CSM_61F-G_P_DS_E_3_1
1
Floatless Level Switch (Plug-in Type)
61F-G@P
Compact, Space-saving Plug-in Type Ideal
for Pump Panels or Building into Equipment.
Large switching capacity: 5 A at 220 VAC (resistive load).
Easy to handle with DIN rail mounting.
Replace for maintenance without rewiring the socket.
Refer to Safety Precautions for Floatless Level
Controllers.
Model Number Legend
Ordering Information
Note: When ordering, specify the desired operating voltage at the end of the model number.
1. Control Applications 2. Type
G1: Automatic water supply with idling prevention
or water shortage alarm
G2: Automatic water supply and drainage with
abnormal water increase alarm
I: Liquid level indication and alarm
Blank: General-purpose
L 2KM: Long-distance (for 2 km)
L 4KM: Long-distance (for 4 km)
H: High-sensitivity
D: Low-sensitivity
21
61F-@P@
Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)
Model Model Model
G1 models 61F-G1P 61F-G1PL 2K 61F-G1PL 4KM
Type High-sensitivity Low-sensitivity
Model Model
G1 models 61F-G1PH 61F-G1PD
Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)
Model Model Model
G2 models 61F-G2P 61F-G2PL 2KM 61F-G2PL 4KM
Type High-sensitivity Low-sensitivity
Model Model
G2 models 61F-G2PH 61F-G2PD
Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)
Model Model Model
I models 61F-IP 61F-IPL 2KM 61F-IPL 4KM
Type High-sensitivity Low-sensitivity
Model Model
I models 61F-IPH 61F-IPD
Example: 61F-G1P [110VAC]
Desired supply voltage
61F-G@P
2
Plug-in Models
Specifications
Note: 1. The relay in the 61F-G1H/-G2H/-IPH de-energizes when there is water present across the Electrodes, whereas the relay in the 61F-GP-
N8HY energizes when there is water present across the Electrodes.
2. Models are available for 2 km and 4 km.
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as
the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers.
4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for
Floatless Level Controllers.
5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
6. High-sensitivity Controllers use advanced operation.
When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-
nal relay will not operate.
When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.
Item General-purpose
Controller
61F-G1P
61F-G2P
61F-IP
Long-distance
Controllers
61F-G1PL
61F-G2PL
61F-IPL
(see note 2)
High-sensitivity
Controllers
61F-G1PH
61F-G2PH
61F-IPH
(see note 1, see note 6)
Low-sensitivity
Controller
61F-G1PD
61F-G2PD
61F-IPD
Controlling materials and
operating conditions
For control of ordinary puri-
fied water or sewage water
For control of ordinary puri-
fied water in cases where
the distance between sew-
age pumps and water tanks
or between receiver tanks
and supply tanks is long or
where remote control is re-
quired.
For control of liquids with
high specific resistance
such as distilled water
For control of liquids with
low specific resistance such
as salt water, sewage water,
acid chemicals, alkali chem-
icals
Supply voltage 100, 110, 200, 220 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Interelectrode voltage 8 VAC 24 VAC 8 VAC
Interelectrode current Approx. 1 mA AC max. Approx.
0.4 mA AC max.
Approx. 1.2 mA AC max.
Power consumption Approx. 6.4 VA max.
Interelectrode operate re-
sistance
0 to approx. 4 kΩ0 to 1.8 kΩ (for 2 km)
0 to 0.7 kΩ (for 4 km)
Approx. 15 kΩ to
approx. 70 kΩ
(see note 5)
0 to approx. 1.8 kΩ
Interelectrode release re-
sistance
Approx. 15 k to ∞Ω 4 k to ∞Ω (for 2 km)
2.5 k to ∞Ω
(for 4 km)
Approx. 300 k to ∞Ω Approx. 5 k to ∞Ω
Response time Operate: 80 ms max.
Release: 160 ms max.
Cable length
(see note 3)
1 km max. 2 km max.
4 km max.
50 m max. 1 km max.
