CSM_G2A_DS_E_3_1
1
Power Relay
G2A
Highly Reliable, 4-pole Miniature Relay Ideal
for Sequence Control
Card lift-off employed for greater life and stable quality.
Long endurance and stable quality are assured by card lift-off
system.
Mounting interchangeability with MY-series Relays.
Operation indicator mechanism incorporated for at-a-glance
monitoring of ON/OFF operation. In addition, a built-in operation
indicator model is also included in this Relay Series.
Ordering Information
Model Number Legend
1. Number of Poles and Contact Form
4: 4PDT
2. Contact Type
3: Crossbar bifurcated
3. Enclosure Construction
2: Casing
4. Terminal Shape
A: Plug-in
1P: PCB
5. Safety Breaking Mechanism
None: No
Y: Arc barrier
6. Special Element
None: Standard
D: Built-in diode
N: Built-in operation indicator
N1: Built-in operation indicator and diode
Note: 1. The coil of the G2A-432A-N1 or a built-in diode model operates with DC only.
2. The G2A Series include the G2A-434A Power Relay and G2AK Latching Relay. Refer to G2A-434 and G2AK for details.
Classification Plug-in terminals/Solder terminals PCB terminals
Standard model G2A-432A G2A-4321P
Arc barrier equipped model G2A-432AY ---
Built-in diode model G2A-432A-D G2A-4321P-D
Built-in operation indicator model G2A-432A-N ---
Built-in operation indicator and diode model G2A-432A-N1 ---
Rated coil voltage
Note: 1. When placing your order, add the coil voltage rating listed in the specifications to the model number as shown below.
Example: G2A-432A 100/110 VAC
2. Built-in diode model and the operating coil of the G2A-432A-N1 are available only with DC ratings.
3. The Latching Relay (G2AK) and Fully sealed Relay (G2A-434A) developed based on the G2A are also available in this se-
ries.
G2A-@@@@@-@
1 2 3 4 5 6
G2A
2
Relays Other than Standard Models
Accessories
Sockets
Note: With monitor terminal.
Relay Hold-down Clips Socket Mounting Plates
Specifications
Coil Ratings
The rated currents for some of the built-in operation indicator models differ from the values given in this table. Refer to note 5 below.
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for AC rated current and
±15% for DC coil resistance.
2. The AC coil resistance and coil inductance values are for reference only.
3. Performance characteristic data is measured at a coil temperature of 23°C.
4. The maximum voltage is one that is applicable instantaneously to the Relay coil at an ambient temperature of 23°C and not continuously.
5. For built-in operation indicator models rated at 6, 12, and 24 VDC, add an LED current of approx. 5 mA to the rated currents.
Arc barrier equipped Built-in diode Built-in operation indicator
G2A-432AY G2A-432A-D G2A-432A-N
The arc barrier equipped model is
a relay designed to prevent arc
short-circuiting between phases
and can be used in a circuit which
has potential difference between
phases. The switching power of
such a circuit with potential differ-
ence must be limited to less than
1/2 the rated load when using this
Relay.
The built-in diode model is a relay
which incorporates a diode for ab-
sorption of the reverse voltage
that may be generated when the
coil is de-energized. Because the
release time of this model is long-
er than the standard model, pay
adequate attention to this point in
designing a circuit. Also, pay at-
tention to the + polarity of the coil.
The reverse-breakdown voltage
of the diode is 1,000 V.
The built-in operation indicator
model has a newly added opera-
tion indicator to the conventional
operation indication mechanism
and facilitates operation monitor-
ing without being affected by am-
bient illumination.
With the -N model (rated at 16,
12, 24, and 48 VDC) and -N1
model rated at 6, 12, 24, 48, and
100 VDC), pay attention to the +
polarity of the coil.
