https://www.phoenixcontact.com/us/products/2806016
09/10/2014Page2/5
Differential current monitoring-RCM-A/50/85-264V-2806016
Technical data
Ambient conditions
IP40 (distributor installation with cover)
Ambient temperature (operation) -25 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
General
Housing material Polycarbonate
Mounting type DIN rail: 35 mm
Common characteristics
Nominal voltage UN85 V AC ... 264 V AC
Nominal frequency fN50 Hz (60 Hz)
Current consumption < 4 VA
Max. required back-up fuse 16 A (B)
Rated response differential current Idyn 3 A
Differential current acquisition characteristic Type A (50 / 60 Hz)
Response differential current IΔn 30, 100, 300, 1000, 3000 mA (adjustable)
Discrimination threshold main alarm 80 % ... 100 % (of the set response differential current IΔn)
Discrimination threshold pre-alarm 10 % ... 90 % (of the main alarm threshold, adjustable)
Response time for 2 x IΔn 0.1 s ... 1 s (adjustable)
Rated surge voltage resistance Uimp 4 kV
Surge voltage category III
Rated voltage Un230 V AC
Pollution degree 2
Connections
Connection method Screw terminal blocks
Tightening torque 0.6 Nm
Stripping length 8 mm
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
Min. conductor cross section, stranded, with ferrule 0.25 mm²
Max. conductor cross section, stranded, with ferrule 2.5 mm²
Remote indication contact
Connection name Pre-alarm