Three Phase External Power Line Filter for Frequency Converters
The FCD filters provide three phase filtering for frequency
inverters and variable speed motor drives. Designed for
very noisy Delta applications, they attenuate conducted
interference at low and high frequency ranges and better
protect programmable logic controllers from RF noise on
the AC power line. These filters perform best when installed
on the line side of the motor drive. The FCD filters better
prevent noise from returning to the line, enabling
equipment to meet strict European regulations on RFI.
Suited for field wiring applications, these filters are ideal for
EMC troubleshooting and field refurbishing. The FCD filters
feature side flanges for easy mounting and DIN type
terminals which eliminate live metal parts, allowing safer
and easier connection. They could also be sold as an
accessory to motor drives marketed into Europe.
Specifications
Maximum leakage current,each line-to-ground
6Amps 16 Amps 25-50 Amps
@120 VAC 60 Hz: 2.9 mA 4.9 mA 5.7 mA
@250 VAC 50 Hz: 4.9 mA 7.7 mA 9.8 mA
Hipot rating (one minute):
line-to-ground 2250 VDC
line-to-line 1450 VDC
Operating frequency: 50/60 Hz
Rated voltage (max.): 480 VAC phase-to-phase
277 VAC phase-to-neutral/ground
Rated current:
06FCD 6A
16FCD 16A
25FCD 25A
36FCD 36A
50FCD 50A
Minimum insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current Frequency–MHz
Rating .01 .03 .05 .1 .5 1 5 10 30
6A 214 23 39 56 52 48 45 33
16A 13 30 36 45 75 75 52 45 35
25A 13 30 36 45 75 75 52 45 35
36A 9 26 32 40 75 75 52 45 35
50A 9 26 32 40 75 75 52 45 35
Line-to-line in 50 ohm circuit
Current Frequency–MHz
Rating .01 .03 .05 .1 .5 1 5 10 30
6A 9 824 40 62 57 50 48 38
16A 9 13 24 55 75 75 75 65 60
25A 9 13 26 55 75 75 75 65 60
36A 913 26 46 75 75 75 65 60
50A 9 13 26 46 75 75 75 65 60
60 Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
FCD Series
FCD Series
CORCOM Product Guide
UL Recognized
Electrical Schematics
Resistor location for reference only.
6Amp
16, 25, 36 & 50 Amps
LINE LOAD
LINE LOAD
FCD10
Three Phase External Power Line Filter for Frequency Converters (Continued)
Case Dimensions
ABCDEF
Part No. (max) (max) (max) (max)
6FCD10 6.00 4.30 2.30 3.74 5.15 2.756
152.4 109.2 58.4 95.0 128.3 70.0
16FCD10 7.20 5.48 2.55 4.92 5.94 2.756
182.9 139.2 64.8 124.97 150.9 70.0
25FCD10 9.69 6.30 2.55 5.71 8.46 4.528
246.1 160.0 64.8 145.0 215.0 115.01
36FCD10 9.69 6.30 2.55 5.71 8.46 4.528
246.1 160.0 64.8 145.0 215.0 115.01
50FCD10 10.5 6.30 2.54 5.71 8.46 4.528
266.7 160.0 64.52 145.0 215.0 115.01
61
Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.corcom.com
Revised 05-07 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject Germany: 49-89-6089-0
are metric equivalents. to change.
RFI Power Line Filters
FCD Series
CORCOM Product Guide
Case Style
Part Numbers
06FCD10
16FCD10
25FCD10
36FCD10
50FCD10
E
A
BD
Slots: .260
6.61 (4)
F
LABEL
L
I
N
E
L
O
A
D
C
Type (qty.) Torque in. lb.
6FCD10, 16FCD10
Phoenix contacts VDFK4 (6) 5.31 min.
Accepts 12 AWG stranded wire. Strip length 0.315
25FCD10, 36FCD10
Phoenix contacts VDFK6 (6) 13.28 min.
Accepts 10 AWG stranded wire. Strip length 0.354
50FCD10
Phoenix contacts HDFK10-VP (6) 13.28 min
Accepts 8 AWG stranded wire. Strip length 0.433
Note: Terminals No. 8-32 (2)