Data sheet
PROmax
PRO MAX3 480W 24V 20A
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date December 20, 2018 10:00:02 PM CET
Catalogue status 07.12.2018 / We reserve the right to make technical changes. 3
General data
AC failure bridging time @ INom min. 20 ms Current limiting > 120 % IN
Degree of efficiency 91.5% Derating > 60°C / 75% @ 70°C
Earth leakage current, max. 3.5 mA Housing version Metal, corrosion resistant
MTBF
>500.000h (25°C, IEC
61709 (SN29500))
Mounting position, installation notice Horizontal on TS35
mounting rail. 50 mm of
clearance at top & bottom
for air circ. Can mount side
by side with no space in
between.
Operating temperature -25 °C...70 °C Power factor (approx.) > 0.85 @ 3*400 V AC
Power loss, idling 5.5 W Power loss, nominal load 36 W
Protection against reverse voltages from
the load 30…35 V DC
Protection degree
IP20
Series switching capability Yes Short-circuit protection Yes
Start-up
≥ -40 °C
Status indication LED red/green and relay
(≥21.6 V DC LED green,
relay on/ ≤20.6 LED red,
relay off)
Surge voltage category III
EMC / shock / vibration
Noise emission in accordance with
EN55032 Class B
Vibration resistance IEC 60068-2-6
2.3 g
Interference immunity test acc. to EN 55024, EN 55022,
IEC61000-3-2,-3,
IEC61000-4-2,-3,-4,-5,-6,-8,-11
Shock resistance IEC 60068-2-27
30 g in all directions
Insulation coordination
Class of protection I, with PE connection Humidity at operating temperature 5...95 %, no condensation
Insulation voltage input / earth 3.5 kV Insulation voltage output / earth 0.5 kV
Insulation voltage, input/output 4 kV Pollution severity 2
Surge voltage category III
Electrical safety (applied standards)
Electrical machine equipment
Acc. to EN60204
For use with electronic equipment Acc. to EN50178 /
VDE0160
Protection against dangerous shock
currents Acc. to VDE0106-101
Protective separation / protection
against electrical shock
VDE0100-410 / acc. to
DIN57100-410
Safety extra-low voltage SELV acc. to EN60950,
PELV acc. to EN60204,
IEC61204
Safety transformers for switch-mode
power supplies
nach EN61558-2-16
Connection data (input)
Conductor cross-section, AWG/kcmil ,
max. 10
Conductor cross-section, AWG/kcmil ,
min. 26
Conductor cross-section, flexible , min. 0.22 mm² Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.18 mm² Connection system Screw connection
Number of terminals 4 for L1/L2/L3/PE Screwdriver blade 0.8 x 4.0, PZ 1
Tightening torque, max. 0.6 Nm Tightening torque, min. 0.5 Nm
Wire connection cross section, flexible
(input), max. 4 mm²