(R) General Data -- Selection Chart Bussmann Buss Fuse Selection Chart (600 Volts or Less) Circuit Load Ampere Fuse Rating Type Symbol Voltage Rating (a-c) Class Interrupting Rating (KA) Remarks All-purpose fuses. Unequaled for combined short-circuit and overload protection. (Specification grade product) Page Conventional Dimensions--Class RK1, RK5 (0-600A), L (601-6000A) All type loads (optimum overcurrent protection). 200,000A Interrupting Rating (rms symmetrical) Current Limiting Motors, welder, transformers, capacitor banks (circuits with heavy inrush currents). Main, Feeder and Branch LOW-PEAK(R) (dual-element, time-delay) LPN-RK_SP LPS-RK_SP 250V 600V RK1 300 601 to 6000A LOW-PEAK(R) (time-delay) KRP-C_SP 600V L 300 0 to 600A FUSETRON(R) (dual-element, time-delay) FRN-R FRS-R 250V 600V RK5 200 0 to 600A DURA-LAGTM (dual-element, time-delay) DLN-R DLS-R 250V 600V RK5 200 601 to 4000A LIMITRON(R) (time-delay) KLU 600V L 200 All-purpose fuse. Timedelay passes surge-currents. 6 KTN-R KTS-R 250V 600V RK1 200 Same short-circuit protection as LOW-PEAK fuses but must be sized larger for circuits with surge-currents; i.e., up to 300%. 13 KTU 600V L 200 A fast acting, high performance fuse. 6 Non-motor loads (circuits with no 0 heavy inrush to currents). 600A LIMITRON fuses _____ particularly suited for 601 to circuit breaker 6000A protection. LIMITRON(R) (fast-acting) Moderate degree of current limitation. Time-delay passes surge currents. 7-9 4-5 10 11 12 Reduced Dimensions For Installation in Restricted Space--Class J(0-600A), T(0-1200A), CC(0-30A), G(0-60A) All type loads (optimum overcurrent protection). __________ Non-motor loads (circuits with no heavy inrush currents). Branch 10,000-50,000 AIC 0-600A General Purpose (noncurrent limiting fuses) 0 to 600A 0 to 1200A LOW-PEAK(R) (dual-element time-delay) LPJ_SP 600V J 300 All-purpose fuses. Unequaled for combined short-circuit and overload protection. (Specification grade product) 15 LIMITRON(R) (quick acting) JKS 600V J 200 Very similar to KTS-R LIMITRON, but smaller. 16 T-TRONTM JJN JJS 300V 600V T 200 The space saver ( the size of KTN-R/KTS-R). 17 Motor loads (circuits with heavy in-rush currents.) 0 to 30A LOW-PEAK(R) (time-delay) LP-CC 600V CC 200 Rejection feature 19 Non-motor loads (circuits with no heavy in-rush currents.) 0 to 30A LIMITRON(R) (fast-acting) KTK-R 600V CC 200 Very compact (TM 1TM); rejection feature. 20 Control transformer circuits and lighting ballasts; etc. 0 to 30A TRON(R) (time-delay) FNQ-R 600V CC 200 Excellent for control transformer protection. 20 General purpose; i.e., lighting panel boards. 0 to 60A SC SC 480V G 100 Current limiting; TM dia. varying lengths per amp rating. 18 Miscellaneous 0 to 600A ONE-TIME NON NOS 250V 600V H or K5 10 Forerunners of the modern 14 Plug fuses can be used for branch circuits and small component protection. 0 to 30A FUSTAT(R) (dual-element, time-delay) FUSETRON(R) (dual-element, time-delay) S 125V S 10 24 T 125V ** 10 Buss Type W W Base threads of Type S differ with amp ratings. T and W have Edison base. T & S fuses recommended for motor circuits. W not recommended for circuits with motor loads. 125V ** 10 24 ** UL Listed as Edison Base Plug Fuse. Some ampere ratings are available as UL Class K5 with a 50,000A interrupting rating. RK1 and RK5 fuses fit standard switches, fuseblocks and holders; however, the rejection feature of class R switches and fuseblocks designed specifically for rejection type fuses (RK1 and RK5) prevent the insertion of the non-rejection fuses (K1, K5, and H). 1 (R) Bussmann General Data - Dimensions (Inches) CLASS T CLASS J CLASS RK5 & RK1 T-TronTM Fuses JJN (300V) JJS (600V) Low-Peak(R) & Limitron(R) Fuses LPJ & JKS (600V) Fusetron(R), Low-Peak(R) & Limitron(R) Fuses (250V & 600V) FRN-R & FRS-R; LPN-RK & LPS-RK; KTN-R & KTS-R Basic dimensions are same as Class H (formerly NEC) ONE-TIME (NON & NOS) and SUPERLAG Renewable RES & REN fuses. NOTE: These fuses can be used to replace existing Class H, RK1 and RK5 fuses relating to dimensional compatibility. A B 250V Ampere -30 35-60 A 2 3 600V B .56 .81 A 5 5.5 B .81 1.06 A B Fusetron & Limitron 250V Ampere 70-100 110-200 225-400 450-600 A 5.88 7.13 8.63 10.38 B 1.06 1.56 2.06 2.59 600V A 7.88 9.63 11.63 13.38 B 1.34 1.84 2.59 3.13 Low-Peak 250V Ampere 70-100 110-200 225-400 450-600 A 5.88 7.13 8.63 10.38 B 1.16 1.66 2.38 2.88 600V A 7.88 9.63 11.63 13.38 B 1.16 1.66 2.38 2.88 CLASS L Low-Peak(R) & Limitron(R) Fuses KRP-C, KTU, & KLU (601 - 4000A) (600V) NOTE: KRP-CL (150A to 600A) fuses have same dimensions as 601A to 800A case size. KTU (200A to 600A) have same dimensions, except tube 3 lgth. 2 dia.; terminal 1fi/* width 1/ thick. 2 (R) Bussmann General Data - Dimensions (Millimeters) CLASS T CLASS J CLASS RK5 & RK1 T-TronTM Fuses JJN (300V) JJS (600V) Low-Peak(R) & Limitron(R) Fuses LPJ & JKS (600V) Fusetron(R), Low-Peak(R) & Limitron(R) Fuses (250V & 600V) FRN-R & FRS-R; LPN-RK & LPS-RK; KTN-R & KTS-R Basic dimensions are same as Class H (formerly NEC) ONE-TIME (NON & NOS) and SUPERLAG Renewable RES & REN fuses. NOTE: These fuses can be used to replace existing Class H, RK1 and RK5 fuses relating to dimensional compatibility. A B 250V Ampere -30 35-60 A 50.8 76.2 B 14.3 20.6 600V A 127.0 139.7 B 20.6 27.0 A B Fusetron & Limitron 250V Ampere 70-100 110-200 225-400 450-600 A 149.2 181.0 219.1 263.5 B 26.9 39.6 52.3 65.8 600V A 200.0 244.5 295.3 339.7 B 34.0 46.7 65.8 79.5 Low-Peak 250V Ampere 70-100 110-200 225-400 450-600 A 149.2 181.0 219.1 263.5 B 29.5 42.2 60.5 73.2 600V A 200.0 244.5 295.3 339.7 B 29.5 42.2 60.5 73.2 CLASS L Low-Peak(R) & Limitron(R) Fuses KRP-C, KTU, & KLU (601 - 4000A) (600V) NOTE: KRP-CL (150A to 600A) fuses have same dimensions as 601A to 800A case size. KTU (200A to 600A) have same dimensions, except tube 76.2mm lgth. x 50.8mm dia.; terminal 41,3mm width x 31.8mm thick. 3 (R) Electrical - Power Fuses Bussmann Low-Peak(R) Time-Delay, Class L Fuses O-RING SEALS Formation of arc gas within fuse body suppresses arcing; lowers arcing I2t energy. O-ring seals maximize pressure build-up during current limiting action. Also volume of sand is critical. Slight loss can adversely impact on current limiting action. O-ring seals insure filler retention. They compensate to a degree for switchgear misalignment, and expansion and contraction of mounting surfaces with change in load to no-load conditions. KRP-C_SP Time-Delay - 4 seconds (minimum) at 500% rated current Ampere Ratings: 601-6000 Amps Voltage Rating: 600 Volts AC (or less), 300 Volts DC for 601-2000 amps. Interrupting Rating: AC: 300,000A RMS Sym. DC: 100,000A Agency Approvals: UL Listed-Special Purpose (meets all performance requirements of UL Standard 248-10 for Class L fuses), Guide JFHR, File E56412 CSA Certified (200,000 AIR), Class 1422-02, File 53787, Class L per CSA C22.2, No. 248.10 Dimensions: See pages 2-3 for Class L dimensional data. Ordering Information Catalog Number Ctn. Qty. Weight** Lbs. Kg. KRP-C-601SP KRP-C-1900SP 1 3.75 1.7 KRP-C-2001SP KRP-C-800SP KRP-C-2400SP KRP-C-801SP KRP-C-2500SP KRP-C-900SP KRP-C-3000SP 1 4.5 2.041 KRP-C-3800SP KRP-C-1200SP KRP-C-4000SP KRP-C-1350SP KRP-C-4500SP KRP-C-1500SP Kg. 1 8.5 3.85 1 17.25 7.824 1 18.25 8.278 1 23.50 10.659 1 6.50 2.948 1 29 13.154 1 36 16.329 99.9% PURE SILVER FUSELINKS Embody "silver-sand" design. 