Highlights & Features
Full corrosion resistant al umi nium cha ssis
Minimum buffering time of 200ms @ 24V/40A
Flexi bl e operating buffering voltage modes:
o Fixed mode at 22Vdc
o Dyn amic m ode for Vin -1V
Supports parallel connection to extend buffering time
Conformal coating on PCBA to prot ect against chemical and
dust pollut ants
Safety S t and ards
CB Cer tified for w or ldwide us e
Model Number: DRB-24V040ABN
Unit Weight: 0.76kg
Dimen sions (L x W x D): 121 x 70 x 120.1 mm
Gen eral Description
Delt a’s CliQ II buffer module offers the m ost wi del y used output voltage of 24V and a m inimum buff eri ng ti me of 200m s at 40A in wide
input range from 22.8Vdc to 28.8Vdc. The buffer module utilizes maintenance-free electrolytic capacitors to store energy, thus
eliminates the need of periodic replacement as compared to costlier batteries which also have shorter functional life span. The
DRB-24V040ABN comes with comprehensive protection features like overvoltage, over current and short circuit protections. The
rugged compact aluminium case is shock and vibrati on resistant according to IEC 60068-2 standard.
Model Inf or m a t io n
CliQ II Buffer Module
Model Number Input Voltage Range Output
V
oltage Output Current
DRB-24V040ABN 22.8-28.8Vdc 24Vdc typ. (Depends on Vin) 40.0A
Model Numbering
DR B – 24V
040A
B
N
DIN Rai l Buffer Module Output Voltage Output Current Cli Q I I Series N - Metal C as e,
wit h out Class I, Div 2
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
2
Specifications
Input Ratings / Charact eri stics
Nominal Input Voltage 24Vdc
Input Voltage Range 22.8-28.8Vdc
Input Curren t Char ging Mode < 0.6A
Max Power Di ssipation Standby Mode 2.5W
Charging Time < 40s
Output Rati ngs / Char acter istics
Output Voltage Range Switch = “Fix 22V 21-22.5Vdc
Vbuff is fixed to 22V. Buffering start s i f terminal voltage f alls
below 22Vdc.
Swit c h = “Vin-1V”
(Factory Sett ing)
Vin-1.5V to Vin+0. 5V
Vbuff
w ill depend on V in. Buffering starts if ter minal voltage is
decreased by > 1V typ. The voltage changes slower than 0.5
V/ s will be i gnored. If termi nal volt age fall s bel ow 22Vdc,
buffering star ts immedi ately.
Out pu t Cur rent 40A Max
Output Power 960W Max (24V/40A)
PARD (2 0 MHz) < 350mVpp, b uf fe ring mode
Bufferin g Time < 200ms Min @ 24V/40A Load,
< 8s Mi n @ 24V/1A Load (Refer t o Fig. 1)
Parallel Connection Yes (to in crea se b uffering current or extend bu f fering ti me)
Series Con nec tion No
Fig. 1 Buf ferin g Ti me at 24V Input ( Typica l Values at “Vin-1V”)
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
3
Mechanical
Case Cover / Chassis Aluminium
Dimensions (L x W x D) 121 x 70 x 120.1 mm
Unit Weight 0.90 kg
LED Indi cators Green LED Off Unit is discha rge d or Vin < 22Vdc
Green LED On Unit is fully charged (Ready)
Gr een L ED Fla shin g
Slowly (1Hz) Unit is charging
Gr een L ED Fla shin g
Q uickl y (1 0Hz) Unit is discha rging (Buffering)
Terminal Input / Output 4 Pins (Rated 300V/30A)
Signal 5 Pi ns (Ra te d 300V/30A)
Wire In p ut / Outp ut AWG 12-10
Signal AWG 24-10
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715
Nois e (1 Meter f rom po w er su pply) Sound Pressur e Level (SPL) < 40dBA
Environment
Surrounding Air Temperature
Operating -25°C to +75°C
Storage -25°C to +85°C
Power De-rating Vertical Mounting > 70°C de-rate p ower by 5% / °C
Horizontal Mounting > 70°C de-rat e po wer by 5% / °C
Operating Humidity 5 to 95% RH (Non-Condensing)
Operating Altitude 0 to 2, 50 0 M eters
Shock Test (Non-Operating) IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 time per direction, 2 times in total
Vibration (Non-Operating) IEC 60068-2-6, 10Hz to 500Hz @ 30m / (3G peak);
60 min per axis f or al l X, Y, Z direc tion
Pollution Degree 2
Protections
Overvoltage Yes, 35Vdc Max (the maximum input voltage that will not
cause damage to the unit)
Overload / Ove rcurrent > 120% of rated load current, Latch-off Mode
Short Cir cuit Yes , N o damage to t he u ni t, Latc h-off Mode
Reverse Pola r ity Protect ion Yes, -35Vdc Max (the maxi mu m input voltage tha t will not
cause damage to the unit)
Degree of Protection IP20
Protection Against Shock Cla ss I with P E * co nnec tion
*PE: Primary Earth
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
4
Reliability Data
MTBF (at Vin-1V Mode) > 800,000 hrs. a s per Telcordia SR-332
I/P: 24Vdc, Standby Mode, Ta: 25°C
Expected Cap Li f e Tim e 10 years (Standby Mode @ 40°C)
Safety Standards / Directives
Electrical Equipment in Power Installations EN 50178 / IEC 62103
Electrical Safety SIQ to EN 60950-1, UL/cUL rec og nized to U L 60950-1 and
CSA C22. 2 No. 60950-1 ( File N o. E1913 95), CB scheme to
IEC 60950-1
Indu str ial Cont rol E quipment UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (F ile
No. E315355), CSA to CSA C22.2 No. 107.1-01 (File No.
