
The Innity S oers DC rectiers and
converters for +24V to -48V applications.
Rectiers and converters are color coded to
quickly identify both the voltage and whether
it is a rectier or converter (orange for +24V
and blue for -48V).
Rectier and Converter Options:
- NE100AC24ATEZ Rectier,
100A/24V Output
- NE050AC48ATEZ Rectier,
50A/48V Output
- NE075DC24 Converter, 75A/24V Output
- NE030DC48 Converter, 30A/48V Output
Pulsar Plus Controller
The Innity S utilizes the industry leading
Pulsar Plus controller with Ethernet and
SNMP communications to deliver extensive
monitoring and control features with
remote access.
Benets
Reliability
Distributed fault tolerance
Proven eld performance
Controller continuity
Intelligence
Industry leading controller features
Ethernet interface for remote access
Centralized network management
Investment Protection
Module Compatibility
Secondary Voltage exibility
+24V / -48V
Flexible Upgrade Options
On Time Delivery
Standard building blocks
4 - 6 week availability
24/7 technical support
Dual Voltage power system with
ultimate exibility
-48V up to 600A (32KW) or
+24V up to 800A (22KW)
Secondary voltage up to 120A
High availability wireless telecom
applications
Telecom service providers
Eciency approaching 97%
Innity S Power System
Compact, Dual Voltage, Rack Mounted Power System
Total Eciency
The GE Total Eciency™ (TE) architecture
reduces energy loss and lowers cooling
costs by 50-70%. TE products will prioritize
sustainable energy sources like solar, wind,
water and fuel cells over traditional utility grid
or diesel generator sources – and they will
intelligently respond to smart grid information
to reduce consumption during peak demand
periods. Active Rectier Management (ARM)
and Battery Charging Optimization (BCO)
features increase eciency on current and
legacy power infrastructures. The Total
Eciency architecture addresses issues end-
to-end based on our proven experience and
expertise in batteries, power distribution, DC
energy systems, AC-DC power supplies, and
DC-DC board mounted power to deliver a
solution that is more safe, reliable and energy
ecient than competitive alternatives.
Page 2
Innity Rectiers and Converters
Applications
Key Features
Specications
Compact1RU form factor providing high power density (24 W/in3)
Dual Voltage compatibility – the unique connector pin designation allows the rectier to be
used in a “universal” power shelf, alongside rectiers or DC-DC converters with dierent
output voltages.
Plug and Play – installation of the rectier in a shelf connected to a compatible system
controller initializes all set up parameters automatically. No adjustments are needed.
Extended service lifeparallel operation with automatic load sharing ensures that parallel
units are not unduly stressed even when a unit fails or is removed.
Monitoring / control – the built in microprocessor controls and monitors all critical rectier
functions and communicates with the system controller using the built in Galaxy Protocol
serial interface.
Fail safe performancehot insertion capabilities allow for converter replacement without
system shutdown; soft start and inrush current protection prevent nuisance tripping of
upstream breakers.
Telecommunications networks
Digital subscriber line (DSL)
Indoor/outdoor wireless
Routers/switches
Fiber in the loop
Transmission
Data networks
PBX
Extended temperature range
Redundant fan cooling
Front panel LED indicators
1U height, hi power density
220/110V AC input
Digital load sharing
Hot pluggable
RoHS compliant
Input NE100AC24ATEZ NE050AC48ATEZ NE030DC48 NE075DC24
Voltage Range 95-275Vac 95-275Vac 21-30Vdc 42-60Vdc
Input Current 15-12A @ 100-120Vac
15A @ 200-240Vac
15-12A @ 100-120Vac
15A @ 200-240Vac
63A @ 27Vdc
81A @ 21Vdc
41A @ 54.5Vdc
54a @ 42Vdc
Input Frequency 45 – 66Hz 45 – 66Hz - -
Power Factor 0.98 at>50% load 0.98 at>50% load - -
Eciency > 95% (Peak 95.6%) > 96% (Peak 96.9%) - -
Total Harmonic Distortion <5% @loads over 50% <5% @loads over 50% - -
Output
Voltage Adjust Range 21-29Vdc 42-58Vdc 46-57Vdc 23-28Vdc
Voltage Nominal 27.25V 54.5V 52.0V 27.2V
Regulation (with controller) ±0.5% ±0.5% ±0.5% ±0.5%
Ripple 100mVrms 100mVrms 100mVrms 100mVrms
Output Current
- High-Line
- Low-Line
100A @27.25V
44A @27.25V
50A @54.5V
22A @54.5V
30A @52.0V
-
-
75A @27.2V
-
-
Heat Dissipation @ max out 174W / 594 BTU/hr 158W / 539 BTU/hr 154W / 525 BTU/hr 202W / 689 BTU/hr
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
TECHNICAL SPECIFICATIONS POWER MODULES
Page 3
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
TECHNICAL SPECIFICATIONS POWER MODULES
Outline Drawing
