Crompton Instruments
ANSI Switchboard Meters
www.crompton-instruments.com
Crompton Instruments
ANSI SWITCHBOARD METERS
Contents Page
ANSI Switchboard Meters General Specs 2 – 3
AC | DC Ammeters, Voltmeters and Frequency
Meters General Specs 4
RMS Reading AC Ammeters 5
RMS Reading AC Voltmeters 6
Expanded Scale AC Voltmeters 6
DC Ammeters 7
DC Voltmeters 8
Frequency Meters 8
AC Wattmeters & AC VArmeters General Specifications 9
AC Wattmeters | VArmeter Scale Selector Guide 10 - 11
AC Wattmeters 12
AC VArmeters 13
DC Transducer Indicators 13
Elapsed Time Meters 14
AC Phase Sequence | Phase Failure 14
DC Indicators for Tachometer Generators 14
AC Power Factor Meters 15
LED Digital | Analog Combination General Specifications 16
LED Digital | Analog AC Voltmeters 17
LED Digital | Analog AC Ammeters 18 - 19
LED Digital | Analog DC Voltmeters 20
LED Digital | Analog DC Ammeters 21
Switchboard Meter Options 22
1
An extensive range of analog and digital/analog meters in the
4½" ANSI case style. Meters utilize a robust pivot and jewel
movement design, and provide 1% accuracy for all RMS AC
and DC ranges. The range offers various customized options
and features UL and CE Listings and Certifications.
Features
Rugged polycarbonate
Class 1 accuracy
Benefits
Meets all requirements of
ANSI C39.1
Customize options and features
Parallax error-free platform dials
Applications
Switchgear
Distribution Systems
Generator Sets
Control Panels
Energy Management
Building Management
Utility Power Monitoring
Process Control
Motor Control
Certifications
Dimension E on OO7 others and 078 products varies with measured parameter.
See product code on following page.
Dimension F on 078 (Amps, Volts & Freq.) products is included with dimension E.
Model Panel Cutout Rear View Side View
Dia A B C D E F G
007 (Amps,
Volts & Freq.) 4.06 3.37 1.69 4.31 0.65 2.41 - 4.05
007 Others 4.06 3.37 1.69 4.31 0.65 - 0.91 4.05
078 4.06 3.37 1.69 4.31 0.63 - 0.91 4.05
ANSI Switchboard Meters
High quality range of switchboard instruments with Class 1
accuracy and which complies with American ANSI-C39.1
(1981) specifications. Available in 4 1/2" case size, the rugged
design characteristics meet the needs of the most demanding
environmental applications. This extensive range of analog
and digital/analog meters utilizes high shock and provides
1% accuracy for all RMS AC and DC ranges. The range offers
various customized options and features.
Description
Our Switchboard Meter series offers two case types; models 007 and 078.
Model 078 is high shock hermetically sealed and all models have heavy gauge
pressed steel cases. Mounting is by four integral studs. Model 078 has a die-cast
bezel and a projecting
moulded toughened glass window, which incorporates a
gas tight zero adjuster.
Model 007 is a one piece flame retardant polycarbonate moulding with a black
matte finished bezel area, and a specially contoured window to minimize reflection
from adjacent light sources.
Scales are 240° moving iron and 250° moving coil with parallax error-free
platform dials. Standard dials are white matte with black printed scales and
bar knife-edge pointers.
Specifications
Performance ANSI C39.1 (1981)
Accuracy Class 1
Terminals 10 - 32 UNF terminals
Response time Approximately 2.5 seconds to full scale (007 and 078)
Dielectric voltage Withstand test 2.3 kV for 1 minute
Standard calibration 23°C
Operating temperature 0°C to +60°C. Model 078: -40°C to +70°C
Storage temperature -10°C to +50°C
Extreme temperature
range -20°C to +65°C
Enclosure integrity Model 007 to IP54 (NEMA 3S) splash proof,
IP55 (NEMA 4) hoseproof is an optional extra Model 078
to IP67 (NEMA 6 and 6P)
Fixing on panel 4 integral 1/4 -28 UNF fixing studs
Certifications c-UL-us, CE
109.40
(4.31")
109.40
(4.31")
61.10
(2.41")
(0.65")
16.60
1/4-28 UNF STUDS
10-32 UNF TERMINALS
OPTIONAL TERMINAL COVER
103.00
(4.06")
(3.37")
85.60
(1.69")
42.80
8.00 (0.31") DIA. FOR PANELS UP TO 8.00 (0.31") THICK
4 Fixing holes.
9.50 (0.37") DIA. FOR PANELS OVER 8.00 (0.31") THICK
2
Dimensions (in inches)
1–4 Fixing holes Ø 8mm. 2–1/4-28 UNF fixing studs. 3–10-32 UNF terminals.
007 Power and 078
007 AMPs | Volts | Frequency Only
Type of instrument Ranges Dimension E Product code
007 078
AC rectified ammeter 1 - 30A 56 86 007/078-05B
AC rectified voltmeter 30 - 800V 56 86 007/078-05W
AC voltmeter expanded scale 110 - 130V 86 86 007/078-05Y
AC RMS ammeter 1 - 30A 56 86 007/078-05F
AC RMS voltmeter 150 - 750V 56 86 007/078-05G
Elapsed time meter (99999.99) 50 or 60Hz / 100 - 440V* and DC 56 56 007/078-155/156/077-151
Frequency meter 50, 60 86 86 007/078-41L
AC wattmeter or VArmeter 0.2 - 10A/100 - 440V* 132 132 007/078-21 or 31
LED synchroscope only 63.5 - 480V**** 86 - 077-14A
LED synchroscope and
synchro check relay 63.5 - 480V**** 86 - 077-14 L/G/D/U
Phase sequence indicator 100 - 150, 151 - 300, 301 - 500V 56 - 077-12P
Transducer operated indicator 1, 5, 10, 20, or 4/20mA 56 56 007/078-05
DC ammeter moving coil 200µA - 30A 56 56 56 007/078-05A
DC voltmeter moving coil 50mV - 600V 56 56 56 007/078-05V
240° phase angle | power factor 1 or 5A, 100 - 400V, 50, 60 132 132 007/078-42
DIGI/Analog AC ammeter 1mA - 10A 86 - 007-DIB
DIGI/Analog AC voltmeter 200mV - 600V 86 - 007-DIW
DIGI/Analog DC ammeter 1mA - 1A 86 - 007-DIA
DIGI/Analog DC voltmeter 20mV - 600V 86 - 007-DIV
DIGI/Analog transducer indicator DC mA 86 - 007-DIT
DIGI/Analog tachometer AC or DC rated 86 - 007-DI2
* 100-440V = (100/125, 200/250, 380/440).
**100-440V = (100/125, 200/250, 380/440). Frequencies 45/55, 55/65, 45/65, 46/54, 50/70, 58/62, 56/64.
****Nominal voltage to be specified.
3
Features
• Rugged pivot and
jewel movement
Class 1 accuracy
Applications
• Switchgear
• Distribution systems
• Generator sets
• Control panels
• Energy management
• Building management
• Utility power monitoring
• Process control
• Motor control
Certifications
Benefits
Meets all the requirements
of ANSI-C39.1 (1981)
• Parallax error-free
platform dials
• Bump, shock and
vibration proof
• Customized options
and features
SIGNAL
INPUT
–/N
+/L
AC and DC Ammeters, Voltmeters
and Frequency Meters
This range of self contained, pivot and jewel moving iron meters
feature 250° linear scale. AC instruments are available with true
RMS converting circuit or RMS compensated rectifier. While
types of frequency meters can be damaged by transient supply
voltage spike, Crompton Instruments 007-41 frequency meters
can withstand, without damage, 10 successive transient spikes
of 1250 volts. The range offers c-UL-us certification.
