A-Series
A-Series
CIRCUIT BREAKER
Well known for their proven reliability, Carling Technologies’ A-Series hydraulic magnetic circuit breakers are
compact, temperature stable and designed for precision operation in OEM markets requiring general purpose
as well as full load amp applications. When front panel operation and aesthetics demand a clean, contemporary
design, the visi-rocker or paddle actuators are ideally suitable. A sealed toggle actuator style is also available and
ideal for harsh environment applications requiring additional sealing protection. Optional rocker-guard and push-
to-reset bezels, which help prevent inadvertent actuation, are also available.
1-6 poles; ratings from 0.02 to 50 amps, up to 277VAC or 80VDC; UL Recognized, UL Listed, UL1500, UL1077,
TUV, VDE & CSA
Product Highlights:
Up to 50 amps in a compact size
Various actuator styles
Sealed metal toggle option tested to
MIL-PRF-55629C. Meets IP68
Requirements
Typical Applications:
Telecom/Datacom
Marine
Military
Renewable Energy
Generators & Welder
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
2 |A-Series Circuit Breaker - General Specications
*Manufacturer reserves the right to change product specification without prior notice.
Electrical
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Mechanical
Physical
Environmental
Designed and tested in accordance with requirements of
specication MIL-PRF-55629 & MIL-STD-202 as follows:
Maximum Voltage 277VAC 50/60 Hz, 80VDC
Current Ratings Standard current coils: 0.100,
0.250, 0.500, 0.750, 1.00, 2.50,
5.00, 7.50, 10.0, 15.0, 20.0, 25.0,
30.0, 35.0, 40.0, 50.0. Other ratings
available - consult ordering
scheme.
Standard Voltage Coils DC-6V, 12V; AC-120V, Other ratings
available, consult ordering scheme.
Auxiliary Switch Rating SPDT; 10.1 A - 250VAC,
1.0 A-65VDC/0.5 A - 80 VDC,
0.1A - 125VAC (with gold contacts).
Insulation Resistance Minimum: 100 Megohms at 500
VDC
Dielectric Strength UL, CSA - 1500V 60 Hz for one
minute between all electrically
isolated terminals. A-Series rocker
circuit breakers comply with the
8mm spacing & 3750V dielectric
requirements from hazardous
voltage to operator accessible
surfaces per EN 60950 and VDE
0805.
Resistance, Impedance Values from Line to Load Terminal
- based on Series Trip Circuit
Breaker.
Endurance 10,000 ON-OFF operations @ 6 per
minute; with rated Current & Voltage.
Trip Free All A-Series Circuit Breakers will trip
on overload, even when the actuator
is forcibly held in the ON position.
Trip Indication The operating actuator moves
positively to the OFF position when
an overload causes the circuit
breaker to trip. When mid-trip
handle is specied, the handle
moves to the mid position on
electrical trip of the circuit breaker.
When mid-trip handle with alarm
switch is specied, the handle
moves to the mid position & the
alarm switch actuates when the
circuit breaker is electrically tripped.
Number of Poles 1 - 6 Poles (handle) and 1-3 poles
(rocker) at 30 Amps or less. 1 and 2
poles at 31 Amps thru 50 Amps.
Internal Circuit Cong. Series, (with or without auxiliary
switch), Shunt and Relay with current
or voltage trip coils, Dual Coil,
Switch Only with or without auxiliary
switch.
Weight Approximately 65 grams/pole.
(Approximately 2.32 ounces/pole)
Standard Colors Housing - Black; Actuator- See
Ordering Scheme.
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short curves
tested @ 90% of rated current.
Vibration Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz,
at rated current per Method 204C,
Test Condition A. Instantaneous and
ultrashort curves tested at 90% of
rated current.
Moisture Resistance Method 106D; ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.56
days @ +85°C, 85% RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C to
+25°C).
Operating Temperature -40° C to +85° C
Pulse Tolerance Curves
CURRENT
(AMPS)
TOLERANCE
(%)
0.10 - 5.0 15
5.1 - 20.0 25
20.1 - 50.0 35
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 3
A-Series Circuit Breaker - General Specications
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted congurations and performance capabilities as a Component Supplementary Protector.
Notes:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
2 Same as note 1, except that backup fuse is limited to 80 A maximum.
3 2 pole protector required (with one pole per power line) for: 125/250 VAC, 1 pole protector required for : 125 VAC, 1Ø Power System.
4 Satises the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
A-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS
Circuit
Conguration
Voltage Current Rating Short Circuit Capacity (Amps) Application Codes Construction
Notes
Max
Rating Frequency Phase Full Load
Amps
General
Purpose
Amps
UL / CSA
With Backup
Fuse
Without
Backup Fuse UL CSA
Series
32 DC --- 0.02 - 15 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
65 DC --- 31  50 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
80 DC --- 0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
--- 31  50 --- 7500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
125 50 / 60 1 0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Rocker Version
125 50 / 60 1 1  50 --- --- 2000 TC1, OL1, U2 TC1, OL1, U2
125 50 / 60 1 41  50 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
125 / 250 50 / 60 1 30.02 - 30 --- --- 3000 TC1, 2, OL1, U2 TC1, 2, OL1, U2 Rocker Version
125 / 250 50 / 60 1 30.02 - 50 --- --- 3000 TC1, 2, OL1, U2 TC1, 2, OL1, U2 Handle
250 50 / 60
1
0.02 - 30 --- --- 1500 TC1, 2, OL0, U2 TC1, 2, OL0, U2 Single Pole Break
0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Two Pole Break
--- --- 3000 TC1, 2, OL0, U1 TC1, 2, OL0, U1
1 41  50 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