Environmental
Operating Temperature -40°C to +75°C (-40 to 167°F)
Storage Temperature -40°C to +85°C (-40 to 185°F)
Humidity < 95% non-condensing
Altitude 4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656º C /100M; 4000M peak temperature rating is 62º C
Mechanical
Length (inch/mm) 13.85 / 351.8
Width (inch/mm) 5.23 / 133
Height (inch/mm) 1.63 / 42
Weight (lb/Kg) 5.05 / 2.2
Safety and Standards Compliance
NEBs Level 3 Evaluated by independent NRTL test lab to Telcordia GR63, Issue 3 & GR 1089, Issue 5
Safety CE mark to Low Voltage Directive 2006/95/EC and EMC Directive 2004/108/E (Rectiers only)
UL 60950-1, 2nd Ed. Recognized
CSA C22.2 No. 60950-1-03 Certied
RoHS Compliant to RoHS EU Directive 2002/95/EC; RoHS 6/6
EMC European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 5
ESD EN61000-4-2, Level 4
Page 4
Pulsar Plus Controller
Applications
Key Features
The Pulsar Plus family of controllers provides
system monitoring and control features for
Innity, CP, and other power systems. These
controllers monitor and control system
components including rectiers, converters,
and distribution modules via a multi-drop
RS485 digital communications bus. System
status, parameters, settings, and alarm
thresholds can be viewed and congured
from the controller’s front panel display.
Assignment and conguration of alarm
inputs and output relays can be performed
from a laptop computer connected to a
local RS-232 or Ethernet port, or by remote
access is through a network connection to the
World Wide Web (internet) or your enterprise
network (intranet). An optional modem is also
available.
This controller utilizes standard network
management protocols allowing for
advanced network supervision. The GE Galaxy
Manager™ software is the centralized visibility
and control component of a comprehensive
power management system designed to meet
engineering, operations and maintenance
needs. The Galaxy Manager client-server
architecture enables remote access to system
controllers across the power network.
Telecommunications networks
Digital subscriber line (DSL)
Indoor/outdoor wireless
Routers/switches
Fiber in the loop
Transmission
Data networks
PBX
Remote Access and Features
Integrated 10/100Base-T Ethernet Network
- TCP/IP
- SNMP V2c for management
- SMTP for email
- Telnet for command line interface
- DHCP for plug-n-play
- FTP for rapid backup and upgrades
- HTTP for standard web pages
and browsers
- Compatible with Galaxy Manager
and other management packages
- Shielded RJ-45 interface referenced
to chassis ground
Password protected security levels: User,
Super-User, Administrator for all access
Ground-referenced RS232 system port
ANSI T1.317 command-line interface
Modem access support
- Remote via external modem
- Callback security
EasyView2, Windows-based GUI software for
local terminal or Modem access
Standard System Features
Monitor and control of more than 40
connected devices
- Robust RS485 system bus
Standard and user dened alarms
- Alarm test
- Assignable alarm severity: Critical,
Major, Minor, Warning, and record-only
- 10 alarm relays (7 user assigned)
Rectier management features
- Automatic rectier restart
- Active Rectier Management
ARM (energy eciency)
- Remote rectier (on/o)
- Reserve Operation
- Automatic rectier sequence control
- N + X redundancy check
Multiple Low Voltage Load and Low Voltage
Battery Disconnect thresholds
Conguration, statistics, and history
- All stored in non-volatile memory
- Remote/local backup and restore of
conguration data
Industry standard defaults
- Customer specic congurations
available
Remote/ local software upgrade
Basic, busy hour, and trend statistics
Detailed event history
User dened events and derived channels
Standard Battery Management Features
Float/boost mode control
- Manual boost
- Manual timed boost locally, T1.317,
and remotely initiated
- Auto boost terminated by time or
current
Battery discharge testing
- Manual (local/remote)
- Periodic
- Plant Battery Test (PBT) input driven
- Congurable threshold or 20%
algorithm
- Graphical discharge data
- Rectiers on-line during test
Slope thermal compensation
- High temperature
- Low temperature
- Step temperature
- STC Enable/Disable, low temperature
Enable/Disable
- Congurable mV/°C slopes
State of charge indication
High temperature disconnect setting
Reserve-time prediction
Recharge current limit
Emergency Power-O input
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
TECHNICAL SPECIFICATIONS - CONTROLLER
Page 5
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
TECHNICAL SPECIFICATIONS - CONTROLLER
Integrated Monitoring Inputs/Outputs
