Please read this document carefully before using this product. The guarantee will be invalidated if the device is damaged by not following instructions detailed in the manual. CAL Controls shall not be responsible for any damage or losses however caused, which may be experienced as a result of the installation or use of this product. Technical Specifications ENVIRONMENTAL CONDITIONS Ambient/storage temperature 0 ... +50C/-25 ... 70C (with no icing) 80%, up to 31C decreasing linearly 50% at 40C Max. relative humidity Rated pollution degree According to EN 60529 Front panel : IP60 Rear panel : IP20 Height Max. 2000m CAL ETC1311 DIGITAL THERMOSTAT Thank you for choosing the CAL ETC1311 thermostat. * 34 x 77mm sized. * On-Off control. * J type Thermocouple or Pt100 input. * Temperature compensation. * In the case of probe failure, heating can be selected on, off or periodical running. * Upper and lower limits of the setpoint can be adjusted. * Set value can be adjusted by using single key. * CE marked according to European Norms. Do not use the device in locations subject to corrosive and flammable gasses. ELECTRICAL CHARACTERISTICS OUT C PRG CAL ETC1311 Safety requirements OUTPUT Order Code : ETC1311--- HEAT OUT 3 3 - Output P..........Relay-16A None...Relay-8A 2 - Supply Voltage 230VAC...230V AC 24VAC.....24V AC 12VAC.....12V AC SM...........9-30V DC SMPS Life expectancy for relay CONTROL Control type Control algorithm Hysteresis Connectyon Dyagram Housing type Dimensions Weight Enclosure material 5 6 7 Equipment is protected throughout by DOUBLE INSULATION. 8 12V AC 10% 50/60Hz 3VA 34mm + 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 Holding screw 0.4-0.5Nm SN: XXXXXXXXX ETC1311-FE-230VAC DIGITALT THERMOSTAT 184-253V AC 50/60Hz 3VA 4 Line 5 Neutral Fuse F 100 mA 250V AC Note: Switch 230V AC Supply Fuse should be connected Cable size: 1,5mm 1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245. 2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator. 1/2 Panel Rubber gasket 1 Panel cut-out 71mm www.cal-controls.com NOTE: SUPPLY: mounting clamp 29mm 4 HEAT OUT 250V AC 8A RESISTIVE LOAD 230V AC +10% -20% 50/60Hz 3VA 230V AC +10% -20% 50/60Hz 3VA HEAT OUT 250V AC 8A RESISTIVE LOAD HEAT OUT 240V AC 16A RESISTIVE LOAD 3 + 2 - 1 J (Fe-CuNi) - + 9 10 11 12 9 10 11 12 8 8 7 Pt100 7 6 2 mounting clamp 6 5 ETC1311 5 4 PRG CAL 8mm Push out the mounting clamp in direction 1 as shown in the figure below. Then, pull out the clamp in direction 2. C 4 3 OUT COMPRESSOR HEAT OUT 1/2HP AC CosF = 0.4 250V240V AC 8A 8 RESISTIVE A 250V AC Cos F=1 LOAD 2 70mm For removing mounting clamps: SN: XXXXXXXXX J (Fe-CuNi) Depth 85mm 230V AC +10% -20% 50/60Hz 3VA 1 Dimensions ETC1311-R-12VAC DIGITAL THERMOSTAT ETC1311-FE-230VAC-P DIGITAL THERMOSTAT SN: XXXXXXXXX J (Fe-CuNi) While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used. www.cal-controls.com www.cal-controls.com Suitable for panel mounting. W77xH34xD70mm Approx. 250g (after packing the device and a probe) Self extinguishing plastics 3 www.cal-controls.com ETC1311-FE-230VAC DIGITAL THERMOSTAT Single-setpoint control On-Off control Adjustable between 1 ... 20C. HOUSING CAL ETC1311 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The electrical connections must be carried out by qualified staff and must be according to the relevant locally applicable regulations. During an installation, all of the cables that are connected to the device must be free of electrical power. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. The cables should not be close to the power cables or components. SN: XXXXXXXXX For ETC1311-XX-XX ; Relay: 250V AC, 8A(for resistive load), NO+NC. For ETC1311-FE-XXP ; Relay: 240V AC, 16A(for resistive load), NO. For ETC1311-XX-XX ; Mechanical 30.000.000; Electrical 100.000 operation. For ETC1311-FE-XXP ; Mechanical 30.000.000; Electrical 30.000 operation. 2 1 - Input FE.....J Type R.......Pt100 2 1 1 230V AC +%10 -%20, 50/60Hz or 12VAC or 24 AC %10, 50/60Hz or optional 9-30V DC %10 . Max. 3VA 2.5mm screw-terminal connections. 0 .... +600C for J Type. -100.... +600C for Pt100 0.5% (of full scale) 1 digit 3 digits, 14mm, 7 parts red LED EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests. The device is designed to operate in controlled electromagnetic environment) EN 61010-1: 2001 (Pollution degree 2, overvoltage category II) Supply voltage Power consumption Wiring Scale Accuracy Indicator EMC Note :1) Panel thickness should be maximum 7 mm. 2) If there is no 60mm free space at the back side of the device, it would be difficult to remove it from the Panel CAL CONTROLS LTD Bury Mead Road, Hitchin, Herts, SG5 1RT, UK. Tel : +44 (0) 1462 436161 Fax : +44 (0) 1462 451801 e-mail: sales@cal-controls.co.uk Web : www.cal-controls.com ETC1311-E-06 HEATING OUT LED Displayed process value in the run mode, parameter name or value in programming mode. Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates. OUT C PRG CAL ETC1311 Used for selecting parameters and decreasing the setpoint value in the programming mode and for decreasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates. Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. PRG While holding key, setpoint value of the selected parameter appears and by using and keys the value can be adjusted. Run mode 1000 100 Process Value 200 199 When pressed or key, temperature set value flashes and by using If no key is pressed for 3 seconds run mode is returned. 200 and If no key is pressed for 3 seconds keys the value can be adjusted. PRG PRG If If key is pressed and held for 3 seconds, programming mode is entered. key is pressed, run mode is entered. Programming Mode Upl Switch hysteresis for the setpoint. The upper limit of the setpoint. Lol The lower limit of the setpoint. Eon In the case of error, on time rate of the relay output. Ect In the case of error, period of the relay output. OoFs Con SeC Con Hys PARAMETER TABLE Cod Aco Ase Access code for menu of security. Enter 311 then press key. Menu of Configuration parameters Hys Switch hysteresis for the setpoint. (When temperature falls to SET-HYS, output relay becomes active.) Upl LoL The upper limit of the setpoint. The lower limit of the setpoint. Security parameter for menu of configuration. Non= Menu is invisible. Pye= Parameters of menu are changeable. Pno= Parameters of menu are only visible. EoFs SEC Security parameter for temperature set value. MAX 20 UNIT DEF.SET C 1 600 600 C 0 C 0 -99 UPL UPL C -99 In the case of error, on time rate of the relay output. 0 100 % Ect 0 In the case of error, period of the relay output. 10 250 sec 30 Offset value. -99 99 C 0 Menu of Parameter security Aco Security parameter for menu of configuration. Non= Menu is invisible. Pye= Parameters of menu are changeable. Pno= Parameters of menu are only visible. ASE Security parameter for temperature set value. Pye= Set value is changeable. Pno= Set value is only visible. Pye= Set value is changeable. Pno= Set value is only visible. 1 LoL Fe-CuNi Pt100 Eon Ect MIN Error Messages Offset value --- Means, temperature value is higher than the scale. ___ Means, temperature value is lower than the scale. Pfa 2/2 Means, temperature sensor is broken or over temperature. ETC1311-E-06