ACDC 120480 Watts DNR Series xppower.com * Up to 90% Efficiency * Wide Adjustment Range * Parallel Function * DC Standby Versions * Full Power from 40 C to +60 C * Connector Options * 3 Year Warranty Specification Input General * 90-132/180-264 VAC, auto select, 210-375 VDC (DNR120AS, DNR240PS) 90-264 VAC, 120-375 VDC (DNR480PS) Input Frequency * 47-63 Hz Input Current * See tables Inrush Current * 24/48 A at 115/230 VAC (DNR120) 30/60 A at 115/230 VAC (DNR240) 25/50 A at 115/230 VAC (DNR480) Power Factor * 0.7 typical (DNR120, DNR240) 0.9 typical (DNR480) Earth Leakage Current * 0.8 mA max Input Protection * T3.15A, 250 VAC (DNR120) T6.3A, 250 VAC (DNR240) T10A, 250 VAC (DNR480) Input Voltage Output Output Voltage Output Voltage Trim Initial Set Accuracy Minimum Load Start Up Delay * * * * * Start Up Rise Time Hold Up Time Line Regulation Load Regulation Parallel Operation * * * * * Transient Response * Ripple & Noise * Overvoltage Protection * Overload Protection Temp. Coefficient * * See tables See tables 1% No minimum load required <1 s (may increase at low temperature extremes) <150 ms 25/30 ms at 115/230 VAC 0.5% max 1% (5% for units in parallel) A maximum of 3 units can be paralleled (not with standby system). Total power available is 90% of the rated current of each unit. Minimum load per unit 10%. Redundancy module DPM10 available for load currents up to 10 A, contact sales. 4% max deviation recovering to within 1% in 2 ms for a 50% load change 50 mV pk-pk (DNR120) 100 mV pk-pk (DNR240, DNR480) 20 MHz bandwidth (may increase at low temperature extremes) Output clamps at 125-140% Vnom, auto recovery 105-145% constant current, auto recovery 0.03%/C Efficiency Isolation Switching Frequency Signals MTBF DIN Rail * See table * 3000 VAC Input to Output 1500 VAC Input to Ground 500 VAC Output to Ground * See table * DC ON indicator Green LED, DC LOW indicator Red LED DC OK: 24 V and standby models * 430 kHrs typical Bellcore, Issue 6 at +40 C, GB * Compatible with TS35/7.5 or TS35/15 Environmental Operating Temperature * DNR120: -35 C to +70 C, derate linearly from +60 C at 2.5%/C, start up at -30 C DNR240: -40 C to +70 C, derate linearly from +60 C at 2.5%/C, start up at -35 C DNR480: -40 C to +70 C, derate linearly from +55 C at 2.5%/C, start up at -35 C (see derating curves) Cooling * Convection-cooled with 25mm free space all sides Operating Humidity * 20-95% RH, non-condensing Storage Temperature * -40 C to +85 C Shock * 15 g, 11 ms, 3 axes, 6 faces, 3 shocks per face Vibration * 2 g, 10 Hz to 500 Hz, along X, Y & Z axis, 60 min/axis, mounted on rail EMC & Safety Emissions Harmonic Currents Voltage Flicker ESD Immunity Radiated Immunity EFT/Burst Surge * * * * * * * Conducted Immunity Magnetic Field Dips & Interruptions * * * Safety Approvals * EN55022, class B conducted & radiated EN61000-3-2, class A EN61000-3-3 EN61000-4-2, level 4 Perf Criteria A EN61000-4-3, level 3 Perf Criteria A EN61000-4-4, level 4 Perf Criteria A EN61000-4-5, installation class 3, Perf Criteria A EN61000-4-6, level 3 Perf Criteria A EN61000-4-8, level 4 Perf Criteria A EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms Perf Criteria A, A, B EN60950-1 UL508 UL60950-1, cUL60950-1 Pollution Degree 2, CE Mark, UL60950-1 Overvoltage Category II, UL508 Overvoltage Category III, ANSI/ISA 12.12.01. (Class 1, Division 2, Groups A,B,C and D) Output Voltage 12 V 24 V 48 V 24 V 48 V 24 V 48 V Input Current (typ.) 115 VAC 230 VAC 2.20 A 0.83 A 2.20 A 0.83 A 2.20 A 0.83 A 4.00 A 1.55 A 4.00 A 1.55 A 4.90 A 2.50 A 4.90 A 2.50 A Output Voltage Trim 11.4-14.5 V 22.5-28.5 V 45.0-55.0 V 22.5-28.5 V 47.0-56.0 V 22.5-28.5 V 47.0-56.0 V Output Current 10.0 A 5.0 A 2.5 A 10.0 A 5.0 A 20.0 A 10.0 A Efficiency (typ.) 84% 86% 87% 89% 90% 89% 90% Typical Switching Frequency 80 kHz 80 kHz 80 kHz 40 kHz 40 kHz 65 kHz 65 kHz Model Number DNR120AS12-I(1,2) DNR120AS24-I(1,2) DNR120AS48-I(1,2) DNR240PS24-I(1,2) DNR240PS48-I(1,2) DNR480PS24-I((1,2) DNR480PS48-I((1,2) Notes 1. Add suffix `D' for detachable connector option. 