Description
Overload protection – trip class 10A
Phase loss sensitivity
Disconnect function
Temperature compensation from -25 … +55 °C
Adjustable current setting for overload protection
Suitable for three- and single-phase application
Trip-free mechanism
Clear switch position indication ON/OFF
Order data
MS116 screw terminal
Setting
range
A
Type Trip
class
Order code
Pack-
ing unit
PCE
Weight
per PCE
kg
0.10...0.16 MS116-0.16 10A 1SAM250000R1001 10.225
0.16...0.25 MS116-0.25 10A 1SAM250000R1002 10.225
0.25...0.40 MS116-0.4 10A 1SAM250000R1003 10.225
0.40...0.63 MS116-0.63 10A 1SAM250000R1004 10.225
0.63...1.00 MS116-1.0 10A 1SAM250000R1005 10.225
1.00...1.60 MS116-1.6 10A 1SAM250000R1006 10.265
1.60...2.50 MS116-2.5 10A 1SAM250000R1007 10.265
2.50...4.00 MS116-4.0 10A 1SAM250000R1008 10.265
4.00...6.30 MS116-6.3 10A 1SAM250000R1009 10.265
6.30...10.0 MS116-10 10A 1SAM250000R1010 10.265
8.00...12.0 MS116-12 10A 1SAM250000R1012 10.265
10.0...16.0 MS116-16 10A 1SAM250000R1011 10.265
16.0...20.0 MS116-20 10A 1SAM250000R1013 10.310
20.0...25.0 MS116-25 10A 1SAM250000R1014 10.310
25.0...32.0 MS116-32 10A 1SAM250000R1015 10.310
Note: MS116 with pre-assembled auxiliary contact HKF1-11,
please order as follow 1SAM250005Rxxxx
Manual motor starters are electro-
mechanical protection devices for the
main circuit. They are used mainly to
switch motors manually ON/OFF
and protect them fuse less against
short-circuit, overload and phase
failures.
Fuse less protection with a manual
motor starter saves costs, space and
ensures a quick reaction under short-
circuit condition, by switching off the
motor within milliseconds. Fuse less
starter combinations are setup together
with contactors.
Manual motor starter MS116
Data sheet
2CDC241001V0013
2 - 2CDC131025D0202
Functional description
2CDC242032F0013
1
2
3
4
1 Terminals 1L1, 3L2, 5L3
2 Test function
3 Current setting range / Adjustable current setting for overload protection
4 Terminals 2T1, 4T2, 6T3
Application
The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole
protection devices with thermal tripping elements for overload protection and electromagnetic tripping elements for short-
circuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and
can be used for the manual switching of loads.
The manual motor starters have a setting scale in amperes, which allows the direct adjusting of the device without any
additional calculation. In compliance with international and national standards, the setting current is the rated current of the
motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current).
Operation mode
2CDC242023F0009
Single-phase operation
2CDC242028F0013
Single-phase operation
2CDC242024F0009
Three-phase operation
Wiring diagram
1L1 3L2 5L3
2T1 4T2 6T3
2CDC242025F0009
2CDC131025D0202 - 3
Resistance and power loss per pole
Type Setting range Resistance per pole Power loss per pole
lower value
A
upper value
A
Ω
at lower value
W
at upper value
W
MS116-0.16 0.10 0.16 66.00 0.7 1.7
MS116-0.25 0.16 0.25 25.50 0.7 1.7