Specifications-General
Manufactured in accordance with American National Standards ANSI C39.1, (1981)
Accuracy ±1% full scale at 23°C (73°F)
Scales arc 250° full scale deflection
Scale length 007 and 078: 175.2 mm (6.9")
Scale plate 2 piece, platform type
Response time 007 and 078: Approximately 2.5 seconds to full scale
Operating temperature 0 to 40°C (32 to 104°F)
Storage temperature -10 to +50°C (14 to 122°F)
Extreme temperature
range -20° to +65°C (-4° to 149°F)
Terminals Standard 10-32 UNF stud. M5 screw clamp is optional
Dielectric withstand 2300V AC for 1 minute between electrical circuit and case
Overshoot 33% maximum
Enclosure code 007: IP54, optional IP55 and 078: IP67A
Certification c-UL-us
Specifications-Ammeters and Voltmeters
Overload rating AC ammeters - 2 x continuous, 50 x for 1 second
AC voltmeters and frequency meters - 1.2 x continuous
DC ammeters - 2 x continuous 10 x for 1 second
DC voltmeters - 1.2 x continuous
Frequency range AC calibration 50/60Hz ±20%
Specifications-Frequency Meters
Response time 3 seconds maximum
External temperature 0.6 times accuracy maximum with ±10°C from
influence reference temperature
External field
influence 2.0 times accuracy maximum with 0.5m T field
Acceptable input
harmonic influence up to 30% distortion
Maximum Frequency - Hz Center Scale - Hz Error in Hz
45-55 50 0.15
46-54 50 0.15
45-65 55 0.25
50-70 60 0.25
55-65 60 0.15
56-64 60 0.15
4
Fig. AA 007-05/007-41
5
AC Ammeter
RMS Reading AC Ammeters
* Other scales are available.
*** For case types 007/078 use 10-32 UNF terminals.
c-UL-us certified.
For AC rectified non-RMS compensated meter, please replace the -05F in the product
code with -05B.
Rating Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
1A 0-1A •007-05FA-LALA-C7 078-05FJ-LALA-C6
1.5A 0-1.5A •007-05FA-LCLC-C7 078-05FJ-LCLC-C6
2A 0-2A •007-05FA-LELE-C7 078-05FJ-LELE-C6
3A 0-3A •007-05FA-LJLJ-C7 078-05FJ-LJLJ-C6
5A 0-5A •007-05FA-LSLS-C7 078-05FJ-LSLS-C6
7.5A 0-7.5A •007-05FA-MFMF-C7 078-05FJ-MFMF-C6
10A 0-10A •007-05FA-MTMT-C7 078-05FJ-MTMT-C6
15A 0-15A •007-05FA-NDND-C7 078-05FJ-NDND-C6
20A 0-20A •007-05FA-NGNG-C7 078-05FJ-NGNG-C6
30A 0-30A •007-05FA-NLNL-C7 078-05FJ-NLNL-C6
5A 0-10A •007-05FA-LSMT-C7 078-05FJ-LSMT-C6
5A 0-15A •007-05FA-LSND-C7 078-05FJ-LSND-C6
5A 0-20A •007-05FA-LSNG-C7 078-05FJ-LSNG-C6
5A 0-25A •007-05FA-LSNJ-C7 078-05FJ-LSNJ-C6
5A 0-30A •007-05FA-LSNL-C7 078-05FJ-LSNL-C6
5A 0-40A •007-05FA-LSNP-C7 078-05FJ-LSNP-C6
5A 0-50A •007-05FA-LSNT-C7 078-05FJ-LSNT-C6
5A 0-75A •007-05FA-LSPB-C7 078-05FJ-LSPB-C6
5A 0-100A •007-05FA-LSPK-C7 078-05FJ-LSPK-C6
5A 0-150A •007-05FA-LSPZ-C7 078-05FJ-LSPZ-C6
5A 0-200A •007-05FA-LSRL-C7 078-05FJ-LSRL-C6
5A 0-250A •007-05FA-LSRS-C7 078-05FJ-LSRS-C6
5A 0-300A •007-05FA-LSRX-C7 078-05FJ-LSRX-C6
5A 0-400A •007-05FA-LSSC-C7 078-05FJ-LSSC-C6
5A 0-500A •007-05FA-LSSF-C7 078-05FJ-LSSF-C6
5A 0-600A •007-05FA-LSSJ-C7 078-05FJ-LSSJ-C6
5A 0-800A •007-05FA-LSSN-C7 078-05FJ-LSSN-C6
5A 0-1000A •007-05FA-LSSS-C7 078-05FJ-LSSS-C6
5A 0-1200A •007-05FA-LSSU-C7 078-05FJ-LSSU-C6
5A 0-1500A •007-05FA-LSTC-C7 078-05FJ-LSTC-C6
5A 0-1600A •007-05FA-LSTE-C7 078-05FJ-LSTE-C6
5A 0-2000A •007-05FA-LSTM-C7 078-05FJ-LSTM-C6
5A 0-2500A •007-05FA-LSTU-C7 078-05FJ-LSTU-C6
5A 0-3000A •007-05FA-LSUA-C7 078-05FJ-LSUA-C6
5A 0-4000A •007-05FA-LSUE-C7 078-05FJ-LSUE-C6
5A 0-5000A •007-05FA-LSUJ-C7 078-05FJ-LSUJ-C6
5A 0-6000A •007-05FA-LSUP-C7 078-05FJ-LSUP-C6
5A 0-7000A •007-05FA-LSUS-C7 078-05FJ-LSUS-C6
5A 0-8000A •007-05FA-LSUW-C7 078-05FJ-LSUW-C6
Product Codes – Self Contained 40/70Hz - Accuracy ±1%, 60Hz***
For AC rectified non-RMS compensated meter, please replace the -05F in the product
code with -05B.
Product Codes – Transformer Rated 40/70Hz - Burden 0.3VA***
6
Rating Scaling* 4 1/2" square flange
Std. case catalog no. Std. case cat. no.
110-130V 110-130V 007-05YA-PNPN-C6 078-05YJ-PNPN-C6
110-130V To suit PT 007-05YA-PN**-C6 078-05YJ-PN**-C6
RMS Reading AC Voltmeters
Rating Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
150V 0-150V •007-05GA-PZPZ-C7 078-05GJ-PZPZ-C6
250V 0-250V •007-05GA-RSRS-C7 078-05GJ-RSRS-C6
300V 0-300V •007-05GA-RXRX-C7 078-05GJ-RXRX-C6
500V 0-500V •007-05GA-SFSF-C7 078-05GJ-SFSF-C6
600V 0-600V •007-05GA-SJSJ-C7 078-05GJ-SJSJ-C6
750V 0-750V 007-05GA-SMSM-C7 078-05GJ-SMSM-C6
150V 0-300V •007-05GA-PZRX-C7 078-05GJ-PZRX-C6
150V 0-600V •007-05GA-PZSJ-C7 078-05GJ-PZSJ-C6
150V 0-750V •007-05GA-PZSM-C7 078-05GJ-PZSM-C6
150V 0-3000V •007-05GA-PZUA-C7 078-05GJ-PZUA-C6
150V 0-5250V •007-05GA-PZUL-C7 078-05GJ-PZUL-C6
150V 0-6000V •007-05GA-PZUP-C7 078-05GJ-PZUP-C6
150V 0-9000V •007-05GA-PZUY-C7 078-05GJ-PZUY-C6
150V 0-15kV •007-05GA-PZWC-C7 078-05GJ-PZWC-C6
150V 0-18kV •007-05GA-PZWD-C7 078-05GJ-PZWD-C6
150V 0-45kV •007-05GA-PZWJ-C7 078-05GJ-PZWJ-C6
250V 0-600V •007-05GA-RSSJ-C7 078-05GJ-RSSJ-C6
Product Codes – Self Contained 50/60Hz ± 20% - Accuracy ±1%***
AC Voltmeter
AC Voltmeter - Expanded Scale
* Other scales are available.
** Scaling information provided at time of order.
*** For case types 007/078 use 10-32 UNF terminals.
c-UL-us listed.
Product Codes – Expanded Scale - Moving Coil Zener Diode ***
Accuracy ±0.3% of Mid-scale Value Self Contained, 20-1000Hz
Product Codes – Transformer Rated 50/60Hz - Accuracy ±1%
0.8VA @ 150V***
For AC rectified non-RMS compensated meter, please replace the -05G in the product
code with -05W.