System plant voltage (accuracy ±0.5%, resolution 0.01V)
One system shunt (accuracy ± 0.5% full scale, resolution 1A)
- Battery or load
- Mounted in the return side of DC bus
Up to 15 binary inputs
- Six inputs close/open to battery
- 9 input close/open to return
- User assignable
Up to 7 Form-C output alarms (60VDC @ .5A)
- User assignable
1-Wire™ bus devices
- Up to 16 temperature probes (QS873)
- Up to 6 mid-string monitors (ES771)
Galaxy Manager Compatible
Centralized web server and database with multiple user access to live
or managed data with drill down to problem details
Monitor and control of more than 40 connected devices
Management information from polling or alarms received from alarm
traps from multiple sites are available on one screen via the inter/
intranet
Trend user selected data over time
Automatic or manual report generation
Standard engineering tools like reserve time calculators and cable
voltage drop analyzer
General
Operating Voltage ±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
Input Power Less than 7W
Operating Temperature Range -40°C to +75°C (-40°F to 167°F)
Operating Relative Humidity 0 - 95% (non-condensing)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F)
Physical Specications Sizes vary by packaging option
Display 8-line by 40-character with alarm
context sensitive backlit LCD Agency Certications
NEBs Level 3 Evaluated by independent NRTL test lab to Telcordia
GR63, Issue 3 and GR1089-CORE, Issue 5
EMC European Directive 2004/108/EC; EN55022,
(CISPR22) Class A, EN55024 (CISPR24)
Safety Underwriters Laboratories (UL) Listed per Subject
Letter 1801: Power Distribution Center for
Communications Equipment, and cUL Certied
(CSA 22.2 950): Safety of Information Technology
Equipment
Safety and Standards Compliance
NEBs Evaluated by independent NRTL test lab to Telcordia
GR63, Issue 3 and GR1089-CORE, Issue 5
Safety CSA C22.2 No. 60950-1-03 Certied for Canada and
U.S.; UL60950-1 1st Ed.
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS
5/6
EMC European Directive 2004/108/EC; EN55022, Class A,
EN55024; FCC, Class A; GR1089-CORE, Issue 5
Page 6
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
TECHNICAL SPECIFICATIONS – SYSTEM
Innity S System
Applications
Key Features
Specications
Innity S may be congured as a +24V or -48V single voltage power system or as a dual voltage
power system that supports rectiers and converters. The primary voltage is supported by +24V
or -48V rectiers and battery reserve, while secondary voltage is supported by DC-DC converters.
Innity-S includes dedicated 24V, 48V and return buses. The primary voltage capacity is 800A at
24V and 600A at 48V. Secondary (-48V) voltage capacity is up to 120A. The system includes low
voltage battery disconnect option for the primary voltage. A low voltage load disconnect option
can be used for load shedding to maintain critical loads.
Wireless Telecom networks
Indoor/outdoor wireless
Transmission
Data networks
ECO Priority Source
Dual Voltage Flexibility
Redundant fan cooling
Front panel LED indicators
1U height, hi power density
220/110 V AC input
Digital load sharing
Hot pluggable
RoHS compliant
Input Min Typ Max
Voltage Range
- High-Line
- Low-Line
175Vac
85Vac
220Vac
110Vac
275Vac
140Vac Only available in 24V Rectiers
Frequency 45Hz 60Hz 66Hz
Power Factor 98% 99.5%
Total Harmonic Distortion 5%
Primary Output
Nominal Voltage 24Vdc -48Vdc
Output Current 1,200A 800A
Vo Setpoint (factory) 27.2Vdc±1% -54.5Vdc±1%
Vo Range +21Vdc to +29Vdc -42Vdc to -58Vdc
Regulation ±0.5%
Secondary Output
Nominal Voltage -48Vdc +24Vdc
Output Current 120A 300A
Vo Setpoint (factory) -54.5Vdc±1% 27.25Vdc±1%
Vo Range -42Vdc to -58Vdc +21Vdc to +29Vdc
Regulation ±0.5%
Mechanical System Only Frame Mounted System
Height (in. /mm) 21.25 / 540 (Base system with 4 power shelves and 2 distributions) 84 / 2134
Width (in. /mm) 23 / 584.2 26 / 660.4
Depth (in. /mm) 21 / 533 21 / 533
Weight (lb / Kg) 108 / 49 (Base system with 4 power shelves and 2 distributions) 292 / 132
Page 7
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
TECHNICAL SPECIFICATIONS – SYSTEM
Outline Drawing
Environmental
Operating Temperature -40°C to +75°C (-40°F to 167 °F)
Storage Temperature -40°C to +85°C (-40°F to 185 °F)
Relative Humidity 95% max, non-condensing
Altitude 4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656º C /100M; 4000M peak temperature rating is 62º C
Safety and Standards Compliance
NEBs Evaluated by independent NRTL test lab to Telcordia GR63, Issue 3 and GR1089-CORE, Issue 5
Safety CSA C22.2 No. 60950-1-03 Certied for Canada and U.S.; UL60950-1 1st Ed.