30.02 - 30 --- 5000 2--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
31  50 --- 2000 1--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
277 50 / 60 1 0.02 - 30 --- 5000 1--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
Dual Coil
32 DC --- 0.02 - 50 --- --- 5000 TC1, OL1, U2 TC1, OL1, U2
65 DC --- 0.02 - 50 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
80 DC --- 0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
--- 31  50 --- 7500 TC1, 2, OL0, U1 TC1, 2, OL0, U1
125 50 / 60 1 0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Rocker Version
1  50 --- --- 2000 TC1, OL1, U2 TC1, OL1, U2
125 50 / 60 1 40.02 - 30 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
125 / 250 50 / 60 1 30.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1 Rocker Version
125 / 250 50 / 60 1 30.02 - 50 --- --- 3000 TC1, 2, OL1, U2 TC1, 2, OL1, U2
250 50 / 60
1 0.02 - 30 --- --- 1500 TC1, OL0, U2 TC1, OL0, U2 Single Pole Break
1 0.02 - 30 --- --- 3000 TC1, OL1, U2 TC1, OL1, U2 Two Pole Break
1 --- 31  50 --- 3000 TC1, 2, OL0, U1 TC1, 2, OL0, U1
1 41  50 --- --- 1000 TC1, OL1, U2 TC3, OL1, U3
30.02 - 30 --- 5000 2--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
31  50 --- 2000 1--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
277 50 / 60 1 0.02 - 30 --- 5000 1--- TC1, 2, OL1, U1 TC1, 2, OL1, U1
Shunt
80 DC --- 0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
125 / 250 50 / 60 1 0.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
250 50 / 60 1 0.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
3 0.02 - 30 --- 5000 2--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
277 50 / 60 1 0.02 - 30 --- 5000 1--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
Relay
80 DC --- 0.02 - 30 --- --- 7500 TC1, 2, OL1, U1 TC1, 2, OL1, U1
125 / 250 50 / 60 1 30.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
250 50 / 60 1 0.02 - 30 --- --- 3000 TC1, 2, OL1, U1 TC1, 2, OL1, U1
3 0.02 - 30 --- 5000 2--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
277 50 / 60 1 0.02 - 30 --- 5000 1--- TC1, 2, OL1, C1 TC1, 2, OL1, C1
Switch Only
65 DC --- 0.02 - 50 ---
not applicable
80 DC --- 0.02 - 30 ---
250 50 / 60 1 --- 31  50
3 0.02 - 50 ---
277 50 / 60 1 0.02 - 30 31  50
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
4 |A-Series Circuit Breaker - General Specications
1
2
3
2
3
2
3
Electrical Tables
Table B: Lists UL Recognized, CSA Accepted, VDE & TUV Certied congurations & performance capabilities as a Component
Supplementary Protector.
Notes:
1 General Purpose Ratings for UL/CSA Only.
2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
3 Same as note 2, except that backup fuse is limited to 80 A maximum.
4 Satises the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 5
A-Series Circuit Breaker - General Specications
SERIES
14
1 DC --- 0.02 - 50 5000 TC1,OL1,U1 TC1,OL1,U1
32
1DC --- 0.02 - 50 5000 TC1,OL1,U2 TC1,OL1,U2
65 DC --- 0.02 - 50 3000 TC1,OL1,U1 TC1,OL1,U1
125 50 / 60 1 0.02 - 50 3000 TC1,OL1,U2 TC1,OL1,U2
125 / 250 50 / 60
1
20.02 - 50 3000 TC1,OL1,U2 TC1,OL1,U2
250 50 / 60 1 0.02 - 30 1500 TC1,OL1,U1 TC1,OL1,U1
Notes:
1 Available with Special Catalog Number Only (consult factory)
2 2 pole protector required (with one per power line) for 125 / 250 VAC. 1 pole protector required for 125 VAC 1 phase power system
CSA
SHORT CIRCUIT
CAPACITY (AMPS) APPLICATION CODES
A-SERIES TABLE C: UL1500 (Marine Ignition Protected)
UL
VOLTAGE
CIRCUIT
CONFIGURATION
CURRENT
RATING
FULL LOAD AMPS WITHOUT BACKUP
FUSE
MAX. RA
TING
FREQUENCY PHASE
Electrical Tables
Table C: Lists UL Recognized, CSA Accepted congurations and performance capabilities as Protectors, Supplementary for Marine
Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classied Small Craft Electrical Devices,
Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Table D: Lists UL Listed congurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
Notes:
1 Available with special catalog number only (consult factory).
2 2 pole protector required (with one per power line) for 125 / 250 VAC. 1 pole protector required for 125 VAC 1 phase power system
Notes:
1 Parallel Pole Construction
Agency Certifications
UL Recognized
UL Standard 1077
UL Standard 508
UL Standard 1500
UL Listed
UL Standard 489A
CSA Accepted
TUV Certied
VDE Certied
Component Recognition Program
as Protectors Supplementary
(Guide CCN/QVNU2, File E75596)
Switches, Industrial Control
(Guide CCN/NRNT2, File E148683)
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
Communications Equipment
(Guide CCN/DITT, File E189195)
Component Supplementary
Protector under Class 3215 30,
File 047848 0 000 CSA
Standard C22.2 No. 235
EN60934, under License No.
R72103448
EN60934, VDE 0642 under File
No. 10537
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 |A-Series Circuit Breaker - Handle UL Recognized – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
4
Circuit
A A B 1 13 0 B C10 450
1 SERIES
A
2 ACTUATOR 1
A Handle, one per pole
B Handle, one per multipole unit
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
8 TERMINAL 9
1 10 Push-On 0.250 Tab (Q.C.) E 11 Screw M4 (Bus Type)
2 Screw 8-32 with upturned lugs F Screw M5 with upturned lugs
3 11 Screw 8-32 (Bus Type) & 30° bend
4 Screw 10-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
5 11 Screw 10-32 (Bus Type) H 11 Screw M5 (Bus Type)
6 Screw 8-32 with upturned lugs L 12 0.250 Q.C./ Solder Lug
& 30° bend M 11 M6 Threaded Stud
7 Screw 8-32 (Bus Type) Q 14 Push-In Stud
& 30° bend R Screw M4 with upturned lugs
8 Screw 10-32 with upturned lugs & 30° bend
& 30° bend T 11 Screw M4 (Bus Type)
9 Screw 10-32 (Bus Type) & 30° bend
& 30° bend P 13 Printed Circuit Board Terminals
B Screw M5 with upturned lugs S 13 Push-On 0.110 Tab (Q.C.)
