FUSETRONTM 250V Class RK5 FRN-R -- 250Vac/125Vdc, 70-600A, Dual Element, Time-Delay Fuses Dimensions - in 8.63" 0.094 5.88" 1.06" 2.38" 0.020 225 to 400A 70 to 100A 10.38" 0.094 7.13" 1.56" 450 to 600A 110 to 200A Description: Advanced protection, energy efficient Class RK5 dual element, current-limiting, time-delay fuses. Time-delay - 10 seconds (minimum) at 500% of rated current. Catalog Symbol: FRS-R-(amp) Ratings: Volts -- 250Vac -- 125Vdc (110-200A) -- 250Vdc (225-600A) Amps -- 70-600A IR -- 200kA Vac RMS Sym. -- 20kA Vdc Agency Information: CE, UL Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273 CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787 Catalog Numbers (amps) FRN-R-70 FRN-R-75 FRN-R-80 FRN-R-85 FRN-R-90 FRN-R-100 FRN-R-110 FRN-R-125 FRN-R-150 FRN-R-175 FRN-R-200 FRN-R-225 FRN-R-250 FRN-R-300 Carton Quantity and Weight Amp Rating 70-100 101-200 201-400 401-600 Carton Qty. 5 1 1 1 FRN-R-350 FRN-R-400 FRN-R-450 FRN-R-500 FRN-R-600 2.88" 0.020 Features: * Provides motor overload, ground fault and short-circuit protection * Helps protect motors against burnout from overloads and single-phasing when sized properly * Simplifies and improves blackout prevention (selective coordination) * Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection * The overload element provides protection against low level overcurrent of overloads and will hold on inrush current which is five times greater than the amp rating of the fuse for a minimum of ten seconds Recommended Fuse Blocks Fuse Amps 70-100 110-200 225-400 450-600 1-Pole RM25100-1CR RM25200-1CR RM25400-1CR RM25600-1CR 2-Pole RM25100-2CR RM25200-2CR RM25400-2CR RM25600-2CR 3-Pole RM25100-3CR RM25200-3CR RM25400-3CR RM25600-3CR For additional information on the RM Series of 250 volt fuse blocks, see product brochure # 3192. Fuse Reducers For Class R Fuses Equipment Fuse Clips 200A 400A 600A Desired Fuse (Case) Size 100A 100A 200A 100A 200A 400A Catalog Numbers (Pairs) 250V NO.2621-R NO.2641-R NO.642-R NO.2661-R NO.2662-R NO.2664-R Single reducer only (pair not required). For additional information on Class R fuse reducers, see Data Sheet # 1118. 0713 BU-SB13731 Page 1 of 3 Data Sheet # 1020 FUSETRONTM Class RK5 FRN-R -- 250Vac/125Vdc, 70-600A, Dual Element, Time-Delay Fuses Time-Current Curves - Average Melt 600 400 200 100 TIME IN SECONDS 60 AMP RATING CURRENT IN AMPS 0713 BU-SB13731 Page 2 of 3 Data Sheet # 1020 FUSETRONTM Class RK5 FRN-R -- 250Vac/125Vdc, 70-600A, Dual Element, Time-Delay Fuses Current-Limitation Curves B 400000 300000 INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS AMP RATING 200000 100000 90000 80000 70000 60000 50000 600A 400A 200A 40000 30000 100A 20000 10000 9000 8000 7000 6000 5000 4000 3000 A 2000 200000 50000 60000 70000 80000 90000 100000 30000 40000 20000 4000 5000 6000 7000 8000 9000 10000 3000 2000 1000 1000 PROSPECTIVE SHORT-CIRCUIT CURRENT - SYMMETRICAL RMS AMPS Current-Limiting Effects Prosp. Let-Through Current S.C.C. (Apparent RMS Symmetrical Vs. Fuse Rating) 100A 200A 400A 600A 5000 3000 5000 5000 5000 10,000 4000 7000 10,000 10,000 15,000 5000 8000 11,000 15,000 20,000 5000 8000 12,000 16,000 25,000 6000 9000 13,000 17,000 30,000 6000 10,000 14,000 18,000 35,000 6000 10,000 15,000 19,000 40,000 7000 11,000 15,000 20,000 50,000 7000 11,000 17,000 21,000 60,000 8000 12,000 18,000 22,000 70,000 8000 13,000 19,000 23,000 80,000 8000 13,000 19,000 24,000 90,000 9000 14,000 20,000 25,000 100,000 9000 14,000 21,000 26,000 150,000 10,000 16,000 24,000 29,000 200,000 11,000 18,000 26,000 32,000 The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 0713 BU-SB13731 Page 3 of 3 Data Sheet # 1020