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS 5/6
EMC European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 5
Agency Certications
CSA CSA C22.2 No 60950-1-03 and UL 60950-1 1st Ed
EMI/EMC European Directive 2004/108/EC; EN55022 (CISPR22) Class A; EN55024 (CISPR24)
NEBS LEVEL 3 GR1089-CORE, Issue 5
Page 8
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
ORDERING INFORMATION INFINITY S POWER SYSTEM
Ordering Guide
Features
Innity S may be congured as a +24V or -48V single voltage power
system or as a “dual voltage” power system that supports rectiers and
converters. The primary voltage is supported by +24V or -48V rectiers
and battery reserve, while secondary voltage is supported by DC-DC
converters. The primary voltage capacity is 800A at 24V and 600A at
48V. Secondary voltage capacity is up to 120A.
Innity S systems may be equipped in a 7ft framework, a half height
(42”) frame for mounting on battery stands, or supplied frameless for
eld install applications.
Innity Series Rectiers for +24V and -48V applications.
Dual Voltage Bus architecture for easy growth and voltage migration
DC-DC Converter support for dual voltage systems
DC Distribution for both voltages, with Selectable Voltage panel
availability
Temperature hardened harsh environments. (-40ºC to +75ºC)
Compact size: Base System with 1 power shelf occupies
5 RU (8.75 in) of 23” rack space (18” depth)
Frame options Factory installed in 7ft or 42” tall, 23” wide frame or
eld installed in user supplied frame
Battery connections, LVBD and LVLD options.
Plug-N-Play Pulsar Plus controller with Web based interface for local
and remote (LAN) access.
Distribution options include 3A-250A bullet style circuit breakers, and
GMT fuses
Ordering Information – Innity S Power System
Page 9
Type Description Schematic
AC1 Dual Feed, Molex
Mini-t Sr
AC3 Individual Feed, IEC-320 C19
Receptacles
AC5 Individual Feed, Terminal Strip
Rear cover is equipped with a 1”
conduit knockout
23” Shelves
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
ORDERING INFORMATION INFINITY S POWER SYSTEM
AC Input Types
Page 10
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
ORDERING INFORMATION INFINITY S POWER SYSTEM
Type Description Schematic
DC1E Single External Bullet Breaker Distribution Panel
26 Positions for 23” conguration
Ratings: 600A output (600A discharge), 250A max breaker (65°C Ambient)
DC2E Dual External Bullet Breaker Distribution Panel
52 Positions for 23” conguration
Ratings: 600A output (800A discharge), 250A max breaker (65°C Ambient)
DC Output Types -48V Single Voltage
Page 11
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Type Description Schematic
DC1E Single External Dual Voltage Bullet Breaker Distribution Panel
26 Positions for 23” conguration
Ratings: 800A primary voltage output (800A discharge) and up to 300A secondary voltage output, 250A max breaker (65°C Ambient)
DC2E Dual External Dual Voltage Bullet Breaker Distribution Panel
52 Positions for 23” conguration
Ratings: 800A primary voltage output (800A discharge) and up to 300A secondary voltage output, 250A max breaker (65°C Ambient)
DC Output Types For Dual Voltage Systems
Page 12
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Step 1: Select the Base Power System
ORDERING INFORMATION INFINITY S POWER SYSTEM
Single Voltage System -48V
Output
Rating Description AC Input LVD Frame Ordering
Code Model Photo
200A
200A Innity S
Power system
equipped with 4
rectier positions
and 26 distribution
positions selectable
between -48V Load
and Battery
Dual Molex No CC109163696 NES48 -23 -AC1 -PS4 -DC1E
Individual C19 No CC109163663 NES48 -23 -AC3 -PS4 -DC1E
Ind. Term Block No 150029007 NES48 -23 -AC5 -PS4 -DC1E
Dual Molex LVBD CC109160438 NES48 -23 -AC1 -PS4 -DC1E -LVBD
Individual C19 LVBD CC109167904 NES48 -23 -AC3 -PS4 -DC1E -LVBD
Ind. Term Block LVBD 150029001 NES48 -23 -AC5 -PS4 -DC1E -LVBD
400A
400A Innity S
Power system
equipped with 8
rectier positions