C Screw M4 with upturned lugs
10 MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multipole only) yes
Front panel Snap-In, 0.75” wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8 without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
3 POLES
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
5 AUXILIARY / ALARM SWITCH 5 5 S.P.S.T., 0.093 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 7 S.P.S.T., 0.110 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)
4 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
(Gold Contacts) 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
42 7 50/60Hz Short, Hi-Inrush
44 7 50/60Hz Medium, Hi-Inrush
46 7 50/60Hz Long, Hi-Inrush
52 7 DC, Short,Hi-Inrush
54 7 DC, Medium, Hi-Inrush
56 7 DC, Long, Hi-Inrush
11 AGENCY APPROVAL
C UL Recognized & CSA Accepted
D VDE Certied, UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
9 ACTUATOR COLOR & LEGEND
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black
Black C D 2 White
Red F G 3 White
Green H J 4 White
Blue K L 5 White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
Black (short handle)15 T U 9 White
4 CIRCUIT
A 2 Switch Only (No Coil) F 3 Relay Trip (Current)
B Series Trip (Current) G 3 Relay Trip (Voltage)
C Series Trip (Voltage) H 3,4 Dual Coil with Shunt Trip
D 3 Shunt Trip (Current) Voltage Coil
E 3 Shunt Trip (Voltage) K 3,4 Dual Coil with Relay Trip
Voltage Coil
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles
5 pole - three handles at center poles 6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with
circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a
protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps,
select Current Code 630. For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 50A amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils
require 30VA minimum power to trip and are rated for intermittent duty only.
5 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A - supplied with
standard half shells. 35-50A - supplied with extended boat (B-Style) half shells.
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10 and 20.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA
Accepted & TUV Certied to 50 amps.
8 VDE Certication available with single pole breakers with DC Delay only. UL Recognition
and CSA Accepted available in one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G, H, M and Q..
10 Terminal Code 1: VDE Certication up to 25 amps and UL Recognition and CSA
Certication up to 30 amps, but not recommended over 20 amps.
11 Terminal Codes 3, 5, E and H (Bus Type) with VDE, are supplied with Lock Washers,
and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat
Washers. These breakers are only VDE Certied when the washers are used.
12 Terminal Code L: VDE Certied available up to 12A. UL Recognized & CSA Accepted
available up to 30A.
13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps
with VDE Certication and 50 amps with UL Recognition and CSA Accepted, with Circuit
Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are
available up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B and C.
14 Terminal Code Q not available with VDE certication.
15 Single pole only.
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 8 35.000
640 8 40.000
645 8 45.000
650 8 50.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 7
A-Series Circuit Breaker - Handle UL489A – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Max. Appl.
Rating
12
Agency
Approval
4
Circuit
A A B 1 11 0 B M T14 450
1 SERIES
A
2 ACTUATOR 1
A Handle, one per pole
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
3 POLES 2
1 One
2 Two
3 Three
4 Four
5 AUXILIARY/ALARM SWITCH 2 7 S.P.S.T., 0.110 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
52 3 DC, Short,Hi-Inrush
54 3 DC, Medium, Hi-Inrush
56 3 DC, Long, Hi-Inrush
12 AGENCY APPROVAL
T UL489A Listed
K UL489A Listed, VDE Certied
J UL489A Listed, TUV Certied
11 MAXIMUM APPLICATION RATING
M 80 DC
9 ACTUATOR COLOR & LEGEND
Actuator Color ON-OFF Dual Legend Color
White B 1 Black
Black D 2 White
Red G 3 White
Green J 4 White
Blue L 5 White
Yellow N 6 Black
Gray Q 7 Black
Orange S 8 Black
Black (short handle) 10 U 9 White
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker.
2 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
3 VDE Certied to 30 amps. UL489A Listed to 50 amps.
4 VDE Certication available with single pole breakers only. UL489A Listing available with one
and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps
are only available with Terminal Codes 5, 9 G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with VDE Certication and 30 amps with
UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only VDE Certied when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
30 amps with VDE Certication and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certication.
10 Single pole only.
4 CIRCUIT
B Series Trip (Current)
8 TERMINAL 5
1 6 Push-On 0.250 Tab (Q.C.) 9 Screw 10-32 (Bus Type)
2 Screw 8-32 with upturned lugs & 30° bend
3 7 Screw 8-32 (Bus Type) B Screw M5 with upturned lugs
4 Screw 10-32 with upturned lugs F Screw M5 with upturned lugs
5 7 Screw 10-32 (Bus Type) & 30° bend
6 Screw 8-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
& 30° bend H Screw M5 (Bus Type)
7 Screw 8-32 (Bus Type) M 7 M6 Threaded Stud
& 30° bend P 8 Printed Circuit Board Terminals
8 Screw 10-32 with upturned lugs Q 9 Push-In Stud
& 30° bend
10 MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multipole only) yes
Front panel Snap-In, 0.75” wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8 without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
7 CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 3 35.000
640 3 40.000
645 3 45.000
650 3 50.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
8 |A-Series Circuit Breaker - Handle WORLD – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
4
Circuit
A A B 1 13 0 A P14 450
1 SERIES
A
2 ACTUATOR 1
A Handle, one per pole
B Handle, one per multipole unit
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
8 TERMINAL 9
1 10 Push-On 0.250 Tab (Q.C.) B Screw M5 with upturned lugs
2 Screw 8-32 with upturned lugs C Screw M4 with upturned lugs
3 11 Screw 8-32 (Bus Type) E 11 Screw M4 (Bus Type)
4 Screw 10-32 with upturned lugs F Screw M5 with upturned lugs
5 11 Screw 10-32 (Bus Type) & 30° bend
6 Screw 8-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
& 30° bend H 11 Screw M5 (Bus Type)
7 Screw 8-32 (Bus Type) R Screw M4 with upturned lugs
& 30° bend & 30° bend
8 Screw 10-32 with upturned lugs T 11 Screw M4 (Bus Type)
& 30° bend & 30° bend
9 Screw 10-32 (Bus Type)
& 30° bend
10 MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 x 0.195 inches yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multipole only) yes