99.9% pure silver links; silicasand filler. The high conductivity of silver gives low watt loss and low operating temperature at normal current levels; minimizes total clearing I2t fault energy let-thru... state-of-art fuse design. High degree of current limitation holds down fault currents and levels of destructive energy. (Although other link materials can provide current limitation, they do not equal that of silver.) * All-purpose silver linked fuse for both overload and shortcircuit protection for high capacity systems (mains and large feeders). * Time-delay (minimum of four seconds at five times amp rating) for close sizing. * Current limiting action of the fuse generally affords considerable reduction in bus bracing. * Interrupting rating of 300,000 amperes complies with NEC Sections 110-9 and 230-65 for today's large capacity systems. * O-ring seals maximize pressure build-up during current limiting action and ensure filler retention. * High grade silica-sand filler; accelerates response of fuse to short-circuits by having quenching effect upon the fuse arc. * 99.9% pure silver fuselinks. The high conductivity of silver gives low watt loss and low operating temperature at normal current levels; minimizes total clearing I 2t fault energy let-thru. * Selective coordination (blackout prevention) * Glass melamine tube. * Silver plated end bells. * Reducers not necessary. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. KRP-C-3500SP KRP-C-1100SP KRP-C-1400SP Lbs. KRP-C-2000SP KRP-C-750SP KRP-C-1000SP Weight** Ctn. Qty. KRP-C-1800SP KRP-C-650SP KRP-C-700SP Catalog Number SAND FILLER High grade silica-sand filler. Accelerates response of fuse to short-circuits by having quenching effect upon the fuse arc. Substantially contributes to current limiting action. KRP-C-5000SP KRP-C-6000SP KRP-C-1600SP *Special purpose rating of 300,000 AIR. **Weight per carton. Use KRP-CL for current ratings below 601 Amps. BIF document: 1008 and 1009 4 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann 4000 5000 6000 AMPERE RATING 300 100 AMPERE RATING 100,000 6,000 5,000 4,000 3,000 2,500 2,000 1,600 1,200 800 601 1200 B 400,000 1600 2000 2500 3000 Time-Current Characteristic Curves--Average Melt KRP-C 800A Current Limitation Curves--KRP-C 10 200,000 100,000 10,000 1,000 1,000 A TIME IN SECONDS 10,000 1 PROSPECTIVE SHORT CIRCUIT CURRENT SYMMETRICAL RMS AMPERES Recommended Fuseblocks for Class L: (601-1200 Amps) Catalog Number Poles 51215 1 51235 3 .1 KRP-CL 00,000 00,000 1,000 .01 CURRENT IN AMPERES 10,000 Use KRP-CL for current ratings below 601 Amps. Dimensions: See pages 2-3 for Class L dimensional data. Current Limiting, Time-Delay Construction: Glass Melamine Tube Ampere Ratings: 150-600 Amps. Voltage Rating: 600 Volts AC (or less) These fuses have the same performance characteristics as KRP-C fuses. They are used in applications where there is a need for Class L dimension fuses with 150-600 ampere ratings. KRP-CL fuses have the same dimensions as 800 ampere Class L fuses. Ordering Information Catalog Number (Symbol & Amps) KRP-CL-150 KRP-CL-300 KRP-CL-500 KRP-CL-200 KRP-CL-350 KRP-CL-600 KRP-CL-225 KRP-CL-400 KRP-CL-250 KRP-CL-450 Weight of each is 3.75 lbs. BIF document: 1016 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 5 (R) Electrical - Power Fuses Bussmann Limitron(R) Class L Fuses KTU KLU Fast Acting, Bolt Mount Ampere Ratings: 601-6000 Amps. Voltage Rating: 600 Volts AC (or less) Interrupting Rating: 200,000 RMS Sym. Agency Approvals: Std. 248-10, Class L UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class L dimensional data. Time-Delay - 5 seconds (minimum) at 500% rated current Bolt Mount Ampere Ratings: 601-4000 Amps. Voltage Rating: 600 Volts AC (or less) Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-10, Class L UL Listed, Guide JDDZ, File E4273 CSA Certified, CSA Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class L dimensional data. Ordering Information Catalog Number Ctn. Qty. Weight** Lbs. Kg. Catalog Number KTU-601 KTU-1800 KTU-650 KTU-2000 KTU-700 1 3.75 1.70 KTU-2400 KTU-750 KTU-2500 KTU-800 KTU-3000 KTU-801 KTU-3001 KTU-900 KTU-4000 KTU-1100 1 4.25 1.927 KTU-4500 KTU-1200 KTU-5000 KTU-1350 KTU-6000 KTU-1400 KTU-1500 1 6 Weight** Ctn. Qty. Lbs. Kg. 1 8.5 3.855 1 17 7.711 1 17.25 7.824 1 24 10.886 1 31 14.061 1 34 15.422 Recommended Fuseblocks for Class L: (601-1200 Amps) 1 3 Kg. KLU-700 KLU-1000 KLU-1500 KLU-1600 Catalog Number Weight** Ctn. Qty. Lbs. Kg. 1 8.50 3.86 KLU-1800 KLU-2000 1 3.75 1.70 KLU-2500 KLU-3000 1 4.25 1.93 1 6.00 2.72 KLU-4000 **Weight per carton. * For protection of circuit breakers with lower interrupting ratings and non-inductive loads such as lighting and heating circuits. * 99.9% pure silver-links. * Reducers not necessary. 51235 Weight** Lbs. KLU-650 KLU-1200 **Weight per carton. 51215 Ctn. Qty. KLU-800 KTU-1600 Poles Catalog Number KLU-601 2.721 Catalog Number Ordering Information * KLU Limitron(R) general purpose copper link fuses. * Current limiting--provides component short-circuit protection. * Fuse reducers not necessary. * See KRP-CL for current ratings below 601 Amps. Recommended Fuseblocks: (601-1200 Amps) Catalog Number Poles 51215 1 51235 3 CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1010 6 BIF document: 1013 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Low-Peak(R) Dual-Element, Time-Delay, Class RK1 Fuses LPN-RK_SP (250V) LPS-RK_SP (600V) Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current (8 seconds for 0-30A sizes) Ampere Ratings: -600 Amps. Voltage Rating: LPN-RK: 250 Volts AC (or less), 125 Volts DC (-60 A); 250 VDC (70-600 A) LPS-RK: 600 Volts AC (or less), 300 Volts DC Current Limiting RK1 Fuse Interrupting Rating: 300,000A RMS Sym. (50,000A @ 300V DC) Agency Approvals: UL Listed - Special Purpose**, Guide JFHR, File E56412 CSA Certified (200,000 AIR), Class RK1 per CSA C22.2, No. 248.12, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class RK1 dimensional data. Catalog Numbers (250V AC/125V DC) * Current limitation for maximum short-circuit protection. High speed of response is highly sensitive to fault currents, but insensitive to starting current and transient surges. * Provides long time-delay for temporary motor start-up. * Time-delay permits 125% FLA sizing for back-up, motor running protection. Catalog Numbers (600V AC/300V DC) LPS-RK-SP LPS-RK-2TMSP LPS-RK-12SP LPS-RK-110SP LPS-RK-SP LPS-RK-2SP LPS-RK-15SP LPS-RK-125SP LPS-RK-SP LPS-RK-3SP LPS-RK-17TMSP LPS-RK-150SP