2. For DC standby, remove `-I' and add `#' to the end of the model number. Derating Curves DNR120 (A) - 240 (B) 100 Load (%) 80 60 B A 40 20 0 -40 -35 0 10 20 30 40 50 60 70 50 60 70 Ambient Temp (C) DNR480PS 100 Load (%) 80 60 40 20 0 -40 -10 0 10 20 30 40 Ambient Temp (C) DC OK Volt free contact closed when voltage at unit output is within specification. In standby system configured as shown this voltage may be provided by the PSU or battery. DCOK Open = Output fail Closed = Output good DCOK Contact Rating: 0.3 A at 60 VDC 500 VDC isolation ACDC DNR120480 Models and Ratings ACDC DNR120/240 Mechanical Details 120 W Models Optional detatchable connector ('D' Option) 4.57 (116.0) DC Output 0.39 (10.0) 1 6 6 1 -V -V +V +V DC DC OK OK Single Parallel DC Output DC LO ON 4.92 (125.0) Voltage Trim 5.59 (142.0) AC Input N L 1 3 1 3 2.50 (63.5) Notes 1. 2. 3. 4. 5. DNR120 Connections Pin Designation 1 Ground AC 2 Line Input 3 Neutral 1 DC OK * 2 DC OK * DC 3 Positive 4 Positive Output 5 Negative 6 Negative Conn All dimensions in inches (mm). Weight 2.0 lb (920 g) approx. Tolerance: 0.02 (0.5) maximum. Screw terminal: 10-24 AWG cable size. Detachable connector version: 14-24AWG cable size. Connection screw maximum torque: Input: 9 lbs-in (1.0 Nm), Output: 5.5 lbs-in (0.6 Nm) * 24 V & standby models only. 240 W Models Optional detatchable connector ('D' Option) 4.39 (111.3) 6 0.3 (7.0) 1 1 6 -V -V +V +V DC DC OK OK Single DC Output Parallel 4.92 (125.0) DC LO ON Voltage Trim 5.59 (142.0) AC Input L N 1 3 1 3 3.27 (83.0) Notes 1. 2. 3. 4. 5. All dimensions in inches (mm). Weight 3.0 lb (1360 g) approx. Tolerance: 0.02 (0.5) maximum. Screw terminal: 10-24 AWG cable size. Detachable connector version: 14-24AWG cable size. Connection screw maximum torque: Input: 9 lbs-in (1.0 Nm), Output: 5.5 lbs-in (0.6 Nm) DNR240 Connections Pin Designation 1 Ground AC 2 Line Input 3 Neutral 1 DC OK* 2 DC OK* DC 3 Positive 4 Positive Output 5 Negative 6 Negative Conn * 24 V & standby models only. 480 W Models 6.89 (175.0) 0.3 (7.0) 4.57 (116.0) 4.92 (125.0) 5.59 (142.0) DC Output AC Input N DC ON Voltage Trim DC DC OK OK +V +V -V -V L 1 Parallel Single 3 DC LO 1 6 Optional detachable connector (`-D' option) DNR480PS Connections Conn Pin Designation 1 Ground AC 2 Neutral Input 3 Line 1 DC OK* 2 DC OK* DC 3 Positive 4 Positive Output 5 Negative 6 Negative Notes 1. All dimensions in inches (mm). 2. Weight 4.2 lb (1920 g) approx. 3. Tolerance: 0.02 (0.5) maximum. 4. Screw terminal: 10-24 AWG cable size. Detachable connector version: 14-24 AWG cable size. 5. Connection screw maximum torque: Input: 9 lbs-in (1.0 Nm), Output: 5.5 lbs-in (0.6 Nm) * 24 V and standby models only. Standby Versions Maximum current drain from battery by PSU when inactive 22 mA. 6 1 +V +V DC OK DC OK DC Output Voltage Trim DC LO ON D1 e.g. IN4001 Relay Control Coil -V -V +V +V DC DC OK OK LOAD L 1 -V N 3 1 AC Input 2 3 Fuse AC Input Conn Pin DNR120-480 Connections Designation Conn Pin 1 Ground 2 3 DC Output Line 4 5 Neutral 6 Designation DC OK DC OK Positive Positive Negative Negative Lead Acid Battery -V Notes 1. Suffix # indicates DC standby version. 2. With AC in, unit provides power to the load and to charge the battery. The DC OK signal acts by sensing a voltage on +V and holds the relay closed. 3. With loss of AC in, battery voltage is present on +V. DC OK signal holds the relay closed. Battery supplies power to the load. 4. As the battery discharges, its voltage falls. When this falls below the level shown in the table the DC OK signal switches off to allow the relay to open to disconnect and protect the battery. Model(1) DNR120AS12# DNR120AS24# DNR120AS48# DNR240PS24# DNR240PS48# DNR480PS24# DNR480PS48# Output Set Voltages For Standby Versions DC OK Voltage Current Signal Off 13.6 V 10.30-11.30 V 8.8 A 27.2 V 21.10-22.10 V 4.4 A 54.5 V 42.70-43.70 V 2.2 A 27.2 V 21.10-22.10 V 8.8 A 54.5 V 42.70-43.70 V 4.4 A 27.2 V 21.10-22.10 V 17.6 A 54.5 V 42.70-43.70 V 8.8 A DC OK Shutoff 10.8 V 5% 21.6 V 5% 43.2 V 5% 21.6 V 5% 43.2 V 5% 21.6 V 5% 43.2 V 5% 20-Oct-14 ACDC DNR480 Mechanical Details