181564)
CE In conformance with EMC Directive 2004/108/EC and Low
Voltage Directive 2006/95/EC
Mat erial and Parts RoHS Directive 2011/65/EU Compliant
Galvanic Isolation Input & Output / PE 1.5KVac
Signa l / PE 1.5KVac
EMC
EMC / Emis si o ns CISPR 22, EN 55022, EN 55011, FCC Ti tle 47: Class B
Component Power Supply for General Use EN 61204-3
Immunity to EN 55024, EN 61000-6-2
Electrostatic Discharge IEC 61000-4-2 Level 4 Cri teri a A
1)
Air D is ch arge: 15kV
Contact Discharge: 8kV
Radiated F ield IEC 61000-4-3 L evel 3 Criteria A
1)
80MHz-1GHz, 10V/M, 80% modulation (1KHz)
1.4GHz-2GHz, 3V/M, 80% modu la tion (1KHz )
2GHz-2. 7GHz , 1V/M , 80% modu la tion (1KHz )
Conducted IEC 61000-4-6 Level 3 C r iter ia A
1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields IEC 61000-4-8 Cr iter ia A
1)
30A/Meter
Note: Product intended to be used as Apparatus with AC-DC Power Supply, EMC compliance to be verified in correspondence to the connected units.
1) Criteria A: Normal performance within the specification limits
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
5
Blo ck Diagram
Device Description
1) Inp ut / Outp ut termi nal block connector
2) Signal terminal block connector
3) Select s w itch (operat ion mod e)
4) LED display status
5) Universal mounting rail system
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
6
Dimensions
L x W x D: 121 x 70 x 120.1 mm
Engi neering Data
De-rating
Note
1. The uni t may degrade, or be damaged, when
it is continuously used outside the shaded
region, refer to the graph shown in Fig. 2.
2. In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance of 20mm (Vertical
Mounting) or 50mm (Horizontal Mounting)
with adjacent units while the device is in
operation.
3.
Depending on the surrounding air
t emp era tur e an d out put l oad deliver ed b y t he
power su pply, the device can b e very h ot!
4. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
Fig. 2 De-rating for Vertical and Horizontal Mounting Orientation
> 70°C de-r ate power by 5% / °C
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
7
Assembl y & In st all at ion
The uni t can be m ounted on 35mm DIN rails in accordance with EN 60715. The d evic e s h ould b e i n st al l ed wi t h Input / Output terminal
block at the top.
Each device is delivered ready to insta ll.
Mounting
Dismounting
Fig. 3.1 Mounting
Snap on the DIN rai l as shown in Fig. 3.1:
1. Tilt the unit upwards and insert it ont o the DI N rail.
2. Push downwards until stopped.
3. Pre ss against the bottom fron t side for locking.
4. Shake the uni t slightly to ensure that it is secured.
Fig. 3.2 Dismounting
To uni nstall, pull or sl ide down the lat ch wit h scr ew dri ver as
shown i n Fig. 3.2. Then slide the unit in the opposite directi on,
release the latch and pull out the uni t from the rail.
In accordance t o EN 60950 / UL 50950, flexibl e cables require ferr ules.