Track mounting Front-connecting
Socket
Screw terminals Solder terminals Wire-wrap terminals PCB
terminals
Without Hold-
down Clip
With Hold-down
Clip
Without Hold-
down Clip
With Hold-down
Clip
PYF14A PYF14(-E), PYF14A-
TU, PYF14T
PY14, PY14-3
(see note)
PY14-Y2 PY14QN(2) PY14QN(2)-Y2 PY14-0,
PY14-02
For Front-connecting Socket PYC-A2
For Back-connecting Socket PYC-3/PYC-5
For Socket Mounting Plate PYC-2
For one Socket PYP-1
For 18 Sockets PYP-18
For 36 Sockets PYP-38
Rated
voltage
Rated current Coil
resistance
Coil inductance (ref.
value)
Must
operate
Must
release
Max.
voltage
Power
consumption
50 Hz 60 Hz Armature
OFF
Armature
ON
% of rated voltage
6 VAC 295 mA 233 mA 8.9 0.048 H 0.065 H 80 % max. 30 % min. 110 % Approx. 1.4 VA
12 VAC 148 mA 117 mA 34 0.166 H 0.257 H
24 VAC 73 mA 58 mA 136 0.691 H 1.04 H
50 VAC 35 mA 28 mA 530 3.08 H 4.53 H
100/
110 VAC
17.7/
21.4 mA
14/
16.8 mA
2,200 12.42/
12.38 H
18/16.4 H
200/
220 VAC
8.9/
10.8 mA
7/8.4 mA 8,800 42.2/
41.8 H
72/65.5 H
6 VDC 176 mA 34 0.14 H 0.26 H 10 % min. 110 % Approx. 1.1 W
12 VDC 88 mA 136 0.6 H 1.0 H
24 VDC 45 mA 530 2.7 H 4.6 H
48 VDC 22 mA 2,200 11 H 19 H
100 VDC 11.4 mA 8,800 43 H 73 H
G2A
3
Contact Ratings
Characteristics
Note: 1. The data shown above are initial values.
2. The contact resistance was measured with 0.1 A at 5 VDC using the voltage drop method.
3. The operate or release time was measured with the rated voltage imposed with any contact bounce ignored at an ambient temperature
of 23°C.
4. The insulation resistance was measured with a 500-VDC megger applied to the same places as those used for checking the dielectric
strength.
5. The electrical endurance was measured at an ambient temperature of 23°C.
6. This value was measured at a switching frequency of 60 operations per minute.
Load Resistive load (cosφ = 1) Inductive load (cosφ = 0.4) (L/R = 7 ms)
Contact type Crossbar bifurcated
Contact material Movable: AgAu-clad AgPd
Fixed: AgPd
Rated load 0.3 A at 110 VAC
0.5 A at 24 VDC
0.2 A at 110 VAC
0.3 A at 24 VDC
Rated carry current 3 A
Max. switching power 250 VAC, 125 VDC
Classification Standard/Acr barrier equipped/Built-in operation
indicator models (G2A-@-N)
Built-in diode/Built-in operation indicator models
(G2A-@-N1)
Contact resistance
(see note 2)
100 m max.
Operate time (see note 3) 15 ms max.
Release time (see note 3) 15 ms max. 30 ms max.
Max. operating frequency Mechanical: 18,000 operations/hour
Electrical: 1,800 operations/hour (under rated load)
Insulation resistance
(see note 4)
100 M min. (at 500 VDC)
Dielectric strength 1,500 VAC, 50/60 Hz for 1 min between coil and contacts and contacts of different polarities (700 VAC be-
tween contacts of same polarity)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Shock resistance Destruction: 1,000 m/s2
Malfunction: 100 m/s2
Error rate (level P)
(Reference value)
(see note 6)
1 mA at 100 mVDC
Endurance Mechanical: 100,000,000 operations min. (at operating frequency of 18,000 operations/hour)
Electrical: 5,000,000 operations min. (under rated load and at operating frequency of
1,800 operations/hour) (see note 5)
Ambient temperature Operating:–10°C to 40°C (with no icing or condensation)
Ambient humidity Operating:5% to 85%
Weight Approx. 38 g
G2A
4
Engineering Data
Maximum Switching Power Endurance
Switching current (A)
Switching voltage (V) Switching current (A)
DC resistive load
AC resistive load
DC inductive load
L/R = 7 ms
24-VDC resistive load
24-VDC
inductive load
L/R = 7 ms
110-VAC
resistive load
110-VAC
inductive load
cosφ = 0.4
AC inductive load
(cosφ = 0.4)
10
50
100
500
1,000
5,000
10,000
Endurance (x10 operations)
3
Ambient Temperature vs.
