G7SA
3
Specifications
JRATINGS
Operation Coil
Number of
contacts
Rated
voltage
Rated
current
Coil
resistance
Minimum operate
voltage
Release
voltage
Max. voltage Power
consumption
4 poles 24 VDC 15 mA 1,600 Ω75% max. (V) 10% min. (V) 110% (V) Approx. 360 mW
6 poles 20.8 mA 1,152 Ω
Approx. 500 mW
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of ±15%.
2. Performance characteristics are based on a coil temperature of 23°C.
3. The voltage is based on an ambient operating temperature of 23°C maximum.
Switching Section (Contact Ratings)
Load type Resistive load (cos θ=1)
Rated load 250 VAC: 6 A, 30 VDC: 6 A
Rated carry current 6A
Max. switching voltage 250 VAC, 125 VDC
Max. switching current 6A
JCHARACTERISTICS
Contact resistance 100 mΩmax. (Measurement conditions: 5 VDC, 1 A, voltage drops)
Operating time (Rated voltage operation, does
20 ms max.
Release time
not include bounce time) 20 ms max.
Response time
(SeeNote2.)
10 ms max.
Maximum operating frequency Mechanical 36,000 operations/hr
Rated load 1,800 operations/hr
Insulation resistance
(SeeNote3,4.)
100 MΩ
Dielectric strength Between coil contacts/different poles: 4,000 VAC, 50/60 Hz for 1 min.
Between poles 3-4 (4 poles)
Between contacts of same polarity: 1,500 VAC, 50/60 Hz for 1 min.
Vibration 10 to 55 Hz, 1.5-mm double amplitude
Shock Destruction 1,000 m/s2(approx. 100G)
Malfunction 100 m/s2(approx. 10G)
Life expectancy Mechanical 10,000,000 operations min. (at approx. 36,000 operations/hr)
Electrical 100,000 operations min. (at the rated load and approx. 1,800 operations/hr)
Ambient temperature
Operating -- 4 0 °Cto85°C(-40°F to 185°F) no icing
(SeeNote5.) Storage -- 4 0 °Cto85°C(-40°F to 185°F) no icing
Ambient humidity Operating 35% to 85%
Storage 35% to 85%
Weight 4 poles: Approx. 22 g
6 poles: Approx. 25 g
Note: 1. The values listed above are initial values.
2. The response time is the time it takes for the NO contacts to open after the coil voltage is turned OFF.
3. Pole 3: poles 31-32 or 33-34, pole 4: poles 43-44, pole 5: poles 53-54, pole 6: poles 63-64.
4. When using a P7SA socket, the dielectric strength between coil contacts/different poles is 2,500 VAC, 50/60 Hz for 1 min.
5. When operating at a temperature between 70°C and 85°C, reduce the rated carry current (6 A at 70°C or less) by 0.1 A for
each degree above 70°C.
JCHARACTERISTICS OF SAFETY RELAY SOCKET
Model Continuous current Dielectric strength Insulation resistance
P7SA-14j6A 2,500 VAC for 1 min. between poles 100 MΩmin. (See Note.)
Note: Measurement conditions: Measurement of the same points as for the dielectric strength at 500 VDC.