Control output 2 A, 200 VAC (Inductive load: cosφ = 0.4)
5 A, 200 VAC (Resistive load)
Ambient temperature Operating: –10 to 55°C
Ambient humidity Operating: 45% to 85% RH
Insulation resistance
(see note 4)
100 MΩ min. (at 500 VDC)
Dielectric strength
(see note 4)
2000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min.
Weight Approx. 495 g
61F-G@P
3
Internal Circuit Diagrams
Note: The 61F-G@PH High-sensitivity Controller uses advanced operation. The internal relay will operate on the NO contact side when power is
supplied and then will operate according to the liquid level.
61F-G1P/-G1PL/-G1PD 61F-G2P/-G2PL/-G2PD61F-G1PH
61F-G2PH 61F-IPH61F-IP/-IPL/-IPD
Control circuit
714 6 5 12 43
89 1 2
15 10 11
U1
U1
U2
U2
U2
24 V
24 V
8 V
Control circuit
Power
supply
7 14 6 5 12 4 3
8 9 1 215 10 11
8 V
U1Control circuit
7 14 6 5 12 4 3
8 9 1 215 10 11
U1
U1
U1
U2
U2
24 V
24 V
24 V
Control circuit
Power
supply
U2
Control circuit
7 14 6 5 12 4 3
8 9 1 215 10 11
U1
U1
U2
U2
U2
24 V
24 V
8 V
Control circuit
Power
supply
Control circuit
7 14 6 5 12 4 3
8 9 1 215 10 11
U1
U1
U2
U2
U2
24 V
24 V
8 V
Control circuit
Power
supply
Control circuit
7 14 6 5 12 4 3
8 9 1 215 10 11
U1
U1
U2
U2
U2
24 V
24 V
8 V
Control circuit
Power
supply
U1
Control circuit
7 14 6 5 12 4 3
8 9 1 215 10 11
U1
U1
U2
U2
U2
24 V
24 V
24 V
Control circuit
Power
supply
U1
61F-G@P
4
Connections
Automatic Water Supply Control with Pump Idling Prevention Automatic Water Supply Control with Abnormal Water Shortage Alarm
Plug-in Type
61F-G1P
Dimensions:
Page 7
Automatic Water Supply Control with Pump
Idling Prevention and Abnormal Water
Shortage Alarm
U1
U2
U2
U1
U1
MCCB
RS
M
T
Commercial Voltage
61F-G1P
PS-3S
(See note.)
7146 5124 3
E2
E3
E1
PS-3S
E2'
E3
E1'
P
8 V
Power
supply
0 V 24 V
24 V
Alarm
B
Pushbutton
switch
Control
circuit
U2
8 9 15 10 1 11 2
Control
circuit
Contactor
Water
supply
source
Water
tank
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Insert a pushbutton switch between terminals 11 and 15 as
shown by the dotted lines.
Do not press the pushbutton if the low-water alarm sounds and
the pump stops during normal operation (water below E2').
If the supply water level is below E1' when starting operation or
when recovering from a power interruption, press the pushbutton
to momentarily close the circuit to start the pump.
Test Operation/Recovering from Power Interruptions
Connections
U1
U2
U2
U1
U1
MCCB
RS
M
T
Commercial Voltage
61F-G1P
PS-4S
(See note.)
7146 5124 3
E2
E4
E3
E1
P
8 V
0 V 24 V
24 V
Alarm
B
Pushbutton switch
Control
circuit
U2
8 9 15 10 1 11 2
Control
circuit
Contac-
tor
Water supply
source Water
tank
Power
supply
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
14PFA (Front-connecting)
PL15 (Rear-connecting)
Insert a pushbutton switch between terminals 11 and 15 as
shown by the dotted lines.
If the pump stops when the pushbutton switch is released,
press it again.
If the supply water level is below E4 when starting operation or
when recovering from a power interruption, press the pushbutton
to momentarily close the circuit to start the pump.
