https://www.phoenixcontact.com/us/products/2806016
09/10/2014Page1/5
Differential current monitoring-RCM-A/50/85-264V-2806016
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Differential current monitor in type A version for detecting pulsing AC and DC leakage currents at 50/60 Hz.
Product Features
Residual current detection characteristics type A (50/60 Hz)
Detects pulsating DC and AC residual currents
Adjustable residual response current of 30 mA to 3 A
Adjustable pre-alarm threshold and delay time
Actual residual current can be read via LED display
Remote signaling for main and pre-alarm
Residual current monitoring devices act as a form of fire prevention
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 200.0 GRM
Custom tariff number 90303310
Country of origin Germany
Technical data
Dimensions
Height 89.7 mm
Width 71.6 mm
Depth 62.2 mm
Horizontal pitch 4 Div.
Ambient conditions
Degree of protection IP20
https://www.phoenixcontact.com/us/products/2806016
09/10/2014Page2/5
Differential current monitoring-RCM-A/50/85-264V-2806016
Technical data
Ambient conditions
IP40 (distributor installation with cover)
Ambient temperature (operation) -25 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
General
Housing material Polycarbonate
Mounting type DIN rail: 35 mm
Common characteristics
Nominal voltage UN85 V AC ... 264 V AC
Nominal frequency fN50 Hz (60 Hz)
Current consumption < 4 VA
Max. required back-up fuse 16 A (B)
Rated response differential current Idyn 3 A
Differential current acquisition characteristic Type A (50 / 60 Hz)
Response differential current IΔn 30, 100, 300, 1000, 3000 mA (adjustable)
Discrimination threshold main alarm 80 % ... 100 % (of the set response differential current IΔn)
Discrimination threshold pre-alarm 10 % ... 90 % (of the main alarm threshold, adjustable)
Response time for 2 x IΔn 0.1 s ... 1 s (adjustable)
Rated surge voltage resistance Uimp 4 kV
Surge voltage category III
Rated voltage Un230 V AC
Pollution degree 2
Connections
Connection method Screw terminal blocks
Tightening torque 0.6 Nm
Stripping length 8 mm
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Min. conductor cross section, stranded, with ferrule 0.25 mm²
Max. conductor cross section, stranded, with ferrule 2.5 mm²
Remote indication contact
Connection name Pre-alarm
https://www.phoenixcontact.com/us/products/2806016
09/10/2014Page3/5
Differential current monitoring-RCM-A/50/85-264V-2806016
Technical data
Remote indication contact
Switching function PDT contact
Connection name Main alarm
Switching function PDT contact
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Maximum operating voltage Umax. AC 230 V AC
Max. operating current Imax 5 A (cos phi > 0.9)
Max. required back-up fuse 4 A (gL)
Standards and Regulations
Standards/specifications DIN EN 62020
DIN EN 60664
Classifications
eCl@ss
eCl@ss 4.0 27371105
eCl@ss 4.1 27371105
eCl@ss 5.0 27371802
eCl@ss 5.1 27371802
eCl@ss 6.0 27371802
eCl@ss 7.0 27371802
eCl@ss 8.0 27371802
ETIM
ETIM 2.0 EC001440
ETIM 3.0 EC001440
ETIM 4.0 EC001440
ETIM 5.0 EC001440
UNSPSC
UNSPSC 6.01 30211916
UNSPSC 7.0901 39121535
UNSPSC 11 39121535
UNSPSC 12.01 39121535
UNSPSC 13.2 39121535
https://www.phoenixcontact.com/us/products/2806016
09/10/2014Page4/5
Differential current monitoring-RCM-A/50/85-264V-2806016
Approvals
Approvals
Approvals
VDE Zeichengenehmigung
Ex Approvals
Approvals submitted
Approval details
VDE Zeichengenehmigung
Drawings
Dimensioned drawing
62,2
71,6
4,7
89,7
11,1 11,1
Circuit diagram
A1
=
l
k
A2
12 14
11
Alarm
Pre-alarm
12 14
11
https://www.phoenixcontact.com/us/products/2806016
09/10/2014Page5/5
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com