Front panel Snap-In, 0.75” wide bezel
5 without Handleguard no
6 without Handleguard (multipole only) yes
Front panel Snap-In, 0.96” wide bezel
7 without Handleguard, 1-pole 0.96” wide; no
multipole units have .105” bezel overhang on all sides
8 without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
3 POLES
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
5 AUXILIARY / ALARM SWITCH 5
0 without Aux Switch
2 S.P.D.T., 0.110 Q.C. Term.
4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
42 7 50/60Hz Short, Hi-Inrush
44 7 50/60Hz Medium, Hi-Inrush
46 7 50/60Hz Long, Hi-Inrush
52 7 DC, Short,Hi-Inrush
54 7 DC, Medium, Hi-Inrush
56 7 DC, Long, Hi-Inrush
11 AGENCY APPROVAL
P TUV Certied, UL Recognized & CSA Accepted
Q UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
9 ACTUATOR COLOR & LEGEND
Actuator Color I-O Dual Legend Color
White A 1 Black
Black C 2 White
Red F 3 White
Green H 4 White
Blue K 5 White
Yellow M 6 Black
Gray P 7 Black
Orange R 8 Black
Black (short handle)15 T 9 White
4 CIRCUIT
A 2 Switch Only (No Coil) D 3 Shunt Trip (Current)
B Series Trip (Current) E 3 Shunt Trip (Voltage)
C Series Trip (Voltage) H 3,4 Dual Coil with Shunt Trip
Voltage Coil
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit
codes B, C, D, E, and H.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a
protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select Current Code 630.
For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require
30VA minimum power to trip and are rated for intermittent duty only.
5 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10, 20 & 30.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA
Accepted & TUV Certied to 50 amps.
8 Available up to two poles with AC or DC delays.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G and H.
10 Terminal Code 1: TUV Certication up to 30 amps, but not recommended over 20 amps.
11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers.
These breakers are only TUV Certied when the washers are used.
12 Single pole only.
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 8 35.000
640 8 40.000
645 8 45.000
650 8 50.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 9
A-Series Circuit Breaker - Rocker UL489A – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Max. Appl.
Rating
12
Agency
Approval
4
Circuit
A F B 1 11 0 3 M T14 450
1 SERIES
A
10 MOUNTING / BARRIERS 11
STANDARD ROCKER BEZEL BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
ROCKERGUARD & PUSH-TO-RESET BEZEL
Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel
8 without Rockerguard (single pole units only) no
H with Rockerguard (single pole units only) no
FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel
9 without Rockerguard (single pole units only) no
J with Rockerguard (single pole units only) no
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary switch and/or
mixed poles, and have one rocker per breaker.
3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells.
30-50A are supplied with extended boat (B-Style) half shells.
4 VDE Certication available with single pole breakers only. UL489A Listing available with one
and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps
are only available with Terminal Codes 5, 9, G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certication and 30
amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only TUV or VDE Certied when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps
with VDE Certication and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certication.
10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U.
Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes
N & O. Rockerguard available with actuator codes C through K
2 ACTUATOR 1
Two Color Visi-Rocker Push-To-Reset, Visi-Rocker
C Indicate ON, vertical legend N Indicate OFF, vertical legend
D Indicate ON, horizontal legend O Indicate OFF, horizontal legend
F Indicate OFF, vertical legend
G Indicate OFF, horizontal legend
Single color Push-To-Reset , Single color
J Vertical legend R Vertical legend
K Horizontal legend U Horizontal legend
9 ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color
Visi-Color 10 ON-OFF Dual
10 Single Color Visi-Rocker
White B 1 Black White
Black D 2 White n/a
Red G 3 White Red
Green J 4 White Green
Blue L 5 White Blue
Yellow N 6 Black Yellow
Gray Q 7 Black Gray
Orange S 8 Black Orange
3 POLES 2
1 One
2 Two
3 Three
5 AUXILIARY / ALARM SWITCH 2 7 S.P.S.T., 0.110 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
52 DC, Short,Hi-Inrush
54 DC, Medium, Hi-Inrush
56 DC, Long, Hi-Inrush
12 AGENCY APPROVAL
T UL489A Listed
K UL489A Listed, VDE Certied
J UL489A Listed, TUV Certied
11 MAXIMUM APPLICATION RATING
M 80 DC
4 CIRCUIT
B Series Trip (Current)
8 TERMINAL 5
1 6 Push-On 0.250 Tab (Q.C.) 9 Screw 10-32 (Bus Type)
2 Screw 8-32 with upturned lugs & 30° bend
3 7 Screw 8-32 (Bus Type) B Screw M5 with upturned lugs
4 Screw 10-32 with upturned lugs F Screw M5 with upturned lugs
5 7 Screw 10-32 (Bus Type) & 30° bend
6 Screw 8-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
& 30° bend H Screw M5 (Bus Type)
7 Screw 8-32 (Bus Type) M 7 M6 Threaded Stud
& 30° bend P 8 Printed Circuit Board Terminals
8 Screw 10-32 with upturned lugs Q 9 Push-In Stud
& 30° bend
7 CURRENT RATING (AMPERES)
CODE AMPERES
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 4 35.000
640 4 40.000
645 4 45.000
650 4 50.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
10 |A-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 Alarm Switch available with .110 x .020 Q.C. & Solder Lug Terminals Only.
Circuit & Terminal Diagrams: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 11
A-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 Alarm Switch available with .110 x .020 QC & solder lug terminals only.
Circuit & Terminal Diagrams: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
12 |A-Series Circuit Breaker - Handle - Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ± 0.20 [.51] unless otherwise specied.
3 For agency code P = .150 [3.81].
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 13
A-Series Circuit Breaker - Handle – Front Panel Snap-In Mounting Style 5 - Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 Recommended panel thickness: .040 [1.02] to .100 [2.54].
3 Tolerance ±.020 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
14 |A-Series Circuit Breaker - Handle – Front Panel Snap-In Mounting Style 7 - Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 Recommended panel thickness: .040 [1.02] to .100 [2.54].
3 Tolerance ±.020 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 15
A-Series Circuit Breaker - Sealed Toggle UL Recognized – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
4
Circuit
A M B 1 11 0 0 C10 450
1 SERIES
A
2 ACTUATOR 1
M Sealed Toggle, one per unit
10 MOUNTING / BARRIERS
MOUNTING STYLE BARRIERS
1 Standard Hex Nut no
A Standard Hex Nut (multipole only) yes
3 POLES
1 One
2 Two
3 Three
9 LEGEND PLATE
0 No legend plate
Notes:
1 Actuator Code M: Handle location as viewed from front of panel:
2 pole - right pole 3 pole - center pole
2 Switch Only circuits, rated up to 50 amps and 3 poles. Only available when tied to a
protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps,
select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required. With
Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require
30VA minimum power to trip and are rated for intermittent duty only.