Test Operation/Recovering from Power Interruptions
Connections
Pump
OFF
Pump
ON
E
1
'
E
2
'
E
3
Water supply source
Water
shortage
BL
E
1
E
2
E
3
Water tank
Water
supply
P
(U1 indicator ON)
(U2 indicator ON)
(U1 indicator OFF)
(U2 indicator OFF)
Principles of Operation
The pump starts when the water level in the tank drops below
E2 and stops when the water level reaches E1.
When the level of water supply source drops below E2', the
pump stops. Pumping idling is prevented and the alarm
sounds.
E1
E2
E4
E3
Water tank
Pump OFF
Pump ON
P
Water
supply
Water
shortage
BL
(U2 indicator ON)
(U2 indicator OFF)
(U1 indicator OFF)
The pump stops when the water level reaches E1 and starts
when the water level in the tank drops below E2.
If the water level drops below E4 for any reason, the pump
stops and the alarm sounds.
Principles of Operation
61F-G@P
5
Automatic Water Supply with Abnormal Water Increase Alarm Automatic Drainage Control with Abnormal Water Increase Alarm
Plug-in Type
61F-G2P
Dimensions:
Page 7
Automatic Water Supply and Drainage
Control with Abnormal Water Increase
Alarm
E1
E2
E3
E4
U1
U2
U2U1
Water supply source
MCCB
RS
M
T
Commercial Voltage
61F-G2P
(See note.)
714 6 5 12 4 3
P
8 V
Power
supply
0 V 24 V
24 V
Alarm
B
Control
circuit
U2
82
PS-4S
91011115
Control
circuit
Contac-
tor
Water
tank
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
14PFA (Front-connecting)
PL15 (Rear-connecting)
Connect terminal 14 to power supply terminal 9. (Terminal 8 is
not connected.)
The power supply depends on the specifications of the model.
Connections
Reservoir
U1
U2
U2U1
Wastewater
tank
MCCB
RS
M
T
Commercial Voltage
61F-G2P
(See note.)
714 6 5 12 4 3
PS-4S
E1
E2
E3
E4
P
8 V
0 V 24 V
24 V
Alarm
B
U2
2
Control
circuit
891510111
Control
circuit
Contac-
tor
Motor
protection
relay
Power
supply
Note: Be sure to ground the common Electrode E3 (the
longest Electrode).
Connection Sockets
14PFA (Front-connecting)
PL15 (Rear-connecting)
Connect terminal 8 to power supply terminal 9.
Connections
E
3
Upper
limit
Pump OFF
Pump ON
B
L
E
4
E
1
E
2
P
Water
supply
(U
1
indicator ON)
(U
2
indicator ON)
(U
2
indicator OFF)
The pump starts when the water level drops below E2 and
stops when the water level reaches E1.
If the water level drops below E4 for any reason, the pump
stops and the alarm sounds.
E
3
Upper
limit
Pump OFF
Pump ON
BL
Water drainage
P
E
4
E
1
E
2
(U
1
indicator ON)
(U
2
indicator ON)
(U
2
indicator OFF)
The pump starts when the water level reaches E1 and stops
when the water level drops below E2.
If the water level drops below E4 for any reason, the pump
stops and the alarm sounds.
Principles of Operation
61F-G@P
6
Liquid Level Indication and Alarm
Plug-in Type
61F-IP
Dimensions:
Page 7
Liquid Level Indication and Alarm
MCCB
RS
MP
T
Commercial Voltage
61F-IP
Alarm
Upper limit
Intermediate
Upper limit
Upper alarm
PS-3S
Lower alarm
Intermediate
(See note.)
E1
8 9 15 10 1 11 2
7146 512
BPLPLPL
43
Control
circuit
8 V
Power
supply
0 V 24 V
24 V
U1
U1U1U2
U2
U2
Control
circuit
E2
E3
Water supply
source
Water
tank
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Connection Sockets
14PFA (Front-connecting)
PL15 (Rear-connecting)
Connections
B
LL
E2
E3
Water tank
Lower
limit
Middle
Upper
limit
(U1 indicator ON)
(U1 indicator OFF)
(U2 indicator ON)
(U2 indicator OFF)
B
LH
LM
E1
When the water level drops E2, the lower-limit indicator turns ON
and the alarm sounds.