For AC rectified non-RMS compensated meter, please replace the -05G in the product
code with -05W.
7
DC Ammeter
DC Ammeters
Product Codes – Self Contained - Accuracy ±1%***
c-UL-us certified.
Specify shunt lead resistance value
if in excess of 0.05 ohms for
calibration purposes.
DC shunt rated ammeters have
thermistor circuit ambient
temperature compensation.
Separate shunt and shunt leads are
not included.
* Other scales are available.
** Specify scale required.
*** Other mV ratings and scale options
available upon request.
**** For case types 007/078
use 10-32 UNF terminals.
Product Codes – Millimeters - Suppressed Zero, No Zero Adjust
Unless Specified
Product Codes – Zero Left For Use With 50 mV Shunts and
0.05 Ohm Shunt Leads***and ****
Product Codes – Shunt Rated - Accuracy ±1%***
Rating Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
0-200µA 0-200µA •007-05AA-EAEA 078-05AJ-EAEA
0-300µA 0-300µA •007-05AA-EEEE 078-05AJ-EEEE
0-500µA 0-500µA •007-05AA-EMEM 078-05AJ-EMEM
0-800µA 0-800µA •007-05AA-EWEW 078-05AJ-EWEW
0-1mA 0-1mA •007-05AA-FAFA 078-05AJ-FAFA
0-2mA 0-2mA •007-05AA-FGFG 078-05AJ-FGFG
0-5mA 0-5mA •007-05AA-FXFX 078-05AJ-FXFX
0-10mA 0-10mA •007-05AA-HAHA 078-05AJ-HAHA
0-20mA 0-20mA •007-05AA-HFHF 078-05AJ-HFHF
0-30mA 0-30mA •007-05AA-HMHM 078-05AJ-HMHM
0-50mA 0-50mA •007-05AA-HXHY 078-05AJ-HXHY
0-100mA 0-100mA •007-05AA-JRJR 078-05AJ-JRJR
0-200mA 0-200mA •007-05AA-KAKA 078-05AJ-KAKA
0-300mA 0-300mA •007-05AA-KGKG 078-05AJ-KGKG
0-500mA 0-500mA •007-05AA-KMKM 078-05AJ-KMKM
0-800mA 0-800mA •007-05AA-KWKW 078-05AJ-KWKW
0-1A 0-1A •007-05AA-LALA 078-05AJ-LALA
0-5A 0-5A •007-05AA-LSLS 078-05AJ-LSLS
0-10A 0-10A •007-05AA-MTMT 078-05AJ-MTMT
0-15A 0-15A •007-05AA-NDND 078-05AJ-NDND
0-20A 0-20A •007-05AA-NGNG 078-05AJ-NGNG
0-30A 0-30A •007-05AA-NLNL 078-05AJ-NLNL
1/5mA To Suit •007-05RA-GM** 078-05RJ-GM**
4/20mA To Suit •007-05RA-HG** 078-05RJ-HG**
10/50mA To Suit •007-05RA-HZ** 078-05RJ-HZ**
Rating Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
50mV •007-05AA-EY** 078-05AJ-EY**
50-0-50mV •007-05CA-GB** 078-05CJ-GB**
100mV •007-05AA-GB** 078-05AJ-GB**
100-0-100mV •007-05CA-GM** 078-05CJ-GM**
50mV 0-15A •007-05AA-EYND 078-05AJ-EYND
50mV 0-20A •007-05AA-EYNG 078-05AJ-EYNG
50mV 0-30A •007-05AA-EYNL 078-05AJ-EYNL
50mV 0-40A •007-05AA-EYNP 078-05AJ-EYNP
50mV 0-75A •007-05AA-EYPB 078-05AJ-EYPB
50mV 0-100A •007-05AA-EYPK 078-05AJ-EYPK
50mV 0-150A •007-05AA-EYPZ 078-05AJ-EYPZ
50mV 0-200A •007-05AA-EYRL 078-05AJ-EYRL
50mV 0-300A •007-05AA-EYRX 078-05AJ-EYRX
50mV 0-400A •007-05AA-EYSC 078-05AJ-EYSC
50mV 0-500A •007-05AA-EYSF 078-05AJ-EYSF
50mV 0-750A •007-05AA-EYSM 078-05AJ-EYSM
50mV 0-1000A •007-05AA-EYSS 078-05AJ-EYSS
50mV 0-1200A •007-05AA-EYSU 078-05AJ-EYSU
50mV 0-1500A •007-05AA-EYTC 078-05AJ-EYTC
50mV 0-2000A •007-05AA-EYTM 078-05AJ-EYTM
50mV 0-3000A •007-05AA-EYUA 078-05AJ-EYUA
To suit
shunt
rating
DC Voltmeters
Rating Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
500MV-800V To suit •007-05VA-** 078-05VJ-**
0-15V 0-15V •007-05VA-NDND 078-05VJ-NDND
0-30V 0-30V •007-05VA-NLNL 078-05VJ-NLNL
0-50V 0-50V •007-05VA-NTNT 078-05VJ-NTNT
0-75V 0-75V •007-05VA-PBPB 078-05VJ-PBPB
0-150V 0-150V •007-05VA-PZPZ 078-05VJ-PZPZ
0-300V 0-300V •007-05VA-RXRX 078-05VJ-RXRX
0-400V 0-400V •007-05VA-SCSC 078-05VJ-SCSC
0-500V 0-500V •007-05VA-SFSF 078-05VJ-SFSF
0-600V 0-600V •007-05VA-SJSJ 078-05VJ-SJSJ
0-750V 0-750V 007-05VA-SMSM 078-05VJ-SMSM
0-800V 0-800V 007-05VA-SNSN 078-05VJ-SNSN
150-0-150V 150-0-150V •007-05NA-RXRX 078-05NJ-RXRX
300-0-300V 300-0-300V •007-05NA-SJSJ 078-05NJ-SJSJ
500-0-500V 500-0-500V •007-05NA-SSSS 078-05NJ-SSSS
600-0-600V 600-0-600V •007-05NA-SUSU 078-05NJ-SUSU
Ratings Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
50Hz +/-0.15 45-55Hz •007-41LA-PNAG-AG 078-41LJ-PNAG-AG
50Hz +/-0.15 46-54Hz •007-41LA-PNAH-AH 078-41LJ-PNAH-AH
50Hz +/-0.25 45-65Hz •007-41LA-PNAJ-AJ 078-41LJ-PNAJ-AJ
60Hz +/-0.25 50-70Hz •007-41LA-PNAL-AL 078-41LJ-PNAL-AL
60Hz +/-0.15 55-65Hz •007-41LA-PNAN-AN 078-41LJ-PNAN-AN
60Hz +/-0.15 56-64Hz •007-41LA-PNAO-AO 078-41LJ-PNAO-AO
60Hz+/-0.08 58-62Hz •007-41LA-PNAT-AT 078-41LJ-PNAT-AT
Frequency Meters
Product Codes – 120V Self Contained***
Product Codes – Sensitivity 1000 Ohms / Volt - Accuracy ±1%***
DC Voltmeter
Frequency Meter
For alternative voltage rating
200-250V, use code RN instead
of PN.
For alternative voltage rating
380-480V, case types 007/078
use code SE instead of PN.
10-32 UNF terminals.
* Other scales are available.
** Specify scale required.
***For case types 007/078
use 10-32 UNF terminals.
c-UL-us certified.
8
Product Codes – Zero Center - Sensitivity 2000 Ohms / Volt
Accuracy ±1%***
AC Wattmeters and VArmeters
The Crompton Instruments Switchboard series of AC Wattmeters and
VArmeters incorporate a DC moving coil, pivot and jewel indicator
with a micro-circuit watt transducer PCB to read power on single
or three-phase systems. The most frequently selected wattmeter
scale marking for common current and voltage transformers are
listed on the following pages. In addition, these instruments may
be supplied with zero-left or center-zero scale.