5 Auxiliary Switch available on Series Trip & Switch Only circuits, limited to 30 amps.
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
6 Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
7 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA
Accepted & TUV Certied to 50 amps.
8 UL Recognition and CSA Certication available on one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over
30 amps are only available with Terminal Codes 5, 9, B, F, G, H, M and Q.
10 Terminal Code 1: UL Recognition and CSA Certication up to 30 amps, but not
recommended over 20 amps.
11 Terminal Code L : available up to 30A.
12 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
50 amps, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P
(Printed Circuit Board) are available up to 40 amps with Circuit Codes A, B and C.
8 TERMINAL 9
1 10 Push-On 0.250 Tab (Q.C.) E Screw M4 (Bus Type)
2 Screw 8-32 with upturned lugs F Screw M5 with upturned lugs
3 Screw 8-32 (Bus Type) & 30° bend
4 Screw 10-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
5 Screw 10-32 (Bus Type) H Screw M5 (Bus Type)
6 Screw 8-32 with upturned lugs L 12 0.250 Q.C./ Solder Lug
& 30° bend M M6 Threaded Stud
7 Screw 8-32 (Bus Type) Q Push-In Stud
& 30° bend R Screw M4 with upturned lugs
8 Screw 10-32 with upturned lugs & 30° bend
& 30° bend T Screw M4 (Bus Type)
9 Screw 10-32 (Bus Type) & 30° bend
& 30° bend P 12 Printed Circuit Board Terminals
B Screw M5 with upturned lugs S Push-On 0.110 Tab (Q.C.)
C Screw M4 with upturned lugs
5 AUXILIARY / ALARM SWITCH 5 5 S.P.S.T., 0.093 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 7 S.P.S.T., 0.110 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)
4 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
(Gold Contacts) 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
42 7 50/60Hz Short, Hi-Inrush
44 7 50/60Hz Medium, Hi-Inrush
46 7 50/60Hz Long, Hi-Inrush
52 7 DC, Short,Hi-Inrush
54 7 DC, Medium, Hi-Inrush
56 7 DC, Long, Hi-Inrush
11 AGENCY APPROVAL
C UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
4 CIRCUIT
A 2 Switch Only (No Coil) F 3 Relay Trip (Current)
B Series Trip (Current) G 3 Relay Trip (Voltage)
C Series Trip (Voltage) H 3,4 Dual Coil with Shunt Trip
D 3 Shunt Trip (Current) Voltage Coil
E 3 Shunt Trip (Voltage) K 3,4 Dual Coil with Relay Trip
Voltage Coil
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 6
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 8 35.000
640 8 40.000
645 8 45.000
650 8 50.000
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
16 |A-Series Circuit Breaker - Sealed Toggle - Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 17
A-Series Circuit Breaker - Rocker UL Recognized – Ordering Scheme
2 ACTUATOR 1
Two Color Visi-Rocker
C Indicate ON, vertical legend
D Indicate ON, horizontal legend
F Indicate OFF, vertical legend
G Indicate OFF, horizontal legend
H Indicate OFF, no legend
Push-To-Reset, Visi-Rocker
N Indicate OFF, vertical legend
O Indicate OFF, horizontal legend
P Indicate OFF, no legend
Single color
J Vertical legend
K Horizontal legend
L No legend
Push-To-Reset , Single color
R Vertical legend
U Horizontal legend
V No legend
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
4
Circuit
A F B 2 11 0 3 D24 630
1 SERIES
A
3 POLES
1 One 2 Two 3 Three
11 AGENCY APPROVAL
C UL Recognized & CSA Accepted
D VDE Certied, UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary switch and/or mixed
poles, and have one rocker per breaker.
3 Switch Only circuits, rated up to 50 amps & 3 poles, are available only when tied to a protected pole
(Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630.
For 35 - 50 amps, select Current Code 650.
4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
5 Consult factory for Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA
minimum power to trip and are rated for intermittent duty only.
6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with
standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
7 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
9 Available with Circuit Codes B & D only. VDE Certied to 30 amps. UL Recognized, CSA Accepted
& TUV Certied to 50 amps.
10 Series Trip current ratings: VDE Certication available with single pole breakers with DC Delay only.
UL Recognition & CSA Accepted available in one and two pole breakers.
11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only
available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: VDE Certication up to 25 amps and UL Recognition and CSA Accepted up to 30
amps, but not recommended over 20 amps.
13 Terminal Codes 3, 5 E & H (Bus Type) with VDE, are supplied with Lock Washers; Terminal Code M
(M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE
Certied when the washers are used.
14 VDE Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps.
15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with
VDE Certication and 50 amps with UL Recognition and CSA Accepted, with Circuit Codes A, B & C.
Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with
UL Recognition and CSA Certication with Circuit Codes A, B and C.
16 Terminal Code Q not available with VDE.
17 Terminal Code S used on voltage coil circuit constructions only.
18 Color shown is visi and legend with remainder of rocker black.
19 Dual = ON-OFF/I-O legend with actuator. None = no legend on actuator
20 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R, & U. Legend on
Push-to-reset bezel/shroud matches Visi-color of rocker with actuator codes N & O.
Rockerguard available with actuator codes C through L.
8 TERMINAL 11
1 12 Push-On 0.250 Tab (Q.C.) E 13 Screw M4 (Bus Type)
2 Screw 8-32 with upturned lugs F Screw M5 with upturned lugs
3 13 Screw 8-32 (Bus Type) & 30° bend
4 Screw 10-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
5 13 Screw 10-32 (Bus Type) H 13 Screw M5 (Bus Type)