and 26 distribution
positions selectable
between -48V Load
and Battery
Dual Molex No CC109163705 NES48 -23 -AC1 -PS8 -DC1E
Individual C19 No CC109163671 NES48 -23 -AC3 -PS8 -DC1E
Ind. Term Block No 150029008 NES48 -23 -AC5 -PS8 -DC1E
Dual Molex LVBD CC109165998 NES48 -23 -AC1 -PS8 -DC1E -LVBD
Individual C19 LVBD CC109165981 NES48 -23 -AC3 -PS8 -DC1E -LVBD
Ind. Term Block LVBD 150029002 NES48 -23 -AC5 -PS8 -DC1E -LVBD
600A
600A Innity S
Power system
equipped with 12
rectier positions
and 26 distribution
positions selectable
between -48V Load
and Battery
Dual Molex No CC109163713 NES48 -23 -AC1 -PS12 -DC1E
Individual C19 No CC109163688 NES48 -23 -AC3 -PS12 -DC1E
Ind. Term Block No 150029009 NES48 -23 -AC5 -PS12 -DC1E
Dual Molex LVBD CC109167920 NES48 -23 -AC1 -PS12 -DC1E -LVBD
Individual C19 LVBD CC109167912 NES48 -23 -AC3 -PS12 -DC1E -LVBD
Ind. Term Block LVBD 150029003 NES48 -23 -AC5 -PS12 -DC1E -LVBD
600A
600A Innity S Power
system equipped
with 12 rectier
positions and 52
total distribution
positions, 26 of
which selectable
between -48V Load
and Battery
Dual Molex No CC109171286 NES48 -23 -AC1 -PS12 -DC2E
Individual C19 No CC109171261 NES48 -23 -AC3 -PS12 -DC2E
Ind. Term Block No 150029011 NES48 -23 -AC5 -PS12 -DC2E
Dual Molex LVBD CC109171278 NES48 -23 -AC1 -PS12 -DC2E -LVBD
Individual C19 LVBD CC109171253 NES48 -23 -AC3 -PS12 -DC2E -LVBD
Ind. Term Block LVBD 150029006 NES48 -23 -AC5 -PS12 -DC2E -LVBD
600A
600A Innity S
Power system
equipped with 16
rectier positions
and 26 distribution
positions selectable
between -48V Load
and Battery
Ind. Term Block No 150029010 NES48 -23 -AC5 -PS16 -DC1E
Ind. Term Block LVBD 150029004 NES48 -23 -AC5 -PS16 -DC1E -LVBD
800A
800A Innity S
Power system
equipped with 4
rectier positions
and 52 total
distribution
positions, 26 of
which selectable
between -48V Load
and Battery
Ind. Term Block No 150029012 NES48 -23 -AC5 -PS16 -DC2E
Ind. Term Block LVBD 150029006 NES48 -23 -AC5 -PS16 -DC2E -LVBD
Page 13
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Step 1: Select the Base Power System (cont.)
ORDERING INFORMATION INFINITY S POWER SYSTEM
Dual Voltage Innity S Power Systems, -48V Primary with +24V Secondary
Output
Rating Description AC Input LVD Frame Ordering
Code Model Photo
400A
400A Innity S
Power system
equipped with 8
universal positions
and 26 distribution
positions selectable
between -48V
Load and +24V
Converter load
Dual Molex No 150022649 NES4824-23-AC1-PS8-DC1E
Individual C19 No 150022653 NES4824-23-AC3-PS8-DC1E
Dual Molex LVBD 150022648 NES4824-23-AC1-PS8-DC1E-LVBD
Individual C19 LVBD 150022652 NES4824-23-AC3-PS8-DC1E-LVBD
400A
400A Innity S
Power system
equipped with
8 universal
positions and 52
total distribution
positions, 26
dedicated to -48V
and 26 of which
selectable between
-48V Load and 24V
Converter Load
Dual Molex LVBD 150024038 NES4824-23-AC1-PS8-DC2E-LVBD
Individual C19 LVBD 150024039 NES4824-23-AC3-PS8-DC2E-LVBD
800A
800A Innity S
Power system
equipped with 16
universal positions
and 26 distribution
positions selectable
between -48V
Load and +24V
Converter load
Dual Molex No 150022651 NES4824-23-AC1-PS16-DC1E
Individual C19 No 150022655 NES4824-23-AC3-PS16-DC1E
Dual Molex LVBD 150022650 NES4824-23-AC1-PS16-DC1E-LVBD
Individual C19 LVBD 150022654 NES4824-23-AC3-PS16-DC1E-LVBD
800A
800A Innity S Power
system equipped
with 16 universal
positions and 52
total distribution
positions, 26
dedicated to -48V
and 26 of which
selectable between
-48V Load and 24V
Converter Load
Dual Molex No CC109172508 NES4824-23-AC1-PS16-DC2E
Individual C19 No 150022657 NES4824-23-AC3-PS16-DC2E
Ind. Term Block No 150027199 NES4824-23-AC5-PS16-DC2E
Dual Molex LVBD CC109170643 NES4824-23-AC1-PS16-DC2E-LVBD
Individual C19 LVBD 150022656 NES4824-23-AC3-PS16-DC2E-LVBD
Ind. Term Block No 84"
Zone 4 150027200 NES4824-23-AC5-PS16-DC2E-7FTR
Page 14
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Step 1: Select the Base Power System (cont.)