LPS-RK-SP LPS-RK-3SP LPS-RK-20SP LPS-RK-175SP LPS-RK-TMSP LPS-RK-3TMSP LPS-RK-25SP LPS-RK-200SP LPS-RK-flSP LPS-RK-4SP LPS-RK-30SP LPS-RK-225SP LPS-RK-SP LPS-RK-4TMSP LPS-RK-35SP LPS-RK-250SP LPS-RK-1SP LPS-RK-5SP LPS-RK-40SP LPS-RK-300SP LPS-RK-1*SP LPS-RK-5flSP LPS-RK-45SP LPS-RK-350SP LPS-RK-1SP LPS-RK-6SP LPS-RK-50SP LPS-RK-400SP LPS-RK-1SP LPS-RK-6SP LPS-RK-60SP LPS-RK-450SP LPN-RK-SP LPN-RK-3TMSP LPN-RK-60SP LPS-RK-1TMSP LPS-RK-7SP LPS-RK-70SP LPS-RK-500SP LPN-RK-fiSP LPN-RK-4SP LPN-RK-70SP LPS-RK-1flSP LPS-RK-8SP LPS-RK-80SP LPS-RK-600SP LPN-RK-SP LPN-RK-4TMSP LPN-RK-80SP LPS-RK-1SP LPS-RK-9SP LPS-RK-90SP LPN-RK-SP LPN-RK-5SP LPN-RK-90SP LPS-RK-2SP LPS-RK-10SP LPS-RK-100SP LPN-RK-SP LPN-RK-5flSP LPN-RK-100SP **Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses. LPN-RK-TMSP LPN-RK-6SP LPN-RK-110SP LPN-RK-flSP LPN-RK-6SP LPN-RK-125SP LPN-RK-SP LPN-RK-8SP LPN-RK-150SP LPN-RK-1SP LPN-RK-9SP LPN-RK-175SP LPN-RK-1*SP LPN-RK-10SP LPN-RK-200SP LPN-RK-1SP LPN-RK-12SP LPN-RK-225SP LPN-RK-1SP LPN-RK-15SP LPN-RK-250SP LPN-RK-1flSP LPN-RK-17TMSP LPN-RK-300SP LPN-RK-1SP LPN-RK-20SP LPN-RK-350SP LPN-RK-2SP LPN-RK-25SP LPN-RK-400SP LPN-RK-2SP LPN-RK-30SP LPN-RK-450SP LPN-RK-2TMSP LPN-RK-35SP LPN-RK-500SP LPN-RK-2SP LPN-RK-40SP LPN-RK-600SP LPN-RK-3SP LPN-RK-45SP LPN-RK-3SP LPN-RK-50SP Carton Quantity and Weight LPN-RK (250 Volts AC) Ampere Ratings Carton Qty. LPS-RK (600 Volts AC) Weight* Lbs. 0.5 Weight* Kg Carton Qty. Lbs. Kg 0.227 10 1.6 0.725 0-30 10 35-60 10 1.2 0.544 10 2.6 1.178 70-100 5 1.5 0.680 5 4.0 1.814 110-200 1 0.69 0.313 1 2.0 0.906 225-400 1 1.75 0.793 1 4.6 2.086 450-600 1 3.25 1.474 1 5.6 2.540 *Weight per carton. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. **Meets all performance requirements of UL Standard 248-12 for Class RK1 fuses. 0-60 Amp fuses available with Albaloy plate option. 70-600 Amp fuses available with Tin plate option. BIF document: (LPN-RK) 1003 (0-60) & 1004 (70-600) BIF document: (LPS-RK) 1001 (0-60) & 1002 (70-600) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 7 (R) Electrical - Power Fuses Bussmann Low-Peak(R) Dual-Element, Time-Delay, Class RK1 Fuses Current Limitation Curves--LPN-RK (250V) -- Clip CU only 1 R25030-1 R60030-1 SR PR CR COR QR** to 2 R25030-2 R60030-2 SR PR CR COR QR** 30 3 R25030-3 R60030-3 SR PR CR COR QR** 1 1 R25060-1 R60060-1 SR* PR CR COR -- to 2 R25060-2 R60060-2 SR* PR CR COR -- 60 3 R25060-3 R60060-3 SR* PR CR COR -- 61 1 R25100-1 R60100-1 -- -- CR COR -- to 2 R25100-2 R60100-2 -- -- CR COR -- 100 3 R25100-3 R60100-3 -- -- CR COR -- to 200 1 R25200-1 R25200-3 R60200-1 R60200-3 -- -- -- -- CR CR COR -- -- -- to 400 1 R25400-1 R25400-3 R60400-1 R60400-3 -- -- -- -- CR* CR COR* -- -- -- to 600 1 R25600-1 R25600-3 R60600-1 R60600-3 -- -- -- -- CR CR -- -- -- -- *UL Recognized, No CSA Certification. **Quick connect not available on 600V blocks. B 400,000 AMPERE RATIN Pres. -- Plate QuickConnect 100,000 600 400 200 100 60 10,000 30 A 1,000 200,000 Box Lug w/ 100,000 Poles Screw w/ 10,000 Amps Catalog Number (250V) (600V) INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS Terminal Type (Suffix No.) 1,000 Recommended Fuseblocks for Class RK1 fuses RMS SYMMETRICAL CURRENTS IN AMPERES A-B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS) B AMPERE RATING 400,000 100,000 600 400 200 100 60 10,000 30 200,000 100,000 1,000 10,000 A 1,000 INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS Current Limitation Curves--LPS-RK (600V) RMS SYMMETRICAL CURRENTS IN AMPERES A-B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS) BIF document: (LPN-RK) 1003 (0-60) & 1004 (70-600), 1110 (Fuseblock) 8 BIF document: (LPS-RK) 1001 (0-60) & 1002 (70-600), 1111 (600V Fuseblock) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Low-Peak(R) Dual-Element, Time-Delay, Class RK1 Fuses Time-Current Characteristic Curves--Average Melt AMPERE RATING AMPERE RATING LPN-RK 250V TIME IN SECONDS TIME IN SECONDS LPS-RK 600V 61/4 10 2 32/10 11/4 / / / 1 16/10 21/2 4 5 8 12 AMPERE RATING 8 10 / 2 10 / / / / 3 10 4 10 1 10 15 100 AMPERE RATING LPN-RK 1 2 6 10 CURRENT IN AMPERES 6.25 2.5 1.25 .5 .2 .3 .4 .6 .8 1 1.6 2 3.2 4 5 8 10 12 300 .1 .15 CURRENT IN AMPERES LPS-RK 600V 250V 100 TIME IN SECONDS 1 CURRENT IN AMPERES 00 00 CURRENT IN AMPERES 10 .01 1 .1 .1 TIME IN SECONDS 10 BIF document: (LPN-RK) 1003 (0-60) & 1004 (70-600) BIF document: (LPS-RK) 1001 (0-60) & 1002 (70-600) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 9 (R) Electrical - Power Fuses Bussmann Fusetron(R) Dual-Element, Time-Delay, Class RK5 Fuses * Provides motor overload, ground fault and short-circuit protection. * Helps protect motors against burnout from overloads. * Helps protect motors against burnout from single phasing on three phase systems. * Simplifies and improves blackout prevention (selective coordination). Fuse Reducers For Class R Fuses Desired Fuse (Case) Size Equipment Fuse Clips 60A FRN-R (250V) Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current Ampere Ratings: -600 Amps. Voltage Rating: 250 Volts AC (or less), 125 Volts DC Current Limiting RK5 Fuse Interrupting Rating: 200,000A RMS Sym. (20,000A @ 125V DC) Agency Approvals: Std. 248-12, Class RK5 UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-01, File 53787 Dimensions: See pages 2-3 for Class RK5 dimensional data. 100A 200A 400A 600A Catalog Number (Pairs) 250V 30A No. 263-R 30A No. 213-R 60A No. 216-R 60A No. 226-R 100A No. 2621-R 100A No. 2641-R 200A No. 242-R 100A No. 2661-R 200A No. 2662-R 400A No. 2664-R* *Single reducer only (pair not required). Fuseblocks for Class R 250V Fuses (Clip Retaining Spring Standard, Suffix "R") Terminal Type (Suffix No.) Catalog Numbers (250V AC/125V DC) Basic Catalog Number FRN-R- FRN-R-2 FRN-R-10 FRN-R-100 FRN-R-* FRN-R-2 FRN-R-12 FRN-R-110 Amps 1 R25030-1 Poles Screw w/ -- Pres. Plate SR PR Box Lug w/ -- Clip CU only QuickConnect CR FRN-R-fi FRN-R-2TM FRN-R-15 FRN-R-125 COR QR FRN-R- FRN-R-2 FRN-R-17TM FRN-R-150 to 2 R25030-2 SR PR CR COR QR FRN-R-175 30 3 R25030-3 SR PR CR COR QR 1 R25060-1 SR -- CR COR -- -- FRN-R- FRN-R-3 FRN-R-20 FRN-R- FRN-R-3 FRN-R-25 FRN-R-200 31 FRN-R- FRN-R-3TM FRN-R-30 FRN-R-225 to 2 R25060-2 SR -- CR COR 3 R25060-3 SR -- CR COR -- FRN-R-TM FRN-R-4 FRN-R-35 FRN-R-250 60 FRN-R-fl FRN-R-4TM FRN-R-40 FRN-R-300 70 1 R25100-1 -- -- CR COR -- FRN-R- FRN-R-5 FRN-R-45 FRN-R-350 to 2 R25100-2 -- -- CR COR -- 100 3 R25100-3 -- -- CR COR -- 1 R25200-1 -- -- CR -- -- 3 R25200-3 -- -- CR -- -- FRN-R-1 FRN-R-5fl FRN-R-50 FRN-R-400 FRN-R-1* FRN-R-6 FRN-R-60 FRN-R-450 FRN-R-1 FRN-R-6 FRN-R-70 FRN-R-500 FRN-R-1 FRN-R-7 FRN-R-75 FRN-R-600 FRN-R-1TM FRN-R-7TM FRN-R-80 FRN-R-1fl FRN-R-8 FRN-R-85 FRN-R-1 FRN-R-9 to 400 to 600 FRN-R-90 Carton Quantity and Weight Ampere Ratings to 200 1 R25400-1 -- -- CR -- -- 3 R25400-3 -- -- CR -- -- 1 R25600-1 -- -- CR -- -- 3 R25600-3 -- -- CR -- -- Time-Current and Current Limitation Curves located on page 203. Weight* Carton