6 Screw 8-32 with upturned lugs L 14 0.250 Q.C./ Solder Lug
& 30° bend M 13 M6 Threaded Stud
7 Screw 8-32 (Bus Type) P 15 Printed Circuit Board Terminals
& 30° bend Q 16 Push-In Stud
8 Screw 10-32 with upturned lugs R Screw M4 with upturned lugs
& 30° bend & 30° bend
9 Screw 10-32 (Bus Type) S 17 Push-On 0.110 Tab (Q.C.)
& 30° bend & 30° bend
B Screw M5 with upturned lugs T Screw M4 (Bus Type)
C Screw M4 with upturned lugs & 30° bend
5 AUXILIARY / ALARM SWITCH 6,7 5 S.P.S.T., 0.093 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 7 S.P.S.T., 0.110 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)
4 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
(Gold Contacts) 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
42 9 50/60Hz Short, Hi-Inrush
44 9 50/60Hz Medium, Hi-Inrush
46 9 50/60Hz Long, Hi-Inrush
52 9 DC, Short,Hi-Inrush
54 9 DC, Medium, Hi-Inrush
56 9 DC, Long, Hi-Inrush
4 CIRCUIT F 4 Relay Trip (Current)
A 3 Switch Only (No Coil) G 4 Relay Trip (Voltage)
B Series Trip (Current) H 4,5 Dual Coil with Shunt Trip
C Series Trip (Voltage) Voltage Coil
D 4 Shunt Trip (Current) K 4,5 Dual Coil with Relay Trip
E 4 Shunt Trip (Voltage) Voltage Coil
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 8
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 8 35.000
640 8 40.000
645 8 45.000
650 8 50.000
10 MOUNTING / BARRIERS 20
STANDARD ROCKER BEZEL BARRIERS
Threaded Insert, 2 per pole
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
ROCKERGUARD & PUSH-TO-RESET BEZEL
Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel
8 without Rockerguard (single pole units only) no
H with Rockerguard (single pole units only) no
FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel
9 without Rockerguard (single pole units only) no
J with Rockerguard (single pole units only) no
9 ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color
Visi-Color 12 I-O ON-OFF Dual
12 Single Color Visi-Rocker
White A B 1 Black White
Black C D 2 White n/a
Red F G 3 White Red
Green H J 4 White Green
Blue K L 5 White Blue
Yellow M N 6 Black Yellow
Gray P Q 7 Black Gray
Orange R S 8 Black Orange
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
18 |A-Series Circuit Breaker - Flat Rocker UL Recognized – Ordering Scheme
3 POLES 2
1 One 2 Two 3 Three
11 AGENCY APPROVAL
C UL Recognized & CSA Accepted
E TUV Certied, UL Recognized & CSA Accepted
I UL Recognized STD 1077, UL Recognized 1500 (ignition protected),
& CSA Accepted
1 SERIES
A
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Agency
Approval
4
Circuit
A 1 B 2 11 0 3 E24 630
2 ACTUATOR 1
Two Color Visi-Rocker
1 Indicate OFF, vertical legend
2 Indicate OFF, horizontal legend
Single color
3 Vertical legend
4 Horizontal legend
Push-To-Reset, Visi-Rocker
5 Indicate OFF, vertical legend
6 Indicate OFF, horizontal legend
Push-To-Reset , Single color
7 Vertical legend
8 Horizontal legend
10 MOUNTING / BARRIERS 18
STANDARD ROCKER BEZEL BARRIERS
Threaded Insert, 2 per pole
FLAT ROCKER ACTUATOR
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
RECESSED OFF SIDE ROCKER ACTUATOR 19
5 6-32 x 0.195 inches no
E 6-32 x 0.195 inches (multi-pole units only) yes
6 ISO M3 x 5mm no
F ISO M3 x 5mm (multi-pole units only) yes
PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary switch and/or
mixed poles, and have one rocker per breaker.
3 Switch Only circuits, rated up to 50 amps & 3 poles. Only available when tied to a protected
pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
5 Consult factory for Dual Coil options, as special catalog number is required. With Shunt
construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA
minimum power to trip and are rated for intermittent duty only.
6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with
standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
7 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
9 Available with Circuit Codes B & D only. UL Recognized, CSA Accepted & TUV Certied to 50 amps.
10 UL Recognition, CSA Acceptance & TUV Certication available in one and two pole breakers.
11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are
only available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: Available up to 30 amps, but not recommended over 20 amps.
13 Terminal Codes 3, 5 E & H (Bus Type) with TUV, are supplied with Lock Washers; Terminal
Code M (M6 Threaded Stud) with TUV is supplied with Lock and Flat Washers. These breakers
are only TUV Certied when the washers are used.
14 TUV Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps.
15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 50 amps
with UL Recognition, CSA Accepted & TUV Certication, with Circuit Codes A, B and C. Two
pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL
Recognition and CSA Accepted with Circuit Codes A, B and C.
16 Terminal Code S used on voltage coil circuit constructions only.
17 Color shown is visi and legend with remainder of rocker black, Dual = ON-OFF/I-O legend.
18 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend
on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes 5 & 6.
19 Recessed “off-side” available with actuator codes 1, 2, 3 & 4. Legends on rocker are available
in ink stamping only.
8 TERMINAL 11
1 12 Push-On 0.250 Tab (Q.C.) E 13 Screw M4 (Bus Type)
2 Screw 8-32 with upturned lugs F Screw M5 with upturned lugs
3 13 Screw 8-32 (Bus Type) & 30° bend
4 Screw 10-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
5 13 Screw 10-32 (Bus Type) H 13 Screw M5 (Bus Type)
6 Screw 8-32 with upturned lugs L 14 0.250 Q.C./ Solder Lug
& 30° bend M 13 M6 Threaded Stud
7 Screw 8-32 (Bus Type) P 15 Printed Circuit Board Terminals
& 30° bend Q Push-In Stud
8 Screw 10-32 with upturned lugs R Screw M4 with upturned lugs
& 30° bend & 30° bend
9 Screw 10-32 (Bus Type) S 16 Push-On 0.110 Tab (Q.C.)
& 30° bend & 30° bend
B Screw M5 with upturned lugs T Screw M4 (Bus Type)
C Screw M4 with upturned lugs & 30° bend
5 AUXILIARY / ALARM SWITCH 6,7 5 S.P.S.T., 0.093 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 7 S.P.S.T., 0.110 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts)
4 S.P.D.T., 0.110 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
(Gold Contacts) 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 6 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 6 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
31 DC, 50/60Hz Ultra Short
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
42 9 50/60Hz Short, Hi-Inrush
44 9 50/60Hz Medium, Hi-Inrush
46 9 50/60Hz Long, Hi-Inrush
52 9 DC, Short,Hi-Inrush
54 9 DC, Medium, Hi-Inrush
56 DC, Long, Hi-Inrush
4 CIRCUIT F 4 Relay Trip (Current)
A 3 Switch Only (No Coil) G 4 Relay Trip (Voltage)
B Series Trip (Current) H 4,5 Dual Coil with Shunt Trip
C Series Trip (Voltage) Voltage Coil
D 4 Shunt Trip (Current) K 4,5 Dual Coil with Relay Trip
E 4 Shunt Trip (Voltage) Voltage Coil
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE) 8
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 8 35.000
640 8 40.000
645 8 45.000
650 8 50.000
9 ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color
Visi-Color 17 ON-OFF Dual
17 Single Color Visi-Rocker
White B 1 Black White
Black D 2 White n/a
Red G 3 White Red
Green J 4 White Green
Blue L 5 White Blue
Yellow N 6 Black Yellow
Gray Q 7 Black Gray
Orange S 8 Black Orange
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 19
A-Series Circuit Breaker - Flat Rocker UL 489A – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Max. Appl.