Scaling
Wattmeter and VArmeter current circuits should have equal carrying capacity
because they are frequently connected in series. This means that the sum of the left
and right end-scale values of the VArmeters should be equal to or greater than the
full scale value of the Wattmeter (or have higher end-scale values if the instruments
are center or offset-zero). Instruments measuring 10,000 kilowatts and over are
marked in megawatts. Center-zero or offset-zero Watt and VArmeters are marked
“IN” for left deflection and “OUT” for right deflection. On ordering, Wattmeter and
VArmeter scales will be calculate, the nearest preferred scale will be offered from
the charts on the following pages. Custom scales are available but at an extra cost.
Calibration
For full load value of Watts or VAr, assuming unity power factor:
1-phase 2-wire Watts = amps x volts
3-phase 3-wire Watts = amps x line-to-line volts x 3
3-phase 4-wire Watts = amps x line-to-neutral volts x 3
Minimum scale values are obtained by multiplying resultant Watts, using the above
formula x 0.7 and selecting next higher standard scale.
For maximum scale value, multiply x 1.3 and select the next lowest standard.
If scale calculates to an exact listed value, use this value rather than the next higher
or lower value.
Note: When ordering Wattmeters and VArmeters, please specify CT ratio, VT ratio
and required scale.
Specifications
Burden per element Current circuit: 2VA | Voltage Circuit: 1VA
Accuracy Class 1.0
Ambient range 0° to ± 60° (32° to 104°F) std. calibration 20°C (68°F)
Ambient influence 0.05% per 1°C maximum
Overloads-current 10 x rating for 5 seconds, 1.2 x continuously
Voltage influence 2 x rating for 5 seconds, 1.2 x continuously voltage
Accuracy maintained, 80 - 110% rated voltage
Power factor influence Accuracy maintained, 0.1 lag to 0.1 lead
Enclosure code 007 IP54 optional IP55 | 078 IP67
Response time 007 and 078 approximately 2.5 seconds
Dielectric withstand Live parts to case including panel 2600V RMS for 1 minute
9
Wattmeter | VArmeter Scale Selector Guide Wattmeter | VArmeter Scale Selector Guide
120 208 240 480 600 2400 3600 4200 4800 6000 7200 8400
Primary potential transformer (1:1) (1.73:1) (2:1) (4:1) (5:1) (20:1) (30:1) (35:1) (40:1) (50:1) (60:1) (70:1)
voltage system
3-phase 3-wire (L-L) 120 208 240 480 600 2400 3600 4200 4800 6000 7200 8400
system voltage
3-phase 4-wire (L-N) 69 120 139 277 347 1390 2100 2400 2770 3500 4160 4800
current transformer
RATIO Normal 5KW 10KW 10KW 20KW 25KW 100KW 150KW 175KW 200KW 250KW 300KW 350KW
25/5 Max. 6 10 12 25 30 120 200 200 250 300 400 450
(5:1) Min. 3 5 6 12.5 15 60 100 100 125 150 200 225
RATIO Normal 10KW 20KW 20KW 40KW 50KW 200KW 300KW 350KW 400KW 500KW 600KW 700KW
50/5 Max. 12 20 25 50 60 250 400 450 500 600 800 900
(10:1) Min. 6 10 12.5 25 30 125 200 250 250 300 400 450
RATIO Normal 15KW 25KW 30KW 60KW 75KW 300KW 500KW 500KW 600KW 750KW 900KW 1000KW
75/5 Max. 20 30 40 80 100 400 600 700 800 1000 1200 1200
(15:1) Min. 10 15 20 40 50 200 300 350 400 500 600 600
RATIO Normal 20KW 30KW 40KW 75KW 100KW 400KW 600KW 700KW 800KW 1000KW 1200KW 1200KW
100/5 Max. 25 40 50 100 120 500 800 900 1000 1200 1500 1500
(20:1) Min. 12.5 20 25 50 60 250 400 450 500 600 750 750
RATIO Normal 30KW 50KW 50KW 100KW 150KW 600KW 800KW 1000KW 1200KW 1500KW 1800KW 2000KW
150/5 Max. 40 70 75 150 200 800 1200 1200 1500 2000 2400 2500
(30:1) Min. 20 35 35 75 100 400 600 600 750 1000 1000 1250
RATIO Normal 40KW 75KW 75KW 150KW 200KW 800KW 1200KW 1200KW 1500KW 2000KW 2500KW 3000KW
200/5 Max. 50 80 100 200 250 1000 1500 1500 2000 2500 3000 3500
(40:1) Min. 25 40 50 100 125 500 750 750 1000 1250 1500 1500
RATIO Normal 70KW 100KW 100KW 200KW 300KW 1200KW 1500KW 2000KW 2500KW 3000KW 3500KW 4500KW
300/5 Max. 75 120 150 300 400 1500 2000 2500 3000 4000 4000 5000
(60:1) Min. 35 60 75 150 200 750 1000 1250 1500 2000 2000 2500
RATIO Normal 75KW 125KW 150KW 300KW 400KW 1500KW 2500KW 3000KW 3000KW 4000KW 5000KW 6000KW
400/5 Max. 100 150 200 400 500 2000 3000 3600 4000 5000 6000 7000
(80:1) Min. 50 75 100 200 250 1000 1500 1500 2000 2500 3000 3500
RATIO Normal 125KW 200KW 200KW 450KW 600KW 2000KW 3000KW 4000KW 5000KW 6000KW 7500KW 8000KW
600/5 Max. 150 250 300 600 800 3000 4000 5000 6000 8000 8000 10MW
(120:1) Min. 75 125 150 300 400 1500 2000 2500 3000 4000 4000 5000KW
RATIO Normal 150KW 250KW 300KW 600KW 800KW 3000KW 5000KW 6000KW 6000KW 8000KW 10MW 12MW
800/5 Max. 200 350 400 800 1000 4000 6000 7500 8000 10MW 12 15
(160:1) Min. 100 175 200 400 500 2000 3000 3000 40000 5000KW 6000KW 7500KW
RATIO Normal 200KW 350KW 400KW 800KW 1000KW 4000KW 6000KW 6000KW 8000KW 10MW 12MW 15MW
1000/5 Max. 250 450 500 1000 1200 5000 8000 8000 10MW 12 15 18
(200:1) Min. 125 225 250 500 600 2500 4000 4000 5000KW 6000KW 7500KW 10
RATIO Normal 250KW 400KW 500KW 1000KW 1200KW 5000KW 7000KW 8000KW 10MW 12MW 15MW 10MW
1200/5 Max. 300 500 600 1200 1500 6000 8000 10MW 12 15 18 20
(240:1) Min. 150 250 300 600 750 3000 4000 5000KW 6000KW 7500KW 10 10
RATIO Max. 300KW 500KW 600KW 1200KW 1500KW 6000KW 10MW 10MW 12MW 15MW 20MW 20MW
1500/5 Max. 400 700 750 1500 2000 8000 12 12 15 20 20 25
(300:1) Min. 200 350 375 1000 1000 4000 6000KW 6000KW 7500KW 10 10 12.5
RATIO Normal 400KW 750KW 800KW 1600KW 2000KW 8000KW 12MW 12MW 15MW 20MW 25MW 30MW
2000/5 Max. 500 800 1000 2000 2500 10MW 15 15 20 25 30 35
(400:1) Min. 250 400 500 750 1250 5000 7500KW 7500KW 10 12.5 15 20
RATIO Normal 750KW 1000KW 1200KW 2000KW 3000KW 12MW 18MW 20MW 25MW 30MW 35MW 40MW
