Ordering information AC-DC Power Supplies DIN Rail Type KLEA/KLNA120F KLO 1 A 120 2 3 F 4 Example recommended EMI/EMC filter NAC-04-472-D R UL508 High voltage pulse noise type : NAP series Low leakage current type : NAM series * A higher current rating EMI/EMC filter may be recommended in view of the other devices that could be connected in parallel with the power supply. -OO -O 5 6 1 Series name KLE : Euro Style I/O Terminals KLN : Barrier Blocks Style I/O Terminals 2 Single output 3 Output wattage 4 Universal input 5 Output voltage 6 Option C : with Coating N2 : Screw mounting *Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations. MODEL MAX OUTPUT WATTAGE[W] DC OUTPUT KLEA/KLNA120F-24 120 24V 5A KLEA/KLNA120F-48 120 48V 2.5A SPECIFICATIONS MODEL VOLTAGE[V] CURRENT[A] ACIN 115V ACIN 230V FREQUENCY[Hz] ACIN 115V ACIN 230V ACIN 115V POWER FACTOR ACIN 230V INRUSH CURRENT[A] ACIN 115V *1 ACIN 230V LEAKAGE CURRENT[mA] VOLTAGE[V] CURRENT[A] *2 LINE REGULATION[mV] LOAD REGULATION[mV] *2 0 to +70C *3 -20 - 0C RIPPLE[mVp-p] Io=0 - 30% 0 to +70C OUTPUT RIPPLE NOISE[mVp-p] *3 -20 - 0C Io=0 - 30% 0 to +70C TEMPERATURE REGULATION[mV] -20 to +70C *4 DRIFT[mV] START-UP TIME[ms] HOLD-UP TIME[ms] OUTPUT VOLTAGE ADJUSTMENT RANGE[V] OUTPUT VOLTAGE SETTING[V] PROTECTION OVERCURRENT PROTECTION CIRCUIT AND OVERVOLTAGE PROTECTION[V] OTHERS DC_OK LAMP INPUT-OUTPUT INPUT-PE ISOLATION OUTPUT-PE OPERATING TEMP.,HUMID.AND ALTITUDE STORAGE TEMP.,HUMID.AND ALTITUDE ENVIRONMENT *7 VIBRATION IMPACT SAFETY AND AGENCY APPROVALS CONDUCTED NOISE NOISE REGULATIONS HARMONIC ATTENUATOR *6 CASE SIZE OTHERS WEIGHT COOLING METHOD INPUT EFFICIENCY[%] KLEA/KLNA120F-24 KLEA/KLNA120F-48 AC85 - 264 1f (Output derating is required) *9 1.2typ 0.6typ 50 / 60 (45 - 66) 86.5typ 88.0typ 0.98typ 0.90typ 20typ (Io=100%)(at cold start Ta=25C) 40typ (Io=100%)(at cold start Ta=25C) 0.45 / 0.75max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60950-1 and DEN-AN) 24 48 5 2.5 96max (Io=30-100%) *8 192max (Io=30-100%) *8 150max (Io=30-100%) *8 300max (Io=30-100%) *8 150max 150max 240max 240max 500max 650max 180max 180max 300max 300max 500max 650max 240max 480max 290max 600max 96max 192max 500typ (ACIN 115V, Io=100%) 20typ (ACIN 115V, Io=100%) 21.60 to 26.40 43.20 to 52.80 24.00 to 24.96 48.00 to 49.92 Works over 105% of rating and recovers automatically 27.60 to 33.60 54.00 to 67.20 LED (Green) AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW minAt Room Temperature AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW minAt Room Temperature AC500V 1minute, Cutoff current = 100mA, DC500V 50MW minAt Room Temperature -20 to +70C, 20 - 90%RH (Non condensing), Type tested for -40C start-up (Required to Derating) -30 to +85C, 20 - 90%RH (Non condensing) 10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60 minutes along Z axis (Non operating, mounted on DIN Rail) 196.1m/s2 (20G), 11ms, once each X, Y and Z axis (Packing state) UL60950-1, C-UL (CSA60950-1), EN60950-1, UL508, Complies with DEN-AN Complies with FCC-B, VCCI-B, CISPR22-B, EN55011-B, EN55022-B Complies with IEC61000-3-2Class A) *5 38X124X117mm (WXHXD) [1.5X4.88X4.61 inches] 580g max Convection *1 The value is primary surge. The current of input surge to a built-in EMI/EMC Filter(0.2ms or less)is excluded. *2 Please contact us about dynamic load and input response. *3 This is the value that measured on measuring board with capacitor of 22mF and 0.1mF at 150mm from output terminal. Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to KEISOKU-GIKEN: RM103). Please refer to the instruction manual 2.5. KL-2 *4 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/ output. *5 Please contact us about another class. *6 Case size contains neither the umbo. *7 Only as standard mounting orientation (A). Refer to the instruction manual 4.1. If install other than standard mounting orientation (A), please fix the power supply for withstand the vibration and impact. *8 *9 * * Burst operation at 30% load or less. Please contact us about DC input voltage. To meet the specifications. Do not operate over-loaded condition. A sound may occur from power supply at light or peak loading. KL series Block diagram FUSE 250V 4A AC IN 85 NOISE FILTER 264V RECTIFIER INRUSH CURRENT LIMIT PE BOOSTER INDUCTOR CURRENT SENSING TRANSFORMER RECTIFIER AND FILTER RECTIFIER AND FILTER INVERTER DC OUT INVERTER CURRENT SENSING Photocoupler CONTROL Photocoupler OVER VOLTAGE PROTECTION CONTROL External view 8.6 [0.34] 38 [4.77] [1.5] AC(L) AC(N) PE [0.44] [0.35] [4.38] 10 [0.39] 38 [5.26] 133.5 [4.29] 124 [4.88] 111.2 Name plate (65.7) [2.59] 0.5 14.6 TB1 11.2 9 108.9 [4.15] 105.4 [5.26] 121.2 LED(DC_OK) Output voltage adjustable potentiometer [0.02] [0.57] 4.2 117 [4.61] [0.08] 69 (65.7) 6.6 [0.26] 9.5 [0.37] [0.17] 9.5 [2.59] [4.46] 124 [4.88] 69 7.5 [0.44] [0.3] TB1 11.2 [0.37] Name plate [2.72] 109 [4.29] LED (DC_OK) Output voltage adjustable potentiometer AC(L) AC(N) PE 133.5 TB2 +VOUT -VOUT 113.2 TB2 +VOUT -VOUT 2 6-M4 [0.57] 10 [0.39] 14.6 9 [0.35] [2.72] [4.38] 9.3 6.6 111.2 [0.37] 6.4 [0.25] [0.26] 9.5 [0.37] 117 [4.61] 121.2 [4.77] [1.5] Tolerance : 1.5 [0.06] Weight : 580g max PCB Material/thickness : FR-4 / 1.6mm [0.06] Chassis material : Aluminum Case material : Stainless steel Din rail attachment material : Aluminum, Stainless steel, Nylon Dimensions in mm, [ ] = inches Screw tightening torque : 1N m max Tolerance : 1.5 [0.06] Weight : 580g max PCB Material/thickness : FR-4 / 1.6mm [0.06] Chassis material : Aluminum Case material : Stainless steel Din rail attachment material : Aluminum, Stainless steel, Nylon Dimensions in mm, [ ] = inches Screw tightening torque : 1.6N m max KL-3 Ordering information AC-DC Power Supplies DIN Rail Type KLEA/KLNA240F KLO 1 A 240 2 3 F 4 Example recommended EMI/EMC filter NAC-06-472-D R UL508 High voltage pulse noise type : NAP series Low leakage current type : NAM series * A higher current rating EMI/EMC filter may be recommended in view of the other devices that could be connected in parallel with the power supply. -OO -O 5 6 1 Series name KLE : Euro Style I/O Terminals KLN : Barrier Blocks Style I/O Terminals 2 Single output 3 Output wattage 4 Universal input 5 Output voltage 6 Option C : with Coating N2 : Screw mounting *Make sure necessary tests will be carried out on your end equipment with the power supply installed in accordance with any required EMC/EMI regulations. MODEL MAX OUTPUT WATTAGE[W] DC OUTPUT KLEA/KLNA240F-24 240 24V 10A KLEA/KLNA240F-48 240 48V 5A SPECIFICATIONS MODEL VOLTAGE[V] CURRENT[A] ACIN 115V ACIN 230V FREQUENCY[Hz] ACIN 115V ACIN 230V ACIN 115V POWER FACTOR ACIN 230V INRUSH CURRENT[A] ACIN 115V *1 ACIN 230V LEAKAGE CURRENT[mA] VOLTAGE[V] CURRENT[A] *2 LINE REGULATION[mV] LOAD REGULATION[mV] *2 0 to +70C *3 RIPPLE[mVp-p] -20 - 0C 0 to +70C RIPPLE NOISE[mVp-p] *3 OUTPUT -20 - 0C 0 to +70C TEMPERATURE REGULATION[mV] -20 to +70C *4 DRIFT[mV] START-UP TIME[ms] HOLD-UP TIME[ms] OUTPUT VOLTAGE ADJUSTMENT RANGE[V] OUTPUT VOLTAGE SETTING[V] PROTECTION OVERCURRENT PROTECTION CIRCUIT AND OVERVOLTAGE PROTECTION[V] OTHERS DC_OK LAMP INPUT-OUTPUT INPUT-PE ISOLATION OUTPUT-PE OPERATING TEMP.,HUMID.AND ALTITUDE STORAGE TEMP.,HUMID.AND ALTITUDE ENVIRONMENT *7 VIBRATION IMPACT SAFETY AND AGENCY APPROVALS CONDUCTED NOISE NOISE REGULATIONS HARMONIC ATTENUATOR *6 CASE SIZE OTHERS WEIGHT COOLING METHOD INPUT EFFICIENCY[%] KLEA/KLNA240F-24 KLEA/KLNA240F-48 AC85 - 264 1f (Output derating is required) *8 2.4typ 1.3typ 50 / 60 (45 - 66) 88typ 90typ 0.98typ 0.90typ 20typ (Io=100%)(at cold start Ta=25C) 40typ (Io=100%)(at cold start Ta=25C) 