ORDERING INFORMATION INFINITY S POWER SYSTEM
Dual Voltage Innity S Power Systems, +24V Primary with -48V Secondary
Output
Rating Description AC Input LVD Frame Ordering
Code Model Photo
800A
800A Innity S
Power system
equipped with 8
universal positions
and 26 distribution
positions selectable
between +24V Load
and -48V Converter
load
Dual Molex No CC109172524 NES2448-23-AC1-PS8-DC1E
Individual C19 No 150022660 NES2448-23-AC3-PS8-DC1E
Dual Molex LVBD CC109172516 NES2448-23-AC1-PS8-DC1E-LVBD
Individual C19 LVBD 150022659 NES2448-23-AC3-PS8-DC1E-LVBD
1000A
1000A Innity S
Power system
equipped with 16
universal positions
and 26 distribution
positions selectable
between+24V Load
and -48V Converter
load
Dual Molex No CC109163135 NES2448-23-AC1-PS16-DC1E
Individual C19 No 150022662 NES2448-23-AC3-PS16-DC1E
Dual Molex LVBD CC109160818 NES2448-23-AC1-PS16-DC1E-LVBD
Individual C19 LVBD 150022661 NES2448-23-AC3-PS16-DC1E-LVBD
1000A
1000A Innity S
Power system
equipped with 16
universal positions
and 52 total
distribution positions,
26 dedicated to +24V
and 26 of which
selectable between
+24V Load and -48V
Converter Load
Dual Molex No CC109172540 NES2448-23-AC1-PS16-DC2E
Individual C19 No 150022664 NES2448-23-AC3-PS16-DC2E
Ind. Term Block No 150027197 NES2448-23-AC5-PS16-DC2E
Dual Molex LVBD CC109172532 NES2448-23-AC1-PS16-DC2E-LVBD
Individual C19 LVBD 150022663 NES2448-23-AC3-PS16-DC2E-LVBD
Ind. Term Block No 84"
Zone 4 150027198 NES2448-23-AC5-PS16-DC2E-7FTR
Page 15
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Rectiers
Ordering Code Model Photo
CC109160834 95 - 145Vac input, 24V, 44A Output, 175 - 275Vac input, 24V, 100A output;
145 - 175 linear output increase from 44A to 100A
100A NE100AC24ATEZ
150027075 95 - 145Vac input, 24V, 44A Output, 175 - 275Vac input, 24V, 100A output;
145 - 175 linear output increase from 44A to 100A
100 - 310 VDC input from Solar resource with full power above 250VDC.
100A NE100ECO24ATEZ
CC109158878 95 - 145Vac input, 48V, 22A Output, 175 - 275Vac input, 48V, 50A output;
145 - 175 linear output increase from 22A to 50A
50A NE050AC48ATEZ
150027074 95 - 145Vac input, 48V, 22A Output, 175 - 275Vac input, 48V, 50A output;
145 - 175 linear output increase from 22A to 50A
100 - 310 VDC input from Solar resource with full power above 250VDC.
50A NE050ECO48ATEZ
Step 2: Select Rectiers and Converters
ORDERING INFORMATION INFINITY S POWER SYSTEM
Converters
Ordering Code Model Photo
CC109112471 21-29 Vdc input, 48V, 30A output
30A NE030DC48
CC109142881 42-58 Vdc input, 24V, 75A output
75A NE075DC24
Page 16
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Alarm Cables
Ordering Code Model Photo
CC848865980 15ft Auxiliary input alarm cable for Pulsar Plus Controller
CC848817651 50ft Auxiliary input alarm cable for Pulsar Plus Controller
CC848817668 150ft Auxiliary input alarm cable for Pulsar Plus Controller
CC109157442 15ft alarm cable for Pulsar Plus Controller
CC848817635 50ft alarm cable for Pulsar Plus Controller
CC848817643 150ft alarm cable for Pulsar Plus Controller
Step 4: Select Alarm Cables
Step 3: Select AC Cord
Example: 208/240VAC for a NES48-AC1-PS4-DC1E-LVBD shelf using 50A rectiers would use a 848710711 AC 8 gauge which provides 2 AC cords;
enough to power 4 rectiers. Customer should provide one 40A protecting circuit breaker per two rectiers. For AC3 cable sets, it is recommended
that a 20A circuit breaker is used per rectier. Note: If PS# of your shelf model number is not listed in table, choose the next higher number. AC cords
are 10 feet long and unterminated on the end. See optional accessories for twist lock connectors.