3000/5 Max. 800 1200 1500 3000 4000 15 20 25 30 40 40 50
(600:1) Min. 400 600 750 1500 2000 7500KW 10 12.5 15 20 20 25
RATIO Normal 800KW 1200KW 1500KW 3000KW 4000KW 15MW 20MW 25MW 30MW 40MW 50MW 50MW
4000/5 Max. 1000 1500 2000 4000 5000 20 30 30 40 50 60 75
(800:1) Min. 500 750 1000 2000 2500 10 15 15 20 25 30 40
RATIO Normal 1000KW 1500KW 2000KW 4000KW 5000KW 20MW 30MW 20MW 40MW 50MW 60MW 75MW
5000/5 Max. 1250 2000 2500 5000 6000 25 40 25 50 60 80 80
(1000:1) Min. 500 1000 1250 2500 3000 12.5 20 12.5 25 30 40 40
RATIO Normal 1200KW 2000KW 2500KW 5000KW 6000KW 25MW 35MW 40MW 50MW 60MW 60MW 80MW
6000/5 Max. 1500 2500 3000 3000 8000 30 40 50 60 80 80 100
(1200:1) Min. 750 1250 1500 1500 4000 15 20 25 30 40 40 50
10
Wattmeter | VArmeter Scale Selector Guide Wattmeter | VArmeter Scale Selector Guide
12kV 14.4kV 24kV 34.5kV 38kV 46kV 92kV 115kV 138kV 345kV 765kV
Primary potential transformer (100:1) (120:1) (200:1) (300:1) (330:1) (400:1) (800:1) (1000:1) (1200:1) (3000:1) (6000:1)
voltage system
3-phase 3-wire (L-L) 12KV 14.4kV 24kV 34.5kV 38kV 46kV 92kV 115kV 138kV 345kV 765kV
system voltage
3-phase 4-wire (L-N) 6900 8300 13.8KV 20kV 22kV 26.5kV 53kV 66kV 80kV 200kV 440kV
current transformer
RATIO Normal 500KW 600KW 1000KW 1500KW 1500KW 1500KW 3000KW 5000KW 6000KW 15MW 30MW
25/5 Max. 650 800 1200 1500 2000 2500 200 200 250 300 400
(5:1) Min. 325 400 600 750 1000 1250 100 100 125 150 200
RATIO Normal 1000KW 1200KW 2000KW 3000KW 3000KW 3500KW 8000KW 10MW 12MW 30MW 60MW
50/5 Max. 1200 1500 2500 3500 4000 5000 10MW 12 15 35 80
(10:1) Min. 600 750 1250 1750 2000 2500 5000KW 6000KW 7500KW 15 40
RATIO Normal 1500KW 1800KW 3000KW 4000KW 5000KW 5000KW 10MW 15MW 15MW 45MW 100MW
75/5 Max 2000 2000 4000 5000 6000 7500 15 15 20 50 125
(15:1) Min. 1000 1000 2000 2500 3000 3000 7500KW 7500KW 10 25 50
RATIO Normal 2000KW 2500KW 4000KW 6000KW 6000KW 7500KW 15MW 20MW 25MW 60MW 125MW
100/5 Max. 2500 3000 5000 7500 8000 10MW 20 25 30 70 150
(20:1) Min. 1250 1500 2500 3000 4000 5000KW 10 12.5 15 35 75
RATIO Normal 3000KW 3500KW 6000KW 10MW 10MW 10MW 20MW 30MW 35MW 90MW 200MW
150/5 Max. 4000 4000 4000 10 12 15 30 35 40 100 250
(30:1) Min. 2000 2000 2000 5000KW 6000KW 7500KW 15 15 20 50 100
RATIO Normal 4000KW 4500KW 8000KW 12MW 12MW 15MW 30MW 35MW 50MW 100MW 250MW
200/5 Max. 5000 6000 5000 15 15 20 40 50 60 150 300
(40:1) Min. 2500 3000 2500 7500KW 7500KW 10 20 25 30 75 150
RATIO Normal 6000KW 7000KW 12MW 18MW 18MW 20MW 45MW 60MW 75MW 150MW 400MW
300/5 Max. 8000 8000 15 20 25 30 60 75 80 200 500
(60:1) Min. 4000 4000 7.5 10 12.5 15 30 30 40 100 250
RATIO Normal 8000KW 10MW 15MW 24MW 25MW 30MW 60MW 80MW 100MW 200MW 500MW
400/5 Max. 10MW 12 20 30 30 40 80 100 120 300 600
(80:1) Min. 5000KW 6000KW 10 15 15 20 40 50 60 150 300
RATIO Normal 12MW 15MW 25MW 35MW 40MW 45MW 90MW 100MW 150MW 350MW 800KW
600/5 Max. 15 18 30 40 50 60 120 150 180 450 1000
(120:1) Min. 7500KW 10 15 20 25 30 60 75 75 225 500
RATIO Normal 15MW 20MW 30MW 50MW 50MW 60MW 120MW 150MW 200MW 500MW 1000MW
800/5 Max. 20 25 40 60 60 80 150 200 200 600 1200
(160:1) Min. 10 12.5 20 30 30 40 75 100 100 300 600
RATIO Normal 20MW 25MW 40MW 50MW 60MW 75MW 150MW 200MW 250MW 600MW 1200MW
1000/5 Max. 25 30 50 60 80 100 200 250 300 750 1500
(200:1) Min. 12.5 15 25 30 40 50 100 125 150 300 750
RATIO Normal 25MW 30MW 50MW 60MW 80MW 100MW 175MW 250MW 300MW 750MW 1500MW
1200/5 Max. 30 35 60 80 100 120 200 300 350 900 2000
(240:1) Min. 15 20 30 40 50 60 100 150 175 450 1000
RATIO Normal 30MW 35MW 60MW 75MW 100MW 120MW 250MW 3000MW 350MW 900MW 2000MW
1500/5 Max. 40 40 80 100 120 150 300 350 450 1000 2500
(300:1) Min. 20 20 40 50 60 75 150 175 225 500 1250
RATIO Normal 40MW 50MW 80MW 100MW 120MW 150MW 300MW 400MW 5000MW 1000MW 2500MW
2000/5 Max. 50 60 100 150 150 200 400 500 600 1500 3000
(400:1) Min. 25 30 50 75 75 100 200 250 300 750 1500
RATIO Normal 60MW 75MW 100MW 150MW 200MW 200MW 400MW 600MW 700MW 1500MW 3500MW
3000/5 Max. 80 80 150 200 250 300 500 750 900 2000 5000
(600:1) Min. 40 40 75 100 125 150 250 350 450 1000 2500
RATIO Normal 80MW 100MW 150MW 200MW 250MW 300MW 5000MW 800MW 1000MW 2000MW 500MW
4000/5 Max. 100 125 200 300 300 400 800 1000 1200 3000 6000
(800:1) Min. 50 60 100 150 150 200 400 500 600 1500 3000
RATIO Normal 100MW 125MW 200MW 250MW 300MW 4000MW 750MW 1000MW 1200MW 3000MW 6000MW
5000/5 Max. 120 150 250 300 400 500 1000 1200 1500 3500 8000
(1000:1) Min. 60 75 125 150 200 250 500 600 750 1750 400
RATIO Normal 120MW 150MW 250MW 350KW 400MW 450MW 1000MW 1200MW 1500MW 3500MW 8000MW
6000/5 Max. 150 175 300 400 500 600 1200 1500 1750 4000 10000
(1200:1) Min. 75 80 150 200 250 300 600 750 800 2000 5000
11
AC Wattmeter
AC Wattmeters
Phases
Wires
Amperes
1VA max. burden
Volts
1 VA max. burden
Measured System Scaling 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
1 2 5 120V To suit •007-215A-QQ**-C7 078-215J-QQ**-C6
1 2 5 240V To suit 007-215A-QS**-C7 078-215J-QS**-C6
3 3 5 120V To suit •007-218A-QQ**-C7 078-218J-QQ**-C6
3 3 5 208V To suit •007-218A-QR**-C7 078-218J-QR**-C6
3 3 5 240V To suit •007-218A-QS**-C7 078-218J-QS**-C6
3 3 5 380V To suit •007-218A-QX**-C7 078-218J-QX**-C6
3 3 5 480V To suit •007-218A-QT-**-C7 078-218J-QT**-C6
3 4 5 69V To suit •007-219A-QL-C7** 078-219J-QL**-C6
3 4 5 120V To suit •007-219A-QQ-C7** 078-219J-QQ**-C6
3 4 5 277V To suit •007-219A-QY-C7** 078-219J-QY**-C6
3 4 5 346V To suit •007-219A-QZ-C7** 078-219J-QZ**-C6
Product Codes – 1-Element, Transformer Rated, 50/60Hz
Integral Transducer - Accuracy 1.0%, 50/60Hz
For connection diagram refer to Figure A1 & A2.