Qty. Lbs. Kg. 0-15 10 0.40 0.181 17.5-30 10 .50 0.227 35-60 10 1.00 0.453 70-100 5 1.5 0.680 101-200 1 0.77 0.349 201-400 1 1.52 0.689 401-600 1 2.94 1.334 CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. *Weight per carton. BIF document: 1019 (0-60), 1020 (70-600) & 1110 (Fuseblock) 10 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Fusetron(R) Dual-Element, Time-Delay, Class RK5 Fuses FRS-R (600V) Fuse Reducers For Class R Fuses Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current Ampere Ratings: -600 Amps. Voltage Rating: 600 Volts AC (or less), 300 Volts DC Current Limiting RK5 Fuse Interrupting Rating: 200,000A RMS Sym. (20,000A @ 300V DC) Agency Approvals: Std. 248-12, Class RK5 UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class RK5 dimensional data. Catalog Numbers (600V AC/ 300V DC) Desired Fuse (Case) Size Equipment Fuse Clips 60A 100A 200A 400A 600A Catalog Number (Pairs) 600V 30A No. 663-R 30A No. 216-R 60A No. 616-R 60A No. 626-R 100A No. 2621-R 100A No. 2641-R 200A No. 642-R 100A No. 2661-R 200A No. 2662-R 400A No. 2664-R* *Single reducer only (pair not required). FRS-R- FRS-R-2 FRS-R-10 FRS-R-100 Fuseblocks for Class R 600V Fuses FRS-R-* FRS-R-2 FRS-R-12 FRS-R-110 (Clip Retaining Spring Standard, Suffix "R") FRS-R-fi FRS-R-2TM FRS-R-15 FRS-R-125 FRS-R- FRS-R-2 FRS-R-17TM FRS-R-150 FRS-R- FRS-R-3 FRS-R-20 FRS-R-175 FRS-R- FRS-R-3 FRS-R-25 FRS-R-200 Amps FRS-R- FRS-R-3TM FRS-R-30 FRS-R-225 FRS-R-TM FRS-R-4 FRS-R-35 FRS-R-250 Terminal Type (Suffix No.) Poles Basic Catalog Number 1 to 2 Screw w/ Box Lug w/ -- Pres. Plate -- Clip CU only R60030-1 SR PR CR COR R60030-2 SR PR CR COR 3 R60030-3 SR PR CR COR FRS-R-fl FRS-R-4TM FRS-R-40 FRS-R-275 30 FRS-R- FRS-R-5 FRS-R-45 FRS-R-300 31 1 R60060-1 SR -- CR COR FRS-R-1 FRS-R-5fl FRS-R-50 FRS-R-325 to 2 R60060-2 SR -- CR COR 3 R60060-3 SR -- CR COR FRS-R-1* FRS-R-6 FRS-R-60 FRS-R-350 60 FRS-R-1 FRS-R-6 FRS-R-70 FRS-R-400 65 1 R60100-1 -- -- CR COR 2 R60100-2 -- -- CR COR FRS-R-1 FRS-R-7 FRS-R-75 FRS-R-450 to FRS-R-1TM FRS-R-7TM FRS-R-80 FRS-R-500 100 3 R60100-3 -- -- CR COR FRS-R-1fl FRS-R-8 FRS-R-85 FRS-R-600 to 200 1 FRS-R-1 R60200-1 R60200-3 -- -- -- -- CR CR -- -- FRS-R-9 FRS-R-90 to 400 1 R60400-1 R60400-3 -- -- -- -- CR CR -- -- to 600 1 R60600-1 R60600-3 -- -- -- -- CR CR -- -- Carton Quantity and Weight Ampere Ratings Weight* Carton Qty. Lbs. Kg. 0-15 10 0.40 0.181 17.5-30 10 0.50 0.227 35-60 10 3.10 1.406 65-100 1 0.54 0.245 101-200 1 1.22 0.544 201-400 1 3.00 1.359 401-600 1 5.00 2.268 Time-Current and Current Limitation Curves located on page 204. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. *Weight per carton. BIF document: 1017 (0-60), 1018 (70-600) & 1111 (Fuseblock) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 11 (R) Electrical - Power Fuses Bussmann Dura-LagTM Dual-Element, Time-Delay, Class RK5 Fuses DLN-R (250V) DLS-R (600V) Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current Ampere Ratings: 1-600 Amps. Voltage Rating: 250 Volts AC (or less), 125V DC Current Limiting RK5 Fuses Interrupting Rating: 200,000A RMS Sym. (20,000A @125V DC) Agency Approvals: Std. 248-12, Class RK5 UL Listed, Guide JDDZ, File E4273 CSA C22.2, No. 106-HRCI-R, File 53787 Dimensions: See pages 2-3 for Class RK5 dimensional data. Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current Ampere Ratings: 1-600 Amps. Voltage Rating: 600 Volts AC (or less), 300V DC Current Limiting RK5 Fuses Interrupting Rating: 200,000A RMS Sym., (20,000A @ 300V DC) Agency Approvals: Std. 248-12, Class RK5 UL Listed, Guide JDDZ, File E4273 CSA C22.2, No. 106-HRCI-R Dimensions: See pages 2-3 for Class RK5 dimensional data. Catalog Numbers (250V AC/125V DC) Catalog Numbers (600V AC/300V DC) DLN-R-1 DLN-R-15 DLN-R-100 DLN-R-2 DLN-R-2TM DLN-R-20 DLN-R-25 DLN-R-125 DLN-R-150 DLN-R-3 DLN-R-3 DLN-R-30 DLN-R-35 DLN-R-175 DLN-R-200 DLN-R-4 DLN-R-5 DLN-R-6 DLN-R-40 DLN-R-45 DLN-R-50 DLN-R-225 DLN-R-250 DLN-R-300 DLN-R-6 DLN-R-8 DLN-R-60 DLN-R-70 DLN-R-400 DLN-R-600 DLN-R-10 DLN-R-12 DLN-R-80 DLN-R-90 Carton Quantity and Weight Ampere Ratings Weight* DLS-R-1 DLS-R-12 DLS-R-100 DLS-R-1fl DLS-R-2 DLS-R-2TM DLS-R-15 DLS-R-17TM DLS-R-20 DLS-R-110 DLS-R-125 DLS-R-150 DLS-R-3 DLS-R-3TM DLS-R-25 DLS-R-30 DLS-R-175 DLS-R-200 DLS-R-4 DLS-R-5 DLS-R-35 DLS-R-40 DLS-R-225 DLS-R-250 DLS-R-6 DLS-R-6 DLS-R-45 DLS-R-50 DLS-R-300 DLS-R-350 DLS-R-7 DLS-R-8 DLS-R-60 DLS-R-70 DLS-R-400 DLS-R-500 DLS-R-9 DLS-R-10 DLS-R-80 DLS-R-90 DLS-R-600 Carton Qty. Lbs. Kg. -30 10 0.56 0.252 35-60 10 1.38 0.621 Ampere Ratings 70-100 5 1.56 0.702 110-200 1 0.90 225-400 1 1.80 450-600 1 3.30 Lbs. Kg. -30 10 1.62 0.729 0.405 35-60 10 3.00 1.35 0.810 70-100 5 3.00 1.35 1.485 110-200 1 1.41 0.635 225-400 1 3.13 1.409 450-600 1 5.28 2.376 Recommended Fuseblocks for Class R 250V Fuses-- See pages 66-67. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. 12 Weight* Carton Qty. *Weight per carton. BIF document: 1021 (0-600) Carton Quantity and Weight *Weight per carton. Recommended Fuseblocks for Class R 600V Fuses-- See pages 68-69. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1022 (0-600) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Limitron(R) Fast Acting, Class RK1 Fuses KTN-R (250V) KTS-R (600V) Fast Acting Ampere Ratings: 1-600 Amps. Voltage Rating: 250 Volts AC (or less). Current Limiting RK1 Fuse (curves on page 205) Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-12, Class RK1 UL Listed, Guide JDDZ, File E54273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class RK1 dimensional data. Fast Acting Ampere Ratings: 1-600 Amps. Voltage Rating: 600 Volts AC (or less). Current Limiting RK1 Fuse (curves on page 206) Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-12, Class RK1 UL Listed, Guide JDDZ, File E54273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class RK1 dimensional data. Catalog Numbers (250V AC) Catalog Numbers (600V AC) KTN-R-1 KTN-R-2 KTN-R-30 KTN-R-35 KTN-R-125 KTN-R-150 KTS-R-1 KTS-R-30 KTS-R-125 KTS-R-2 KTS-R-35 KTS-R-150 KTN-R-3 KTN-R-4 KTN-R-40 KTN-R-45 KTN-R-175 KTN-R-200 KTS-R-3 KTS-R-4 KTS-R-40 KTS-R-45 KTS-R-175 KTS-R-200 KTN-R-5 KTN-R-6 KTN-R-50 KTN-R-60 KTN-R-225 KTN-R-250 KTS-R-5 KTS-R-6 KTS-R-50 KTS-R-60 KTS-R-225 KTS-R-250 KTN-R-8 KTN-R-10 KTN-R-70 KTN-R-75 KTN-R-300 KTN-R-350 KTS-R-8 KTS-R-10 KTS-R-70 KTS-R-75 KTS-R-300 KTS-R-350 KTN-R-12 KTN-R-15 KTN-R-80 KTN-R-90 KTN-R-400 KTN-R-450 KTS-R-12 KTS-R-15 KTS-R-80 KTS-R-90 KTS-R-400 KTS-R-450 KTN-R-20 KTN-R-25 KTN-R-100 KTN-R-110 KTN-R-500 KTN-R-600 KTS-R-20 KTS-R-25 KTS-R-100 KTS-R-110 KTS-R-500 KTS-R-600 Carton Quantity and Weight Carton Quantity and Weight Weight* Ampere Ratings Carton Qty. Lbs. Kg. 1-30 40-60 70-100 110-200 10 10 5 1 .45 1.82 1.85 1.05 0.204 0.824 0.838 0.476 225-400 450-600 1 1 2.38 3.50 1.078 1.587 Ampere Ratings Weight* Carton Qty. Lbs. Kg. 1-30 40-60 10 10 1.45 2.63 0.657 1.262 70-100 110-200 1 1 0.5 1.4 0.226 0.634 225-400 450-600 1 1 2.75 4.25 1.246 1.925 *Weight per carton. *Weight per carton. Recommended Fuseblocks for Class R 250V Fuses-- See pages 66-67. Recommended Fuseblocks for Class R 600V fuses-- See pages 68-69. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1043 (0-600) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 BIF document: 1044 (0-600) 13 (R) Electrical - Power Fuses Bussmann One-Time General Purpose Fuses NON and NOS General Purpose Application Non-Current Limiting Ampere Ratings: *-600 Amps. Voltage Rating: NON: 250 Volts AC, 125 Volts DC (0-100A); NOS: 600 Volts AC Interrupting Rating: 50,000A RMS Sym. (1-60A), 10,000A RMS Sym. (65-600A) 10,000A @ 125V DC (NON 0-100A) Agency Approvals: UL Listed - 250V: Class K5 (0-60A), Std. 248-9 Class H (65-600A), Std. 248-6 600V: Class K5 (0-60A), Std. 248-9 Class H (70-600A,) Std. 248-6 Guide JDDZ, File E4273 CSA Certified - 250V: (0-12, 65-600) 600V: (0-600) Class 1421-01, File 53787 Dimensions: See pages 2-3 for dimensional data under Class RK5/RK1. Catalog Numbers (250V AC) Recommended Fuse Reducers 250 Volt Clip Size 600 Volt Fuse Size Cat. No. (Pair) Weight Carton* (lbs) Clip Size Fuse Size Cat. No. (Pair) Weight Carton* (lbs) 60A 100A 30A 30A No. 263 No. 213 0.38 1.73 60A 100A 30A 30A No. 663 No. 216 1.00 1.73 100A 200A 200A 60A 60A 100A No. 216 No. 226 No. 2621 1.73 3.00 1.63 100A 200A 200A 60A 60A 100A No. 616 No. 626 No. 2621 1.85 3.33 1.63 400A 400A 100 200A No. 2641 No. 2642 4.90 3.50 400A 400A 100 200A No. 2641 No. 2642 4.90 3.50 600A 100A No. 2661 600A 200A No. 2662 600A 400A No. 2664 *Carton quantity--10 pair. 8.70 6.85 4.45 600A 600A 600A 100A 200A 400A No. 2661 No. 2662 No. 2664 8.70 6.85 4.45 NON-* NON-TM NON-5 NON-6 NON-40 NON-45 NON-175 NON-200 NON- NON- NON-1 NON-1 NON-6 NON-7 NON-8 NON-9 NON-50 NON-60 NON-65 NON-70 NON-225 NON-250 NON-300 NON-350 NON-1TM NON-1fl NON-2 NON-10 NON-12 NON-15 NON-75 NON-80 NON-90 NON-400 NON-450 NON-500 NOS-1 NOS-12 NOS-70 NOS-200 NOS-2 NOS-3 NOS-15 NOS-20 NOS-75 NOS-80 NOS-225 NOS-250 NON-2TM NON-3 NON-20 NON-25 NON-100 NON-110 NON-600 -- NON-3 NON-4 NON-30 NON-35 NON-125 NON-150 -- -- NOS-4 NOS-5 NOS-6 NOS-25 NOS-30 NOS-35 NOS-90 NOS-100 NOS-110 NOS-300 NOS-350 NOS-400 NOS-7 NOS-8 NOS-40 NOS-45 NOS-125 NOS-150 NOS-450 NOS-500 NOS-9 NOS-10 NOS-50 NOS-60 NOS-175 -- NOS-600 -- Carton Quantity and Weight Ampere Ratings NON NON NON NON NON NON Weight* Carton Qty. Lbs. Kg. 10 10 5 1 1 1 0.38 1.00 0.79 0.79 1.65 2.76 0.172 0.453 0.358 0.358 0.748 1.25 *-30 35-60 65-100 110-200 225-400 450-600 *Weight per carton. Catalog Symbol & Current Ratings Carton Quantity and Weight Ampere Ratings Weight* Carton Qty. Lbs. Kg. NOS 1-30 NOS 35-60 10 10 1.45 2.6 0.657 1.179 NOS NOS NOS NOS 5 1 1 1 2.80 1.24 3.03 4.63 1.270 0.562 1.374 2.100 70-100 110-200 225-400 450-600 *Weight per carton. Symbol Rating Class Volt IR NON 0-60 70-600 K5 H 250AC 250AC 50,000 10,000 0-100 0-60 70-600 H K5 H 125DC 600 600 10,000 50,000 10,000 NOS Catalog Numbers (600V AC) CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1030 14 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Low-Peak(R) Dual-Element, Time-Delay, Class J Fuses LPJ_SP 600 10A 15A 20A 30A 40A 50A 60A 100 125 200 225 400 5A 300 3A 1A Time-Current Classification Curves--Average Melt AMPERE RATING 100 10 TIME IN SECONDS Dual-Element, Time-Delay - 10 seconds (minimum) at 500% rated current Ampere Ratings: 1-600 Amps. Voltage Rating: 600 Volts AC (or less), 300V DC (110-200A) Current Limiting Interrupting Rating: AC - 300,000A RMS Sym. DC - 20,000A Agency Approvals: UL Listed - Special Purpose**, Guide JFHR, File E56412 CSA Certified (200,000 AIR) Class J per CSA-22.2 No. 248.8, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class J dimensional data. 1 .1 Catalog Numbers LPJ-1SP LPJ-4TMSP LPJ-25SP LPJ-1SP LPJ-5SP LPJ-30SP LPJ-150SP LPJ-1flSP LPJ-5flSP LPJ-35SP LPJ-175SP LPJ-1SP LPJ-6SP LPJ-40SP LPJ-200SP LPJ-2SP LPJ-7SP LPJ-45SP LPJ-225SP LPJ-2SP LPJ-8SP LPJ-50SP LPJ-250SP LPJ-2TMSP LPJ-9SP LPJ-60SP LPJ-300SP LPJ-2SP LPJ-10SP LPJ-70SP LPJ-350SP LPJ-3SP LPJ-12SP LPJ-80SP LPJ-400SP LPJ-3SP LPJ-15SP LPJ-90SP LPJ-450SP LPJ-3TMSP LPJ-17TMSP LPJ-100SP LPJ-500SP LPJ-4SP LPJ-20SP LPJ-110SP LPJ-600SP 0.49 35-60 10 1.78 0.81 70-100 5 1.69 0.77 110-200 5 4.21 1.91 225-400 1 1.67 0.76 450-600 1 2.80 0.27 *Weight per carton. See pages 70-71 for Class J recommended fuseblocks. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. 10 000 1,000 10 1 10,000 AMPERE RATIN 1.09 1,000 A 100 000 Kg. 10 000 Lbs. 0-30 600 400 200 100 60 50 40 30 20 15 000 Weight* Carton Qty. B 100,000 000 Ampere Ratings LPJ Current Limitation Curves 100 Carton Quantity and Weight RMS SYMMETRICAL CURRENT IN AMPERES Current Limitation Curves INSTANTANEOUS PEAK LET-THRU CURRENT IN AMPS **Meets all performance requirements of UL Standard 248-8 for Class J fuses. Available with silver plated terminals. Add SP/ in front of part number. .01 100 LPJ-125SP BIF document: 1006 (0-60) and 1007 (70-600) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 15 (R) Electrical - Power Fuses Bussmann Limitron(R) Quick Acting, Class J Fuses JKS Quick Acting Ampere Ratings: 1-600 Amps. Voltage Rating: 600 Volts AC (or less) Current Limiting Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-8, Class J UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class J dimensional data. Catalog Numbers Mounting Box Screws with Pressure Plate Copper Only Aluminum Panel JP60030-3PR (#10-14 Cu Wire) JP60030-3CR (#2-8 Al or #2-14 Cu) JP60030-3COR (#2-14 Cu) With DIN-Rail Adapter* JP60030-3PRA (#10-14 Cu Wire) JP60030-CRA (#2-8 Al or #2-14 Cu) JP60030-CORA (#2-14 Cu) JKS-70 JKS-225 JKS-2 JKS-20 JKS-80 JKS-250 JKS-3 JKS-25 JKS-90 JKS-300 JKS-4 JKS-30 JKS-100 JKS-350 JKS-5 JKS-35 JKS-110 JKS-400 JKS-6 JKS-40 JKS-125 JKS-450 JKS-45 JKS-150 JKS-10 JKS-50 JKS-175 JKS-12 JKS-60 JKS-200 JKS-500 BIF document: 1108 Standard Class J Fuseblocks Catalog Numbers Amps JKS-600 Weight* 70-100 Kg. 0.43 0.53 0.13 0.39 0.81 1.39 Box Lug Box Lug w/ Retaining Clip Max. Wire Size 2 J60030-2S J60030-2P J60030-2C J60030-2CR S, P, #10 Cu C #2 Cu Al 3 J60030-3S J60030-3P J60030-3C J60030-3CR Carton Quantity and Weight Lbs. 0.95 1.175 0.28 0.86 1.78 3.07 Pressure Plate Screw 1 J60030-1S J60030-1P J60030-1C J60030-1CR 1-30 35-60 Carton Qty. 10 10 5 1 1 1 Poles JKS-15 Ampere Ratings 1-30 35-60 70-100 110-200 225-400 450-600 Catalog Numbers *Adapter Only: Cat. No. JPA-3 (for use with 35mm symmetrical DIN-Rail). JKS-1 JKS-8 Recommended Fuseblocks for Class J Fuses Pyramid J Fuseblock; 30A, 600V; 3-Pole; Panel or 35mm DIN-Rail Mount 110-200 225-400 450-600 1 -- -- 2 -- -- J60060-1C J60060-1CR J60060-2C J60060-2CR 3 -- -- J60060-3C J60060-3CR 3 -- -- -- J60100-3CR 1 -- -- -- J60200-1CR 3 -- -- -- J60200-3CR 1 -- -- -- J60400-1CR 3 -- -- -- J60400-3CR 1 -- -- -- J60600-1CR 3 -- -- -- J60600-3CR #2 Cu Al 1/0 Cu Al 250 MCM Cu Al 500 MCM Cu Al (2) 500 MCM Cu Al BIF document: 1114 *Weight per carton. Fuse