Ordering
Code
AC
Type Gauge Shelf
Termination
Order # of Cords Cord
Type Length User
Termination
120
Vac
208/240
Vac
Shelf Dual Indiv.
CC848801977
AC1 8
Molex 1xSleeved 3' Unterminated x x
CC848830522 Molex 1xSleeved 4' Unterminated
848710711 Molex 1xSleeved 10' Unterminated
CC848906586 Molex 2 x SO 10' Unterminated
CC848773515 10 Molex 2 x SO 15' Unterminated
CC848847368
AC3
12 IEC - No Plug 4 x SO 8' Unterminated x x
CC848850792 12 IEC 5-15P 4 x SO 8' 5-15P x
CC848850801 12 IEC 5-20P 4 x SO 8' 5-20P x
CC848850826 12 IEC 6-15P 4 x SO 8' 6-15P x
CC848850834 12 IEC 6-20P 4 x SO 8' 6-20P x
CC848850842 12 IEC L6-20P 4 x SO 8' L6-20P x
CC848850850 12 IEC L6-30P 4 x SO 8’ L6-30P X
ORDERING INFORMATION INFINITY S POWER SYSTEM
Page 17
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Step 5: Select Distribution Components
Note: Innity S systems all support plug-in (bullet style) breakers or fuse modules. Larger breakers can be 2 or even 3 poles.
The multi-pole breakers MUST be used with the appropriate multi-pole adapter to parallel the poles for proper operation.
Bullet Style Load Circuit Breakers
Ordering Code Amperage CB Positions (Poles) Min Wire Gauge Photo
407998137 3110
407998145 5110
407998152 10 110
407998160 15 110
407998178 16 110
407998186 20 110
407998194 25 110
407998202 30 110
408213486 40 18
407998210 45 18
407998228 50 16
407998236 60 16
407998244 70 12
407998251 80 12
407998269 90 12
407998277 100 12
CC848808551 100 2 2
408185353 125 2 2
408185346 150 21/0
408564941 200 32/0
408573975 225 34/0
408535752 250 34/0
CC848756916 2-pole Adapter bus for 100-150A breakers (order 2 per 2 pole breaker to
accommodate load and return lugs)
850021775 2-pole Adapter bus for 100-150A breakers; used for 3/8” on 1” lugs (order 2 per
2 pole breaker to accommodate load and return lugs)
CC848756924 3-pole Adapter bus for 200-250A breakers (order 2 per 3 pole breaker to
accommodate load and return lugs)
850021955 3-pole Adapter bus for 200-250A breakers; centered connection (order 2 per
3 pole breaker to accommodate load and return lugs)
ORDERING INFORMATION INFINITY S POWER SYSTEM
Page 18
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Bullet Style Fuse Holder and TPS Fuses
Ordering Code Amperage WP-92461 List Min Wire Gauge Photo
406700567 3100 10
406700583 5101 10
406700591 6102 10
406700609 10 103 10
406700617 15 104 10
406700625 20 105 10
406700633 25 106 10
406700641 30 107 10
406700658 40 108 10
406700674 50 109 8
406700682 60 110 6
406700690 70 111 6
402328926 0.18 Alarm Fuse
408548944 Bullet Fuse Holder, TFD-101-011-09
(Alarms on Blown Fuse or Fuse Head Removal)
CC408617410 Bullet Fuse Holder, TFD-101-011-10 (Alarms on Blown Fuse Only)
ORDERING INFORMATION INFINITY S POWER SYSTEM
Step 5: Select Distribution Components (cont.)
Bullet Battery Circuit Breakers (Yellow Handle) (Alarms on Mid-trip and in O position)
Ordering Code Amperage Ordering Code Amperage Photo
CC408612758 30 CC408574387 70
CC408612766 40 CC408574395 100 (2-pole)
CC408612774 45 CC408574404 125 (2-pole)
CC408574370 50 CC408574412 150 (2-pole)
408560123 60 CC408574420 200 (2-pole)
CC109106548 100A battery bullet bus strap (substitute for battery breaker)
Page 19
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Terminal Lugs for Bullet Style Breakers and TPS Fuses (1/4” bolt on 5/8” centers)
Ordering Code STR Wire GA (Class B) Flex Wire GA (Class I) WP-91412 List Photo
406021626 8 8 75
405347519 6 6 3
405347576 4 4 5
405348202 2 - 54
405347683 - 2 8
Terminal Lugs for Battery and Large Breakers (3/8” bolt on 1” centers)
406338665 2 - -
405348228 1/0 - -
405348236 2/0 1/0 -
406021725 -2/0 -
405348251 4/0 - -
405347923 -4/0 -
ORDERING INFORMATION INFINITY S POWER SYSTEM
Step 5: Select Distribution Components (cont.)