Product Codes - 2 -Element, Transformer Rated, 50/60Hz
Taut Band Integral Transducer - Accuracy 1.0%, 50/60Hz
For connection diagram refer to Figure C1 & C2.
For connection diagram refer to Figure B1 & B2.
Product Codes - 2 1/2 - Element, Transformer Rated, 50/60Hz
Taut Band Integral Transducer - Accuracy 1.0%, 50/60Hz
* Other scales are available.
** Specify CT (Current Transformer) and
VT (Voltage Transformer) ratios if used
and preferred scale at time of ordering.
c-UL-us certified.
Fig. A1 Models 007-215
Wattmeter Single Phase
3 2 1
LOAD
CT
H1
H1
X1
X1
CT
Fig. B1 Models 007-218 Wattmeter
3-Phase, 3-Wire Unbalanced Load
Fig. A2 Models 078-215
Wattmeter Single Phase
Fig. B2 Models 078-218 Wattmeter
3-Phase 3-Wire Unbalanced Load
N 3 2 1
LOAD
H1
H1
H1
X1
X1
X1
CT
CT
CT
Fig. C1 Models 007-219 Wattmeter
3-Phase 4-Wire Unbalanced Load
Fig. C2 Models 078-219 Wattmeter
3-Phase 4-Wire Unbalanced Load
12
3 2 1
LOAD
CT
H1
H1 X1
X1 CT
AC VArmeter
AC VArmeters
Phases
Wires
Amperes
1VA max. burden
Volts
1 VA max. burden
Product Codes - Element, Transformer Rated, 50/60Hz
Integral Transducer - Accuracy 1.0%, 50/60Hz
Fig. D1 Models 077-31L VArmeter
3-Phase 3-Wire Unbalanced Load
Fig. D2 Models 078-31L VArmeter
3-Phase 3-Wire Unbalanced Load
Measured System Scaling 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
3 3 5 120V To suit •007-31LA-QQ**-C7 078-31LJ-QQ**-C6
3 3 5 208V To suit •007-31LA-QR**-C7 078-31LJ-QR**-C6
3 3 5 240V To suit •007-31LA-QS**-C7 078-31LJ-QS**-C6
3 3 5 380V To suit •007-31LA-QX**-C7 078-31LJ-QX**-C6
3 3 5 480V To suit •007-31LA-QT**-C7 078-31LJ-QT**-C6
3 4 5 120V To suit •007-31UA-QQ**-C7 078-31UJ-QQ**-C6
3 4 5 208V To suit •007-31UA-QR**-C7 078-31UJ-QR**-C6
3 4 5 480V To suit •007-31UA-QT**-C7 078-31UJ-QT**-C6
For connection diagram refer to Figure D1 & D2.
Product Codes - 2 1/2-Element, Transformer Rated, 50/60Hz
Taut Band Integral Transducer - Accuracy 1.0%, 50/60Hz
For connection diagram refer to Figure D1 & D2.
* Other scales are available.
** Specify CT (Current Transformer) and VT (VoltageTransformer)
ratios if used and preferred scale at time of ordering.
c-UL-us certified.
13
DC Transducer Indicators
Product Codes
Rating Scaling* 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
Watts 1mA To suit •007-055A-FA** 078-055J-FA**
VArs 1mA To suit •007-056A-FA** 078-056J-FA**
Frequency 1mA To suit •007-053A-FA** 078-053J-FA**
Power factor 1mA To suit •007-054A-FA** 078-054J-FA**
AC amps 1mA To suit •007-05AA-FA** 078-05AJ-FA**
AC volts 1mA To suit •007-05VA-FA** 078-05VJ-FA**
Speed 1mA To suit •007-052A-FA** 078-052J-FA**
VA 1mA To suit •007-057A-FA** 078-057J-FA**
For use with the following
transducers: Watts, Vars,
Frequency, Power Factor,
AC amperes, AC volts and
temperature.
*Case types 007/078 use
10-32 UNF terminals.
**Specify scale. Input: 1mA DC
for 4/20mA change “FAto “HG”.
• c-UL-us certified.
DC Transducer Indicator
Elapsed Time Meters
Rating 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
110/130V 50Hz •007-155A-PNZH-C5 078-155J-PNZH-C5
200/250V 50Hz •007-155A-RNZH-C5 078-155J-RNZH-C5
480V 50Hz •007-155A-SEZH-C5 078-155J-SEZH-C5
110/130V 60Hz •007-156A-PNZH-C6 078-156J-PNZH-C6
200/250V 60Hz •007-156A-RNZH-C6 078-156J-RNZH-C6
480V 60Hz •007-156A-SEZH-C6 078-156J-SEZH-C6
12/24/40/110V DC 007-151A-**-ZH-DC Not Available
Rating 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
100/150V 50/60Hz 077-12PA-P2C6 Not available
151/300V 50/60Hz 077-12PA-P3C6 Not available
301/500V 50/60Hz 077-12PA-P4C6 Not available
Product Codes – 99,999.99 Hours, Non Reset, Burden 2.5VA
50 or 60Hz
Elapsed Time Meter
AC Phase Sequence and
Phase Failure Indicator
Select nearest higher rated voltmeter and specify requirement.
* Other ranges are available.
upon request Consult with the factory.
** RI for 10 ohm or R2 for 100 ohm platinum.
*** Specify input and scale.
c-UL-us certified.
Synchronous motor running time meter with a non-resettable indicator.
AC Phase Sequence, Phase Failure Indicators
Product Codes – Neon Bulb Type, Burnden 2.5VA
Two neon bulbs for phase sequence indication - first marked the caption “correct
1-2-3”, the second marked “incorrect 3-2-1”. Three neon bulbs for phase failure
indication - first marked 1, second marked 2, third marked 3.
Rating 4 1/2" square flange
Std. case Std. case hi-shock
catalog number catalog number
DC Volts 007-052A-** 078-052J-***
DC Indicators for Tachometer Generators
Product Code
Fig. E Model 007-12P
Phase Sequence Indicator
3-Phase 3- or 4-Wire systems
For connection diagram refer to Figure E.
14
AC Power Factor Meter
AC Power Factor Meter
Specifications
Ratings, self-contained Current windings 5A. Voltage windings minimum 50V,
maximum 600V
Accuracy Balanced load: Class 1
Overshoot 33%
External temperature
influence 0.5% fid minimum
External field influence 0.5% fid maximum
Frequency range 50Hz or 60Hz standard, 25-3000Hz optional (Specify)
Frequency influence Single phase instruments, 59 to 61Hz 1.0% fid maximum
polyphase instruments ±10% deviation from 69Hz: 1.0%
Overload capacity: Current coils 1000% momentarily, 100% for 15 minutes
25% indefinitely Voltage circuits 25% indefinitely
Burdens Each current circuit, 1.5VA approximately
Each voltage circuit 1VA approximately
Measuring systems 077-427-3 or 4-wire
Ranges available Lag 0.5-1 - 0.5 lead power factor
Lag 0.2-1 - 0.8 lead power factor
Phases
Wires
Amperes
2VA max. burden
Volts
1 VA max. burden
Product Codes - Balanced Load - Accuracy ±1%
Measured System Scaling 4 1/2" square flange
Std. case Std. case
catalog no. hi-shock
catalog no.
1 2 5 120V 0.5-1-0.5 •007-425A-QQAD-C6 078-425J-QQAD-C6
1 2 5 240V 0.5-1-0.5 •007-425A-QSAD-C6 078-427J-QSAD-C6
3 34 5 120V 0.5-1-0.5 •007-427A-QQAD-C6 078-427J-QQAD -C6
3 34 5 208V 0.5-1-0.5 •007-427A-QRAD-C6 078-427J-QRAD-C6
3 34 5 240V 0.5-1-0.5 •007-427A-QSAD-C6 078-427J-QSAD -C6
3 34 5 480V 0.5-1-0.5 •007-427A-QTAD-C6 078-427J-QTAD -C6
Instruments may be used on loads down to 20% of current and between 90%
and 110% of voltage rating.