MS116-0.4 0.25 0.40 10.38 0.7 1.7
MS116-0.63 0.40 0.63 4.36 0.7 1.7
MS116-1.0 0.63 1.00 1.605 0.7 1.7
MS116-1.6 1.00 1.60 0.648 0.7 1.7
MS116-2.5 1.60 2.50 0.292 0.7 1.8
MS116-4.0 2.50 4.00 0.114 0.7 1.8
MS116-6.3 4.00 6.30 0.046 0.7 1.8
MS116-10 6.30 10.0 0.024 0.9 2.4
MS116-12 8.00 12.0 0.016 1.0 2.3
MS116-16 10.0 16.0 0.011 1.1 2.8
MS116-20 16.0 20.0 0.0057 1.5 2.3
MS116-25 20.0 25.0 0.0045 1.8 2.8
MS116-32 25.0 32.0 0.0030 1.9 3.1
Technical diagram
duty ratio
switching frequency
(Op/h)
(%)
t = 1 s
a
t = 1.5 s
a
t = 3 s
a
t = 5 s
a
t = 0.5 s
a
140
120
0
20
40
60
80
100
020406080 100
2CDC232005F0211
Intermittent periodic duty, ta: Motor starting time
4 - 2CDC131025D0202
Dimensions
in mm / inches
0.06"
0.07"
0.55"
3.54"
1.77"
0.55"
1.38"
0.22"
1.77"
2.3"
2.76"
1.71"
3.15"
1.1"
2.95"
1.5
1.7
14 14
90
45
35
5.5
45
57.8
70
43.5
80.1
27.5
75
2CDC242002F0010
1.77"
2.3"
1.38"
0.22"
2.75"
1.7"
3.15"
0.55"
2.95"
3.85"
1.77"
0.55"
0.06"
0.07"
1.1"
45
57.8
35
5.5
69.8
43.3
79.9
14 14
75
97.8
45
1.5
1.7
27.5
2CDC242001F0011
MS116 ≤ 16 A MS116 ≥ 20 A
Ø 0.18" 0.35"
0.21"
0.69"
4.8"
4.33"
Ø 4.5 9
5.4
17.5
122
110
2CDC242003F0010
Ø 0.18" 0.35" 0.21"
0.69"
4.8"
4.33"
Ø 4.5 9 5.4
17.5
122
110
2CDC242002F0011
MS116 ≤ 16 A with screw fixing kit FS116 (accessory) MS116 ≥ 20 A with screw fixing kit FS116 (accessory)
2CDC131025D0202 - 5
Main accessories for manual motor starter
1SBC500341F0000
MS116
UA1
HKF1-11
AA1
SK1
HK1
CK1
CK1
HK1
HK1
SK1
HK1
S1-M1-25
PS1-..-65
BS1-3
PS1-..-65
S1-M2-25
MS132
S1-M1-25
PS1-..-100
BS1-3
SA1
3-phase busbar
up to 100 A
3-phase busbar
up to 65 A
6 - 2CDC131025D0202
Technical data IEC/EN
Data at TA = 40 °C and at rated values, if nothing else indicated
Main circuit
1L1-3L2-5L3
2T1-4T2-6T3
Rated operational voltage Ue690 V AC
- V DC
Setting range - thermal overload protection see table “Order data” on page 1
Rated operational current Iesee table below
Rated instantaneous short-circuit current setting Iisee table below
Rated service short-circuit breaking capacity Ics see table “Short-circuit breaking capacity and back-
up fuses” on page 8
Rated ultimate short-circuit breaking capacity Icu
Trip class see table “Order data” on page 1
Rated frequency 50/60 Hz
Number of poles 3
Resistance per pole see table “Resistance and power loss per pole” on
page 3
Power loss per pole
Isolation data
Rated impulse withstand voltage Uimp 6 kV
Rated insulation voltage Ui690 V
Pollution degree 3
Electrical connection
MS116 ≤ 16 A MS116 ≥ 20 A
Connecting capacity solid 1/2 x 1 ... 4 mm² 1/2 x 1 ... 2.5 mm²
1/2 x 2.5 … 6 mm²
stranded 1/2 x 1 ... 4 mm² 1/2 x 1 ... 2.5 mm²
1/2 x 2.5 … 6 mm²
flexible with ferrule 1/2 x 0.75 ... 2.5 mm² 1/2 x 0.75 … 6 mm²
flexible with insulated ferrule 1/2 x 0.75 ... 2.5 mm² 1/2 x 0.75 … 6 mm²
flexible without ferrule 1/2 x 0.75 ... 2.5 mm² 1/2 x 1 ... 2.5 mm²
1/2 x 2.5 … 6 mm²
Stripping length 9 mm 10 mm
Tightening torque 0.8 … 1.2 Nm 2 Nm
Recommended screw driver M3.5 M4
Type Rated instantaneous
short-circuit current setting li
Rated operational current le
A A
