6111B 1
ASIIOSLDO44
01/2002
Data Sheet 6111B
Function
This module is used to output digital signals.
Features
Four digital signal outputs, each with a load
capacity of 0.5 A
Compact design
Can be mounted in various positions
Indication of AS-i voltage
Indictaion of external auxiliary power
Outputs and sensor supply electronically
protected against short-circuits and over-
loads
Single slave Figure 1 Module view
6 1 0 9 B 0 0 1
6 1 0 9 A 0 0 0
AS-Interface (AS-i) Module With 4 Digital
Outputs
ASIIOSLDO44
26111B
Figure 2 Indicators and connections
Figure 3 Pin assignment of outputs
Figure 4 Pin assignment of AS-i/
supply voltage
Diagnostic and Status Indicators
The module is functioning correctly if
all of the green LEDs are on.
Connections
Pin Assignment of Outputs
Pin Assignment of AS-i/Supply Voltage
Y Y
Y Y
Y Y
Y Y
A U X
A S - I
1
1
6 1 1 1 B 0 0 3
6 1 0 9 A 0 0 4
6 1 0 9 A 0 1 5
Des. Color Meaning
AS-i Green Bus voltage available
AUX Green Supply voltage of the outputs
YY Yellow Status of the outputs
Connection Assignment
1 Outputs 1 to 4
Pin Outputs
1 Not used
30 V
4Output
Pin Assignment
1AS-i +
20 V
3AS-i
4+24 V
ASIIOSLDO44
6111B 3
Internal Circuit Diagram
Figure 5 Internal wiring of the module
A S I 3 +
4
6 1 1 1 B 0 1 0
Key:
Protocol chip
Amplifier
Optocoupler
Status LED
Digital Output
A S I 3 +A S I 3 +A S I 3 +
ASIIOSLDO44
46111B
Installing the Module
Installing the Module
Figure 6 Installing the module
Screw the module directly onto a flat moun-
ting surface.
The bottom (A) or the side (B) of the module
can be the mounting surface.
Connecting the AS-i and the Voltage Supply
Figure 7 Connecting the AS-i and the voltage
supply
Connect the AS-i bus and the power supply
to the M12 connector.
For example, use the connecting cable,
Order No. 27 41 19 2.
6 1 0 9 A 0 0 5
A
B
6 1 0 9 A 0 0
6
ASIIOSLDO44
6111B 5
Connecting Actuators
Figure 8 Connecting the actuators
Connect your actuators to the desired
outputs (M8 connections).
Screw a protective cap
(Order No. 18 82 54 0, some are sup-
plied as standard) onto the
connectors that are not being used.
Connection Example
Figure 9 Typical actuator connection
Connection Notes
Use PELV power supply
The auxiliary supply voltage for the
supply of the outputs must be tapped
from an isolated power supply (PELV
according to IEC 60364-4-41).
6 1 0 9 A 0 0
7
O U T 2
O U T 1
O U T 4
O U T 3
6 1 1 1 B 0 1 1
ASIIOSLDO44
66111B
Programming Data
Configuration Data
I/O code 8hex (8dec)
ID code 0hex (0dec)
AS-i specification 2.0 (single slave)
Data Bit (Output Via AS-i)
Bit Function
D0 Output OUT1
D1 Output OUT2
D2 Output OUT3
D3 Output OUT4
Parameter Bit (Programmable Using AS-i)
Bit Function
P0 Not used
P1 Not used
P2 Not used
P3 Not used
ASIIOSLDO44
6111B 7
Technical Data
Figure 10 Dimensions of the module and mounting plate
General Data
Order Designation ASI IO SL DIO 4/4
Order No. 27 41 12 1
Housing dimensions (width x height x depth) 26 mm x 26 mm x 88.5 mm
(1.024 in. x 1.024 in. x 3.484 in.)
Housing material PBT
Weight (typical) Approximately 100 g
Permissible temperature (operation) -25°C to +70°C (-13°F to +158°F)
Permissible temperature (storage/transport) -25°C to +85°C (-13°F to +185°F)
Degree of protection according to IEC 60529 IP 67
Degree of protection according to IEC 60536 (VDE 0106) Class of protection III
Operating voltage Protected against polarity reversal
from the AS-interface
Maximum operating current 50 mA
6 1 0 9 B 0 1 2
8 8 , 5 m m ( 3 . 4 8 4 " )
7 9 , 5 m m ( 3 . 1 3 0 " )
4 m m
( 0 . 1 5 7 " )
4 m m
( 0 . 1 5 7 " )
2 6 m m
( 1 . 0 2 4 " )
2 6 m m
( 1 . 0 2 4 " )
ASIIOSLDO44
86111B
Connections
AS-interface and external auxiliary power M12 male connector
Outputs M8 female connector
Digital Outputs
Status indicator LED (yellow)
Number 4
Connection method for actuators Two-wire technology
Minimum output voltage UAux = - 0.5 V
Nominal current per output 0.5 A
Total current per module 3 A
ON delay time 1 ms
OFF delay time 1 ms
Derating No
Permissible load per output
Ohmic load 12 W
Inductive load 12 VA
Lamp load 12 W
Permissible switching frequency with
Ohmic load 0 kHz to 1 kHz
Inductive load 0 Hz to 1 Hz
Lamp load 0 Hz to 10 Hz
Limitation of the voltage induced on circuit inter-
ruption
Yes
Protective function Short-circuit-proof
Approvals
CE Yes
AS-i certification Yes
ASIIOSLDO44
6111B 9
Conformance With EMC Directive 89/336/EEC
Noise Immunity Test According to EN 50082-2:1995
Electrostatic discharge (ESD) EN 61000-4-2:1995/
IEC 61000-4-2
Criterion B
6 kV contact discharge
8 kV air discharge
Electromagnetic fields EN 61000-4-3:1993/
IEC 61000-4-3
Criterion A
Field strength: 10 V/m
Fast transients (burst) EN 61000-4-4:1995/
IEC 61000-4-4
Criterion B
Supply lines: 2 kV
Signal/data lines: 2 kV
Conducted interference EN 61000-4-6:1993/
IEC 61000-4-6
Criterion A, test voltage 7 V
Criterion B, test voltage 10 V
Functional reliability can be reduced by the influence of conducted interference caused
by high-frequency fields.
Noise Emission Test in Accordance With EN 50081-2:1993
Noise emission of housing EN 55011:1991 Class A
ASIIOSLDO44
10 6111B
© Phoenix Contact 01/2002 Technical modifications reserved TNR 90 03 55 4
Phoenix Contact GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
+ 49 - (0) 52 35 - 3-00
+ 49 - (0) 52 35 - 3-4 12 00
www.phoenixcontact.com
Worldwide Locations:
www.phoenixcontact.com/salesnetwork
Ordering Data
Description Order Designation Order No.
AS-interface (AS-i) module with 4 digital
outputs
ASIIOSLDO4
4 27 41 12 1
Connecting cable 1 m with connection for two
round cables
ASI CC CAB SL FCAB PWR 27 41 19 2
AS-Interface passive distributor quintuple M12 ASI CC DIST FCAB 5M12 27 41 47 7
Protective caps for replacement (for unused
connections)
PROT-M8 16 82 54 0
Markers
pack of 10
ZB 5/M8:UNBEDRUCKT 5 16 99 94 4
Sensor cable for addressing the S Line modu-
les (0.6 m)
SAC-4P-M12MS/ 0,6-PUR/
M12FS
16 68 36 0
Addressing device ASI CC ADR 27 41 33 8
Additional accessories for connecting the actuators can be found in the Phoenix Contact PLUSCON
catalog.