Rating
12
Agency
Approval
4
Circuit
A 1 B 2 11 0 3 M T14 630
1 SERIES
A
12 AGENCY APPROVAL
T UL489A Listed
J UL489A Listed, TUV Certied
11 MAXIMUM APPLICATION RATING
M 80 DC
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Auxiliary switch and/or
mixed poles, and have one rocker per breaker.
3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half
shells. 30-50A are supplied with extended boat (B-Style) half shells.
4 VDE Certication available with single pole breakers only. UL489A Listing available with one
and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps
are only available with Terminal Codes 5, 9, G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certication and 30
amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers,
and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers.
These breakers are only TUV or VDE Certied when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30
amps with VDE Certication and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certication.
10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U.
12 Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator
codes N & O. Rockerguard available with actuator codes C through K
3 POLES 2
1 One 2 Two 3 Three
2 ACTUATOR 1
Two Color Visi-Rocker
1 Indicate OFF, vertical legend
2 Indicate OFF, horizontal legend
Single color
3 Vertical legend
4 Horizontal legend
Push-To-Reset, Visi-Rocker
5 Indicate OFF, vertical legend
6 Indicate OFF, horizontal legend
Push-To-Reset , Single color
7 Vertical legend
8 Horizontal legend
10 MOUNTING / BARRIERS 12
STANDARD ROCKER BEZEL BARRIERS
Threaded Insert, 2 per pole
FLAT ROCKER ACTUATOR
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
RECESSED OFF SIDE ROCKER ACTUATOR
5 6-32 x 0.195 inches no
E 6-32 x 0.195 inches (multi-pole units only) yes
6 ISO M3 x 5mm no
F ISO M3 x 5mm (multi-pole units only) yes
PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
3 6-32 x 0.195 inches no
C 6-32 x 0.195 inches (multi-pole units only) yes
4 ISO M3 x 5mm no
D ISO M3 x 5mm (multi-pole units only) yes
5 AUXILIARY / ALARM SWITCH 3 7 S.P.S.T., 0.110 Q.C. Term.
0 without Aux Switch (Gold Contacts)
1 S.P.D.T., 0.093 Q.C. Term. 8 S.P.S.T., 0.187 Q.C. Term.
2 S.P.D.T., 0.110 Q.C. Term. 9 S.P.D.T., 0.187 Q.C. Term.
6 FREQUENCY & DELAY
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
52 DC, Short,Hi-Inrush
54 DC, Medium, Hi-Inrush
56 DC, Long, Hi-Inrush
4 CIRCUIT
B Series Trip (Current)
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 4 35.000
640 4 40.000
645 4 45.000
650 4 50.000
9 ACTUATOR COLOR & LEGEND
Actuator or Marking: Marking Color
Visi-Color 11 ON-OFF Dual
11 Single Color Visi-Rocker
White B 1 Black White
Black D 2 White n/a
Red G 3 White Red
Green J 4 White Green
Blue L 5 White Blue
Yellow N 6 Black Yellow
Gray Q 7 Black Gray
Orange S 8 Black Orange
8 TERMINAL 5
1 6 Push-On 0.250 Tab (Q.C.) 9 Screw 10-32 (Bus Type)
2 Screw 8-32 with upturned lugs & 30° bend
3 7 Screw 8-32 (Bus Type) B Screw M5 with upturned lugs
4 Screw 10-32 with upturned lugs F Screw M5 with upturned lugs
5 7 Screw 10-32 (Bus Type) & 30° bend
6 Screw 8-32 with upturned lugs G Screw M5 (Bus Type) & 30° bend
& 30° bend H Screw M5 (Bus Type)
7 Screw 8-32 (Bus Type) M 7 M6 Threaded Stud
& 30° bend P 8 Printed Circuit Board Terminals
8 Screw 10-32 with upturned lugs Q 9 Push-In Stud
& 30° bend
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
20 |A-Series Circuit Breaker - Recessed Paddle – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Auxiliary
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
11
Max. Appl.
Rating
12
Agency
Approval
4
Circuit
A Y B 4 12 0 2 C C24 620
1 SERIES
A
12 AGENCY APPROVAL 7
A Without Approvals
C UL Recognized and CSA Accepted
T UL 489A
11 MAXIMUM APPLICATION RATING 6
A 65 VDC
C 120/240 VAC (Available only on 2 or 3-Pole units)
K 120 VAC
M 80 DC
Notes:
1 All standard catalog numbers are supplied with Vertical Legends. For Horizontal or other
non-standard legends, choose “X” and order as a special catalog number.
2 For rating (T) 2 & 3 Pole not available.
3 Frequency and Time Delay ratings of (03, 20, 21, 22, 24, 26, 42, 44, 46) not
available with approval T.
4 Voltage Coil Ratings starting with (J, K, or L) not available with approval T.
5 “OFF and/or “O” Legends are on Bracket and are only visible when the Paddle Actuator is in
the off position.
