AApppplliiccaattiioonn
For energy management systems and
instrumentation.
FFrreeqquueennccyy
50-400 Hz.
IInnssuullaattiioonn LLeevveell
0.6 kV, 10 kV BIL full wave.
CCoonnssttrruuccttiioonn
The core and windings are encased in U.L.
approved plastic.
CCoonnttiinniioouuss TThheerrmmaall CCuurrrreenntt RRaattiinngg FFaaccttoorr
1.33 at 30°C amb.,
1.0 at 55°C amb.
• Terminals are brass studs No. 8-32
with one flatwasher, lockwasher and
regular nut.
• Flexible leads are UL 1015 105°C, CSA
approved,#16 AWG, 24" long
• Approximate Weight: 1.2 lbs.
PRODUCT PROFILE
WINDOW SIZE 2.00” X 3.50”
These transformers are designed for assembly to an existing electrical installation
without the need for dismantling the primary bus or cables.
CURRENT TRANSFORMER
MODEL 1411-617
SPLIT CORE
REGULATORY AGENCY APPROVALS
Manufactured to meet the requirements of
ANSI/IEEE C57.13.
Classified by U.L. in accordance with IEC 44-1
SPECIFICATIONS
Publication 1411-PP007A-EN-P – August 2005 Copyright ©2005 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.