0.45 / 0.75max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60950-1 and DEN-AN) 24 48 10 5 96max 192max 150max 300max 150max 150max 240max 240max 180max 180max 300max 300max 240max 480max 290max 600max 96max 192max 500typ (ACIN 115V, Io=100%) 20typ (ACIN 115V, Io=100%) 21.60 to 26.40 43.20 to 52.80 24.00 to 24.96 48.00 to 49.92 Works over 105% of rating and recovers automatically 27.60 to 33.60 54.00 to 67.20 LED (Green) AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW minAt Room Temperature AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW minAt Room Temperature AC500V 1minute, Cutoff current = 100mA, DC500V 50MW minAt Room Temperature -20 to +70C, 20 - 90%RH (Non condensing), Type tested for -40C start-up (Required to Derating) -30 to +85C, 20 - 90%RH (Non condensing) 10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60 minutes along Z axis (Non operating, mounted on DIN Rail) 196.1m/s2 (20G), 11ms, once each X, Y and Z axis (Packing state) UL60950-1, C-UL (CSA60950-1), EN60950-1, UL508, Complies with DEN-AN Complies with FCC-B, VCCI-B, CISPR22-B, EN55011-B, EN55022-B Complies with IEC61000-3-2Class A) *5 50X124X117mm (WXHXD) [1.97X4.88X4.61 inches] 750g max Convection *1 The value is primary surge. The current of input surge to a built-in EMI/EMC Filter(0.2ms or less)is excluded. *2 Please contact us about dynamic load and input response. *3 This is the value that measured on measuring board with capacitor of 22mF and 0.1mF at 150mm from output terminal. Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to KEISOKU-GIKEN: RM103). Please refer to the instruction manual 2.5. KL-4 *4 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/ output. *5 Please contact us about another class. *6 Case size contains neither the umbo. *7 Only as standard mounting orientation (A). Refer to the instruction manual 4.1. If install other than standard mounting orientation (A), please fix the power supply for withstand the vibration and impact. *8 Please contact us about DC input voltage. * To meet the specifications. Do not operate over-loaded condition. * A sound may occur from power supply at light or peak loading. KL series Block diagram FUSE 250V 8A AC IN 85 NOISE FILTER 264V RECTIFIER INRUSH CURRENT LIMIT PE BOOSTER INDUCTOR CURRENT SENSING TRANSFORMER RECTIFIER AND FILTER RECTIFIER AND FILTER INVERTER DC OUT INVERTER CURRENT SENSING Photocoupler CONTROL Photocoupler CONTROL OVER VOLTAGE PROTECTION CONTROL External view 8.6 [0.34] [0.39] 7-M4 2 [0.08] TB2 TB2 111.2 [4.38] [0.61] [0.37] 50 [4.77] 10 [0.39] 50 [5.26] 133.5 (65.7) [2.59] [4.29] 124 69 15 [0.59] 0.5 14.6 [0.46] 108.9 [4.15] 105.4 [2.72] [5.26] 121.2 Name plate [0.02] [0.57] 4.2 [4.61] TB1 11.6 9.3 9.5 117 LED(DC_OK) Output voltage adjustable potentiometer AC(L) AC(N) PE [0.37] 15.5 [0.17] 6.6 [0.26] [2.59] (65.7) 69 7.5 [0.3] TB1 11.6 133.5 [4.46] 124 [4.88] 113.2 Name plate [2.72] 109 [4.29] LED(DC_OK) Output voltage adjustable potentiometer AC(L) AC(N) PE [4.88] +VOUT -VOUT +VOUT -VOUT [0.46] 10 [0.39] [4.38] [0.57] 10 111.2 6.6 [0.25] 14.6 6.4 [0.61] [0.26] 15.5 117 [4.61] 121.2 [4.77] [1.97] [1.97] Tolerance : 1.5 [0.06] Weight : 750g max PCB Material/thickness : FR-4 / 1.6mm [0.06] Chassis material : Aluminum Case material : Stainless steel Din rail attachment material : Aluminum, Stainless steel, Nylon Dimensions in mm, [ ] = inches Screw tightening torque : 1N m max Tolerance : 1.5 [0.06] Weight : 750g max PCB Material/thickness : FR-4 / 1.6mm [0.06] Chassis material : Aluminum Case material : Stainless steel Din rail attachment material : Aluminum, Stainless steel, Nylon Dimensions in mm, [ ] = inches Screw tightening torque : 1.6N m max KL-5 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Cosel: KLEA240F-48 KLEA120F-48 KLEA240F-24 KLEA120F-24