6 Maximum Application Ratings (C & K) not available with approval T.
7 Not all approvals are available in all constructions. Consult factory for details.
3 POLES 2
1 One 2 Two 3 Three
2 ACTUATOR 1
Y Single Color Recessed Paddle Actuator with Vertical Legends
10 MOUNTING / BARRIERS BARRIERS
1 6-32 x 0.195 inches no
A 6-32 X 0.195 inches (multi-pole units only) yes
2 ISO M3 x 5mm no
B ISO M3 x 5mm (multi-pole units only) yes
5 AUXILIARY SWITCH
0 without Aux Switch
1 S.P.D.T. with 0.093 Q.C. Terminals
2 S.P.D.T. with 0.110 Q.C. Terminals
3 S.P.D.T. with 0.139 Solder Lug Terminals
4 S.P.D.T. with 0.110 Q.C. Terminals (Gold Contacts)
5 S.P.D.T. with 0.093 Q.C. Terminals (Gold Contacts)
6 S.P.S.T.-N.O. with 0.139 Solder Lug Terminals
7 S.P.S.T.-N.O. with 0.110 Q.C. Terminals (Gold Contacts)
8 S.P.S.T.-N.O. with 0.187 Q.C. Terminals
9 S.P.D.T. with 0.187 Q.C. Terminals
6 FREQUENCY & DELAY 3
3 DC, 50/60 Hz Switch Only
10 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
20 50/60 Hz Instantaneous
21 50/60 Hz Ultra Short
22 50/60 Hz Short
24 50/60 Hz Medium
26 50/60 Hz Long
42 50/60 Hz Short Hi-Inrush
44 50/60 Hz Medium Hi-Inrush
46 50/60 Hz Long Hi-Inrush
52 DC, Short, Hi-Inrush
54 DC, Medium, Hi-Inrush
56 DC, Long, Hi-Inrush
4 CIRCUIT
A Switch-Only (No Coil) F Relay Trip (Current)
B Series Trip (Current) G Relay Trip (Voltage)
C Series Trip (Voltage) H Dual Coil with Shunt Trip Voltage Coil
D Shunt Trip (Current) K Dual Coil with Shunt Trip Current Coil
E Shunt Trip (Voltage)
8 TERMINAL
1 Push-On 0.250 Tab (Q.C.) C Screw, M4 with upturned lugs
2 Screw 8-32 with upturned lugs E Screw, M4 (Bus Type)
3 Screw 8-32 (Bus Type) F Screw M5 with upturned lugs
4 Screw 10-32 with upturned lugs & 30° bend
5 Screw 10-32 (Bus Type) G Screw M5 (Bus Type) & 30° bend
6 Screw 8-32 with upturned lugs H Screw M5 (Bus Type)
& 30° bend L 0.250 Q.C./Solder Lug
7 Screw 8-32 (Bus Type) M M6 Threaded Stud
& 30° bend P Printed Circuit Board Terminals
8 Screw 10-32 with upturned lugs Q Push-In Stud
& 30° bend R Screw, M4 with upturned lugs
9 Screw 10-32 (Bus Type) & 30° Bend
& 30° bend S Screw, M5 with upturned lugs
B Screw M5 with upturned lugs T Screw, M4 with upturned lugs
7 CURRENT RATING (AMPERES) 4
CODE AMPERES
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
CODE AMPERES
A06 6 DC A32 32 DC J12 12 AC J65 65 AC
A12 12 DC A48 48 DC J18 18 AC K20 120 AC
A18 18 DC A65 65 DC J24 24 AC L40 240 AC
A24 24 DC J06 6 AC J48 48 AC
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
645 45.000
650 50.000
9 ACTUATOR COLOR & LEGEND 5
Actuator Color I-O ON-OFF Dual Legend Color
White A B 1 Black
Black C D 2 White
Red F G 3 White
Green H J 4 White
Blue K L 5 White
Yellow M N 6 Black
Gray P Q 7 Black
Orange R S 8 Black
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 21
A-Series Circuit Breaker - Rocker – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 Schematic shown represents current trip circuit.
4 Circuits shown for >30 amps / VDE.
Circuit & Terminal Diagrams: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
22 |A-Series Circuit Breaker - Rocker - Dimensional Specications
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line & load
terminal orientation on indicate OFF is opposite of indicate ON.
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 All dimensions are in inches [millimeters].
4 Tolerance ± 0.20 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 23
A-Series Circuit Breaker - Rocker Snap-In Bracket - Dimensional Specications
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line
& load terminal
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
Orientation on indicate “OFF” is opposite of indicate “ON”
3 Recommended panel thickness: .04 0 [1.02] to .100 [2.54]
4 All dimensions are in Inches [millimeters].
5 Tolerance ±.020 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
24 |A-Series Circuit Breaker - Flat Rocker - Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 Tolerance ± 0.20 [.51] unless otherwise specied.
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 25
A-Series Circuit Breaker - Recessed Paddle - Dimensional Specications
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ± 0.20 [.51] unless otherwise specied
Dimensional Specifications: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
26 |A-Series Circuit Breaker - PC Terminal Diagrams
Notes:
1 Drawing illustrates A-Series with VDE certication.
2 All dimensions are in inches [millimeters].
3 Tolerance ± 0.20 [.51] unless otherwise specied
PC Terminal Diagrams: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 27
Sales Representatives, Distributors & Company Prole
Authorized Sales Representatives and Distributors
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales oces worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-prole.
To view all of Carling’s environmental, quality, health & safety certications please visit
www.carlingtech.com/environmental-certications
Click on a region of the map below to nd your local representatives and distributors or visit
www.carlingtech.com/ndarep.
EUROPE
MIDDLE
EAST
SOUTH
AMERICA
ASIA-PACIFIC
OCEANIA
AFRICA
MEXICO
USA
CANADA
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: sales@carlingtech.com
Northern Region Sales Oce: nrsm@carlingtech.com
Southeast Region Sales Oce: sersm@carlingtech.com
Midwest Region Sales Oce: mrsm@carlingtech.com
West Region Sales Oce: wrsm@carlingtech.com
Latin America Sales Oce: larsm@carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacic Ltd.,
Suite 1607, 16/F Tower 2, The Gateway,
Harbour City, 25 Canton Road,
Tsimshatsui, Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: sales@carlingtech.com.hk
Shenzhen, China: shenzhen@carlingtech.com
Shanghai, China: shanghai@carlingtech.com
Pune, India: india@carlingtech.com
Kaohsiung, Taiwan: taiwan@carlingtech.com
Yokohama, Japan: japan@carlingtech.com
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: ltd.sales@carlingtech.com
Germany: gmbh@carlingtech.com
France: sas@carlingtech.com
www.carlingtech.com REV_05_2017