Bullet Style GMT Fuse Holder and GMT Fuses
Ordering Code Amperage WP-92461 List Min Wire Gauge Photo
405006222 0.25A
3150439 0.5A
405673146 1.33A
405181983 2A
406976985 3A
406159061 5A
405725433 7.5A
406159236 10A
407845197 12A
406473959 15A
CC109103157 6-pos GMT Bullet Fuse Holder (Requires 2 bullet postions)
408515823 Fuse Puller
402099436 Dummy Fuse
Page 20
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Step 6: Select Battery Monitoring
Ordering Code Description Photo
CC109142980 QS873A Thermal Probe (A)
CC848817024 10 ft wire set (B: thermal probe to controller)
CC109157434 20 ft wire set (B:thermal probe to controller)
CC848822560 1 ft wire set (C: thermal probe to thermal probe)
848719803 5 ft wire set (C: thermal probe to thermal probe)
CC848822321 10 ft wire set (C: thermal probe to thermal probe)
850027334 20 ft wire set (C: thermal probe to thermal probe)
108958422 ES771A Battery Voltage Monitor Card
CC848791517 2-1/2 ft wire set (D: ES771A to thermal probe)
CC848797290 6 ft wire set (D: ES771A to thermal probe)
848719829 10 ft wire set (D: ES771A to thermal probe)
CC848791500 4 ft wire set (G: ES771A to ES771A or controller)
848652947 10 ft wire set (G: ES771A to ES771A or controller)
555052-1 In-Line Coupler (for extending item G above)
Temperature/Voltage probes are needed for battery monitoring. They are connected to each battery or battery string to provide slope thermal compensation, temperature
alarms and voltage imbalance alarms.
Temperature Measurement
Temperature and Voltage Measurement
ORDERING INFORMATION INFINITY S POWER SYSTEM
Page 21
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
Mechanical
Height 4RU main cabinet plus 1RU per power shelf – Base system 5RU (8.75 inches / 222mm)
Width (with mounting ears) 23 inches (584mm)
Depth 18 inches (457mm), 21 inches (533mm) for systems equipped with AC5 input
Weight (without rectiers) Approximately 42lbs (19kg) – Base system with 1 rectier shelf
Environmental
NEBs Evaluated by independent NRTL test lab to Telcordia GR63, Issue 3 and GR1089-CORE, Issue 5
Safety CSA C22.2 No. 60950-1-03 Certied for Canada and U.S.; UL60950-1 1st Ed.
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS 5/6
EMC European Directive 2004/108/EC; EN55022, Class A; EN55024; FCC, Class A; GR1089-CORE, Issue 5
Agency Certications
UL CSA C22.2 No 60950-1-03 and UL 60950-1 1st Ed
EMI/EMC European Directive 2004/108/EC; EN55022 (CISPR22) Class A; EN55024 (CISPR24)
NEBS LEVEL 3 GR1089-CORE, Issue 5
Shelf Specications
Product Documentation
H5692448: Ordering Guide. A copy of the appropriate installation manuals below ship with each system.
CC848815325: H5692448 Installation Guide
CC848815341: Advanced Features User Guide for the Pulsar Plus Controller, 167-792-183
Additional Information
ORDERING INFORMATION INFINITY S POWER SYSTEM
Contact Us
For more information, call us toll free
at +1 877 546 3243, or +1 972 244 9288
and visit us on the web at
www.ge.com/powerelectronics
© 2013 General Electric Company. All rights reserved.
Innity S Product Line Brochure01/13
ORDERING INFORMATION INFINITY S POWER SYSTEM
Management Visibility
Galaxy Manager™ software is the centralized visibility and control
component of a comprehensive power management system designed
to meet engineering, operations and maintenance needs. The Galaxy
Manager client-server architecture enables remote access to system
controllers across the power network.
Dashboard display with one-click access to management
information database
Trend analysis
Scheduled or on demand reports
Fault, conguration, asset, and performance management
Training
GE oers on-site and classroom training options based on certication
curriculum. Technical training can be tailored to individual customer
needs. Training enables customers and partners to more eectively
manage and support the power infrastructure. We have built our
training program on practical learning objectives that are relevant to
specic technologies or infrastructure design objectives.
Service & Support
GE eld service and support personnel are trusted advisors to our
customers – always available to answer questions and help with any
project, large or small. Our certied professional services team consists
of experts in every aspect of power conversion with the resources
and experience to handle large turnkey projects along with custom
approaches to complex challenges. Proven systems engineering and
installation best practices are designed to safely deliver results that
exceed our customers’ expectations.
Warranty
GE is committed to providing quality products and solutions. We
have developed a comprehensive warranty that protects you and
provides a simple way to get your products repaired or replaced as
soon as possible.
For full warranty terms and conditions please go to
www.ge.com/powerelectronics.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
GE (General Electric):
848710711