Use appropriate copper cabl es desi gned to sustain oper ating t emperature of:
1. 60°C, 60°C / 75°C for U SA
2. At least 90°C for Canada.
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
8
Safety Instructions
Vertical Mounting
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not
turned O FF, there is risk of expl osi on / severe damage.
To guarantee sufficient convection cooling, keep a distance of 50mm above and below the device as well as a lateral
dista nce of 20mm (Vertical Mounting) or 50 m m (Horizont al Mounting) to other units.
Note that the enclosure of the devi ce can becom e ver y hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
The main power must be tur ned off before connecti ng or disconnect i ng wir es t o the terminals!
DO NOT ins ert an y objec ts into the unit .
Hazardous voltages may be pres en t f or u p to 5 m i n ut es af t er th e i np u t main s v ol t ag e i s di s co n n ect ed . Do n ot to u c h t h e u ni t d uri n g
this time.
The unit is a built-in unit and must be installed in a cabinet or room (condensation free environment and indoor location) that is
relatively free of conductive contami nants.
Horizontal Mounting
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
9
Functions
Buffering, Ready and Inhibit Signal Characteristics
Signal Level Low: < 1V; High: < +VS-2V
Supply Volt age (+VS) Mi n = 10Vdc, Max = 35Vdc
Maximum Signal Output 35V / 10mA
Buffering Si gnal (B) “H igh” = B uffer m od ule is discharging or in buffering mo de
Isolation (Si gna l Port to Power Por t) 1.5KVac
LED Indi cator Green LED Fl ashing Quickly (10Hz)
Ready Signal (R) High” = B uffer m od ule is f ully ch arged or i n standby mode
Isolation (Si gnal Port to Po w er P ort ) 1.5KVac
LED Indi cator Green LED On
Inhibit Signal (I) “Low” = Shuts down buffer module
Isolation (Si gna l Port to Power Por t) 1.5KVac
Operating Diagram Wiring Schematics
Typical Application Notes can be found on
Page 10.
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 40A
/ DRB-24V040ABN
All paramet ers ar e sp eci fied at 25°C ambient unless ot her wise in dicated.
www.DeltaPSU.com (January 2015, Rev. 00)
10
Typical Application Notes
Fig. 4.1 General connection / wiri ng di agr am
Fig. 4.3 Decoupling of buffered branches
Fig. 4.5 Signals supplied from an external voltage
Fig. 4.2 Paralleli ng of buffer unit s
Fig. 4.4 General signals wiring
Fig. 4.6 Connection diagram wit h redundant operation
T ECHNICAL D ATASHEET
CliQ II Buffer Module
24V 20A
/ DRB-24V020AB
All paramet ers ar e sp eci fied at 25° C am bient un less o t herwi se in dicated .
www.DeltaPSU.com (January 2015, Rev. 00)
11
Connectable Power Suppl ies
The buf f er module i s recommended t o be connected with the foll owing power supplies:
Cl iQ Se ries
DRP-24V48W1AA
DRP024V060W1AA
DRP024V060W1AZ
DRP024V120W1AA
DRP024V240W1AA
DRP024V480W1AA
Overload & Overcurrent Protections
When the output current exceeds 120% of IO (Max load) buffer
module will shut down and latch. Normal operation of buffer
module can be resum ed upon removal of fault and power supply
input is re cyc le d (ON/OFF ) or input to buffer module is recycled.
Short Cir c uit Protection
Buffer module is protected by short circuit during buffering mode,
in the event of short circuit the module will shut down and latch.
Operation can be resumed upon removal of fault and power
supply in put is recycled (ON/OFF) or input to buffer module is
recycled.
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substanc es
The European directive 2011/65/EU limits t he m aximum impurity l evel of hom ogeneous mat erials such as l ead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electr onic equi pment. RoHS is the abbrevi ation forRestriction of the use of cer tain hazardous substances in
elec tric al and elec tronic eq uipment”.
This product conforms to this standard.
Conformal Coati ng
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including
under device, and prevents leakage. The conformal coating dipping can be applied to PCBAs or circui t board.
The coating preserves the performance of precision electronic prim arily by preventing ionizable contaminants
such as salt from r eaching ci rcuit nodes, where the material sl umps around sharp edges. This can be a probl em
es pec ially in hig hly con vers ing atmo sp here.
Cl iQ II Series
DRP024V060W1B
DRP024V060W1N
DRP024V120W1B
DRP024V240W1B
DRP024V480W1B
DRP024V060W3B
DRP024V120W3B
DRP024V240W3B
DRP024V480W3B
DRP024V960W3BN
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Delta Electronics:
DRB-24V040ABA