When the water level reaches E2, the indicator turns OFF and
the intermediate indicator turns ON.
When the water level rises to E1, the upper-limit indicator turns
ON and the alarm sounds.
Principles of Operation
61F-G@P
7
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Safety Precautions
Refer to Safety Precautions for All Level Controllers.
6079
72
30
3.5 89
97.5
118
61F-G1P
61F-G2P
61F-IP
14PFA
61F-G1P, -G1PL, -G1PH, -G1PD
61F-G2P, -G2PL, -G2PH, -G2PD
61F-IP, -IPL, -IPH, -IPD
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.9
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
61F-11N 61F-11ND 61F-11NH 61F-11NL2K 61F-11NL4K 61F-11NR 61F-1P AC110 61F-1P-AC220 61F-G1
AC120/240 61F-G1H AC110/220 61F-G1H AC120/240V 61F-G1N-AC120/240 61F-G1ND AC110/120 61F-G1ND
AC120/240 61F-G1NH AC120/240 61F-G1NL AC110/220 2KM 61F-G1NL AC120/240 2KM 61F-G1NL AC120/240
4KM 61F-G1NR AC110/220 61F-G1NR AC120/240 61F-G1P/AC100 61F-G1P AC110 61F-G1P-AC120 61F-G2
AC120/240 61F-G2H AC120/240 61F-G2N AC100/200 61F-G2N AC110/220 61F-G2N AC120/240 61F-G2ND
AC110/220 61F-G2ND AC120/240 61F-G2NH AC110/220 61F-G2NH AC120/240 61F-G2NL AC110/220 2KM 61F-
G2NL AC110/220 4KM 61F-G2NL AC120/240 2KM 61F-G2NL AC120/240 4KM 61F-G2NR AC110/220 61F-G2P
AC100 61F-G2P AC120 61F-G2P-AC200 61F-G2PH AC100 61F-G3H AC100/200 61F-G3H AC110/220 61F-G3H
AC120/240V 61F-G3N AC100/200 61F-G3N AC110/220 61F-G3N AC120/240 61F-G3ND AC110/220 61F-G3ND
AC120/240 61F-G3NH AC110/220 61F-G3NH AC120/240 61F-G3NL AC110/220 2KM 61F-G3NL AC110/220 4KM
61F-G3NL AC120/240 2KM 61F-G3NL AC120/240 4KM 61F-G3NR AC110/220 61F-G3NR AC120/240 61F-G3T
AC110/220 61F-G4 AC120/240 61F-G4H AC110/120 61F-G4N AC110/220 61F-G4N AC120/240 61F-G4ND
AC110/220 61F-G4ND AC120/240 61F-G4NH AC110/220 61F-G4NH AC120/240 61F-G4NL AC110/220 2KM 61F-
G4NL AC110/220 4KM 61F-G4NL AC120/240 2KM 61F-G4NL AC120/240 4KM 61F-G4NR AC110/220 61F-G4NR
AC120/240 61F-G AC100/200 61F-G AC110/220 61F-G AC120/240 61F-GD AC110/220 61F-GL AC100/200 2KM
61F-GL AC100/200 4KM 61F-GN AC110/220 61F-GN AC120/240 61F-GND AC110/220 61F-GND AC120/240 61F-
GNH AC120/240 61F-GNL AC110/220 2KM 61F-GNL AC110/220 4KM 61F-GNL AC120/240 2KM 61F-GNL
AC120/240 4KM 61F-GNR AC120/240 61F-GP-N2 220VAC 61F-GP-N2 240 61F-GP-N2 24VAC 61F-GP-N8 AC100
61F-GP-N8 AC120 61F-GP-N8 AC200 61F-GP-N8 AC24 61F-GP-N8D AC120 61F-GP-N8H AC120 61F-GP-N8H
AC24 61F-GP-N8HY 110VAC 61F-GP-N8L-2KM AC120