MS116-0.16 2.00 0.16
MS116-0.25 3.13 0.25
MS116-0.4 5.00 0.40
MS116-0.63 7.88 0.63
MS116-1.0 12.50 1.0
MS116-1.6 20.00 1.6
MS116-2.5 31.25 2.5
MS116-4.0 50.00 4.0
MS116-6.3 78.75 6.3
MS116-10 150 10
MS116-12 180 12
MS116-16 240 16
MS116-20 300 20
MS116-25 375 25
MS116-32 480 32
2CDC131025D0202 - 7
General data
Mechanical durability 100000
Electrical durability MS116 ≤ 16 A 100000
MS116 ≥ 20 A 50000
Duty time 100 %
Operating frequency without early tripping up to 15 operations/h or 60 operations/h with
40 % duty ratio, if the motor breaking current 6 x In
and the motor starting time does not exceed 1 s
Dimensions (W x H x D) see drawing on page 6
Weight see table “Order data” on page 1
Mounting DIN-rail (EN 60715)
Mounting position position 1-6 (optional for single mounting)
Group mounting on request
Minimum distance to other units same type horizontal 0 mm
vertical 150 mm
Minimum distance to electrical conductive board horizontal, up to 400 V 0 mm
horizontal, up to 690 V > 1.5 mm
vertical 75 mm
Degree of protection housing IP20
main circuit terminals IP10
Utilization category A
Maximum operating altitude permissible 2000 m
Maximum operating frequency 170 cycles/h
Electromagnetic compatibility
Electromagnetic compatibility not applicable
Environmental data
Ambient air temperature
Operation
open - compensated
-25 ... +55 °C
open
-25 ... +70 °C
enclosed (IB132) 0 ... +40 °C
Storage -50 ... +80 °C
Ambient air temperature compensation acc. to IEC/EN 60947-4-1
Resistance to vibrations acc. to IEC 60068-2-6 5g / 3 ... 150 Hz
Resistance to shock acc. to IEC 60068-2-27 25g / 11 ms
Standards / directives
Standards IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
RoHS Directive 2002/95/EC
8 - 2CDC131025D0202
Short-circuit breaking capacity and back-up fuses
lCS Rated service short-circuit breaking capacity
lCU Rated ultimate short-circuit breaking capacity
ICC Prospective short-circuit current at installation location
Note: Maximum rated current of the back-up fuses if ICC > ICS
Type 230 V AC 400 V AC 440 V AC 500 V AC 690 V AC
ICS
kA
ICU
kA
gG, aM
A
ICS
kA
ICU
kA
gG, aM
A
ICS
kA
ICU
kA
gG, aM
A
ICS
kA
ICU
kA
gG, aM
A
ICS
kA
ICU
kA
gG, aM
A
MS116-0.16
No back-up fuse required up to ICC = 50 kA
No back-up fuse required up to ICC = 30 kA
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
10 10 25 10 10 25 5 5 25
MS116-4.0
6 6 25 6 6 25 2 2 25
MS116-6.3
6 6 63 6 6 63 2 2 40
MS116-10
6 6 63 6 6 63 2 2 50
MS116-12
25 25 80 25 25 80 6 6 63 6 6 63 2 2 50
MS116-16
16 16 80 16 16 80 6 6 63 4 4 63 2 2 63
MS116-20
10 15 125 10 15 125 3 6 125 3 4 125 2 2 80
MS116-25
10 15 125 10 15 125 3 6 125 3 4 125 2 2 100
MS116-32
10 10 125 10 10 125 3 6 125 3 4 125 2 2 100
2CDC131025D0202 - 9
Technical data UL/CSA
Main circuit
Maximum operational voltage 600 V
Manual Motor Controller ratings
see table “UL 508 — Manual Motor Controller” on page 10
Motor ratings Horse power see table below
Full load amps (FLA) see table below
Locked rotor amps (LRA) see table below
Electrical connection