Must-operate and Must-release
Voltage
G2A AC (60 Hz)
Must-operate and reset voltage (%)
Number of Relays: 5
Must-operate
voltage
Must-release
voltage
Ambient temperature (°C)
G2A DC
Must-operate and reset voltage (%)
Number of Relays: 5
Must-operate
voltage
Must-release
voltage
Ambient temperature (°C)
Ambient Temperature vs.
Coil Temperature Rise
G2A 110 VAC (50 Hz)
Coil temperature rise ( C)
Contact
carry current
Number of Relays: 5
Ambient temperature (°C)
G2A DC
Coil temperature rise ( C)
°
Contact
carry current
Number of Relays: 5
Ambient temperature (°C)
Malfunctioning Shock
G2A-432A 100/110 VAC
Not energized
Energized
Shock direction Unit: m/s
2
Number of samples = 5
Measurement conditions: Impose a shock of
100 m/s
2
in the ±X, ±Y, and ±Z directions three
times each with the Relay energized and not
energized to check the shock values that cause
the Relay to malfunction.
°
G2A
5
Coil Self-load Life Curve
(Unit: mA)
Contact Reliability
(JIS C 4530 Allen-Bradley Test Circuit)
Contact resistance (m )
Carry contact
Break contact
Make contact
Self-holding
contact
Operations (x 104)
24 VDC
Contact resistance (m )
Carry contact
Break contact
Make contact
Self-holding
contact
Operations (x 104)
Contact Reliability
(Improved Allen-Bradley Test Circuit)
Contact load: 1 mA at 5 VDC (resistive load)
Failure criterion contact resistance: 100
Contact resistance (m )
Carry contact
Break contact
Make contact
Self-holding
contact
Operations (x 104)
λ60 = 0.00153 × 106
100 VAC
λ60 = 0.00153 × 106λ60 = 0.00153 × 106
Model Specifications No. of Relays
123510
G2A-432A 100 VAC, 60 Hz 14 28 42 70 140
24 VDC 45 90 135 225 450
Life (x10 )
4
Number of Relays
100 VAC
24 VDC
Relay Mounting Adjacent Distance vs. Coil Temperature Rise
G2A-432A 24 VDC
Coil temperature rise ( C)
°
Condition: The
saturated coil
temperature is
measured with rated
coil voltage
(24 VDC) imposed.
Relay
mounting
position Upper
Lower
Average of No. 1 and No. 3
Average of No. 4. and No. 6
Average of No. 7 and No. 9
Mounting adjacent distance l (mm)
Coil temperature rise ( C)
Condition: The saturated
coil temperature is
measured with rated
voltage (110 VAC) at 60 Hz
imposed.
Relay
mounting
position
Average of No. 1 and No. 3
Average of No. 4. and No. 6
Average of No. 7 and No. 9
Mounting adjacent distance l (mm)
Upper
Lower
110 VAC
°
G2A
6
Accessories (Order Separately)
Connecting Sockets
Note: 1. The PYF@A-TU is a high-humidity relay with nickel-plated rustproof terminal screws that are the same as the PYF@A in size.
2. The PYF14T is slightly different from the PYF14A(-TU) in shape and size.
3. The PYF@A-E is a finger-protection model, for which round terminals are not available. Use fork-shaped terminals or equivalent ones
instead.
