Fluke 1507/1503 Insulation Resistance Testers 1 of 2 http://us.fluke.com/usen/Products/Fluke+1507+1503.htm?catalog_name=F... Unite d State s [C hang e ] | Fluke [C hang e ] Home | Products | Insulation Testers | Contact us Search Fluke Fluke 1507/1503 Insulation Resistance Testers Resources Products Find Resources Overview Features Specifications Models and Accessories Knowledge and Information AC/DC Voltage Measurement Accuracy Range 600.0 V Resolution 0.1 V 50 Hz to 400 Hz (% of Rdg + Digits) (2 % + 3) Input impedance 3 M (nominal), < 100 pF Common mode rejection ratio (1 k unbalanced): > 60 dB at dc, 50 or 60 Hz Overload Protection 600 V rms or dc Earth bond resistance measurement Range/Resolution 20.00 200.0 2000 20.00 k 0.01 0.1 1.0 0.01 k Accuracy (1.5 % + 3) Overload Protection 2 V rms or dc Open Circuit Test Voltage > 4.0 V, < 8 V Short circuit current > 200.0 mA Insulation specifications Measurement Range 1507: 0.01 M to 10 G 1503: 0.01 M to 2000 M Test voltage 1507: 50 V, 100 V, 250 V, 500 V, 1000 V 1503: 500 V, 1000V Test Voltage Accuracy + 20 %, - 0 % Short circuit current 1 mA nominal Auto Discharge Discharge time < 0.5 second for C = 1 F or less Live circuit indicator Inhibit test if terminal voltage > 30 V prior to initialization of test Maximum Capacitive Load Operable with up to 1 F load Measure Accuracy: 50 V: 100 V: 250 V: 500 V: 1000 V: (3 % + 5) (3 % + 5) (1.5 % + 5) (1.5 % + 5) (1.5 % + 5) to 2000 M, (10 % + 3) above 2000 M General Specifications Maximum voltage applied to any terminal: 600 V ac rms or dc 7/1/2009 3:28 PM Fluke 1507/1503 Insulation Resistance Testers 2 of 2 http://us.fluke.com/usen/Products/Fluke+1507+1503.htm?catalog_name=F... Storage Temperature -40 C to 60 C (-40 F to 140 F) Operating Temperature -20 C to 55 C (-4 F to 131 F) Temperature Coefficient 0.05 x (specified accuracy) per C for temperatures < 18 C or > 28 C (< 64 F or > 82 F) Relative Humidity 0 % to 95 % @ 10 C to 30 C (50 F to 86 F) 0 % to 75 % @ 30 C to 40 C (86 F to 104 F) 0 % to 40 % @ 40 C to 55 C (104 F to 131 F) Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument Shock Electromagnetic compatibility: 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) Safety Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) Certifications: CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition Batteries Battery Life Four AA batteries (NEDA 15A or IEC LR6) Insulation test use: Resistance measurements: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 M with a duty cycle of 5 seconds on and 25 seconds off. Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 with a duty cycle of 5 seconds on and 25 seconds off. Size 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L) Weight 550 g (1.2 lb) IP Rating Altitude Over-range capability: Included accessories: IP40 Operating: 2000 m CAT IV 600 V, 3000 m CAT III 600 V Non-operating (storage): 12,000 m 110 % of range TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe Home | Site Map | Fluke Corporation | Terms and Conditions | Privacy Statement | Disclaimer (c) 1995 - 2009 Fluke Corporation 7/1/2009 3:28 PM