MS116 ≤ 16 A MS116 ≥ 20 A
Connecting capacity stranded 1/2 x AWG 16 ... 12 1/2 x AWG 16 ... 8
flexible without ferrule 1/2 x AWG 16 ... 12 1/2 x AWG 16 ... 8
Stripping length 9 mm 10 mm
Tightening torque 10 ... 12 lb-In 18 lb-In
Recommended screw driver M3.5 M4
Motor rating, single phase
hp Horse power
FLA Full load amps
LRA Locked rotor amps
Type 120 VAC 220-240 VAC
hp FLA LRA hp FLA LRA
MS116-0.16 - 0.16 0.96 - 0.16 0.96
MS116-0.25 -0.25 1.5 -0.25 1.5
MS116-0.4 -0.4 2.4 -0.4 2.4
MS116-0.63 -0.63 3.78 -0.63 3.78
MS116-1.0 - 1 6 -1.0 6.0
MS116-1.6 -1.6 9.6 1/10 1.5 -
MS116-2.5 -2.5 15 1/6 2.2 -
MS116-4.0 1/8 4 24 1/3 3.6 -
MS116-6.3 1/4 6.3 37.8 1/2 4.9 -
MS116-10 1/2 9.8 58.8 1-1/2 10 -
MS116-12 1/2 9.8 58.8 212 -
MS116-16 1 16 96 212 -
MS116-20 1-1/2 20 120 317 92
MS116-25 2 24 144 317 127
MS116-32 2 24 144 528 162
Motor rating, three phase
hp Horse power
FLA Full load amps
LRA Locked rotor amps
Type 220-240 VAC 440-480 VAC 550-600 VAC
hp FLA LRA hp FLA LRA hp FLA LRA
MS116-0.16 - 0.16 0.96 - 0.16 0.96 - 0.16 0.96
MS116-0.25 -0.25 1.5 -0.25 1.5 -0.25 1.5
MS116-0.4 -0.4 2.4 -0.4 2.4 -0.4 2.4
MS116-0.63 -0.63 3.78 -0.63 3.78 -0.63 3.78
MS116-1.0 -1.0 6.0 1.0 6.0 1/2 0.9 8
MS116-1.6 -1.6 9.6 3/4 1.6 12.5 3/4 1.3 10
MS116-2.5 1/2 2.2 20 12.1 15 1-1/2 2.4 16
MS116-4.0 14.2 30 23.4 25 33.9 25.6
MS116-6.3 1-1/2 6.4 40 34.8 32 56.1 36.8
MS116-10 39.6 64 57.6 46 7-1/2 950.8
MS116-12 39.6 64 7-1/2 11 63.5 10 11 64.8
MS116-16 515.2 92 10 20 81 10 11 64.8
MS116-20 515.2 92 10 14 81 15 17 93
MS116-25 7-1/2 22 127 15 21 116 20 22 116
MS116-32 10 28 162 20 27 145 25 27 146
10 - 2CDC131025D0202
UL 508 — Manual Motor Controller
Type Maximum fuse type
K5 o. RK5 per UL/NEC
Maximum short-circuit current
for motor disconnect1) for group installation
480 V / 600 V
A
480 V
kA
600 V
kA
480 V
kA
600 V
kA
MS116-0.16 100 30 518 5
MS116-0.25 100 30 518 5
MS116-0.4 100 30 518 5
MS116-0.63 100 30 518 5
MS116-1.0 100 30 518 5
MS116-1.6 100 30 518 5
MS116-2.5 100 30 518 5
MS116-4.0 100 18 518 5
MS116-6.3 100 18 518 5
MS116-10 100 18 518 5
MS116-12 100 18 518 5
MS116-16 100 18 518 5
MS116-20 100 18 518 5
MS116-25 100 18 518 5
MS116-32 100 18 518 5
1) Suitable as motor disconnect only when provided with padlock SA1 or SA3...
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82
69123 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0
Fax: +49 (0) 6221 7 01-13 25
E-Mail: info.desto@de.abb.com
You can find the address of your
local sales organization on the
ABB home page
http://www.abb.com/contacts
-> Low Voltage Products and Systems
Contact us
Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does
not accept any responsibility whatsoever for
potential errors or possible lack of information in
this document.
We reserve all rights in this document and in
the subject matter and illustrations contained
therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole
or in parts – is forbidden without prior written
consent of ABB AG.
Copyright© 2016 ABB
All rights reserved
Document number 2CDC131025D0202 (04.2016)