For connection diagrams refer to Fig. E and F.
• c-UL-us certified.
LOAD
SOURCE
H1
X1
N 1 2 3
LOAD
H1
X1
Fig. E Models 007-425, 078-425J
Electronic Phase Angle Meter
Single Phase
Fig. F Models 007-427, 078-427J
Electronic Phase Angle Meter
3-phase, 3- or 4-wire Balanced Load
15
LED Digital | Analog Combination
Crompton Instruments model 007-DI features a combination of
the traditional 250° 4 1⁄2" switchboard indicator with the trend
indication plus the benefits of wide angle LED visibility. This rugged
shock and vibration resistant design provides precision accuracy
and instantaneous reading via the bright in-dial mounted 3 1⁄2" digit
LED display.
Description
Model 007-DI digital analog indicators are ideal for all applications where moving
pointer instruments are preferable to indicate trend with the simultaneous display
of a high visibility precision LED readout for increased user interface.
The 007-DI is interchangeable with other analog and digital instruments designed
to directly mount in to a standard ANSI-C39. 4 1⁄2" switchboard cut-out.
Available in side, center, or off-set zero versions, the 007-DI can accept AC and DC
current and voltage inputs as well as a wide range of transducer outputs, making it
suitable for a variety of other applications including low-load current, temperature,
speed, Watt/VArs, percent and level.
Features
Rugged shock and vibration
resistant pivot and jewel
design
High accuracy LED display
Wide selection of AC and
DC inputs
• Maximum trend indication
visiblity
Input isolation
External decimal point
selction option
• Interchangeable with 4 1/2"
switchboard meters
Benefits
Cost effective
Meets all the requirement
of ANSI-C39.1 (1981)
• IP54 (NEMA 3) protection
Optional IP55 (NEMA 4)
gasket
Bump, shock and vibration
proof
• Customized option and
features
Applications
Switchgear
Distribution systems
Generator sets
Control panels
Energy management
Building management
Utility power monitoring
Process control
Motor control
16
Specifications
Inputs DC Voltage: 20mV-600V (1MΩ input impedance as standard)
DC Current: 1mA-1A, 4 to 20mA (Voltage drop 200mV nominal)
External shunt operation (50mV and 100mV)
AC Voltage: 200mV-600V (1 /volt) AC Current: 1mA-999mA
(Using internal shunt, voltage drop 200mV nominal) 1A, 2A, 5A
and 10A using internal current transformer
Common mode rejection =>80dB @ 50/60Hz
Overload Voltage: x 1.2 continuous. x 1.5 for 10 seconds
Current using internal CT: x 1.2 continuous. x 10 for 10 seconds
External power Standard: 120 and 240V ±15%
requirement Optional: 480V ±15% AC 40-60Hz
Burden 3VA @ 60Hz
DC Standard: 12, 24, 48, 110 and 125V ±15%
Display analog Long-scale moving coil. 250° deflection. Scale length 6.8"
Response time less than 2.5 seconds
Display options Center or offset zero. Scale plate in colors other than white
Colored lines or segments on scale
Digital display 3 1⁄2 digit red LED. 7 segment (7.6mm, 0.3" high). Right hand
decimal points. Polarity indication: positive / none. Negative /
horizontal bar “ - ”. Update time (standard): 1 per second
Accuracy - analog DC and AC ±1% of FSD (calibrated at 25°C)
Accuracy - digital DC: ±0.05% of reading ±1 count ±100ppm of reading / °C max
AC current: 0-1 Amp ±0.1% reading ±3 counts ±150ppm of
reading / °C
AC current: 0-10 amps ±0.1% reading ±10 counts ±150ppm of
reading / °C (maximum)
AC voltage: ±0.1% of reading ±3 counts ±150ppm of
reading / °C (maximum)
Zero ±1 count ±0.2 counts/°C (maximum),
DC offset scale only. Warm-up time: 1 minute
Long term stability ±2 counts
Calibration check Recommended 12 monthly intervals
Enclosure code IP54 (optional IP55 using panel gasket)
Operational
temperature 0 to 60°C (32° - 140° F)
Storage temperature -20° to 60°C (-4° - 140° F)
Humidity Up to 90% relative @ 55° C. Tests to BS2011 part 2DA
Isolation test voltage 2kV RMS 60Hz for 1 minute
Interference rejection To IEEE STD472, ANSI C37 90A, SEN 361503, IEC 255-4
* Other scalings are available.
** Specify power supply voltage according to power supply
codes table located on page 22.
*** Case types 007 use 10-32 UNF terminals.
LED Digital | Analog Combination
Rating Scaling* Catalog number
200mV 0-200mV 007-DIWA-KAKA-C6-**
250mV 0-250mV 007-DIWA-KDKD-C6-**
500mV 0-500mV 007-DIWA-KMKM-C6-**
1V 0-1V 007-DIWA-LALA-C6-**
5V 0-5V 007-DIWA-LSLS-C6-**
10V 0-10V 007-DIWA-MTMT-C6-**
15V 0-15V 007-DIWA-NDND-C6-**
30V 0-30V 007-DIWA-NLNL-C6-**
150V 0-150V 007-DIWA-PZPZ-C6-**
250V 0-250V 007-DIWA-RSRS-C6-**
300V 0-300V 007-DIWA-RXRX-C6-**
500V 0-500V 007-DIWA-SFSF-C6-**
600V 0-600V 007-DIWA-SJSJ-C6-**
Product Codes – AC Voltmeters - Direct Reading (40/70Hz)***
Digital accuracy ±0.1% ±3 counts, analog accuracy ±1%
For connection diagrams, refer to Figure H.
Rating Scaling* Catalog number
150V 0-300V 007-DIWA-PZRX-C6-**
150V 0-600V 007-DIWA-PZSJ-C6-**
150V 0-750V 007-DIWA-PZSM-C6-**
150V 0-3000V 007-DIWA-PZUA-C6-**
143V 0-5000V 007-DIWA-PTUJ-C6-**
150V 0-5250V 007-DIWA-PZUL-C6-**
150V 0-6000V 007-DIWA-PZUP-C6-**
150V 0-9000V 007-DIWA-PZUY-C6-**
150V 0-15kV 007-DIWA-PZWC-C6-**
150V 0-18kV 007-DIWA-PZWD-C6-**
150V 0-45kV 007-DIWA-PZWJ-C6-**
150V 0-60kV 007-DIWA-PZWL-C6-**
Product Codes – AC Voltmeters Transformer Rated (40/70Hz)***
For connection diagrams, refer to Figure H.
17
AC Voltmeter
Fig. H Models 007-DI2, 007-DIA
007-DIB, 007-DIC, 007-DIN,
007-DIT, 007-DIV, 007-DIW
LED Digital/Analog Meter
Fig. G Models 007-DA2, 007-DAA
LCD Digital/Analog Meter
Fig. I Models 007-DI2, 007-DIA
007-DIB, 007-DIC, 007-DIN,
007-DIT, 007-DIV, 007-DIW
LED Digital/Analog Meter
Rating Scaling* Catalog number
1A 0-1A 007-DIBA-LALA-C6-**
1.5A 0-1.5A 007-DIBA-LCLC-C6-**
2A 0-2A 007-DIBA-LELE-C6-**
3A 0-3A 007-DIBA-LJLJ-C6-**
5A 0-5A 007-DIBA-LSLS-C6-**
8A 0-8A 007-DIBA-MJMJ-C6-**
10A 0-10A 007-DIBA-MTMT-C6-**
* Other scalings are available.
** Specify power supply voltage according to power supply
codes table located on page 22.
*** Case types 007 use 10-32 UNF terminals.
For connection diagrams, refer to Figure I.
