Bussmann(R) (R) Telpower High Current Switch TPHCS Part Number System-Switches (Pullout and Base) To identify part number, replace block with appropriate suffix to identify amperage, thread type, and alarm option. TPHCS - Amperage (select one) 250 - For Use With 70 to 250 Amp Type TPL-B Fuses 800 - For Use With 300 to 800 Amp Type TPL-C Fuses Thread (select one) M - Metric, M8 x 1.25 E - English, 5/16 - 18 TPHCS800-MAV (shown) TPHCS Telpower(R) High Current Switch For use with Telpower(R) Fuses Type TPL-B AND TPL-C. Patents Pending Ampere Ratings: 70 to 800 Amperes Voltage Rating: 80 Volts DC U.L. Withstand Rating: 100,000A Agency Information: U.L. Recognized (investigated to U.L. 1801) as a disconnect switch for the interruption of load current by means of withdrawing the fuse carrier. U.L. Recognized to meet the requirements for Canadian Standards. General Information: * Innovative new design eliminates need for tools to replace the Telpower(R) type TPL-B or TPL-C fuse. * Easy to install-captive fasteners allow for direct busbar mounting (bolts not included). * Optional new electronic alarm provides both local and remote open-fuse indications. --Bipolar alarm designed for both Central Office and Radio applications. --Local LED alarm indication for ease-of-viewing. --Standard male quick-connect terminal for effortless remote alarm connection (Maximum remote alarm current: 20mA). --Eliminates need for parallel indicating fuses. * Fuse presence window allows for easy viewing of installed fuse ampere rating. * Compact design for today's high power, high-density cabinets. * Available as complete switch or pullout and base may be purchased separately. 5-02-01 SB99155 Alarm (leave blank for non-alarming version) L - LED Only, Requires Input From Customer Alarm Circuit *AV - Alarm, System Voltage *Consult factory for availability Part Number System-Bases To identify part number, replace block with appropriate suffix to identify thread type, and alarm option. TPHCS - B - Thread (select one) M - Metric, M8 x 1.25 E - English, 5/16 - 18 Alarm (leave blank for non-alarming version) L - LED Only, Requires Input From Customer Alarm Circuit *AV - Alarm, System Voltage *Consult factory for availability Catalog Numbers-Switches (Pullout and Base) TPHCS250-M High Current Switch, Metric TPHCS250-E High Current Switch, English TPHCS250-ML High Current Switch, Metric, LED TPHCS250-EL High Current Switch, English, LED TPHCS250-MAV High Current Switch, Metric, Alarm TPHCS250-EAV High Current Switch, English, Alarm TPHCS800-M High Current Switch, Metric TPHCS800-E High Current Switch, English TPHCS800-ML High Current Switch, Metric, LED TPHCS800-EL High Current Switch, English, LED TPHCS800-MAV High Current Switch, Metric, Alarm TPHCS800-EAV High Current Switch, English, Alarm Series Fuse TPL-B TPL-B TPL-B TPL-B TPL-B TPL-B TPL-C TPL-C TPL-C TPL-C TPL-C TPL-C Ampere Rating 70 to 250 Amp 70 to 250 Amp 70 to 250 Amp 70 to 250 Amp 70 to 250 Amp 70 to 250 Amp 300 to 800 Amp 300 to 800 Amp 300 to 800 Amp 300 to 800 Amp 300 to 800 Amp 300 to 800 Amp Catalog Numbers - Components TPHCS250-P Pullout only - 250 A TPHCS800-P Pullout only - 800 A TPHCS-B-M Base only, Metric TPHCS-B-E Base only, English TPHCS-B-ML Base only, Metric, LED TPHCS-B-EL Base only, English, LED TPHCS-B-MAV Base only, Metric, Alarm TPHCS-B-EAV Base only, English, Alarm Series Fuse TPL-B TPL-C -- -- -- -- -- -- Ampere Rating 70 to 250 Amp 300 to 800 Amp 800 Amp Max. 800 Amp Max. 800 Amp Max. 800 Amp Max. 800 Amp Max. 800 Amp Max. Form No. TPHCS Page 1 of 2 BIF Doc #5020 Bussmann(R) (R) Telpower High Current Switch TPHCS-Dimensional Data 41.02 (1.615) 66.4 (2.62) 22.2 (0.88) 122.43 (4.820) 25.9 (1.02) 8.8 (0.34) 12.7 (0.50) NOTE: 1.TPHCS -M and -E are the same with the exception of thread type. mm (in) O 7.62 (0.300) Typ. 4 -M & -E TPHCS TPHCS 17.3 (0.68) -ML & -EL TPHCS 100.5 REF (3.96) 74.6 (2.94) Threaded Insert, 4 Places M8x1.25 (-M Series) 5/16-18 (-E Series) Recommended Torque 15N * m (11 Ft-lb) NOTES: 1. TPHCS250 and TPHCS800 pullouts and bases 24.8 REF are the same with (0.98) exception to the type of fuse, TPL-B or TPL-C, the pullout will carry. 2. Plastic rated UL94 16.76 V-0, 140C RTI. (0.660) Tin Plated Copper Terminals 105.2 (4.14) 139.7 (5.50) See table for part number format LED open-fuse indication when used with customer provided alarm circuit 13.2 (0.52) 61.47 (2.420) 39.2 REF (1.54) BOTTOM VIEW LED alarm connections male quick connects. TPHCS COMPONENTS See Catalog Numbers for complete list PULLOUTS 4700 LED CIRCUIT SCHEMATIC Quick-connect terminals NOTES: 1. TPHCS -ML & -EL are the same with the exception of thread type. 2. Maximum continuous LED current 20mA. TPHCS800-P BASES TPHCS250-P TPHCS-B-M (shown for reference) The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 5-02-01 SB99155 Form No. TPHCS Page 2 of 2 BIF Doc #5020 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Eaton: TPHCS-B-EAV TPHCS250-MAV TPHCS250-EAV TPHCS-B-MAV TPHCS800-EAV TPHCS800-MAV