Thank you for choosing the CAL ETC1311 thermostat.
* 34 x 77mm sized.
* On-Off control.
* CE marked according to European Norms.
* J type Thermocouple or Pt100 input.
* Temperature compensation.
* In the case of probe failure, heating can be
selected on, off or periodical running.
* Upper and lower limits of the setpoint can be
adjusted.
* Set value can be adjusted by using single key.
Connectýon Dýagram
CAL ETC1311 is intended for installation in control panels. Make sure that the device is
used only for intended purpose. The electrical connections must be carried out by
qualified staff and must be according to the relevant locally applicable regulations. During
an installation, all of the cables that are connected to the device must be free of electrical
power. The device must be protected against inadmissible humidity, vibrations, severe
soiling and make sure that the operation temperature is not exceeded. The cables should
not be close to the power cables or components.
1/2
Panel cut-out
Dimensions
Note :1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the
anelP
ETC1311-E-06
Holding screw 0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
34mm
70mm 8mm
85mm
71mm
29mm
mounting
clamp
mounting
clamp
Depth
Rubber
gasket
Panel
For removing mounting clamps:
Push out the mounting clamp
in direction as shown
in the figure below. Then, pull
out the clamp in direction
1
2.
2
1
COMPRESSOR
1/2HP 240V AC Cos = 0.4
8 A 250V AC Cos = 1
F
F
SN: XXXXXXXXX
123456789
10 11 12
ETC1311-FE-230VAC
DIGITALT THERMOSTAT
230V AC +10% -20%
50/60Hz 3VA
J (Fe-CuNi)
-
+
HEAT OUT
250V AC 8A
RESISTIVE LOAD
CAL ETC1311 DIGITAL THERMOSTAT
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
80 , up to 40% 31°C decreasing linearly 50% at °C
Ambient/storage temperature
Max. relative humidity
0 ... +50°C/-25 ... 70°C (with no icing)
Rated pollution degree According to EN 60529 Front panel : IP60
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gasses.
Supply voltage 230V AC +%10 -%20, 50/60Hz or 12VAC or 24 AC %10, 50/60Hz or optional 9-30V DC %10 .
±±
Power consumption Max. 3VA
2.5mm² screw-terminal connections.
3 digits, 14mm, 7 parts red LED
Wiring
Scale
Accuracy
Indicator
EMC
Safety requirements
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
0 .... +600°C for J Type. -100.... +600°C for Pt100
± 0.5% (of full scale) ±1 digit
OUTPUT
HEAT OUT For Relay: 250V AC, 8A( ), NO+NC.ETC1311-XX-XX ; for resistive load
For ETC1311-FE-XXP ; Relay: 240V AC, 16A(for resistive load), NO.
For ETC1311-XX-XX ;
For ETC1311-FE-XXP ; Mechanical 30.000.000; Electrical 30.000 operation.
Mechanical 30.000.000; Electrical 100.000 operation.
Life expectancy for relay
CONTROL
Control type Single-setpoint control
On-Off control
Control algorithm
Hysteresis Adjustable between 1 ... 20°C.
HOUSING
Housing type Suitable for panel mounting.
Dimensions W77xH34xD70mm
Weight Approx. 250g ( )after packing the device and a probe
Enclosure material Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or must not be used.corrosive materials
4
5
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
ETC1311
PRG
CAL
°C
OUT
ETC1311
°C
PRG
OUT
CAL
Pt100
SN: XXXXXXXXX
123456789
10 11 12
ETC1311-R-12VAC
DIGITAL THERMOSTAT
12V AC ±10%
50/60Hz 3VA
HEAT OUT
250V AC 8A
RESISTIVE LOAD
SN: XXXXXXXXX
123456789
10 11 12
ETC1311-FE-230VAC-P
DIGITAL THERMOSTAT
J (Fe-CuNi)
-
+
230V AC +10% -20%
50/60Hz 3VA
HEAT OUT
240V AC 16A
RESISTIVE LOAD
SN: XXXXXXXXX
123456789
10 11 12
ETC1311-FE-230VAC
DIGITAL THERMOSTAT
J (Fe-CuNi)
-
+
230V AC +10% -20%
50/60Hz 3VA
HEAT OUT
250V AC 8A
RESISTIVE LOAD
CAL CONTROLS LTD
Tel : +44 (0) 1462 436161 Fax : +44 (0) 1462 451801
e-mail: sales@cal-controls.co.uk Web : www.cal-controls.com
Bury Mead Road, Hitchin, Herts, SG5 1RT, UK.
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. CAL Controls shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
www.cal-controls.com www.cal-controls.com www.cal-controls.com
www.cal-controls.com
Order Code : ETC1311---
123
1 - Input
FE.....J Type
R.......Pt100
2 - Supply Voltage
230VAC...230V AC
24VAC.....24V AC
12VAC.....12V AC
SM...........9-30V DC SMPS
3 - Output
P..........Relay-16A
None...Relay-8A