18
LED Digital | Analog Combination
Product Codes – AC Ammeters - Direct Reading (40/70Hz)***
AC Ammeter
LED Digital | Analog Combination
Product Codes – AC Ammeters Transformer Rated (40/70Hz)
AC Ammeter
19
Rating Scaling* Catalog number
5A 0-15A 007-DIBA-LSND-C6-**
5A 0-20A 007-DIBA-LSNG-C6-**
5A 0-25A 007-DIBA-LSNJ-C6-**
5A 0-30A 007-DIBA-LSNL-C6-**
5A 0-40A 007-DIBA-LSNP-C6-**
5A 0-50A 007-DIBA-LSNT-C6-**
5A 0-60A 007-DIBA-LSNW-C6-**
5A 0-75A 007-DIBA-LSPB-C6-**
5A 0-80A 007-DIBA-LSPD-C6-**
5A 0-100A 007-DIBA-LSPK-C6-**
5A 0-150A 007-DIBA-LSPZ-C6-**
5A 0-200A 007-DIBA-LSRL-C6-**
5A 0-250A 007-DIBA-LSRS-C6-**
5A 0-300A 007-DIBA-LSRX-C6-**
5A 0-400A 007-DIBA-LSSC-C6-**
5A 0-500A 007-DIBA-LSSF-C6-**
5A 0-600A 007-DIBA-LSSJ-C6-**
5A 0-750A 007-DIBA-LSSM-C6-**
5A 0-800A 007-DIBA-LSSN-C6-**
5A 0-1000A 007-DIBA-LSSS-C6-**
5A 0-1200A 007-DIBA-LSSU-C6-**
5A 0-1500A 007-DIBA-LSTC-C6-**
5A 0-1600A 007-DIBA-LSTE-C6-**
* Other scalings are available.
** Specify power supply voltage, according to power supply codes table
located on page 22.
For connection diagrams, refer to Figure J.
Digital accuracy ±0.1% ±1 counts, analog accuracy ±1%
Fig. J Models 007-DI2, 007-DIA
007-DIB, 007-DIC, 007-DIN,
007-DIT, 007-DIV, 007-DIW
LED Digital/Analog Meter
LED Digital | Analog Combination
Product Codes – DC Voltmeters - Direct Reading
* Other scalings are available.
** Specify power supply voltage, according to power supply codes table
located on page 22.
Rating Scaling* Catalog number
200mV 0-200mV 007-DIVA-KAKA-**
250mV 0-250mV 007-DIVA-KDKD-**
500mV 0-500mV 007-DIVA-KMKM-**
1V 0-1V 007-DIVA-LALA-**
5V 0-5V 007-DIVA-LSLS-**
10V 0-10V 007-DIVA-MTMT-**
15V 0-15V 007-DIVA-NDND-**
30V 0-30V 007-DIVA-NLNL-**
50V 0-50V 007-DIVA-NTNT-**
75V 0-75V 007-DIVA-PBPB-**
80V 0-80V 007-DIVA-PDPD-**
150V 0-150V 007-DIVA-PZPZ-**
300V 0-300V 007-DIVA-RXRX-**
400V 0-400V 007-DIVA-SCSC-**
500V 0-500V 007-DIVA-SFSF-**
600V 0-600V 007-DIVA-SJSJ-**
150-0-150V 150-0-150V 007-DINA-RXRX-**
300-0-300V 300-0-300V 007-DINA-SJSJ-**
600-0-600V 600-0-600V 007-DINA-SUSU-**
For connection diagrams, refer to Figure K.
Digital accuracy ±0.5% ±1 counts, analog accuracy ±1%
DC Voltmeter
Fig. K Models 007-DI2, 007-DIA
007-DIB, 007-DIC, 007-DIN,
007-DIT, 007-DIV, 007-DIW
LED Digital/Analog Meter
20
DC Ammeter
LED Digital | Analog Combination
Product Codes – DC Ammeters - Shunt Rated
Digital accuracy ±0.5% ±1 counts, analog accuracy ±1%
Fig. L Models 007-DI2, 007-DIA
007-DIB, 007-DIC, 007-DIN,
007-DIT, 007-DIV, 007-DIW
LED Digital/Analog Meter
21
Rating Scaling* Catalog number
50mV-4mA 007-DIAA-EY**-**
50-0-50mV-2-0-2mA 007-DICA-GB**-**
100-0-100mV 007-DICA-GM**-**
100-0-100mV-2-0-2mA 007-DICA-FM**-**
For connection diagram, refer to Figure L.
Scaled to suit standard
shunt ratings
Rating Scaling* Catalog number
1-5mA 007-DIAA-GM**-**
4-20mA 007-DIAA-HG**-**
10-50mA 007-DIAA-HZ**-**
Product Codes – DC Ammeters - Suppressed Zero
For connection diagram, refer to Figure L.
Digital accuracy ±0.5% ±1 counts, analog accuracy ±1%
Scaled to suit standard
shunt ratings
Rating Scaling* Catalog number
1mA 0-1mA 007-DIAA-FAFA-**
2mA 0-2mA 007-DIAA-FGFG-**
5mA 0-5mA 007-DIAA-FXFY-**
10mA 0-10mA 007-DIAA-GZGZ-**
20mA 0-20mA 007-DIAA-HFHF-**
30mA 0-30mA 007-DIAA-HMHM-**
50mA 0-50mA 007-DIAA-HYHY-**
100mA 0-100mA 007-DIAA-JRJR-**
200mA 0-200mA 007-DIAA-KAKA-**
300mA 0-300mA 007-DIAA-KGKG-**
500mA 0-500mA 007-DIAA-KMKM-**
800mA 0-800mA 007-DIAA-KWKW-**
1A 0-1A 007-DIAA-LALA-**
Product Codes – DC Ammeters - Direct Reading
For connection diagram, refer to Figure L.
Digital accuracy ±0.5% ±1 counts, analog accuracy ±1%
* Other scalings are available.
** Specify power supply voltage, according to power supply codes table
located on page 22.
Switchboard Meter Options
22
Scale – Options
Options Option
code
Red or colored line or mark (specify position) SL
Colored zones or segments (specify limits and color(s) SZ
Customer | user logo imprinted on dial SM
Construction – Options
Options Option
code
Anti-glare window BR
Polychloroprene panel gasket MG
The suffix option code is added at the end of the complete part number.
A5-120 - 250V AC/DC MU - 12V DC
PQ - 120V AC BD - 24V DC
A2 - 12 - 48V DC NR - 48V DC
PR - 120V DC
PS - 125V DC
Product Codes – Power Supply
Power Supplies
www.crompton-instruments.com
TE Energy
Customer Center
8000 Purfoy Road
Fuquay-Varina, NC 27526-9349
T: 800-327-6996
F: 800-527-8350
For more information and your country
contact person, please visit us at:
cromptonusa.com
crompton-instruments.com
energy.te.com
© 2012 Tyco Electronics Corporation. All rights reserved.
1773466-6 E499 11/12
About TE Connectivity
TE Connectivity is a global, $14 billion company that designs and manufactures over
500,000 products that connect and protect the flow of power and data inside the prod-
ucts that touch every aspect of our lives. Our nearly 100,000 employees partner with
customers in virtually every industry - from consumer electronics, energy and health-
care, to automotive, aerospace and communication networks - enabling smarter, faster,
better technologies to connect products to possibilities.
While TE Connectivity (TE) has made every reasonable effort to ensure the accuracy of the information in this catalogue, TE does not guaran-
tee that it is error-free, nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or
current. TE reserves the right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims
all implied warranties regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or
fitness for a particular purpose. The dimensions in this catalogue are for reference purposes only and are subject to change without notice.
Specifications are subject to change without notice. Consult TE for the latest dimensions and design specifications. TE Connectivity and TE
connectivity (logo) are trademarks. CROMPTON is a trademark of Crompton Parkinson Limited and is used under licence. Other trademarks
are property of their respective owners.
TE Energy – innovative and economical solutions for the electrical power industry: cable accessories, connectors & fittings, insulators &
insulation, surge arresters, switching equipment, street lighting, power measurement and control.