Reducers for J Dimension Fuses CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. Clip Size 60A Fuse Size 30A Cat. No. (Pair) J63 Weight Carton* (lbs) 0.38 Clip Size 400A Fuse Size 100A Cat. No. (Pair) J41 100A 30A J13 1.73 400A 200A J42 2.75 100A 60A J16 1.85 600A 400A J64 3.55 200A 60A J26 2.55 600A 200A J62 3.55 200A 100A J21 1.36 -- -- -- *Carton quantity--10 pair. BIF document: 1026 (1-60A), 1027 (70-600A) 16 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 Weight Carton* (lbs) 4.90 -- (R) Electrical - Power Fuses Bussmann T-Tron(R) Very Fast Acting, Class T Fuses JJN JJS Very Fast Acting Ampere Ratings: 1-1200 Amps. Voltage Rating: 300 Volts AC (or less), (15-600A 160V DC) Current Limiting (curves on page 208) Interrupting Rating: 200,000A RMS Sym. (20,000A DC @ 160V DC) Agency Approvals: Std. 248-15, Class T UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class T dimensional data. Very Fast Acting Ampere Ratings: 1-800 Amps. Voltage Rating: 600 Volts AC (or less) Current Limiting (curves on page 208) Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-15, Class T UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-02, File 53787 Dimensions: See pages 2-3 for Class T dimensional data. Catalog Numbers Catalog Numbers JJN-1 JJN-35 JJN-110 JJN-400 JJS-1 JJS-30 JJS-90 JJS-250 JJN-2 JJN-3 JJN-40 JJN-45 JJN-125 JJN-150 JJN-450 JJN-500 JJS-2 JJS-3 JJS-35 JJS-40 JJS-100 JJS-110 JJS-300 JJS-350 JJN-6 JJN-50 JJN-175 JJN-600 JJS-6 JJS-45 JJS-125 JJS-400 JJN-10 JJN-15 JJN-60 JJN-70 JJN-200 JJN-225 JJN-700 JJN-800 JJS-10 JJS-15 JJS-50 JJS-60 JJS-150 JJS-175 JJS-450 JJS-500 JJN-20 JJN-25 JJN-80 JJN-90 JJN-250 JJN-300 JJN-1000 JJN-1200 JJS-20 JJS-25 JJS-70 JJS-80 JJS-200 JJS-225 JJS-600 JJS-800 JJN-30 JJN-100 JJN-350 Carton Quantity and Weight Carton Quantity and Weight Ampere Ratings Lbs. Kg. Ampere Ratings 1-30 Weight* Carton Qty. Weight* Carton Qty. 10 Lbs. 0.33 Kg. 0.149 1-30 35-60 10 10 0.12 0.23 0.054 0.104 35-60 70-100 10 5 0.82 0.51 0.371 0.231 70-100 110-200 225-400 5 1 1 0.36 0.14 0.25 0.163 0.063 0.113 110-200 225-400 450-600 1 1 1 0.192 0.46 0.85 0.087 0.208 0.385 450-600 700-800 1 1 0.44 0.80 0.200 0.363 800 1 1.65 0.748 1000-1200 1 1.45 0.658 *Weight per carton. *Weight per carton. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. CE logo denotes compliance with European Union Low Voltage Directive (50-1000 VAC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1025 BIF document: 1029 Standard Class T Fuseblocks (300V) Catalog Data Standard Class T Fuseblocks (600V) Catalog Data Catalog Numbers Amps Poles Screw TM to 2 3 30 31 Catalog Numbers Box Lug Amps T30030-2SR T30030-3SR T30030-2CR T30030-3CR 4 2 T30030-4SR T30060-2SR T30030-4CR T30060-2CR to 60 3 4 T30060-3SR T30060-4SR T30060-3CR T30060-4CR 61 to 100 101 to 200 201 to 400 401 to 600 1 2 3 1 3 1 1 -- -- -- -- -- -- -- T30100-1CR T30100-2CR T30100-3CR T30200-1C T30200-3C T30400-1C T30600-1C Poles Screw TM to 30 1 2 3 T60030-1SR T60030-2SR T60030-3SR T60030-1CR T60030-2CR T60030-3CR Box Lug 31 to 1 2 T60060-1SR T60060-2SR T60060-1CR T60060-2CR 60 61 to 100 101 to 200 201 to 400 3 1 2 3 1 3 1 T60060-3SR -- -- -- -- -- -- T60060-3CR T60100-1C T60100-2C T60100-3C T60200-1C 1B0089 T60400-1C 401 to 600 1 -- T60600-1C BIF document: 1115 (300V Fuseblock) and 1116 (600V Fuseblock) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 17 (R) Electrical - Power Fuses Bussmann Time-Delay Class G Fuses Physical Size: Fuse (Amps) A (Length) (Length) SC-TM to -15 1.319 SC-20 1.419 SC-25 to -30 1.639 SC-35 to -60 2.259 .41" (10.3mm) SC Fast Acting (0-6A), Class G Time-Delay (7-60A), Class G Construction: Melamine Tube Ampere Ratings: TM-60A Voltage Rating: 0-20A: 600V AC/170V DC or less Interrupting Rating: 100,000A RMS Sym., 10,000A DC Agency Approvals: Std. 248-5, Class G, UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-01, File 53787 SC-1TM SC-8 SC-35 * Compact branch-circuit units with high interrupting rating and current limitation. * With a 600 volt rating, they can be used in 120/208, 120/240 and 277/480 volt circuits. * Length variations relative to case size make the "rejection" type fuses. * In general, SC fuses are about TM the size of the 600 V NEC fuse type. * SC fuses with ampere ratings above 6 amps have a degree of overload time-delay which permits them to pass temporary overloads. At 200% load, they have a minimum opening time of 12 seconds. SC-2 SC-9 SC-40 Standard SC Fuseblocks Catalog Data SC-2TM SC-10 SC-45 SC-3 SC-12 SC-50 SC-4 SC-15 SC-60 SC-5 SC-20 -- Catalog Symbol & Current Ratings SC-TM SC-6 SC-25 SC-1 SC-7 SC-30 Carton Quantity and Weight Ampere Ratings Carton Qty. Weight* Lbs. Kg. Terminal Type Poles Screw With Quick Connect Pressure Plate w/Quick Connect Box Lug Box Lug w/Retaining Clip TM 1 BG3011SQ BG3011PQ BG3011B -- to 2 BG3012SQ BG3012PQ BG3012B -- 15 3 BG3013SQ BG3013PQ BG3013B -- 1 BG3021SQ BG3021PQ BG3021B -- 2 BG3022SQ BG3022PQ BG3022B -- Amps 20 TM-15 4 0.06 0.03 20 4 0.06 0.03 3 BG3023SQ BG3023PQ BG3023B -- 25-30 2 0.04 0.02 25 1 BG3031S BG3031P BG3031B -- 36-60 2 0.08 0.03 to 2 BG3032S BG3032P BG3032B -- 30 3 BG3033S BG3033P BG3033B 35 1 -- -- to 2 -- 60 3 -- *Weight per carton. Panel-mount Fuseholders for SC Fuses Description Catalog Number Fuse Size Terminal Type HPF-EE 1-15A Solder (w/o leads) HPF-FEE 1-15A Leads; 10 #18 copper insul. wire HPF-JJ 20A Solder (w/o leads) HPF-FF 25-30A Solder (w/o leads) HPS-EE 1-15A Solder (w/o leads) G30060-1CR -- -- G30060-2CR -- G30060-3C G30060-3CR CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1024 (0-60) and 1106 (Fuseblock) 18 -- -- For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Low-Peak(R) Time-Delay, Class CC Fuses 20 25 30 3 3TM 4 4TM 6 8 10 12 15 TM fl 1 1 Time Current Characteristics--Average Melt AMPERE RATING 200 100 10 LP-CC Low-Peak Fuse Time-Delay Current Limiting, Class CC - Rejection Type Physical Size: TM 1TM (10.3mm 38.1mm) Ampere Ratings: TM - 30 Amps. Voltage Rating: 600 Volts AC (or less), 300V DC (TM-2A & 20-30A), 150V DC (3-15A) Interrupting Rating: 200,000A RMS Sym; 20,000A DC Construction: Melamine Tube Agency Approvals: Std. 248-4, Class CC UL Listed, Guide JDDZ, File E4273 CSA Certified; Class 1422-02, File 53787 TIME IN SECONDS (R) 1 .1 Catalog Symbol LP-CC-3 LP-CC-9 LP-CC-1 LP-CC-3 LP-CC-10 LP-CC-1* LP-CC-3TM LP-CC-12 LP-CC-1 LP-CC-4 LP-CC-15 LP-CC-1 LP-CC-4TM LP-CC-20 LP-CC-1TM LP-CC-5 LP-CC-25 LP-CC-1fl LP-CC-5fl LP-CC-30 LP-CC-1 .01 1000 LP-CC-8 LP-CC- 100 LP-CC-7TM LP-CC-2 10 LP-CC-2TM LP-CC-fl 1 LP-CC-TM .4 600 Volts AC CURRENT IN AMPERES Current-Limiting Effects Prospective ShortCircuit Current *Let-Thru Current (Apparent RMS Symmetrical) 1 A 2A 15A 25A 30A 1000 100 135 240 305 380 435 LP-CC-6 3000 140 210 350 440 575 580 LP-CC-2 LP-CC-6 5000 165 255 420 570 690 710 LP-CC-2 LP-CC-7 10,000 210 340 540 700 870 1,000 20,000 260 435 680 870 1,090 1,305 30,000 290 525 800 1,030 1,300 1,520 40,000 315 610 870 1,150 1,390 1,700 50,000 340 650 915 1,215 1,520 1,820 60,000 350 735 1,050 1,300 1,650 1,980 80,000 390 785 1,130 1,500 1,780 2,180 100,000 420 830 1,210 1,600 2,000 2,400 200,000 525 1,100 1,600 2,000 2,520 3,050 Recommended Fuseblocks for Class CC Fuses No. of Poles Screw Terminal Pressure Plate 1 BC6031S BC6031P Screw Box Terminal BC6031B Pressure QuickConnect BC6031SQ QuickConnect BC6031PQ 2 BC6032S BC6032P BC6032B BC6032SQ BC6032PQ 3 BC6033S BC6033P BC6033B BC6033SQ BC6033PQ 20A *RMS Symmetrical Amperes Short-Circuit NOTE: To calculate Ip (Ipeak) multiply IRMS value 2.3. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1023 (0-30) and 1105 (Fuseblock) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 19 (R) Electrical - Power Fuses Bussmann Class CC Rejection-Type Fuses FNQ-R KTK-R Limitron(R) Fuse Time-Delay, Rejection Type Branch Circuit Fuse Class CC Physical Size: TM 1TM (10.3mm 38.1mm) Construction: Melamine Tube Ampere Ratings: -30 Amps. Voltage Rating: 600V AC or less Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-4, Class CC UL Listed, Guide JDDZ, File E4273 CSA Certified, Class 1422-01, File 53787 Fast Acting; Branch Circuit Fuse Class CC - Rejection Feature Physical Size: TM 1TM (10.3mm 38.1mm) Construction: Melamine Tube Ampere Ratings: -30 Amps. Voltage Rating: 600 Volts AC (or less). Interrupting Rating: 200,000A RMS Sym. Agency Approvals: Std. 248-4, Class CC UL Listed, Guide JDDZ, File E4273 CSA Certified, File 53787, Class 1422-02 Catalog Symbol & Current Ratings 600 Volts AC Catalog Symbol & Current Ratings KTK-R- KTK-R-1 KTK-R-7 FNQ-R- FNQ-R-1TM FNQ-R-6 KTK-R-* KTK-R-1TM KTK-R-8 FNQ-R- FNQ-R-1fl FNQ-R-6 KTK-R- KTK-R-2 KTK-R-9 FNQ-R- FNQ-R-1 FNQ-R-7 KTK-R- KTK-R-2TM KTK-R-10 FNQ-R-TM FNQ-R-2 FNQ-R-7TM KTK-R- KTK-R-3 KTK-R-12 FNQ-R-fl FNQ-R-2 FNQ-R-8 KTK-R- KTK-R-3TM KTK-R-15 FNQ-R- FNQ-R-2TM FNQ-R-9 KTK-R-TM KTK-R-4 KTK-R-20 FNQ-R- FQN-R-2 FNQ-R-10 KTK-R-fl KTK-R-5 KTK-R-25 FNQ-R-1 FNQ-R-3 FNQ-R-12 KTK-R- KTK-R-6 KTK-R-30 FNQ-R-1* FNQ-R-3 FNQ-R-15 FNQ-R-1 FNQ-R-3TM FNQ-R-20 FNQ-R-1 FNQ-R-4 FNQ-R-25 FNQ-R-1 FNQ-R-5 FNQ-R-30 600 Volts AC Time-Current and Current Limitation Curves on page 209. Time-Current and Current Limitation Curves on page 210. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1014 BIF document: 1015 Recommended Fuseblocks for Class CC Fuses Screw Box Terminal Pressure QuickConnect No. of Poles Screw Terminal Pressure Plate QuickConnect 1 BC6031S BC6031P BC6031B BC6031SQ BC6031PQ 2 BC6032S BC6032P BC6032B BC6032SQ BC6032PQ 3 BC6033S BC6033P BC6033B BC6033SQ BC6033PQ BIF document: 1105 20 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann TM 1* Supplementary Fuses BBS KTQ Fast Acting Physical Size: TM 1* (10.3mm 35mm) Construction: Fibre Cartridge Interrupting Rating: 10,000A RMS Sym. Ampere Ratings: -30A Voltage Rating: 600V AC (-5A), 250V AC (6-10A), 48V AC (12-30A) Agency Approvals: Std. 248-14 UL Listed, 0-5A/600V, Guide JDYX, File E19180 CSA Certified, 0-5A/600V, Class 1422-01, File 53787 Fast Acting Physical Size: TM 1* (10.3mm 34.9mm) Construction: Fibre Cartridge Ampere Ratings: 1-6A Voltage Rating: 600V AC Interrupting Rating: 10,000A RMS Sym. Agency Approvals: Std. 248-14 UL Recognized, 4-6A, Guide JDYX2, File E19180 600 Volts AC KTQ-1 Catalog Symbol & Current Ratings 600 Volts AC BBS- BBS- BBS- BBS- BBS-TM BBS-fl BBS- BBS- BBS-1 BBS-1TM BBS-1fl BBS-1 BBS-2 BBS-3 BBS-4 BBS-5 250 Volts AC BBS-6 BBS-7 BBS-8 BBS-10 -- -- -- -- -- -- -- -- -- -- -- -- Catalog Symbol & Current Ratings 48 Volts AC BBS-12 BBS-15 BBS-20 BBS-25 BBS-30 -- -- -- -- -- -- -- -- -- -- -- KTQ-1fl KTQ-2 KTQ-3 KTQ-4 KTQ-5 KTQ-6 Recommended Fuseblocks Amps Poles Terminal Type Screw with Quick Connect Amps Poles Box Lug 1 BM6031SQ BM6031PQ BM6031B to 2 BM6032SQ BM6032PQ BM6032B 30 3 BM6033SQ BM6033PQ Recommended Fuseblocks Terminal Type Screw with Quick Connect Pressure Plate w/ Quick Connect BM6033B BIF document: 1104 Pressure Plate w/ Quick Connect Box Lug 1 BM6031SQ BM6031PQ BM6031B to 2 BM6032SQ BM6032PQ BM6032B 30 3 BM6033SQ BM6033PQ BM6033B CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 2010 (0-30A) and 1104 (Fuseblock) BIF document: 2045 and 1104 (Fuseblock) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 21 (R) Bussmann Electrical - Power Fuses TM 1TM Supplementary Fuses BAF BAN KTK and KLM Fast Acting Physical Size: TM 1TM (10.3mm 38.1mm) Construction: Fibre Tube; Albaloy Plated Brass Endcaps Voltage Rating: 250V AC (-15A), 125V AC (20-30A) Interrupting Rating: 10,000A at 125V AC Agency Approvals: Std. 248-14 UL 0-15/250V, Guide JDYX, File E19180 CSA Certified, 0-15/250V, Class 1422-01, File 53787 Fast Acting Physical Size: TM 1TM (10.3mm 38.1mm) Construction: Fibre Tube Voltage Rating: 250V AC Interrupting Ratings: 35A (0-1A), 100A (1TM-3A), 200A (4-8A), 750A (10-15A), 10,000A (20-30A) Fast Acting Physical Size: TM 1TM (10.3mm 38.1mm) Construction: Melamine Tube; Albaloy Plated Brass Endcaps Voltage Rating: KTK - 600V AC or less KLM - 500V AC/DC or less (0-10A @ 500V DC, 12-30A @ 600V DC) Interrupting Rating: 100,000A - KTK; 10,000A - KLM, RMS SYM. (UL) Agency Approvals: Std. 248-14 KTK-UL Listed, Guide JDYX, File E19180 KLM-UL Recognized, Guide JFHR2, File E56412 CSA Certified, File 53787, Class 1422-01, HRC-Misc Catalog Symbol & Current Ratings Catalog Symbol & Current Ratings 250 Volts IR* BAF- 250 Volts IR* BAF-1TM 250 Volts IR* BAF-6 BAF- BAF-1 BAF-7 BAF-TM BAF-fl IR IR BAF-2 100A BAF-8 35A BAF-2TM BAF-9 BAF- BAF-3 BAF-1 BAF-4 -- BAF-5 -- BAF-6 125 Volts BAF-20 250 Volts 250 Volts 250 Volts 250 Volts BAN-1 BAN-5 BAN-12 BAN-30 BAN-2 BAN-6 BAN-15 -- BAN-3 BAN-8 BAN-20 -- BAN-4 BAN-10 BAN-25 -- Recommended Fuseblocks Amps Poles Terminal Type Screw Pressure with Plate w/ Quick Quick Connect Connect 1 BM6031SQ BM6031PQ BM6031B to 2 BM6032SQ BM6032PQ BM6032B 30 3 BM6033SQ BM6033PQ BM6033B IR BAF-25 10000A IR 200A BAF-30 -- BAF-10 -- IR BAF-12 750A -- IR -- 200A BAF-15 -- -- Box Lug Catalog Symbol & Current Ratings 600 Volts AC - UL Listed and C.S.A. KTK- KTK- KTK-4 KTK-12 KTK-* KTK-1 KTK-5 KTK-15 KTK- KTK-1 KTK-6 KTK-20 KTK- KTK-1TM KTK-7 KTK-25 Recommended Fuseblocks KTK- KTK-2 KTK-7TM KTK-30 Terminal Type Screw Pressure with Plate w/ Quick Quick Connect Connect KTK- KTK-2TM KTK-8 -- KTK-TM KTK-3 KTK-9 -- KTK-fl KTK-3TM KTK-10 -- *All have interrupting rating of 10,000A at 125V. Amps Poles Box Lug 1 BM6031SQ BM6031PQ BM6031B to 2 BM6032SQ BM6032PQ BM6032B 30 3 BM6033SQ BM6033PQ BM6033B 500 Volts AC/DC - UL Recognized and C.S.A. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 2011 (0-30) and 1104 (Fuseblock) 22 KLM- KLM-TM KLM-3 KLM-10 KLM-* KLM- KLM-4 KLM-15 KLM- KLM-1 KLM-5 KLM-20 KLM- KLM-1TM KLM-6 KLM-25 KLM- KLM-2 KLM-8 KLM-30 CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 2046 (0-30) and 1104 (Fuseblock) BIF document: KTK-1011 KLM-2020 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann TM 1TM Supplementary Fuses FNM Fusetron(R) Fuse FNQ Time-Delay Physical Size: TM 1TM (5 AG) (10.3mm 38.1mm) Construction: Fibre Tube Ampere Ratings: - 30 Amps. Voltage Rating: 250 Volts AC (or less). Interrupting Rating: See Table Below. Agency Approvals: Std. 248-14 UL Listed, 0-10/250V; 12-15/125V; File E19180, Guide JDYX CSA Certified, 1-10/250V; Class 1422-01, 12-15/125V; File 53787 Time-Delay Physical Size: TM 1TM (5 AG) (10.3mm 38.1mm) Construction: Fibre Tube Ampere Ratings: - 30 Amps. Voltage Rating: 500V AC or less Interrupting Rating: 10,000A RMS Sym. Agency Approvals: Std. 248-14 UL Listed, Guide JDYX, File E19180 CSA Certified, Class 1422-01, File 53787 Catalog Symbol & Current Ratings 500 Volts AC 250 Volts AC FNM- FNM-* FNM-fi FNM- FNM- FNM- FNM- FNM-TM FNM-fl FNM- FNM- FNM-1 -- 250 Volts AC IR 35A @ 250V AC 10,000A @ 125V AC IR FNM-4 FNM-4TM FNM-5 FNM-5fl FNM-6 FNM-6 FNM-7 FNM-8 FNM-9 FNM-10 200A @ 250V AC 10,000A @ 125V AC 250 Volts AC FNM-1* FNM-1 FNM-1 FNM-1TM FNM-1fl FNM-1 FNM-2 FNM-2 FNM-2TM FNM-2 FNM-3 FNM-3 FNM-3TM 125 Volts AC FNM-12 FNM-15 -- -- 32 Volts AC FNM-20 FNM-25 FNM-30 -- -- IR 100A @ 250V AC 10,000A @ 125V AC IR Catalog Symbol & Current Ratings FNQ- FNQ- FNQ-3 FNQ-8 FNQ-* FNQ-1 FNQ-3TM FNQ-9 FNQ-fi FNQ-1* FNQ-4 FNQ-10 FNA- FNQ-1 FNQ-4TM FNQ-12 FNQ- FNQ-1TM FNQ-5 FNQ-14 FNQ- FNQ-1fl FNQ-5fl FNQ-15 FNQ- FNQ-2 FNQ-6 FNQ-20 FNQ- FNQ-2 FNQ-6 FNQ-25 FNQ-TM FNQ-2TM FNQ-7 FNQ-30 FNQ-fl FNQ-3 -- -- CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. 10,000A @ 125V AC CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 2028 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 BIF document: 1012 23 (R) Bussmann Electrical - Power Fuses Plug Fuses W Series SL and TL Series S and T Series Fast Acting Ampere Ratings: TM - 30 Amps Voltage Rating: 125V AC Element is a simple fusible, metal link. For general purpose circuit protection. Quickly opens when short-circuit or overload occurs. Use for lighting and other non-motor circuits. Edison base. Agency Approvals: Std. 248-11 UL Listed, Guide JEFV, File E12112 Time-Delay, Loaded Link Ampere Ratings: 15 - 30 Amps Voltage Rating: 125V AC Heat absorbing metal bead on element link for time-delay. Passes motor overload starting currents without needlessly opening. Edison base (TL), Rejection base (SL). Agency Approvals: Std. 248-11 UL Listed, Guide JEFV, File E12112 Time-Delay, Dual-Element Ampere Ratings: Type S: - 30 Amps Type T: - 30 Amps Voltage Rating: 125V AC For all-purpose application. Like two fuses in one. A simple link element for short-circuits and dangerous overloads plus a series-connected element which lets the harmless overload starting currents of motors pass without opening. Uses less energy; operates cooler; provides superior protection. Edison base (T), Rejection base (S). Agency Approvals: Std. 248-11 Type S: UL Listed (0-6) Guide JFHR, File E56412 (7-30A) Guide JEFV, File E12112; CSA Certified, Class 1423-01, File 53787 Type W W-TM W-4 W-10 W-1 W-5 W-12 W-1 W-2 W-6 W-6TM W-15 W-20 W-2TM W-3 W-7 W-8 W-25 W-30 Type SL SL-15 Type TL TL-15 SL-20 SL-25 TL-20 TL-25 SL-30 TL-30 CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. Type S S- S- S- S-TM S-fl S- S-1 S-1* S-1 S-1 S-1fl S-1 S-2 S-2 S-2TM S-2 S-3 S-3 S-3TM S-4 S-4TM S-5 S-5fl S-6 S-6 S-7 S-8 S-9 S-10 S-12 S-14 S-15 S-20 S-25 S-30 Type T T- T- T-TM T-fl T- T-1 T-1* T-1 T-1 T-1fl T-1 T-2 T-2 T-2TM T-2 T-3 T-3 T-3TM T-4 T-4TM T-5 T-5fl T-6 T-6 T-7 T-8 T-9 T-10 T-12 T-14 T-15 T-20 T-25 T-30 CE logo denotes compliance with European Union Low Voltage Directive (50-1000V AC, 75-1500V DC). Refer to BIF document #8002 or contact Bussmann Application Engineering at 636-527-1270 for more information. BIF document: 1036 24 BIF document: 1033 (SL) & 1035 (TL) BIF document: 1032 (S) & 1034 (T) For complete specification data, call Bussmann Information Fax ~ 636.527.1450 (R) Electrical - Power Fuses Bussmann Plug Fuses Dual-Element Fustat(R) Fuses and Adaptors for Small Motor Protection. (Both Motor Running and Short-Circuit Protection) Fuses Cat No. Adapter Cat. No. Other Accepted Ampere Ratings S, STM, S S, Sfl, S1 SA1 1 amp and Smaller S1*, S1 SA1 All smaller Fustat Fuse Adaptors S1, S1fl SA1fl All smaller Fustat Adaptors (various ampere ratings) screw into the "Edison" Thread fuse sockets of standard household fuse boxes. Adaptors serve the purpose of preventing the wrong size fuse from being used. S1, S2 SA2 S2, S2TM SA2TM 1, 2 S2, S3, S3 SA3 1, 2, 2, 2TM S3TM, S4 SA4 S4TM, S5 SA5 3TM, 4 S5fl, S6 SA6 3TM, 4, 4TM, 5 S7, S8 SA8 S9, S10 SA10 7, 8 S12, S14 SA15 7, 8, 9, 10 Catalog Number Symbol and Amperes SA(Branch Circuits) 15, 20, 30 SA(Single Motor Circuits) 1, 1, 1fl, 2, 2TM, 3, 4, 5, 6, 8, 10 EDA Edison base dummy ENA Edison base neutral Carton Qty. 4 Wt. 0.03 (lbs) -- -- -- Branch Circuit Protection S15 SA15 -- S20 SA20 -- S25 SA30 S30 SA30 For complete specification data, call Bussmann Information Fax ~ 636.527.1450 -- 20, 25, 30 25 (R) Electrical - Power Fuses Bussmann Cable Limiters & Welder Limiters K Series 68000 & 64000 Series Cable Limiters Interrupting Rating: 200,000 Amps., 600 Volts AC RMS Symmetrical Welder Limiters for Class H and J Fuseholders Voltage Rating: 600 Volts AC or less Interrupting Rating: 200,000 Amps RMS Symmetrical Catalog Symbol & Current Ratings Copper Cable Limiter -- 600 Volts Catalog Symbol Cable Size Catalog Symbol Cable Size Type Fuseholder Tubular Terminals KCY #4 KCF 4/0 KCZ #3 KCH 250 MCM KCA #2 KCJ 350 MCM KCB #1 KCM 500 MCM KCC 1/0 KCR 750 MCM KCD 2/0 KCS 1000 MCM KCE 3/0 Tubular Terminal and Offset Bolt-Type Terminal KQV #12 KDD 2/0 KQT #10 KDE 3/0 KFZ #8 KDF 4/0 KIG #6 KDH 250 MCM KDY #4 KDJ 350 MCM KDA #2 KDM 500 MCM KDB #1 KDR 750 MCM KDC 1/0 Compression Connector Rod Terminal and Tubular Terminal KEX 4/0 KQO 350 MCM KFH-A 250 MCM KDT 500 MCM Class H Class J Catalog Number Amp Rating (Nominal) 68150 150 68200 200 Carton Quantity Weight Each Lbs. Kg. 1 1.40 0.63 1 2.75 1.25 68300 300 68400 400 68600 600 1 4.25 1.92 64200 200 1 1.00 0.45 64300 300 1 1.75 0.79 64400 400 1 1.75 0.79 64600 600 1 3.50 1.59 * Current-limiting devices designed specially for use on welder circuits only. * Time-current characteristics are designed to hold on the intermittent overloading encountered in welder operation, while providing short-circuit protection to the circuit and equipment. * Welder limiters have excess current capacity in the operating range as needed for this type of service. * Because of the special characteristics of the welder limiters, they are not intended for application on general-use circuits. *Center Bolt-Type Terminal and Off-Set Bolt-Type Terminal KPF 4/0 KDP 500 MCM KFT 250 MCM KFM 750 MCM KEW 350 MCM Also available with molded rubber boots. Add "-B" to end of part number. *Copper or aluminum cable; sizes of all other limiters pertain to copper only. BIF document: 1042 26 BIF document: 1045 For complete specification data, call Bussmann Information Fax ~ 636.527.1450