Relay Hold-down Clips
Note: When using a Relay Hold-down Clip for the built-in operation indicator model, use of the PYC-A2 or PYC-5, which allows easy viewing of
the indicator, is recommended.
Front-connecting
Socket
Back-connecting Socket
DIN track/screw
mounting
Solder terminals Wire-wrap terminals PCB terminals
PYF14A(-E)
PYF14A-TU
PYF14T
PY14
PY14-Y3 PY14-Y2
(with Relay
Hold-down Clip)
PY14QN(2) PY14QN(2)-Y2
(with Relay
Hold-down Clip)
PY14-0 PY14-02
PY14-3 Back-connecting Socket
(with check terminals for operation monitoring)
Check terminal for operation monitoring
Built-in operation monitoring lamp possible
Panel Cutout
81
56
28
38.5
29 (7.7)
0.334.5±0.4
2-dia. hole
Three, 1.2-dia. holes
Shorting lead
78+0.3
0
36+0.3
0
77.5+0
0.4
Relay Mounting Height with Socket
With Front-connecting Socket With Back-connecting Socket
Note: PYF14A can be used for both DIN
track mounting and screw mounting.
73
76.5
45.5
G2A G2A
PYF14A
PY14 Socket
For Front-connecting Socket For Back-connecting Socket For Socket mounting plate
PYC-A2 PYC-3 PYC-5 PYC-2
G2A
7
Dimensions
Note: 1. All units are in millimeters unless otherwise indicated.
2. Dimensional tolerances are ±0.1 mm.
Built-in Operation Indicator Models
Color of operation indicator
AC model: Red
DC model: Green
Note: Do not reverse the polarity of the coil of DC Relays that have a built-in indicator or diode.
G2A-432A-N
Solder Terminal Models PCB Terminal Models Mounting Holes on PCB
(Bottom View)
Terminal Arrangement/Internal Connections
(Bottom View)
Standard Models Make-before-break
Contact Models
Arc Barrier Equipped Models Built-in Diode Models
5
4.1
12.65
4.4
Fourteen, 1.5-dia. holes
4.4
13.2
6.35
7.3
0.5
21.5 max.
28.5 max.
1.8
42.5 max. 4
0.5
1
2.6
21.5 max.
0.5
28.5 max.
Fourteen, 1.2-dia. 1.2 holes x 3 elliptic holes
1.8
42.5 max. 5.4
2.6
100/110, 200/220 VAC
6, 12, 24, 50 VDC
6, 12, 24 VDC 48, 100 VDC
G2A-432A-N1
6, 12, 24 VDC 48, 100 VDC
G2A
8
Safety Precautions
Refer to Safety Precautions for All Relays.
A DC coil model with a built-in indicator or built-in diode has coil
polarity. Be sure to wire the terminals correctly, otherwise the diode
may be broken or the operating indicator may not be lit. Furthermore,
as a result of the short-circuiting of the built-in diode, the devices in
the circuit may be damaged.
Socket Mounting Plates (t = 1.6 mm)
Use any of these plates when mounting two or more Sockets side-by-side
PYP-1 (for Single Socket Mounting) PYP-18 (for Mounting 18 Sockets) PYP-36 (for Mounting 36 Sockets)
Note: PYP-18 and PYP-36 can be cut to a desired length for
mounting less than 18 or 36 Sockets, respectively.
49
Two, 3.4-dia. holes
28
Square
hole
492
72 elliptic holes 21.6 4.5
3.4
13.1
49
27.4 x 17 = 465.8±0.6
±0.15
42±0.1
42±0.1
492
72 elliptic holes 21.6 4.5
3.4
13.1
R1.7
86.4
21.6
13.1
27.4 x 17 = 465.8±0.6
27.4
±0.15
39.7±0.2
39.7±0.2
21.4+0.2
0
R1.7
27.4
27.4 x 17 = 465.8±0.6
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.