100518/20 LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 1/4
IPN = 100 .. 1000 A
Features
VFD and SCR waveforms current ●
measurement
True RMS output ●
4-20 mA current output ●
Panel mounting ●
Eliminates insertion loss ●
Isolated plastic case recognized ●
according to UL94-V0
Advantages
Large aperture for cable up to ●
Ø32mm
High isolation between primary ●
and secondary circuits
Easy installation ●
Applications
VFD Controlled Loads ●
VFD output indicates how the
motor and attached load are
operating.
SCR Controlled Loads ●
Acurate measurement of phase
angle red or burst red (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
Switching Power Supplies and ●
Electronic Ballasts
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Application domain
Energy and Automation ●
AC/DC Current Transducer DHR-C420
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 4-20 mA
current output.
Electrical data
Primary Nominal Primary AC Current Output current Type
DC & AC Current Max. Peak Value 1)
IPN (A.t.RMS) IP (A) IOUT (mA DC)
100 600 4-20 DHR 100 C420
200 600 4-20 DHR 200 C420
300 1000 4-20 DHR 300 C420
400 1000 4-20 DHR 400 C420
500 2) 1800 4-20 DHR 500 C420
600 2) 1800 4-20 DHR 600 C420
1000 2) 1800 4-20 DHR 1000 C420
RL Load resistance < 300 W
VC Supply voltage + 20 .. 50 V DC
IC Current consumption 30 mA + IOUT
ISL Output current limitation < 25 mA
ÎP Overload capability (Ampere Turns) 30000 A.t
Performance data
X Accuracy @ IPN, TA = 25°C (excluding offset) < ± 1 % of IPN
eL Linearity error (1% of IPN .. ± IPN) < ± 1.0 % of IPN
IOE Electrical offset current, TA = 25°C 4 mA
TCIOE Temperature coefcient of IOE ( 0..+60 °C) ± 3.2 mA/K
(-40..+70 °C) ± 6.4 mA/K
TCIOUT Temperature coefcient of IOUT (% of reading) ± 0.1 %/K
tr Response time to 90 % of IPN step < 150 ms
BW Frequency bandwidth (± 1 dB) DC 20..6000 Hz
General data
TA Surrounding operating temperature - 40 .. + 70 °C
TS Surrounding storage temperature - 40 .. + 85 °C
m Mass 260 g
IPxx Protection degree IP20
Notes :
1) The Max. Peak AC Current is the highest peak level of the primary
signal that is taken into account for accurate True RMS calculation. Yet
the device is designed for maximum continuous True RMS value equal to
IPN, whereas the output is limited by the above specied output limitation.
2) According to the UL 508 Standard for Safety for Industrial Control
Equipment the primary current must not exceed 475 A.t.RMS through the
transducer hole.