https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) LSA-PLUS plug (COMTRAB CTM) with protective circuit for 2-conductor signal circuits grounded on one side. Nominal voltage: 12 V DC Your advantages Space-saving due to compact design Flexible fields of application with modular protective plug Can be used in LSA-PLUS disconnect and control strips or CT-TERMIBLOCK via adapted connection technology Key Commercial Data Packing unit 1 pc GTIN GTIN 4017918819606 Weight per Piece (excluding packing) 10.560 g Custom tariff number 85363010 Country of origin Germany Technical data Dimensions Height 21 mm Width 9.5 mm Depth 53.5 mm Ambient conditions Ambient temperature (operation) -25 C ... 75 C Degree of protection IP20 01/02/2021Page1/8 https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Technical data General Housing material PA Flammability rating according to UL 94 V-0 Color black Standards for cearances and creepage distances DINVDE0110-1 IEC60664-1 Overvoltage category II Degree of pollution 2 Mounting type On CT-TERMIBLOCK and LSA-PLUS disconnect strip Type LSA-PLUS module Number of positions 2 Direction of action Line-Line & Line-Earth Ground Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.10 Protective circuit IEC test classification B2 C1 C2 C3 D1 VDE requirement class B2 C1 C2 C3 D1 Nominal voltage UN 12 VDC Maximum continuous voltage UC 15 VDC 10 VAC Rated current 380 mA AC (25C) Operating effective current IC at UC 5 A Residual current IPE 2 A Nominal discharge current In (8/20) s (line-earth) 5 kA Pulse discharge current Iimp (10/350)s (line-earth) 1 kA Total discharge current Itotal (8/20)s 10 kA Total discharge current Itotal (10/350)s 2.5 kA Max. discharge current Imax (8/20) s maximum (line-earth) 10 kA (in total) Nominal pulse current Ian (10/1000) s (line-earth) 100 A Output voltage limitation at 1 kV/s (line-earth) spike 28 V 01/02/2021Page2/8 https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Technical data Protective circuit Output voltage limitation at 1 kV/s (line-earth) static 22 V Residual voltage at In (line-earth) 32 V Residual voltage with Ian (10/1000) s (line-earth) 18 V Voltage protection level Up (line-earth) 60 V (C2 - 10 kV/5 kA, spike) 30 V (C3 - 7.5 kV / 100 A, spike) Response time tA (line-earth) 1 ns Input attenuation aE, asym. 0.3 dB ( 400 kHz) Cut-off frequency fg (3 dB), asym. (PE) in 100 Ohm system 1.5 MHz Capacity (line-earth) 1.5 nF (f=1 MHz / VR= 0 V) Resistance per path 3.3 10% Surge protection fault message none Impulse durability (line-earth) C2 - 4kV / 2kA C3 - 100A B2 - 4kV / 100A D1 - 1kA Alternating current carrying capacity (line-earth) 5A-1s Connection data Connection method can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips Connection method IN COMTRAB plug-in system Connection method OUT COMTRAB plug-in system Connection technology LSA-PLUS Connection, equipotential bonding Connection method Spring contact Standards and Regulations Standards/regulations IEC61643-21 Standards/specifications IEC61643-21 2000 Environmental Product Compliance REACh SVHC Lead 7439-92-1 China RoHS Environmentally friendly use period: unlimited = EFUP-e No hazardous substances above threshold values Drawings 01/02/2021Page3/8 https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Pictogram Dimensional drawing 18,5 9,4 52,4 38 U Circuit diagram 1' 1 IN OUT 2 2' Classifications eCl@ss eCl@ss 10.0.1 27130807 eCl@ss 11.0 27130807 eCl@ss 4.0 27130800 eCl@ss 4.1 27130800 eCl@ss 5.0 27130800 eCl@ss 5.1 27130800 eCl@ss 6.0 27130800 eCl@ss 7.0 27130807 eCl@ss 8.0 27130807 eCl@ss 9.0 27130807 ETIM ETIM 2.0 EC000943 ETIM 3.0 EC000943 ETIM 4.0 EC000943 ETIM 5.0 EC000943 ETIM 6.0 EC000943 01/02/2021Page4/8 https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Classifications ETIM ETIM 7.0 EC000943 UNSPSC UNSPSC 6.01 30212010 UNSPSC 7.0901 39121610 UNSPSC 11 39121610 UNSPSC 12.01 39121610 UNSPSC 13.2 39121620 UNSPSC 18.0 39121620 UNSPSC 19.0 39121620 UNSPSC 20.0 39121620 UNSPSC 21.0 39121620 Approvals Approvals Approvals UL Listed / EAC Ex Approvals Approval details UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168 EAC RU CDE.*09.B.00169 Accessories Necessary add-on products 01/02/2021Page5/8 https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Accessories Disconnect strip-CT 10-TL-2765356 LSA-PLUS disconnect strip to hold the CTM and CT 10 protection modules. Version: 10 double conductors, dimension A: 124 mm. Grounding rail-CT 1-10-ES-2765547 Ground rail for CTM protective plug when used in combination with LSA-PLUS disconnect strip. Version: 10 double conductors Screw termination block-CT-TERMIBLOCK 10 DA-0441711 Screw termination block with disconnect contacts for accommodating protective plugs CT and CTM. Use in MCR and telecommunications systems. Design: 10 double wires Magazine-CTM 10-MAG-2838610 Magazine with a grounding rail to accommodate up to 10 LSA-PLUS protective plugs (COMTRAB CTM), to insert in CTTERMIBLOCK or LSA-PLUS disconnect strip Additional products Mounting clip-CT 10-MB/ 3-2765372 Mounting clip, for holding 3 disconnect or ground wire strips. Version: 10 double conductors, dimensions: A 104.5 mm, B 65 mm. 01/02/2021Page6/8 https://www.phoenixcontact.com/us/products/2838584 Surge protection plug-CTM 2X1- 12DC-2838584 Accessories Mounting clip-CT 10-MB/10-2765385 Mounting clip, for holding 10 disconnect or ground wire strips. Version: 10 double conductors, dimensions: A 104.5 mm, dimensions B 245.5 mm Cable feed-through sleeve-CT-KDT-2765518 Cable bush for assembly troughs, for protection of the lines guided through the laminated frame Short-circuit connector-CTM EST-2838649 LSA-PLUS grounding plug (COMTRAB CTM) to short-circuit and ground potentials in CT-TERMIBLOCK... and disconnect strip CT 10... Shield connection-SSA 3-6-2839295 Shield fast connection for 3 ... 6 mm cable diameter. Potential connecting cable: 200 mm, 1 mm, color: black Shield connection-SSA 5-10-2839512 Shield fast connection for 5 ... 10 mm cable diameter. Potential connecting cable: 200 mm, 1 mm, color: black 01/02/2021Page7/8 https://www.phoenixcontact.com/us/products/2838584 Phoenix Contact 2021 (c) - all rights reserved http://www.phoenixcontact.com 01/02/2021Page8/8