https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page1/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR analog frequency converter for converting standard analog signals into frequency signals or PWM signals,
with spring-cage connection. Replacement part: 2902032 MINI MCR-2-UI-FRO-PT.
Your advantages
Power supply possible via the foot element (TBUS)
Error indication via diagnostic LED and analog signal
Highly-compact analog-to-frequency transducer for electrical isolation, amplification, conversion, and filtering of standard signals to create
frequencies or PWM signals
Configurable interference filter
3-way isolation
PWM output of 5 ... 95%
Input and output signals can be configured via DIP switches
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4017918996062
Weight per Piece (excluding packing) 65.400 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Dimensions
Width 6.2 mm
Height 93.1 mm
https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page2/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Technical data
Dimensions
Depth 102.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Degree of protection IP20
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Input data
Configurable/programmable Yes
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
0 mA ... 10 mA
2 mA ... 10 mA
Input resistance current input approx. 50 Ω
Voltage input signal 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
2 V ... 10 V
Input resistance of voltage input approx. 110 kΩ
Output data
Number of outputs 1
Frequency output
Frequency output: signal 0 Hz ... 10 kHz
0 Hz ... 5 kHz
0 Hz ... 2.5 kHz
0 Hz ... 1 kHz
0 Hz ... 500 Hz
0 Hz ... 250 Hz
0 Hz ... 100 Hz
0 Hz ... 50 Hz
Frequency output: min. load 4 mA ≤ (UL / RL) ≤ 20 mA
PWM output: signal 7.8 kHz (10 bit)
3.9 kHz (10 bit)
1.9 kHz (12 bit)
https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page3/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Technical data
Frequency output
977 Hz (12 bit)
488 Hz (14 bit)
244 Hz (14 bit)
122 Hz (16bit)
61 Hz (16bit)
PWM output: min. load 12 mA ≤ (UL / RL) ≤ 20 mA
Maximum switching voltage 30 V
Load current maximum 20 mA
Overrange/underrange Can be set (via DIP switch)
Type of protection Short-circuit protection, polarity reversal protection
Step response (0–99%) < 15 ms (+ (1/f) smallest filter)
< 1 s (+ (1/f) largest filter)
Power supply
Nominal supply voltage 24 VDC
Supply voltage range
19.2 VDC ... 30 VDC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to EN60715))
Max. current consumption < 10 mA (at 24 V DC)
Power consumption < 200 mW
Connection data
Connection method Spring-cage connection
Stripping length 8 mm
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 12
General
No. of channels 1
Maximum transmission error ≤ 0.1 % (> 7 kHz ≤ 0.2%)
Maximum temperature coefficient < 0.02 %/K
Temperature coefficient, typical < 0.02 %/K
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 30 VAC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page4/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Technical data
General
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color green
Housing material PBT
Mounting position any
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN61000-4-3
Typical deviation from the measuring range final value 2 %
Designation Fast transients (burst)
Standards/regulations EN61000-4-4
Typical deviation from the measuring range final value 2 %
Designation Conducted interferences
Standards/regulations EN61000-4-6
Typical deviation from the measuring range final value 2 %
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Designation Electromagnetic RF field
Standards/regulations EN61000-4-3
EN61000-4-4
EN61000-4-5
Designation Conducted interferences
Standards/regulations EN61000-4-6
Electrical isolation Basic insulation according to EN 61010
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Environmental Product Compliance
https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page5/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Technical data
Environmental Product Compliance
China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram Diagram
PWMoutput(pulsewidthmodulation)
Variablepulse-pauseratio/FixedperioddurationT
Frequencyoutput
Variablefrequency/PerioddurationT
T T T T T T
T T T T T T
Classifications
eCl@ss
eCl@ss 10.0.1 27210120
eCl@ss 4.0 27210100
eCl@ss 4.1 27210100
eCl@ss 5.0 27210100
eCl@ss 5.1 27210100
eCl@ss 6.0 27210100
eCl@ss 7.0 27210120
eCl@ss 8.0 27210120
eCl@ss 9.0 27210120
ETIM
ETIM 4.0 EC002653
ETIM 5.0 EC002653
ETIM 6.0 EC002653
ETIM 7.0 EC002653
UNSPSC
UNSPSC 6.01 30211506
https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page6/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Classifications
UNSPSC
UNSPSC 7.0901 39121008
UNSPSC 11 39121008
UNSPSC 12.01 39121008
UNSPSC 13.2 39121008
UNSPSC 19.0 39121008
Accessories
Accessories
DIN rail connector
DIN rail bus connectors-ME 6,2 TBUS-2 1,5/5-ST-3,81 GN-2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Power module
Power terminal block-MINI MCR-SL-PTB-2864134
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw connection,
maximum current consumption of up to 2A
Power terminal block-MINI MCR-SL-PTB-SP-2864147
MCR feed-in terminal for supplying several MINI Analog modules via a DIN rail connector, with spring-cage connection,
maximum current consumption of up to 2A. Replacement part: 2902067 MINI MCR-2-PTB-PT.
Power supply
https://www.phoenixcontact.com/us/products/2810243
01/16/2021Page7/7
Frequency transducer-MINI MCR-SL-UI-F-SP-2810243
Accessories
Power supply unit-MINI-SYS-PS-100-240AC/24DC/1.5-2866983
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
Power supply unit-MINI-PS-100-240AC/24DC/1.5/EX-2866653
Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the
potentially explosive area
Phoenix Contact 2021 © - all rights reserved